Mon Feb 28 08:37:39 CST 2005
The Btuh Gain for 195 SqFt of North and Shaded Double Pane Glass =
3900
The Btuh Gain for 50 SqFt of NorthEast and NorthWest
Double Pane Glass = 3500
There is no calculation for East and West
Glass
There is no calculation for SouthEast and SouthWest Glass
There is
no calculation for South Glass
There is no calculation for SkyLights
The
Btuh Gain for 60 SqFt of Windows in Doors = 792
The Btuh Gain for 122 SqFt of Wood R-11 & 1/2" Gypsum Wall Number
1 = 317.2
There is no calculation for Wall Number 2
There is no
calculation for Wall Number 3
There is no calculation for Wall Number 4
The Btuh Gain for 4580 SqFt of Roof Only 3" - 3.5" R-11; Ceiling
Number 1 = 37556
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 76 People = 760
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 4580 SqFt of Area Lighting in an Office = 13740
The wattage for 3 Gallon Coffee Machines = 1410
The wattage
for 20 SqFt of Electric Food Warmers = 2400
There is no
calculation for Gas Food Warmers
There is no calculation for Electric Fry
Kettle
There is no calculation for Gas Fry Kettle
There is no
calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
The wattage for 4580
4-Slice Toasters = 2460
There is no calculation for other
appliances of known wattages
The Total Outside Fresh Air CFM = 1140
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 116083.2
The Total Tons of HVAC needed = 9.6736