Fri Nov 4 15:34:31 CST 2005
The Btuh Gain for 0 SqFt of North and Shaded Single Pane Glass = 0
There is no calculation for NorthEast and NorthWest Glass
The Btuh
Gain for 72.4998 SqFt of East and West Double Pane Glass = 6887.481
The Btuh Gain for 0 SqFt of SouthEast and SouthWest Single Pane
Glass = 0
The Btuh Gain for 0 SqFt of South Single Pane Glass
= 0
The Btuh Gain for 0 SqFt of SkyLights = 0
The
Btuh Gain for 0 SqFt of Windows in Doors = 0
The Btuh Gain for 268.50674 SqFt of Wood R-19 & 1/2" Gypsum Wall
Number 1 = 456.461458
There is no calculation for Wall Number 2
There is no calculation for Wall Number 3
There is no calculation for
Wall Number 4
The Btuh Gain for 779.5195 SqFt of Ceiling and Roof Combo R-19;
Ceiling Number 1 = 3741.6936
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
There is no calculation for People
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 779.5195 SqFt of Area Lighting in an Office = 2338.5585
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for
other appliances of known wattages
The Total Outside Fresh Air CFM = 109.13273
This
is in accordance with International Mechanical Code 2003
The Total BTUh Gain = 16698.176458
The Total Tons of HVAC needed = 1.39151470483333