Project Textron SSC Government Office HVAC Calculations Thu Sep 8 10:59:28 CDT 2011 There is no calculation for North & Shaded Glass There is no calculation for NorthEast and NorthWest Glass The Btuh Gain for _ 46.4 _ SqFt of East and West Single Pane Glass = _ 5104 _ There is no calculation for SouthEast and SouthWest Glass There is no calculation for South Glass There is no calculation for SkyLights There is no calculation for Windows in Doors The Btuh Gain for _ 1488 _ SqFt of Wood R-11 & 1/2" Gypsum Wall Number 1 = _ 3868.8 _ The Btuh Gain for _ 512 _ SqFt of Wood R-11 & 1/2" Gypsum Wall Number 2 = _ 1331.2 _ The Btuh Gain for _ 1632 _ SqFt of Wood R-11 & 1/2" Gypsum Wall Number 3 = _ 4243.2 _ The Btuh Gain for _ 272 _ SqFt of Wood R-11 & 1/2" Gypsum Wall Number 4 = _ 707.2 _ The Btuh Gain for _ 2750 _ SqFt of Roof Only 3" - 3.5" R-11; Ceiling Number 1 = _ 22550 _ There is no calculation for Ceiling Number 2 The Btuh Gain for _ _ SqFt of Above Grade R-5 Floor Number 1 = _ 21175 _ There is no calculation for Floor Number 2 The Btuh Gain for _ 20 _ People = _ 200 _ The Btuh Gain for Motor _ .125 _ HP = _ 437.5 _ There is no calculation for Ducts Out of Conditioned Spaces The Btuh Gain for _ 2750 _ SqFt of Area Lighting in an Office = _ 8250 _ The wattage for _ 1 _ Gallon Coffee Machines = _ 470 _ There is no calculation for Electric Food Warmers There is no calculation for Gas Food Warmers There is no calculation for Electric Fry Kettle There is no calculation for Gas Fry Kettle There is no calculation for Electric Griddle There is no calculation for Gas Griddle There is no calculation for Hair Dryer Helmets There is no calculation for 4-Slice Toaster _ 6000 _ watts are being calculated as _ 20400 _ of BTUh There is no calculation for Outside Fresh Air #1 There is no calculation for Outside Fresh Air #2 There is no calculation for Outside Fresh Air #3 / The Office Space Outside Fresh Air #4 = _ 400 _cfm / The Btuh Gain for Outside Fresh Air #4 = _ 12000 _ There is no calculation for Outside Fresh Air #5 There is no calculation for Outside Fresh Air #6 / The Total Outside Fresh Air CFM = _ 400 _ This is in accordance with International Mechanical Code 2003 / The Total BTUh Gain = _ 101864.9 _ The Total Tons of HVAC needed = _ 8.48874166666667 _