Wed May 24 12:51:13 CDT 2006
The Btuh Gain for 0 SqFt of North and Shaded Single Pane Glass = 0
The Btuh Gain for 0 SqFt of NorthEast and NorthWest Single Pane
Glass = 0
The Btuh Gain for 0 SqFt of East and West Single
Pane Glass = 0
The Btuh Gain for 0 SqFt of SouthEast and
SouthWest Single Pane Glass = 0
The Btuh Gain for 0 SqFt of
South Single Pane Glass = 0
The Btuh Gain for 0 SqFt of
SkyLights = 0
The Btuh Gain for 0 SqFt of Windows in Doors =
0
The Btuh Gain for 569 SqFt of Wood R-13 & 1/2" Gypsum Wall Number
1 = 1308.7
The Btuh Gain for 625 SqFt of Wood R-13 & 1/2"
Gypsum Wall Number 2 = 1437.5
The Btuh Gain for 867 SqFt of
Wood R-13 & 1/2" Gypsum Wall Number 3 = 1994.1
The Btuh Gain for
795 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 4 = 1351.5
The Btuh Gain for 4591 SqFt of Roof Only No Insulation; Ceiling Number
1 = 197413
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 8 People = 80
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 4590 SqFt of Area Lighting in a Retail Store = 18360
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for
other appliances of known wattages
The Total Outside Fresh Air CFM = 4131
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 345874.8
The Total Tons of HVAC needed = 28.8229