Project La Quinta Biloxi Area 2 HVAC HVAC Calculations

Fri Nov 4 15:34:31 CST 2005

The Btuh Gain for 0 SqFt of North and Shaded Single Pane Glass = 0
There is no calculation for NorthEast and NorthWest Glass
The Btuh Gain for 72.4998 SqFt of East and West Double Pane Glass = 6887.481
The Btuh Gain for 0 SqFt of SouthEast and SouthWest Single Pane Glass = 0
The Btuh Gain for 0 SqFt of South Single Pane Glass = 0
The Btuh Gain for 0 SqFt of SkyLights = 0
The Btuh Gain for 0 SqFt of Windows in Doors = 0

The Btuh Gain for 268.50674 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 1 = 456.461458
There is no calculation for Wall Number 2
There is no calculation for Wall Number 3
There is no calculation for Wall Number 4

The Btuh Gain for 779.5195 SqFt of Ceiling and Roof Combo R-19; Ceiling Number 1 = 3741.6936

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

There is no calculation for People

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 779.5195 SqFt of Area Lighting in an Office = 2338.5585

There is no calculation for Coffee Machines
There is no calculation for Electric Food Warmers
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for other appliances of known wattages

The Office Space Outside Fresh Air #1 = 109.13273 cfm
The Btuh Gain for Outside Fresh Air #1 = 3273.9819
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
There is no calculation for Outside Fresh Air #4
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 109.13273
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 16698.176458

The Total Tons of HVAC needed = 1.39151470483333