Wed Apr 27 12:16:59 CST 2005
The Btuh Gain for 0 SqFt of North and Shaded Single Pane Glass = 0
The Btuh Gain for 140 SqFt of NorthEast and NorthWest Single Pane
Glass = 12600
There is no calculation for East and West Glass
There is no calculation for SouthEast and SouthWest Glass
There is no
calculation for South Glass
There is no calculation for SkyLights
The
Btuh Gain for 42 SqFt of Windows in Doors = 554.4
The Btuh Gain for 45 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 1
= 76.5
The Btuh Gain for 200 SqFt of Wood R-19 & 1/2"
Gypsum Wall Number 2 = 340
There is no calculation for Wall Number 3
There is no calculation for Wall Number 4
The Btuh Gain for 1200 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 1 = 6240
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 12 People = 120
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 1200 SqFt of Area Lighting in an Office = 3600
The wattage for 1 Gallon Coffee Machines = 470
There is no
calculation for Electric Food Warmers
There is no calculation for Gas Food
Warmers
There is no calculation for Electric Fry Kettle
There is no
calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair
Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no
calculation for other appliances of known wattages
The Total Outside Fresh Air CFM = 240
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 32328.9
The Total Tons of HVAC needed = 2.694075