2nd Street Soup Kitchen HVAC ProjectProject 2nd Street Soup Kitchen HVAC Calculations Tue Aug 2 13:27:57 CDT 2005 The Btuh Gain for 30 SqFt of North and Shaded Single Pane Glass = 900 There is no calculation for NorthEast and NorthWest Glass The Btuh Gain for 122 SqFt of East and West Single Pane Glass = 13420 There is no calculation for SouthEast and SouthWest Glass The Btuh Gain for 45 SqFt of South Single Pane Glass = 3600 There is no calculation for SkyLights There is no calculation for Windows in Doors The Btuh Gain for 3222 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 1 = 8377.2 There is no calculation for Wall Number 2 There is no calculation for Wall Number 3 There is no calculation for Wall Number 4 The Btuh Gain for 2212 SqFt of Roof Only 3" - 3.5" R-11; Ceiling Number 1 = 18138.4 There is no calculation for Ceiling Number 2 There is no calculation for Floor Number 1 There is no calculation for Floor Number 2 The Btuh Gain for 25 People = 250 There is no calculation for Motor HP There is no calculation for Ducts Out of Conditioned Spaces The Btuh Gain for 2212 SqFt of Area Lighting in an Office = 6636 The wattage for 10 Gallon Coffee Machines = 4700 The wattage for 38 SqFt of Electric Food Warmers = 4560 The wattage for 12 SqFt of Gas Food Warmers = 1440 The wattage for 5 SqFt of Electric Fry Kettle = 7000 There is no calculation for Gas Fry Kettle The wattage for 5 SqFt of Electric Griddle = 7000 There is no calculation for Gas Griddle There is no calculation for Hair Dryer Helmets The wattage for 2212 4-Slice Toasters = 2460 There is no calculation for other appliances of known wattages The Kitchen Outside Fresh Air #1 = 210 cfm The Btuh Gain for Outside Fresh Air #1 = 6300 The Dining Room Outside Fresh Air #2 = 1050 cfm The Btuh Gain for Outside Fresh Air #2 = 31500 There is no calculation for Outside Fresh Air #3 There is no calculation for Outside Fresh Air #4 There is no calculation for Outside Fresh Air #5 There is no calculation for Outside Fresh Air #6 The Total Outside Fresh Air CFM = 1260 This is in accordance with International Mechanical Code 2003 The Total BTUh Gain = 181465.6 The Total Tons of HVAC needed = 15.1221333333333