Wed Aug 12 16:05:29 EDT 2009
The Btuh Gain for 115.2083 SqFt of North and Shaded Double Pane Glass
= 2304.166
The Btuh Gain for 115.2083 SqFt of NorthEast and
NorthWest Double Pane Glass = 8064.581
There is no calculation for
East and West Glass
There is no calculation for SouthEast and SouthWest
Glass
There is no calculation for South Glass
There is no calculation
for SkyLights
There is no calculation for Windows in Doors
The Btuh Gain for 459 SqFt of Wood R-13 & 1/2" Gypsum Wall Number
1 = 1055.7
The Btuh Gain for 252 SqFt of Wood R-11 & 1/2"
Gypsum Wall Number 2 = 655.2
The Btuh Gain for 459 SqFt of
Wood R-11 & 1/2" Gypsum Wall Number 3 = 1193.4
The Btuh Gain for
252 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 4 = 655.2
The Btuh Gain for 1428 SqFt of Ceiling and Roof Combo R-22; Ceiling
Number 1 = 6854.4
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 85 People = 850
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 1428 SqFt of Area Lighting in a Retail Store = 5712
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
5000 watts are being
calculated as 17000 of BTUh
The Total Outside Fresh Air CFM = 420
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 56944.647
The Total Tons of HVAC needed = 4.74538725