Insul-Tech Office HVAC HVAC ProjectProject Insul-Tech Office HVAC HVAC Calculations Wed May 10 17:39:06 CDT 2006 There is no calculation for North & Shaded Glass There is no calculation for NorthEast and NorthWest Glass The Btuh Gain for 180 SqFt of East and West Single Pane Glass = 19800 There is no calculation for SouthEast and SouthWest Glass There is no calculation for South Glass There is no calculation for SkyLights There is no calculation for Windows in Doors The Btuh Gain for 1600 SqFt of Mason Above Grade R-5 Wall Number 1 = 4960 The Btuh Gain for 580 SqFt of Mason Above Grade No Insulation Wall Number 2 = 6322 The Btuh Gain for 840 SqFt of Mason Above Grade No Insulation Wall Number 3 = 9156 The Btuh Gain for 1120 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 4 = 2912 The Btuh Gain for 2860 SqFt of Roof Only 3" - 3.5" R-11; Ceiling Number 1 = 23452 There is no calculation for Ceiling Number 2 There is no calculation for Floor Number 1 There is no calculation for Floor Number 2 The Btuh Gain for 15 People = 150 There is no calculation for Motor HP There is no calculation for Ducts Out of Conditioned Spaces The Btuh Gain for 2860 SqFt of Area Lighting in an Office = 8580 There is no calculation for Coffee Machines There is no calculation for Electric Food Warmers There is no calculation for Gas Food Warmers There is no calculation for Electric Fry Kettle There is no calculation for Gas Fry Kettle There is no calculation for Electric Griddle There is no calculation for Gas Griddle There is no calculation for Hair Dryer Helmets There is no calculation for 4-Slice Toaster There is no calculation for other appliances of known wattages There is no calculation for Outside Fresh Air #1 There is no calculation for Outside Fresh Air #2 There is no calculation for Outside Fresh Air #3 The Reception Area Outside Fresh Air #4 = 45 cfm The Btuh Gain for Outside Fresh Air #4 = 1350 The Office Space Outside Fresh Air #5 = 240 cfm The Btuh Gain for Outside Fresh Air #5 = 7200 There is no calculation for Outside Fresh Air #6 The Total Outside Fresh Air CFM = 285 This is in accordance with International Mechanical Code 2003 The Total BTUh Gain = 83882 The Total Tons of HVAC needed = 6.99016666666667