Revised 2nd Str Feeding Ministry HVAC ProjectProject Revised 2nd Str Feeding Ministry HVAC Calculations Mon Aug 14 12:10:10 CDT 2006 There is no calculation for North & Shaded Glass There is no calculation for NorthEast and NorthWest Glass The Btuh Gain for 36 SqFt of East and West Single Pane Glass = 3960 There is no calculation for SouthEast and SouthWest Glass There is no calculation for South Glass There is no calculation for SkyLights The Btuh Gain for 60 SqFt of Windows in Doors = 792 The Btuh Gain for 80000 SqFt of Wood R-13 & 1/2" Gypsum Wall Number 1 = 184000 There is no calculation for Wall Number 2 There is no calculation for Wall Number 3 There is no calculation for Wall Number 4 The Btuh Gain for 4000 SqFt of Roof Only 8" - 9.5" R-30; Ceiling Number 1 = 12800 There is no calculation for Ceiling Number 2 The Btuh Gain for SqFt of Above Grade R-5 Floor Number 1 = 30800 There is no calculation for Floor Number 2 The Btuh Gain for 94 People = 940 There is no calculation for Motor HP There is no calculation for Ducts Out of Conditioned Spaces The Btuh Gain for 4000 SqFt of Area Lighting in a Retail Store = 16000 The wattage for 10 Gallon Coffee Machines = 4700 The wattage for 8 SqFt of Electric Food Warmers = 960 The wattage for 10 SqFt of Gas Food Warmers = 1200 There is no calculation for Electric Fry Kettle The wattage for 8 SqFt of Gas Fry Kettle = 16000 There is no calculation for Electric Griddle There is no calculation for Gas Griddle There is no calculation for Hair Dryer Helmets There is no calculation for 4-Slice Toaster There is no calculation for other appliances of known wattages There is no calculation for Outside Fresh Air #1 There is no calculation for Outside Fresh Air #2 There is no calculation for Outside Fresh Air #3 The Dining Room Outside Fresh Air #4 = 1660 cfm The Btuh Gain for Outside Fresh Air #4 = 49800 The Kitchen Outside Fresh Air #5 = 165 cfm The Btuh Gain for Outside Fresh Air #5 = 4950 There is no calculation for Outside Fresh Air #6 The Total Outside Fresh Air CFM = 1825 This is in accordance with International Mechanical Code 2003 The Total BTUh Gain = 381766 The Total Tons of HVAC needed = 31.8138333333333