<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA      UFGS-07 21 13 (April 2006)<BRK/>
                                    ------------------------------<BRK/>
Preparing Activity:  <PRA>NAVFAC</PRA>         Replacing without change<BRK/>
                                    UFGS-07214 (August 2004)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 07 21 13</SCN><BRK/>
<BRK/>
<STL>BOARD AND BLOCK INSULATION</STL><BRK/>
<DTE>04/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>board and block 
thermal insulation</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification is intended for both retrofit of existing buildings 
and new construction.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify board-type insulations for masonry and concrete walls and under 
concrete floor slabs.  Also specify board-type insulation where the type of 
construction favors their economical usage and their application would be less 
difficult than blanket or loose fill insulations.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  On the drawings, show:</NPR><BRK/>
<BRK/>
<NPR>1.  Locations where insulation will be used.</NPR><BRK/>
<BRK/>
<NPR>2.  Thermal resistance value (R-Value) for each location.</NPR><BRK/>
<BRK/>
<NPR>3.  Location of vapor retarder, if required.</NPR><BRK/>
<BRK/>
<NPR>4.  Method of attachment of insulation board.</NPR><BRK/>
<BRK/>
<NPR>5.  Location and size of attic ventilation openings where required.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Attic Ventilation</NPR><BRK/>
<BRK/>
<NPR>1.  Provide net, unobstructed attic ventilation areas over insulated ceilings 
as recommended by ASHRAE Handbook of Fundamentals, Chapter 21, and as follows:</NPR><BRK/>
<BRK/>
<NPR>2.  For attics with vapor retarder, provide<MET> 0.1 square meter</MET><ENG> one square foot</ENG>
 of net ventilation area for each<MET> 30 square meters</MET><ENG> 300 square feet</ENG> of attic 
floor area.</NPR><BRK/>
<BRK/>
<NPR>3.  For attics without vapor retarder, provide<MET> 0.1 square meter</MET><ENG> one square foot</ENG>
 of net ventilation area for each<MET> 15 square meters</MET><ENG> 150 square feet</ENG> of attic 
floor area.</NPR><BRK/>
<BRK/>
<NPR>4.  For insulation of cathedral ceilings, provide at least a<MET> 50 mm</MET><ENG> 2 inch</ENG> gap 
between upper face of insulation and underside of roof sheathing.  Provide ventilation 
openings at bottom and top of ventilated cavity; show on drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM C 1289</RID><RTL>(2008) Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board</RTL><BRK/><BRK/><RID>ASTM C 165</RID><RTL>(2007) Standard Test Method for Measuring Compressive Properties of Thermal Insulations</RTL><BRK/><BRK/><RID>ASTM C 203</RID><RTL>(2005a) Breaking Load and Flexural Properties of Block-Type Thermal Insulation</RTL><BRK/><BRK/><RID>ASTM C 272</RID><RTL>(2001; R 2007) Water Absorption of Core Materials for Structural Sandwich Constructions</RTL><BRK/><BRK/><RID>ASTM C 552</RID><RTL>(2007) Standard Specification for Cellular Glass Thermal Insulation</RTL><BRK/><BRK/><RID>ASTM C 553</RID><RTL>(2008) Standard Specification for Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial Applications</RTL><BRK/><BRK/><RID>ASTM C 578</RID><RTL>(2008b) Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation</RTL><BRK/><BRK/><RID>ASTM C 591</RID><RTL>(2008) Standard Specification for Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation</RTL><BRK/><BRK/><RID>ASTM C 612</RID><RTL>(2004e1) Mineral Fiber Block and Board Thermal Insulation</RTL><BRK/><BRK/><RID>ASTM C 930</RID><RTL>(2005) Potential Health and Safety Concerns Associated with Thermal Insulation Materials and Accessories</RTL><BRK/><BRK/><RID>ASTM D 1621</RID><RTL>(2004a) Compressive Properties of Rigid Cellular Plastics</RTL><BRK/><BRK/><RID>ASTM D 3833/D 3833M</RID><RTL>(1996; R 2006) Water Vapor Transmission of Pressure-Sensitive Tapes</RTL><BRK/><BRK/><RID>ASTM D 4397</RID><RTL>(2008) Standard Specification for Polyethylene Sheeting for Construction, Industrial, and Agricultural Applications</RTL><BRK/><BRK/><RID>ASTM D 828</RID><RTL>(1997; R 2002) Tensile Properties of Paper and Paperboard Using Constant-Rate-of-Elongation Apparatus</RTL><BRK/><BRK/><RID>ASTM E 136</RID><RTL>(2004) Behavior of Materials in a Vertical Tube Furnace at 750 Degrees C</RTL><BRK/><BRK/><RID>ASTM E 154</RID><RTL>(2008a) Water Vapor Retarders Used in Contact with Earth Under Concrete Slabs, on Walls, or as Ground Cover</RTL><BRK/><BRK/><RID>ASTM E 84</RID><RTL>(2008a) Standard Test Method for Surface Burning Characteristics of Building Materials</RTL><BRK/><BRK/><RID>ASTM E 96/E 96M</RID><RTL>(2005) Standard Test Methods for Water Vapor Transmission of Materials</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 211</RID><RTL>(2006) Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances</RTL><BRK/><BRK/><RID>NFPA 31</RID><RTL>(2006; Errata 2006; Errata 2007) Installation of Oil Burning Equipment</RTL><BRK/><BRK/><RID>NFPA 54</RID><RTL>(2008) National Fuel Gas Code</RTL><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/></REF><REF><ORG>TECHNICAL ASSOCIATION OF THE PULP AND PAPER INDUSTRY (TAPPI)</ORG><BRK/><BRK/><RID>TAPPI T803 OM</RID><RTL>(2006) Puncture Test of Container Board</RTL><BRK/><BRK/></REF><REF><ORG>U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)</ORG><BRK/><BRK/><RID>29 CFR 1910.134</RID><RTL>Respiratory Protection</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Block or board insulation</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Vapor retarder</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Pressure sensitive tape</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Protection board or coating</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Accessories</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-08 Manufacturer's Instructions</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Block or Board Insulation</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Adhesive</SUB></ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   DELIVERY, STORAGE, AND HANDLING</TTL><BRK/>
<BRK/>
<SPT><TTL>1.3.1   Delivery</TTL><BRK/>
<BRK/>
<TXT>Deliver materials to the site in original sealed wrapping bearing manufacturer's name and brand designation, 
specification number, type, grade, R-value, and class.  Store and handle to protect from damage.  Do not allow 
insulation materials to become wet, soiled, crushed, or covered with ice or snow.  Comply with manufacturer's 
recommendations for handling, storing, and protecting of materials before and during installation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3.2   Storage</TTL><BRK/>
<BRK/>
<TXT>Inspect materials delivered to the site for damage; unload and store out of weather in manufacturer's original 
packaging.  Store only in dry locations, not subject to open flames or sparks, and easily accessible for inspection 
and handling.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.4   SAFETY PRECAUTIONS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include the first paragraph below only for installations in which mineral 
fibers are released into the atmosphere, such as where mineral fiber boards 
are cut on the job site.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT>[<TTL>1.4.1   Respirators</TTL><BRK/>
<BRK/>
<TXT>Provide installers with dust/mist respirators, training in their use, and protective clothing, all approved by 
National Institute for Occupational Safety and Health (NIOSH)/Mine Safety and Health Administration (MSHA) in 
accordance with <RID>29 CFR 1910.134</RID>.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>1.4.2   Other Safety Considerations</TTL><BRK/>
<BRK/>
<TXT>Consider safety concerns and measures as outlined in <RID>ASTM C 930</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   <SUB>BLOCK OR BOARD INSULATION</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select type of insulation board based on job and application requirements 
regarding strength, vapor retardancy, and water absorption, and on manufacturer's 
recommendations.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide only thermal insulating materials recommended by manufacturer for type of application indicated.  Provide 
board or block thermal insulation conforming to the following standards and the physical properties listed below:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">[a.  Cellular Glass:  <RID>ASTM C 552</RID>]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Extruded Preformed Cellular Polystyrene:  <RID>ASTM C 578</RID>]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[c.  Mineral Fiber Block and Board:  <RID>ASTM C 612</RID>]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[d.  Unfaced Preformed Rigid Polyurethane and Polyisocyanurate Board: <RID>ASTM C 591</RID>]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[e.  Faced Rigid Cellular Polyisocyanurate and Polyurethane Insulation: <RID>ASTM C 1289</RID>]</ITM><BRK/>
<BRK/>
<ITM>[1.  Type I Aluminum Foil on both major surfaces.  [Class 1 - Non-reinforced core foam.]  [Class 
2 - Glass fiber reinforced core.]]</ITM><BRK/>
<BRK/>
<ITM>[2.  Type II Fibrous felt or glass fiber mat membrane on both major surfaces of the core foam.]</ITM><BRK/>
<BRK/>
<ITM>[3.  Type III Perlite insulation board on one major surface of the core foam and a fibrous felt 
or glass fiber mat membrane on the other major surface of the core foam.]</ITM><BRK/>
<BRK/>
<ITM>[4.  Type IV Cellulosic fiber insulating board on the one major surface of the core foam and 
fibrous felt or glass fiber mat membrane on the other major surface of the core foam.]</ITM><BRK/>
<BRK/>
<ITM>[5.  Type V Oriented strand board or water-board on one major surface of the core foam and fibrous 
felt or glass fiber mat membrane or aluminum foil on the other major surface of the core foam.]</ITM><BRK/>
<BRK/>
<ITM>[6.  Type VI Perlite insulation board on both major surfaces of the core foam.]</ITM><BRK/>
<BRK/>
<SPT><TTL>2.1.1   Thermal Resistance</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Board and block thermal insulating materials have different thermal properties.  
Specify insulation to provide the R-Value required to meet the energy budget 
indicated in MIL-HDBK-1190, Facility Planning Design Guide.  Indicate R-values 
on the project drawings.  If not, specify in the appropriate blanks.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where board insulation is installed in masonry cavity walls, the wall 
cavity must be sized to accommodate the insulation thickness required to provide 
the specified R-Value and a<MET> 25 mm</MET><ENG> one inch</ENG> free air space.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[As indicated] [Ceiling [R-_____] Wall [R-_____] Floor [R-_____]].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   Fire Protection Requirement</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Fire Safety Provisions</NPR><BRK/>
<BRK/>
<NPR>1.  Most vapor retarder materials and some thermal insulations are combustible.  
Do not leave such material exposed to accessible spaces, but cover with fire 
retardant finish.</NPR><BRK/>
<BRK/>
<NPR>2.  See MIL-HDBK-1008, and local building code for fire retardant classifications 
required, flame spread and smoke developed ratings and distance of insulation 
and vapor retarder from heat producing devices and other fire protection requirements, 
such as finish materials required in various occupancies.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Do not use cellular plastic insulation exposed to the interior.  Separate 
the insulation from the interior by at least a 15 minute fire separation.  If 
no separation is provided, select cellular glass block insulation.  Edit this 
paragraph and the paragraph entitled "Insulation on Vertical Surfaces" as required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">[a.  Flame spread index of [75] [100] [_____] or less when tested in accordance with <RID>ASTM E 84</RID>
.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Smoke developed index of [200] [150] [_____] or less when tested in accordance with <RID>ASTM E 84</RID>
.]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.3   Other Material Properties</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include only those properties that are required for the particular application.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide thermal insulating materials with the following properties:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">[a.  Rigid cellular plastics:  Compressive Resistance at Yield:  Not less than<MET> [170] [_____] 
kilopascals (kPa)</MET><ENG> [10] [_____] pounds per square inch (psi)</ENG> when measured according to <RID>ASTM D 1621</RID>
.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Mineral fiber board:  Compressive strength:  Minimum load required to produce a reduction 
in thickness of 10 percent,<MET> kg/m2</MET><ENG> lbf/sft</ENG>: <MET> [120] [4900]</MET><ENG> [25] [1000]</ENG> when tested according to <RID>
ASTM C 165</RID>.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Flexural strength:  Not less than<MET> [275] [_____] kPa</MET><ENG> [25] [_____]  psi</ENG> when measured according 
to <RID>ASTM C 203</RID>.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[c.  Water Vapor Permeance:  Not more than<MET> [6.3 x 10-8] [_____] g/Pa.s.m2</MET><ENG> [1.1] [_____] Perms</ENG>
 or less when measured according to <RID>ASTM E 96/E 96M</RID>, desiccant method, in the thickness required 
to provide the specified thermal resistance, including facings, if any.]</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify allowable moisture content for rigid cellular plastic as absorption 
and for mineral fiber board as adsorption.  Delete d. or e. below if only one 
material is allowed.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">[d.  Water Absorption:  Not more than [2] [_____] percent by total immersion, by volume, when 
measured according to <RID>ASTM C 272</RID>.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[e.  Water Adsorption:  Not more than [1] [_____] percent by volume when measured in accordance 
with paragraph 14 of <RID>ASTM C 553</RID>.]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.4   Premolded Concrete Masonry Insert</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM C 578</RID>.  Install inserts in concrete masonry units at the masonry unit manufacturing plant.  Provide insert 
with thickness not less than<MET> 32 mm</MET><ENG> 1 1/4 inches</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.5   Recycled Materials</TTL><BRK/>
<BRK/>
<TXT>Provide thermal insulation containing recycled materials to the extent practicable, provided that the material 
meets all other requirements of this section.  The minimum required recycled material contents (by weight, not 
volume) are:</TXT><BRK/>
<BRK/>
<TXT>Polyisocyanurate/Polyurethane:  9 percent</TXT><BRK/>
<TXT>Phenolic Rigid Foam :           5 percent</TXT><BRK/>
<TXT>Perlite Board:                 23 percent</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.6   Prohibited Materials</TTL><BRK/>
<BRK/>
<TXT>Do not provide materials containing more than one percent of asbestos.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>2.2   <SUB>VAPOR RETARDER</SUB> AND DAMPPROOFING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:</NPR><BRK/>
<BRK/>
<NPR>1.  Determine the need for a water vapor retarder and its required permeance 
value based on a project and climate specific moisture analysis.  For guidance 
see ASHRAE Handbook of Fundamentals, Chapter 20, "Thermal Insulations and Vapor 
Retarders;" ASTM C 755, "Selection of Vapor Retarders for Thermal Insulations;" 
and MIL-HDBK-1011/1, "Tropical Engineering" (for humid climates).  The computer 
Program "MOIST" which is on CCB, is a user friendly tool based on hourly weather 
data that provides information on moisture content of materials and on the duration 
of high moisture content excursions. Traditionally, vapor retarders were considered 
materials having a permeance of<MET> 5.72 x 10-8 g/Pa.s.m2</MET><ENG> 1 perm (grain/h*ft2*in.Hg)</ENG>
 or less.  However, that value may not be adequate for the particular construction 
or climate and in some instances a much lower value should be specified.</NPR><BRK/>
<BRK/>
<NPR>2.  Vapor retarders, where required, can be provided as membranes or, alternatively, 
vapor retardant finishes labeled by manufacturer as having a water vapor permeance 
of no more than the required value can be used.  Alternate materials include:  
Paints, vinyl wall coverings, or foil-faced gypsum board. Specify these in Sections 
09 90 00, PAINTS AND COATINGS, Section 09 72 00, WALLCOVERINGS, or Section 09 
29 00, GYPSUM BOARD, respectively and delete all paragraphs and references relating 
to vapor retarders from this section.</NPR><BRK/>
<BRK/>
<NPR>3.  A vapor retarder is only effective if it prevents diffusion of water vapor 
as well as the passage of moisture laden air through openings and around material.  
Accordingly, proper installation to assure air tightness by sealing of joints, 
tears, and around utility penetrations is as important as proper selection of 
water vapor retarder materials.</NPR><BRK/>
<BRK/>
<NPR>4.  Vapor retarders not only retard movement of water vapor into building envelope 
cavities, but also retard drying out of moisture that may have infiltrated the 
cavity.  Accordingly, use vapor retarders only where their need is indicated 
by the moisture analysis.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.2.1   Vapor Retarder in Frame Walls and Roofs</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">[a. <MET> 0.15 mm</MET><ENG> 6 mil</ENG> thick polyethylene sheeting conforming to <RID>ASTM D 4397</RID> and having a water 
vapor permeance of<MET> 5.72 x 10-8g/Pa.s.m2</MET><ENG> one perm</ENG> or less when tested in accordance with <RID>ASTM E 96/E 96M</RID>
.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Membrane with the following properties:</ITM><BRK/>
<BRK/>
<ITM>Water Vapor Permeance:  <RID>ASTM E 96/E 96M</RID>: <MET> 5.72 x 10-8 g/Pa.s.m2</MET><ENG> [1] [_____] perm</ENG></ITM><BRK/>
<ITM>Maximum Flame Spread:  <RID>ASTM E 84</RID>:  [25] [50] [_____]</ITM><BRK/>
<ITM>Combustion Characteristics:  Passing <RID>ASTM E 136</RID></ITM><BRK/>
<ITM>Puncture Resistance:  <RID>TAPPI T803 OM</RID>:  [15] [25] [50]</ITM><BRK/>
<ITM>Tensile Strength:  <RID>ASTM D 828</RID>:  [15] [20] [35]]</ITM><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.2.2   Dampproofing for Masonry Cavity Walls</TTL><BRK/>
<BRK/>
<TXT>[Bituminous material is specified in Section <SRF>07 11 13</SRF> BITUMINOUS DAMPPROOFING.] [Parging material is specified 
in Section <SRF>04 20 00</SRF> MASONRY.]</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.3   Vapor Retarder under Floor Slab</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Water vapor permeance:  <MET> 1.14 x 10-8 g/Pa.s.m2</MET><ENG> 0.2 Perm</ENG> or less when tested in accordance 
with <RID>ASTM E 96/E 96M</RID>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Puncture resistance:  Maximum load no less than<MET> 18 kilograms</MET><ENG> 40 pounds</ENG> when tested according 
to <RID>ASTM E 154</RID>.</ITM><BRK/>
<BRK/>
]</SPT>]</SPT><SPT><TTL>2.3   <SUB>PRESSURE SENSITIVE TAPE</SUB></TTL><BRK/>
<BRK/>
<TXT>As recommended by manufacturer of vapor retarder and having a water vapor permeance rating of<MET> 5.72 x 10-8 g/Pa.s.m2</MET><ENG>
 one perm</ENG> or less when tested in accordance with <RID>ASTM D 3833/D 3833M</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4   <SUB>PROTECTION BOARD OR COATING</SUB></TTL><BRK/>
<BRK/>
<TXT>As recommended by insulation manufacturer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5   <SUB>ACCESSORIES</SUB></TTL><BRK/>
<BRK/>
<SPT><TTL>2.5.1   <SUB>Adhesive</SUB></TTL><BRK/>
<BRK/>
<TXT>As recommended by insulation manufacturer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.2   Mechanical Fasteners</TTL><BRK/>
<BRK/>
<TXT>Corrosion resistant fasteners as recommended by the insulation manufacturer.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   EXISTING CONDITIONS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>Note:  For retrofit projects, inspect facility to determine conditions which 
may adversely affect execution of work or create safety hazard.  Identify relevant 
conditions on the drawings and, if required, develop additional specification 
sections for corrective actions.  Conditions that warrant investigation:</NPR><BRK/>
<BRK/>
<NPR>1.  Discolorations or mold growth indicating previous water leaks.</NPR><BRK/>
<BRK/>
<NPR>2.  Heat producing devices, such as recessed lighting fixtures, chimneys, and 
flues.</NPR><BRK/>
<BRK/>
<NPR>3.  Faulty electrical systems:</NPR><BRK/>
<BRK/>
<NPR>(a)  Lights dimming or flickering</NPR><BRK/>
<BRK/>
<NPR>(b)  Fuses blowing</NPR><BRK/>
<BRK/>
<NPR>(c)  Circuit breakers tripping frequently</NPR><BRK/>
<BRK/>
<NPR>(d)  Electrical sparks and "glowing" from receptacles</NPR><BRK/>
<BRK/>
<NPR>(e)  Cover plates on switches and outlets warm to touch.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Before installing insulation, ensure that all areas that will be in contact with the insulation are dry and free 
of projections which could cause voids, compressed insulation, or punctured vapor retarders.  If installing perimeter 
or under slab insulation, check that the fill is flat, smooth, dry, and well tamped. If moisture or other conditions 
are found that do not allow the proper installation of the insulation, do not proceed but notify the Contracting 
Officer of such conditions.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   PREPARATION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.2.1   Blocking Around Heat Producing Devices</TTL><BRK/>
<BRK/>
<TXT>Unless using insulation board that passes <RID>ASTM E 136</RID> in addition to the requirements in Part 2, install non-combustible 
blocking around heat producing devices to provide the following clearances:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Recessed lighting fixtures, including wiring compartments, ballasts, and other heat producing 
devices, unless certified for installation surrounded by insulation: <MET> 75 mm</MET><ENG> 3 inches</ENG> from outside 
face of fixtures and devices or as required by <RID>NFPA 70</RID>and, if insulation is to be placed above 
fixture or device,<MET> 600 mm</MET><ENG> 24 inches</ENG> above fixture.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Masonry chimneys or masonry enclosing a flue: <MET> 50 mm</MET><ENG> 2 inches</ENG> from outside face of masonry.  
Masonry chimneys for medium and high heat operating appliances:  Minimum clearances required 
by <RID>NFPA 211</RID>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Vents and vent connectors used for venting products of combustion, flues, and chimneys other 
than masonry chimneys:  minimum clearances as required by <RID>NFPA 211</RID>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Gas Fired Appliances:  Clearances as required in <RID>NFPA 54</RID>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Oil Fired Appliances:  Clearances as required in <RID>NFPA 31</RID>.</ITM><BRK/>
<BRK/>
<TXT>Blocking is not required if chimneys or flues are certified by the Manufacturer for use in contact with insulating 
materials.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.3   INSTALLATION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.3.1   Insulation Board</TTL><BRK/>
<BRK/>
<TXT>Install and handle insulation in accordance with the manufacturer's installation instructions.  Keep material 
dry and free of extraneous materials.  Observe safe work practices.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.2   Electrical Wiring</TTL><BRK/>
<BRK/>
<TXT>Do not install insulation in a manner that would sandwich electrical wiring between two layers of insulation.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.3.3   Cold Climate Requirement</TTL><BRK/>
<BRK/>
<TXT>Place insulation to the outside of pipes.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.3.4   Continuity of Insulation</TTL><BRK/>
<BRK/>
<TXT>Butt tightly against adjoining boards, studs, rafters, joists, sill plates, headers and obstructions.  Provide 
continuity and integrity of insulation at corners, wall to ceiling joint, roof, and floor.  Avoid creating any 
thermal bridges or voids.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Foil sided board reflects heat. Indicate on drawings the side on which 
the foil is to be faced. Coordinate use with mechanical designer.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/></SPT>
</SPT><SPT><TTL>3.4   INSTALLATION ON WALLS</TTL><BRK/>
<BRK/>
<SPT><TTL>3.4.1   Installation using Furring Strips</TTL><BRK/>
<BRK/>
<TXT>Install insulation [between] [on] members as recommended by insulation manufacturer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4.2   Installation on Masonry Walls</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use the first paragraph below for insulation on the outside or inside 
of masonry walls.  Use the second paragraph for insulating individual masonry 
units within their hollow cores.  Insulating the cores only can lead to thermal 
bridges and condensation at the web locations of the masonry units.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Apply board directly to masonry with adhesive or fasteners as recommended by the insulation manufacturer.  Fit 
between obstructions without impaling board on ties or anchors.  Apply in parallel courses with joints breaking 
midway over course below.  Put ends in moderate contact with adjoining insulation without forcing.  Cut and shape 
as required to fit around wall penetrations, projections or openings to accommodate conduit or other services.  
Seal around cut-outs with sealant.  Install board in wall cavities so that it leaves at least a nominal<MET> 25 mm</MET><ENG>
 one inch</ENG> free air space outside of the insulation to allow for cavity drainage.]</TXT><BRK/>
<BRK/>
<TXT>[Insert premolded or board insulation into masonry unit hollow cores as recommended by the insulation manufacturer.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4.3   Adhesive Attachment to Concrete and Masonry Walls</TTL><BRK/>
<BRK/>
<TXT>Apply adhesive to wall and completely cover wall with insulation.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">[a.  Full back bed method] [or]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Spot method:  Provide at least six spots having diameter of approximately<MET> 100 mm</MET><ENG> 4 inches</ENG>
, located at each corner and mid-points of each of the longer sides of each board.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[c.  As recommended by the insulation manufacturer].</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Use only full back method for pieces of<MET> 0.1 square meter</MET><ENG> one square foot</ENG> or less.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Butt all edges of insulation and seal edges with tape.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4.4   Mechanical Attachment on Concrete and Masonry Walls</TTL><BRK/>
<BRK/>
<TXT>Cut insulation to cover walls.  Apply adhesive to wall and set clip or other mechanical fastener in adhesive 
as recommended by manufacturer.  After curing of adhesive, install insulation over fasteners, bend split prongs 
flush with insulation.  Butt all edges of insulation and seal with tape.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.4.5   Protection Board or Coating</TTL><BRK/>
<BRK/>
<TXT>Install protection board or coating in accordance with manufacturer's instructions.  Install protection over 
all exterior exposed insulation board and down to<MET> 300 mm</MET><ENG> 1 foot</ENG> below grade.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.5   INSTALLATION ON UNDERSIDE OF CONCRETE FLOOR SLAB</TTL><BRK/>
<BRK/>
<SPT>[<TTL>3.5.1   Mechanically Fastened Systems</TTL><BRK/>
<BRK/>
<TXT>Size insulation to cover underside of slab.  Apply adhesive to slab and set fasteners in adhesive as recommended 
by manufacturer.  After curing of adhesive, install insulation over fasteners, bend split prongs flush with insulation.  
Butt all edges of insulation and seal with tape.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.5.2   Adhesively Bonded Systems</TTL><BRK/>
<BRK/>
<TXT>Apply adhesive to underside of the and completely cover wall with insulation.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">[a.  Full back bed method] [or]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Spot method:  Provide at least six spots having a diameter of approximately<MET> 100 mm</MET><ENG> 4 inches</ENG>
, located at each corner and mid-point of each of the longer sides.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[c.  As recommended by insulation manufacturer].</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Use full back method for insulation pieces<MET> 0.1 square meter</MET><ENG> one square foot</ENG> or less.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Butt all edges of insulation and seal with tape.</ITM><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.6   PERIMETER AND UNDER SLAB INSULATION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide for and coordinate foundation draining as required by insulation 
manufacturer.</NPR><BRK/>
<BRK/>
<NPR>Provide R-Values and extent as indicated in the following Table EXTENT AND R-VALUE 
FOR PERIMETER AND UNDER-SLAB THERMAL INSULATION.</NPR><BRK/>
<BRK/>
<MET><TBL><THD><BRK/>
 <HL4>EXTENT AND R-VALUE FOR PERIMETER AND UNDER-SLAB THERMAL INSULATION</HL4><BRK/></THD>
<BRK/>
_______________________________________________________________________<BRK/>
|Weather  |          Minimum Required R-Values For Perimeter          |<BRK/>
|Region by|             Insulation per Position and Width             |<BRK/>
|Heating  |___________________________________________________________|<BRK/>
|Degree   |       Unheated Slab         |       Heated Slab           |<BRK/>
|Days     |___________________________________________________________|<BRK/>
|(Base    | Millimeters  | Millimeters  | Millimeters  | Millimeters  |<BRK/>
|18 deg.C |  Vertical    |  Horizontal  |  Vertical    |  Horizontal  |<BRK/>
|         |___________________________________________________________|<BRK/>
|         |600 |900 |1200|600 |900 |1200|600 |900 |1200|600 |900 |1200|<BRK/>
|_____________________________________________________________________|<BRK/>
| Over    | NP | NP |1.06| NP | NP |2.64| NP | NP |1.41| NP | NP |2.99|<BRK/>
| 4150    | *  | *  |    | *  | *  |    | *  | *  |    | *  | *  |    |<BRK/>
|_____________________________________________________________________|<BRK/>
| 3601 to |1.41|1.06| .70|3.17|2.71|1.97|1.76|1.41|1.06|3.52|3.06|2.32|<BRK/>
| 4150    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
| 3046 to |1.41|1.06| .70|3.17|2.71|1.97|1.76|1.41|1.06|3.52|3.06|2.32|<BRK/>
| 3600    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
| 2491 to |1.41|1.06| .70|3.17|2.71|1.97|1.76|1.41|1.06|3.52|3.06|2.32|<BRK/>
| 3045    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
| 1941 to |1.41|1.06| .70|3.17|2.71|1.97|1.76|1.41|1.06|3.52|3.06|2.32|<BRK/>
| 2490    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
| 1526 to |1.34|1.02| .70|2.99|2.46|1.90|1.69|1.37|1.06|3.34|2.82|2.25|<BRK/>
| 1940    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
| 1111 to |1.27| .99| .70|2.69|2.32|1.80|1.62|1.34|1.02|3.04|2.68|2.15|<BRK/>
| 1525    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
|  556 to |1.13| .85| .70|2.18|1.87|1.51|1.48|1.20|1.06|2.53|2.22|1.87|<BRK/>
|  1110 **|    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
|  0 to   |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |<BRK/>
|  555    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
|  0 to   |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |<BRK/>
|  555    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
|  556 to |1.13| .85| .70|2.18|1.87|1.51|1.48|1.20|1.06|2.53|2.22|1.87|<BRK/>
|  1110 **|    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
______________________________________________________________________|<BRK/>
<BRK/>
*  NP:  Not Permitted<BRK/>
<BRK/>
** Perimeter Insulation is not required in weather regions 8 and 11 where     there are less than 830 Heating 
Degree Days (18 degrees C).<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
  <HL4>EXTENT AND R-VALUE FOR PERIMETER AND UNDER-SLAB THERMAL INSULATION</HL4><BRK/></THD>
<BRK/>
_______________________________________________________________________<BRK/>
|Weather  |         Minimum Required R-Values For Perimeter           |<BRK/>
|Region by|            Insulation per Position and Width              |<BRK/>
|Heating  |___________________________________________________________|<BRK/>
|Degree   |        Unheated Slab        |         Heated Slab         |<BRK/>
|Days     |___________________________________________________________|<BRK/>
|(Base    |    Inches    |    Inches    |    Inches    |    Inches    |<BRK/>
|65 deg.F)|   Vertical   |  Horizontal  |   Vertical   |  Horizontal  |<BRK/>
|         |___________________________________________________________|<BRK/>
|         | 24 | 36 | 48 | 24 | 36 | 48 | 24 | 36 | 48 | 24 | 36 | 48 |<BRK/>
|_____________________________________________________________________|<BRK/>
|Over     | NP | NP | 6.0| NP | NP |15.0| NP | NP | 8.0| NP | NP |17.0|<BRK/>
|15000    | *  | *  |    | *  | *  |    | *  | *  |    | *  | *  |    |<BRK/>
|_____________________________________________________________________|<BRK/>
|13001    | 8.0| 6.0| 4.0|18.0|15.4|11.2|10.0| 8.0| 6.0|20.0|17.4|13.2|<BRK/>
|15000    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
|11001 to | 8.0| 6.0| 4.0|18.0|15.4|11.2|10.0| 8.0| 6.0|20.0|17.4|13.2|<BRK/>
|13000    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
| 9001 to | 8.0| 6.0| 4.0|18.0|15.4|11.2|10.0| 8.0| 6.0|20.0|17.4|13.2|<BRK/>
|11000    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
| 7001 to | 8.0| 6.0| 4.0|18.0|15.4|11.2|10.0| 8.0| 6.0|20.0|17.4|13.2|<BRK/>
| 9000    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
| 5501 to | 7.6| 5.8| 4.0|17.0|14.0|10.8| 9.6| 7.8| 6.0|19.0|16.0|12.8|<BRK/>
| 7000    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
| 4001 to | 7.2| 5.6| 4.0|15.3|13.2|10.2| 9.2| 7.6| 6.0|17.3|15.2|12.2|<BRK/>
| 5500    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
| 2001 to | 6.4| 4.8| 4.0|12.4|10.6| 8.6| 8.4| 6.8| 6.0|14.4|12.6|10.6|<BRK/>
| 4000 ** |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
| 0 to    |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |<BRK/>
| 2000    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
| 0 to    |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |  0 |<BRK/>
| 2000    |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
|_____________________________________________________________________|<BRK/>
| 2001 to | 6.4| 4.8| 4.0|12.4|10.6| 8.6| 8.4| 6.8| 6.0|14.4|12.6|10.6|<BRK/>
| 4000 ** |    |    |    |    |    |    |    |    |    |    |    |    |<BRK/>
_______________________________________________________________________<BRK/>
<BRK/>
*  NP:  Not Permitted<BRK/>
<BRK/>
** Perimeter Insulation is not required in weather regions 8 and 11 where there are less than 3000 Heating Degree 
Days (65 degrees F).<BRK/></TBL>
</ENG><AST/><BRK/></NTE>
<BRK/>
<TXT>Install perimeter thermal insulation where heated spaces are adjacent to exterior walls or slab edges in slab-on-grade 
or floating-slab construction.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.6.1   Manufacturer's Instructions</TTL><BRK/>
<BRK/>
<TXT>Install, attach, tape edges, provide vapor retarder and other requirements such as protection against vermin, 
insects, damage during construction as recommended in manufacturer's instructions.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.6.2   Insulation on Vertical Surfaces</TTL><BRK/>
<BRK/>
<TXT>Install thermal insulation [as indicated.] [on exterior of foundation walls] [on grade beams] [partially] [below 
grade] [and] [on edges of slabs on grade.]  Fasten insulation with [adhesive] [or] [mechanical fasteners].</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.6.3   Insulation Under Slab</TTL><BRK/>
<BRK/>
<TXT>Provide insulation horizontally under [entire] slab on grade [for a distance of [_____]<MET> mm</MET><ENG> feet</ENG> from the edge 
of slab] [as indicated].  [Turn insulation up at slab edge, and extend full height of slab.]  Install insulation 
on top of vapor retarder and turn retarder up over the outside edge of insulation to top of slab.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.6.4   Protection of Insulation</TTL><BRK/>
<BRK/>
<TXT>Protect insulation on vertical surfaces from damage during construction and back filling by application of protection 
board or coating.  Do not leave installed vertical insulation unprotected overnight.  [Install protection over 
entire exposed exterior insulation board.]  [Provide protection extending at least<MET> 300 mm</MET><ENG> one foot</ENG> below grade.]</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT>[<TTL>3.7   VAPOR RETARDER</TTL><BRK/>
<BRK/>
<TXT>Apply a continuous vapor retarder as indicated.  Overlap all joints at least<MET> 150 mm</MET><ENG> 6 inches</ENG> and seal with pressure 
sensitive tape.  Seal at sill, header, windows, doors and utility penetrations.  Repair punctures or tears with 
pressure sensitive tape.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.8   ACCESS PANELS AND DOORS</TTL><BRK/>
<BRK/>
<TXT>Affix insulation to all access panels greater than<MET> 0.1 square meter</MET><ENG> one square foot</ENG> and all access doors in insulated 
floors and ceilings.  Use insulation with same R-Value as that for floor or ceiling.</TXT><BRK/>
<BRK/>
]</SPT></PRT>    <END/><BRK/></SEC>