<SCN>SECTION 05 21 16</SCN><BRK/>
<BRK/>
<STL>LONGSPAN STEEL JOIST FRAMING</STL><BRK/>
<DTE>07/07</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>deep longspan steel 
joist framing and accessories</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable item(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use Section <SRF>05 21 23</SRF> for STEEL JOIST GIRDER FRAMING.  Use Section 
<SRF>05 21 19</SRF> for OPEN WEB STEEL JOIST FRAMING.  Use Section <SRF>05 21 13</SRF> for DEEP LONGSPAN 
STEEL JOIST FRAMING.<BRK/>
<BRK/>
Show the following information on the project drawings:</NPR><BRK/>
<BRK/>
<NPR>1.  Joist series and size, joist spacing, and kg (kip) load on each panel point, 
span, and slope.</NPR><BRK/>
<BRK/>
<NPR>2.  Design loads, including uplift and lateral forces in addition to gravity 
(dead and live) loads.</NPR><BRK/>
<BRK/>
<NPR>3.  Method of anchoring, framing at openings, spacing and type of bridging.</NPR><BRK/>
<BRK/>
<NPR>4.  Accessory details as applicable.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification.  The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
<BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
<BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>AMERICAN WELDING SOCIETY (AWS)</ORG><BRK/><BRK/><RID>AWS B2.1</RID><RTL>(2005; Errata 2006; Errata 2006) Welding Procedure and Performance Qualification</RTL><BRK/><BRK/><RID>AWS D1.1/D1.1M</RID><RTL>(2008) Structural Welding Code - Steel</RTL><BRK/><BRK/></REF><REF><ORG>STEEL JOIST INSTITUTE (SJI)</ORG><BRK/><BRK/><RID>SJI 279167 SPECS/LOADS</RID><RTL>(2006) 42nd Edition Standard Specifications and Load Tables for Steel Joists and Joist Girders</RTL><BRK/><BRK/><RID>SJI MANUAL</RID><RTL>(2003) 75 Year Manual, 1928-2003</RTL><BRK/><BRK/><RID>SJI TD 10</RID><RTL>(2003) Technical Digest for the Design of Fire Resistive Assemblies with Steel Joists</RTL><BRK/><BRK/><RID>SJI TD 8</RID><RTL>(1983) Technical Digest for the Welding of Open Web Steel Joists</RTL><BRK/><BRK/><RID>SJI TD 9</RID><RTL>(2006) Technical Digest for the Handling and Erection of Steel Joists and Joist Girders</RTL><BRK/><BRK/></REF><REF><ORG>THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)</ORG><BRK/><BRK/><RID>SSPC PS 14.01</RID><RTL>(1982; E 2004) Steel Joist Shop Painting System</RTL><BRK/><BRK/><RID>SSPC Paint 15</RID><RTL>(1999; E 2004) Steel Joist Shop Primer/Metal Building Primer</RTL><BRK/><BRK/></REF><REF><ORG>U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)</ORG><BRK/><BRK/><RID>29 CFR 1910.1200</RID><RTL>Hazard Communication</RTL><BRK/><BRK/><RID>29 CFR 1926</RID><RTL>Safety and Health Regulations for Construction</RTL><BRK/><BRK/><RID>29 CFR 1926.757</RID><RTL>Steel Erection; Open Web Steel Joists</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section <SRF>01 33 00</SRF> SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy, Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are for [Contractor Quality Control approval.][information only.  When used, a designation following the "G" 
designation identifies the office that will review the submittal for the Government.]  Submit the following in 
accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-01 Preconstruction Submittals</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Welder qualification</SUB></ITM><BRK/>
<ITM><SUB>Material Safety Data Sheet</SUB> (MSDS) in accordance with OSHA 1910.1200</ITM><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Longspan Steel Joist Framing</SUB>; <SUB>G</SUB></ITM><BRK/>
<BRK/>
<ITM>  Detailed drawings including fabrication and erection details, specifications for shop painting, 
and identification markings of joists [and joist girders].</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Erection inspection</SUB></ITM><BRK/>
<ITM><SUB>Welding inspections</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Accessories</SUB></ITM><BRK/>
<ITM><SUB>Certification of Compliance</SUB></ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   GENERAL REQUIREMENTS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The structural steel design must meet the requirements of OSHA Steel 
Erection Standard, 29 CFR Part 1926, Subpart R-Steel Erection, Effective Date 
January 18, 2002, and  29 CFR 1926.757.<BRK/>
<BRK/>
Drawings must show size, spacing and method of anchoring.  Indicate size by 
reference to appropriate SJI designations.  Mechanical and electrical layout 
drawings and specifications for ceiling suspensions must contain notes indicating 
that hanger loads between panel points in excess of 222 N (50 pounds) must have 
the excess hanger loads suspended from panel points.<BRK/>
<BRK/>
When joists or girders are to be designed to resist uplift and/or lateral forces, 
such joists and girders and the forces they must resist must be indicated on 
the drawings.  Also,indicate all proper anchorages and bracing designed to resist 
those forces, as required.<BRK/>
<BRK/>
The standard joist tables cannot be used verbatim when the depth of the joist 
is reduced near the ends to accommodate two-way top chord slopes in excess of 
10 mm per meter (l/8 inch per foot).  Before using standard designations for 
these joists, the designer must verify the adequacy of the joist members.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Designate Longspan Steel Joists on the drawings in accordance with the standard designations of the Steel Joist 
Institute.  Joists of other standard designations or joists with properties other than those shown may be substituted 
for the joists designated provided the structural properties are equal to or greater than those of the joists 
shown and provided all other specified requirements are met.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   REGULATORY REQUIREMENT</TTL><BRK/>
<BRK/>
<TXT>All longspan joist framing must conform to <RID>29 CFR 1926.757</RID>.  Secure all joist bridging and anchoring in place 
prior to the application of any construction loads.  Distribute temporary loads so that joist capacity is not 
exceeded.  Do not apply loads to bridging.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5   DELIVERY AND STORAGE</TTL><BRK/>
<BRK/>
<TXT>Handle, transport, and store joists [and joist girders] in a manner to prevent damage affecting their structural 
integrity.  Store all items off the ground in a well drained location protected from the weather and easily accessible 
for inspection and handling.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<TXT>All work must comply with the requirements set forth in <RID>29 CFR 1926</RID>.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.6.1   Drawing Requirements</TTL><BRK/>
<BRK/>
<TXT>Submit drawings for <SUB>longspan steel joist framing</SUB>.  Show joist type and size, layout in plan, and erection details 
including methods of anchoring, framing at openings, type and spacing of bridging, [requirements for field welding,] 
and details of <SUB>accessories</SUB> as applicable.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6.2   Certification of Compliance</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use the SJI MANUAL reference for projects involving existing joist girder 
and joist systems.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Prior to construction commencement, submit <SUB>Material Safety Data Sheet</SUB> in accordance with <RID>29 CFR 1910.1200</RID> for 
longspan steel joists , and certification for <SUB>welder qualification</SUB>, compliance with <RID>AWS B2.1</RID>, welding operation, 
and tacker, stating the type of welding and positions qualified for, the code and procedure qualified under, 
date qualified, and the firm and individual certifying the qualification tests.  Submit <SUB>certification of compliance</SUB>
 for the following:</TXT><BRK/>
<BRK/>
[<LST><RID>SJI MANUAL</RID></LST>]<BRK/>
<LST><RID>SJI TD 8</RID></LST><BRK/>
<LST><RID>SJI TD 9</RID></LST><BRK/>
<LST><RID>SJI TD 10</RID></LST><BRK/>
<LST><RID>29 CFR 1926</RID></LST><BRK/>
<LST><RID>29 CFR 1926.757</RID></LST><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   LONGSPAN STEEL JOISTS</TTL><BRK/>
<BRK/>
<TXT>Longspan steel joists must conform to <RID>SJI 279167 SPECS/LOADS</RID>, LH-Series.  Joists designated LH must be designed 
to support the loads given in the applicable standard load tables of <RID>SJI 279167 SPECS/LOADS</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2   ACCESSORIES AND FITTINGS</TTL><BRK/>
<BRK/>
<TXT>Accessories and fittings, including end supports and bridging, must be in accordance with the standard specifications 
under which the members were designed.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3   SHOP PAINTING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The requirements of the paragraph will be coordinated with the requirements 
of Section <SRF>09 90 00</SRF> PAINTS AND COATINGS.  In crawl spaces and other high humidity 
areas where greater protection than that provided by a primer paint is required 
and the joists or girders will not be finish painted, the paragraph will be 
revised to require that the joists or girders be shop painted with a corrosion 
resistant type paint as recommended by SSPC.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Longspan Joists [, joist girders] and accessories must be shop painted with a rust-inhibiting primer paint.  
For joists [and joist girders] which require finish painting under Section <SRF>09 90 00</SRF> PAINTS AND COATINGS, the 
primer paint must conform to <RID>SSPC Paint 15</RID> and <RID>SSPC PS 14.01</RID>.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   ERECTION</TTL><BRK/>
<BRK/>
<TXT>Installation of longspan joists [and joist girders] must conform to <RID>SJI 279167 SPECS/LOADS</RID> for the joist series 
indicated, and the requirements of <RID>29 CFR 1926</RID> and <RID>29 CFR 1926.757</RID>.  Handling and setting of joists [and joist 
girders] must  avoid damage to the members..  Damaged joists [and joist girders] must be removed from the site, 
except when field repair is approved and such repairs are satisfactorily made in accordance with the manufacturer's 
recommendations.  All welding must conform to <RID>AWS B2.1</RID> and <RID>AWS D1.1/D1.1M</RID>.</TXT><BRK/>
<BRK/></SPT>
[<SPT><TTL>3.2   BEARING PLATES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use this paragraph for masonry or cast-in-place concrete applications 
only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide bearing plates to accept full bearing after the supporting members have been plumbed and properly positioned, 
but prior to placing superimposed loads.  The area under the plate must be damp-packed solidly with bedding mortar, 
except where nonshrink grout is indicated on the drawings.  Bedding mortar and grout must be as specified in 
Section <SRF>03 31 00.00 10</SRF> CAST-IN-PLACE STRUCTURAL CONCRETE.</TXT><BRK/>
<BRK/></SPT>
]<SPT><TTL>3.3   PAINTING</TTL><BRK/>
<BRK/>
<SPT><TTL>3.3.1   Touch-Up Painting</TTL><BRK/>
<BRK/>
<TXT>After erection of joists [and joist girders], touch-up connections and areas of abraded shop coat with paint 
of the same type used for the shop coat.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.3.2   Field Painting</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Omit bracketed text when field painting is not required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Paint joists [and joist girders] requiring a finish coat in conformance with the requirements of Section 
<SRF>09 90 00</SRF> PAINTS AND COATINGS.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.4   VISUAL INSPECTIONS</TTL><BRK/>
<BRK/>
<TXT><TST><RID>AWS D1.1/D1.1M</RID>, Section 6.  Perform <SUB>erection inspection</SUB> and field <SUB>welding inspections</SUB> with AWS certified welding 
inspectors.  Welding inspectors must visually inspect and mark welds.</TST></TXT><BRK/>
<BRK/></SPT>
[<SPT><TTL>3.5   SCHEDULE</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete this paragraph for non-metric projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<MET><BRK/>
<TXT>SI dimensioning in this section is based on a mathematical conversion of inch-pound dimensions following the 
SJI specification <RID>SJI 279167 SPECS/LOADS</RID>.  The SI and I-P units for the dimensions shown are as follows.</TXT><BRK/>
<TBL><THD><BRK/>
                   <HL1>Inch-Pound Units</HL1>            <HL1>SI Units</HL1><BRK/></THD>
<BRK/>
                        20 feet                 6096 mm<BRK/>
                        30 ksi                  207 MPa<BRK/></TBL>
</MET></SPT>]<BRK/></PRT>