Wings-Pizza-N-Things HVAC ProjectProject Wings-Pizza-N-Things HVAC Calculations Tue Nov 7 19:44:38 CST 2006 There is no calculation for North & Shaded Glass There is no calculation for NorthEast and NorthWest Glass The Btuh Gain for 660 SqFt of East and West Single Pane Glass = 72600 There is no calculation for SouthEast and SouthWest Glass The Btuh Gain for 600 SqFt of South Single Pane Glass = 48000 There is no calculation for SkyLights The Btuh Gain for 40 SqFt of Windows in Doors = 528 There is no calculation for Wall Number 1 There is no calculation for Wall Number 2 There is no calculation for Wall Number 3 There is no calculation for Wall Number 4 The Btuh Gain for 3960 SqFt of Ceiling and Roof Combo No Insulation; Ceiling Number 1 = 110880 There is no calculation for Ceiling Number 2 There is no calculation for Floor Number 1 There is no calculation for Floor Number 2 The Btuh Gain for 113 People = 1130 There is no calculation for Motor HP There is no calculation for Ducts Out of Conditioned Spaces The Btuh Gain for 3960 SqFt of Area Lighting in a Retail Store = 15840 There is no calculation for Coffee Machines There is no calculation for Electric Food Warmers There is no calculation for Gas Food Warmers There is no calculation for Electric Fry Kettle There is no calculation for Gas Fry Kettle There is no calculation for Electric Griddle There is no calculation for Gas Griddle There is no calculation for Hair Dryer Helmets There is no calculation for 4-Slice Toaster There is no calculation for other appliances of known wattages There is no calculation for Outside Fresh Air #1 There is no calculation for Outside Fresh Air #2 There is no calculation for Outside Fresh Air #3 The Dining Room Outside Fresh Air #4 = 3672 cfm The Btuh Gain for Outside Fresh Air #4 = 110160 The Kitchen Outside Fresh Air #5 = 75 cfm The Btuh Gain for Outside Fresh Air #5 = 2250 There is no calculation for Outside Fresh Air #6 The Total Outside Fresh Air CFM = 3747 This is in accordance with International Mechanical Code 2003 The Total BTUh Gain = 361388 The Total Tons of HVAC needed = 30.1156666666667