Thu May 10 13:24:54 CDT 2007
There is no calculation for North & Shaded Glass
There is no
calculation for NorthEast and NorthWest Glass
There is no calculation for
East and West Glass
There is no calculation for SouthEast and SouthWest
Glass
The Btuh Gain for 90 SqFt of South Single Pane Glass = 7200
There is no calculation for SkyLights
The Btuh Gain for 42
SqFt of Windows in Doors = 554.4
The Btuh Gain for 1020 SqFt of Wood R-11 & 1/2" Gypsum Wall Number
1 = 2652
There is no calculation for Wall Number 2
There is no
calculation for Wall Number 3
There is no calculation for Wall Number 4
The Btuh Gain for 2043 SqFt of Roof Only No Insulation; Ceiling Number
1 = 87849
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 189 People = 1890
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 2000 SqFt of Area Lighting in a Retail Store = 8000
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for
other appliances of known wattages
The Total Outside Fresh Air CFM = 300
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 117145.4
The Total Tons of HVAC needed = 9.76211666666667