<SCN>SECTION 08 53 00</SCN><BRK/>
<BRK/>
<STL>PLASTIC WINDOWS</STL><BRK/>
<DTE>07/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>residential, commercial 
and heavy commercial grade prime and replacement PVC windows</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify the following items of related work under other sections of the 
specifications:</NPR><BRK/>
<BRK/>
<NPR>1.  Glass and glazing and the furnishing of glazing clips and gaskets.</NPR><BRK/>
<BRK/>
<NPR>2.  Calking and sealants.</NPR><BRK/>
<BRK/>
<NPR>3.  Structural building supports at window mullions.</NPR><BRK/>
<BRK/>
<NPR>4.  Wood or metal subframes for windows in frame walls.</NPR><BRK/>
<BRK/>
<NPR>5.  Drilling and tapping for attachment of window shades, drapery rods, and 
venetian blinds.  The drilling and tapping of window frames to receive brackets 
for shades, venetian blinds, and curtain rods has been omitted from this specification.  
It is contemplated that this work will be done after erection of windows by 
the trade for the item to be installed.  On projects where factory drilling 
for these items is required, revise this specification accordingly.</NPR><BRK/>
<BRK/>
<NPR>6.  Brackets and supports for window shades, drapery rods, and venetian blinds.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  On the drawings, show:</NPR><BRK/>
<BRK/>
<NPR>1.  Sizes and types of windows; subframes, casings, stools, and hardware.</NPR><BRK/>
<BRK/>
<NPR>2.  Sizes, location, and swing of ventilators; direction of slide for sliding 
ventilators; location and details of fixed sash.</NPR><BRK/>
<BRK/>
<NPR>3.  Typical window sections and details.  Show glass thickness and air spaces 
of insulating glass. Show special glazing, if any.</NPR><BRK/>
<BRK/>
<NPR>4.  Method of anchoring windows to adjoining construction; size and types of 
clips, anchors, screws, and other fasteners.</NPR><BRK/>
<BRK/>
<NPR>5.  Details of nonstructural mullions and mullion covers; details of anchoring 
and reinforcing nonstructural mullions at windows to receive window cleaner 
anchors.  Details of transom bars.</NPR><BRK/>
<BRK/>
<NPR>6.  Number of window cleaner anchors required and locations.</NPR><BRK/>
<BRK/>
<NPR>7.  Types and details of accessories to be furnished, such as, trim, screens, 
grills, and integral venetian blinds.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Issue (date) of references included in project specifications need not 
be more current than provided by the latest guide specification.  Use of SpecsIntact 
automated reference checking is recommended for projects based on older guide 
specifications.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)</ORG><BRK/><BRK/><RID>AAMA 101</RID><RTL>(2005) Standard Specification for Windows, Doors, and Unit Skylights</RTL><BRK/><BRK/><RID>AAMA 1503</RID><RTL>(1998) Voluntary Test Method for Thermal Transmittance and Condensation Resistance of Windows, Doors and Glazed Wall Sections</RTL><BRK/><BRK/></REF><REF><ORG>ASME INTERNATIONAL (ASME)</ORG><BRK/><BRK/><RID>ASME A39.1</RID><RTL>(1995) Safety Requirements for Window Cleaning</RTL><BRK/><BRK/></REF><REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM D 1972</RID><RTL>(1997; R 2005) Standard Practice for Generic Marking of Plastic Products</RTL><BRK/><BRK/><RID>ASTM D 3656</RID><RTL>(2007) Insect Screening and Louver Cloth Woven from Vinyl-Coated Glass Yarns</RTL><BRK/><BRK/><RID>ASTM D 4099</RID><RTL>(1995) Poly(Vinyl Chloride) (PVC) Prime Windows and Sliding Glass Doors</RTL><BRK/><BRK/><RID>ASTM E 2129</RID><RTL>(2005) Standard Practice for Data Collection for Sustainability Assessment of Building Products</RTL><BRK/><BRK/></REF><REF><ORG>GREEN SEAL (GS)</ORG><BRK/><BRK/><RID>GS-36</RID><RTL>(2000) Commercial Adhesives</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FENESTRATION RATING COUNCIL (NFRC)</ORG><BRK/><BRK/><RID>NFRC 100</RID><RTL>(2004) Procedure for Determining Fenestration Product U-Factors</RTL><BRK/><BRK/><RID>NFRC 200</RID><RTL>(2004) Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence</RTL><BRK/><BRK/></REF><REF><ORG>SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)</ORG><BRK/><BRK/><RID>SCAQMD Rule 1168</RID><RTL>(1989; R 2005) Adhesive and Sealant Applications</RTL><BRK/><BRK/></REF><REF><ORG>U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)</ORG><BRK/><BRK/><RID>Energy Star</RID><RTL>(1992; R 2006) Energy Star Energy Efficiency Labeling System</RTL><BRK/><BRK/></REF><REF><ORG>U.S. GREEN BUILDING COUNCIL (USGBC)</ORG><BRK/><BRK/><RID>LEED</RID><RTL>(2002; R 2005) Leadership in Energy and Environmental Design(tm) Green Building Rating System for New Construction (LEED-NC)</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Submittals must be limited to those necessary for adequate quality control.  
The importance of an item in the project should be one of the primary factors 
in determining if a submittal for the item should be required.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy projects.<BRK/>
<BRK/>
Submittal items not designated with a "G" are considered as being for information 
only for Army projects and for Contractor Quality Control approval for Navy 
projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Windows</SUB>; <SUB>G, [_____]</SUB></ITM><BRK/>
<BRK/>
<ITM>  Indicate elevations of windows, full-size sections, thicknesses of PVC, reinforcing members, 
fastenings, proposed method of anchoring, size and spacing of anchors, details of construction, 
method of glazing, details of operating hardware, [mullion details,] [method and materials for 
weatherstripping,] [method of attaching screens,] [material and method of attaching subframes,] 
[fins,] [stools,] [casings,] [sills,] [trim,] [window cleaner anchors,] accessories, installation 
details, window flashings and other related items.</ITM><BRK/>
<BRK/>
<ITM>Schedule of <SUB>windows</SUB>; <SUB>G, [_____]</SUB></ITM><BRK/>
<BRK/>
<ITM>  Submit with drawings indicating location of each window unit.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Windows</SUB>; <SUB>G, [_____]</SUB><TAI OPT="NAVY">; (<RID>LEED</RID>)</TAI></ITM><BRK/>
<BRK/>
<ITM>  Documentation for <RID>Energy Star</RID> Qualifications</ITM><BRK/>
<BRK/>
<ITM><SUB>Fasteners</SUB><TAI OPT="NAVY">; (<RID>LEED</RID>)</TAI></ITM><BRK/>
<BRK/>
<TAI OPT="NAVY"><ITM>  Submit documentation indicating percentage of post-industrial and post-consumer recycled content 
per unit of product.  Indicate relative dollar value of recycled content products to total dollar 
value of products included in project.</ITM></TAI><BRK/>
<BRK/>
<ITM><SUB>Hardware</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Screens</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Weatherstripping</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Accessories</SUB></ITM><BRK/>
<BRK/>
[<ITM><SUB>Adhesives</SUB><TAI OPT="NAVY">; (<RID>LEED</RID>)</TAI></ITM><BRK/>
<BRK/>
<ITM>  Submit manufacturer's product data, indicating VOC content.</ITM>]<BRK/>
<BRK/>
[<TAI OPT="NAVY"><ITM><SUB>Local/Regional Materials</SUB>; (<RID>LEED</RID>)</ITM></TAI><BRK/>
<BRK/>
<TAI OPT="NAVY"><ITM>  Submit documentation indicating distance between manufacturing facility and the project site.  
Indicate distance of raw material origin from the project site.  Indicate relative dollar value 
of local/regional materials to total dollar value of products included in project.</ITM>]</TAI><BRK/>
<BRK/>
[<TAI OPT="NAVY"><ITM><SUB>Environmental Data</SUB></ITM>]</TAI><BRK/>
<BRK/>
<LST><SUB>SD-04 Samples</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Windows</SUB>; <SUB>G, [_____]</SUB></ITM><BRK/>
<BRK/>
<ITM>  Submit one full-size window of each type, complete with certification label indicating conformance 
to <RID>AAMA 101</RID> or <RID>ASTM D 4099</RID>, glazing, hardware, [fins,] anchors, and other accessories.  [Where 
screens or weatherstripping are required, fit sample windows with such items that are to be 
provided.]  After approval, install each sample in the work, clearly identified, and record 
its location.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Windows</SUB>; <SUB>G, [_____]</SUB></ITM><BRK/>
<BRK/>
<ITM>  Submit for each window type attesting that identical or larger windows have been tested and 
meet the requirements specified herein for conformance to <RID>AAMA 101</RID> or <RID>ASTM D 4099</RID> and the specified 
minimum Condensation Resistance Factor (CRF).</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Windows</SUB></ITM><BRK/>
<BRK/>
<ITM>  Submit NFRC Certification documentation.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Windows</SUB>, Data Package 1; <SUB>G, [_____]</SUB></ITM><BRK/>
<BRK/>
<ITM>  Submit data package in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE DATA.</ITM><BRK/>
<BRK/>
<TAI OPT="NAVY"><ITM><SUB>Plastic Identification</SUB></ITM><BRK/>
<BRK/>
<ITM>  When not labeled, identify types in Operation and Maintenance Manual.</ITM></TAI><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.3.1   Labels</TTL><BRK/>
<BRK/>
<TXT>Each window unit shall bear a certification label from an independent, nationally recognized testing organization 
validating that the product complies with <RID>AAMA 101</RID> for the type, grade, and performance class specified or that 
the product complies with <RID>ASTM D 4099</RID> for the grade specified.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3.2   Certification</TTL><BRK/>
<BRK/>
<TXT>Certified test reports attesting that the window units meet the requirements of <RID>AAMA 101</RID> or <RID>ASTM D 4099</RID> as specified 
will be acceptable in lieu of product labeling or marking.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.4   DELIVERY, STORAGE, AND HANDLING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include bracketed sentence for cold climate installations of PVC windows.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Deliver windows to the project site in an undamaged condition.  Use care in handling and hoisting windows during 
transportation and at the job site. Store windows and components out of contact with the ground, under a weathertight 
covering, to prevent bending, warping, or otherwise damaging the windows.  [Store windows and components so they 
will not have to be handled at minus<MET> 28 degrees C</MET><ENG> 20 degrees F</ENG> or colder.]  Repair damaged windows to an "as 
new" condition as approved.  Provide new units if windows cannot be repaired.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5   PROTECTION</TTL><BRK/>
<BRK/>
<TXT>Protect finished surfaces during shipping and handling using the manufacturer's standard method, except do not 
apply coatings or lacquers on surfaces to receive caulking and glazing compounds.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6   SUSTAINABLE DESIGN REQUIREMENTS</TTL><BRK/>
<BRK/>
<SPT><TTL>1.6.1   <SUB>Local/Regional Materials</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Using local materials can help minimize transportation impacts, including 
fossil fuel consumption, air pollution, and labor.  Using materials harvested 
and manufactured within a 500 mile radius from the project site contributes 
to the following LEED credit: MR5.  Coordinate with Section 01 33 29 LEED(tm) 
DOCUMENTATION.  Use second option if Contractor is choosing local products in 
accordance with Section 01 33 29 LEED(tm) DOCUMENTATION.  First option shall 
nto be used for USACE projects.  Army projects shall include second option only 
if pursuing this LEED credit.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Use materials or products extracted, harvested, or recovered, as well as manufactured, within a <ENG>[500][_____] 
mile </ENG><MET>[800][_____] kilometer </MET>radius from the project site, if available from a minimum of three sources.][See 
Section <SRF>01 33 29</SRF> LEED(tm) DOCUMENTATION for cumulative total local material requirements.  Window materials may 
be locally available.]</TXT><BRK/>
<BRK/></SPT>
<TAI OPT="NAVY"><SPT><TTL>1.6.2   <SUB>Environmental Data</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  ASTM E 2129 provides for detailed documentation of the sustainability 
aspects of products used in the project.  This level of detail may be useful 
to the Contractor, Government, building occupants, or the public in assessing 
the sustainability of these products.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Submit Table 1 of <RID>ASTM E 2129</RID> for the following products: [_____].]</TXT><BRK/>
<BRK/></SPT>
</TAI><TAI OPT="NAVY"><SPT><TTL>1.6.3   <SUB>Plastic Identification</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The marking system indicated below is intended to provide assistance 
in identification of products for making subsequent decisions as to handling, 
recycling, or disposal.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Verify that plastic products to be incorporated into the project are labeled in accordance with <RID>ASTM D 1972</RID>.  
Where products are not labeled, provide product data indicating polymeric information in Operation and Maintenance Manual.<BRK/>
Type 1:  Polyethylene Terephthalate (PET, PETE).<BRK/>
Type 2:  High Density Polyethylene (HDPE).<BRK/>
Type 3:  Vinyl (Polyvinyl Chloride or PVC).<BRK/>
Type 4:  Low Density Polyethylene (LDPE).<BRK/>
Type 5:  Polypropylene (PP).<BRK/>
Type 6:  Polystyrene (PS).<BRK/>
Type 7:  Other. Use of this code indicates that the package in question is made with a resin other than the six 
listed above, or is made of more than one resin listed above, and used in a multi-layer combination.</TXT><BRK/>
<BRK/></SPT>
</TAI></SPT></PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification presents nonproprietary materials.  When the 
guide specification is edited or supplemented to suit project requirements, 
care shall be exercised to present a project specification section which contains 
no proprietary materials.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.1   GENERAL REQUIREMENTS FOR WINDOWS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit to indicate materials and items required.  Consult AAMA 1503, "Voluntary 
Test Method for Thermal Transmittance and Condensation Resistance of Windows, 
Doors, and Glazed Wall Sections" and select the minimum Condensation Resistance 
Factory (CRF) required for the particular project conditions.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Window properties are critical to energy performance and visual satisfaction.  
Specify low U value (rate of heat transfer) to reduce winter heat loss and summer 
heat gain.</NPR><BRK/>
<BRK/>
<NPR>Energy Star labeling is applicable to residential units only.  For nonresidential 
applications, designer shall input SHGC and U values based on ASHRAE 90.1, using 
either prescriptive envelope option or energy performance modeling as applicable 
to project design.  Coordinate with Section 08 81 00.  Designer must verify 
availability and adequate competition for products meeting bracketed energy 
performance requirements before specifying and edit as needed.</NPR><BRK/>
<BRK/>
<TAI OPT="NAVY"><NPR>In southern states, windows shall have a U factor of 0.75 or lower and a SHGC 
of 0.40 or lower; in the middle states, windows shall have a U factor of 0.40 
or lower and SHGC of 0.55 or lower; and in northern states, windows shall have 
a U factor of 0.35 or lower with any SHGC.</NPR></TAI><BRK/>
<BRK/>
<NPR>Installing energy efficient windows contributes to the following LEED credits: 
EA Prerequisite 2; EA1.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Windows shall conform to <RID>AAMA 101</RID> or <RID>ASTM D 4099</RID> and to requirements specified herein.  Provide windows of materials, 
types, grades, performance classes, combinations and sizes indicated or specified. Each window shall be a unit 
consisting of [subframe,] frame, sash, glass, hardware, [mullions,] [fins,] [trim,] [casing,] [screen,] [weatherstripping,] 
anchors and accessories complete.  Design windows to accommodate glass, hardware, [screens,] [weatherstripping,] 
and accessories to be furnished.  Glass shall be factory or field installed.  Provide windows with a minimum 
CRF of [_____] when tested in accordance with <RID>AAMA 1503</RID>.<BRK/>
<BRK/>
[Residential plastic windows (including frames and glass) shall be <RID>Energy Star</RID> qualified products as apprpriate 
to[ Northern][ North/Central][ South/Central][ Southern] climate zone.][  Non-residential plastic windows (including 
frames and glass) shall be certified by the National Fenestration Rating Council with a whole-window Solar Heat 
Gain Coefficient (SHGC) maximum of [_____] determined according to <RID>NFRC 200</RID> procedures and a U-factor maximum 
of [_____]<ENG> Btu per square foot x hr x degree F</ENG><MET> W per square m x K</MET> in accoirdance with <RID>NFRC 100</RID>.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2   MATERIALS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.2.1   <SUB>Windows</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use of materials with recycled content, calculated on the basis of post-industrial 
and post-consumer percentage content, contributes to the following LEED credit: 
MR4.  Coordinate with Section 01 33 29 LEED(tm) DOCUMENTATION.  Designer must 
verify suitability, availability and adequate competition (including verification 
of bracketed percentages included in this guide specification) before specifying 
product recycled content requirements.  Use second option if Contractor is choosing 
recycled content products in accordance with Section 01 33 29 LEED(tm) DOCUMENTATION.  
Army projects shall specify recycled content only if pursuing this LEED(tm) 
credit.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide PVC, reinforcing members, fasteners, hardware, weatherstripping, and anchors conforming to <RID>AAMA 101</RID> or <RID>
ASTM D 4099</RID> and as specified herein.  [Plastic [and metal] window components shall contain a minimum of [5][10][_____] 
percent post-consumer recycled content, or a minimum of [20][40][_____] percent post-industrial recycled content.][See 
Section <SRF>01 33 29</SRF> LEED(tm) DOCUMENTATION for cumulative total recycled content requirements.  Metal and plastic 
materials may contain post-consumer or post-industrial recycled content.]</TXT><BRK/>
<BRK/></SPT>
<TAI OPT="NAVY"><SPT><TTL>2.2.2   Sash Insulation</TTL><BRK/>
<BRK/>
<TXT>Use hollow PVC or fiberglass profile insulated with foam or fiberglass, or use foamed PVC for good sash insulation 
performance.</TXT><BRK/>
<BRK/></SPT>
</TAI><SPT><TTL>2.2.3   Glass and Glazing</TTL><BRK/>
<BRK/>
<TXT>As specified in Section <SRF>08 81 00</SRF> GLAZING.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.4   Calking and Sealing</TTL><BRK/>
<BRK/>
<TXT>As specified in Section <SRF>07 92 00</SRF> JOINT SEALANTS.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.5   <SUB>Adhesives</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Adhesives are potential sources of VOCs in indoor air.  Using interior 
low-VOC products contributes to the following LEED credit: EQ4.  Designer must 
verify suitability, availability and adequate competition (includign verification 
of bracketed requirements included in this guide specification) before specifying 
product VOC requirementts.  Coordinate with Section 01 33 29 LEED (tm) DOCUMENTATION.  
Army proejcts shall specify bracketed LEED (tm) VOC option only if pursuing 
LEED (tm) credit.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Comply with applicable regulations regarding toxic and hazardous materials, <RID>GS-36</RID>, [<RID>SCAQMD Rule 1168</RID>,] and as 
specified in Section <SRF>07 92 00</SRF> JOINT SEALANTS.][  Adhesives must meet the requirements of LEED (tm) low emitting 
materials credit.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.6   Insect Screening</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM D 3656</RID>, Class 2, 18 by 14 mesh, color [charcoal] [grey] [_____].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.7   Accessories</TTL><BRK/>
<BRK/>
<TXT>As standard with the manufacturer and as specified herein.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.3   WINDOW TYPES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  AAMA 101 includes a window designation system, with a three part product 
nomenclature representing Product Type, (window) Grade and Performance Class 
(example DH-C20).  The Product Type is an abbreviation for window type (A for 
awning, C for casement, DH for double hung, etc.).  The (window) Grade represents 
the product's intended use (R for residential, C for commercial, and HC for 
heavy commercial).  The Performance Class represents the design pressure to 
which the window is constructed.</NPR><BRK/>
<BRK/>
<NPR>AAMA 101 establishes a minimum Performance Class for each (window) Grade:  15 
for residential (R) windows (corresponding to a design pressure of<MET> 72 kg/sq 
m</MET><ENG> 15 psf</ENG>); 20 for commercial (C) windows (corresponding to a design pressure 
of<MET> 96 kg/sq m</MET><ENG> 20 psf</ENG>); and 40 for heavy commercial (HC) windows (corresponding 
to a design pressure of<MET> 192 kg/sq m</MET><ENG> 40 psf</ENG>).</NPR><BRK/>
<BRK/>
<NPR>AAMA 101 also includes criteria for specifying windows required to meet higher 
design pressures if the minimum design pressure for the particular (window) 
Grade is determined to be inadequate. These windows are designated as Optional 
Performance Class windows.  The Performance Class for Optional Performance Class 
windows should be specified in increments of<MET> 24 kg/sq m</MET><ENG> 5 psf</ENG> above the minimum 
Performance Class.</NPR><BRK/>
<BRK/>
<NPR>ASTM D 4099 classifies window units by Grades based on design pressure.  A Grade 
15 window is constructed to a design pressure of<MET> 72 kg/sq m</MET><ENG> 15 psf</ENG>, a Grade 
20 window is constructed to a design pressure of<MET> 96 kg/sq m</MET><ENG> 20 psf</ENG>, etc.  Thus, 
for each window type included, specify an ASTM D 4099 Grade level equivalent 
to the required AAMA 101 Performance Class.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit for window types to be included in the project.  Consult AAMA/NWDDA 
101 and the AAMA "Window Selection Guide" or the Society of the Plastics Industry 
(SPI) Certified Products Directory for definitions of each type and design consideration.  
The most commonly used window types have been listed in this specification; 
windows are available in other types and can be made in various combinations 
and custom fabrications.  Select window types on basis of functional requirements 
and economic considerations.  Functional requirements include operation of window, 
weather environment, conditions of usage and aesthetic factors.  Economic considerations 
include initial cost as well as maintenance costs over life of the facility.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Consult AAMA 101 to calculate design pressure(s) applicable to the project.  
Adjust "design factors" because naval facilities  are typically less than 100 
miles from hurricane oceanline.</NPR><BRK/>
<BRK/>
<NPR>The Performance Classes listed in brackets represent minimum design pressures 
to which windows meeting AAMA 101 will be constructed.  When design pressure 
is determined to be less than minimum design pressure for selected (window) 
Grade, specify minimum Performance Class.  When design pressure is determined 
to be greater than minimum design pressure for selected (window) Grade, an Optional 
Performance Class window must be specified.  Specify Optional Performance Class 
window with numerical designation to next higher increment of 5 above calculated 
design pressure.</NPR><BRK/>
<BRK/>
<NPR>Specify an ASTM D 4099 Grade equivalent to AAMA 101 Performance Class required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Windows shall be of the following types, as indicated.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.3.1   Awning Windows</TTL><BRK/>
<BRK/>
<TXT><RID>AAMA 101</RID>, Type A- [R 15] [C 20] [[_____] (Optional Performance Class)] or <RID>ASTM D 4099</RID>, Grade [_____].<TAI OPT="NAVY">  Provide 
compression-type weatherstripping.</TAI></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.2   Casement Windows</TTL><BRK/>
<BRK/>
<TXT><RID>AAMA 101</RID>, Type C- [R 15] [C 20] [HC 40] [[_____] (Optional Performance Class)] or <RID>ASTM D 4099</RID>, Grade [_____].  
Ventilators shall be [rotary crank] [handle] operated.  Provide ventilators over<MET> 1675 mm</MET><ENG> 66 inches</ENG> high with 
two separate locking devices or a two-point locking device operated by rods from a single lever handle.  Conceal 
rods where possible.  <TAI OPT="NAVY">Provide compression-type weatherstripping.  </TAI>[Provide casement windows in combination with 
[fixed] [projected] windows specified below.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.3   Double Hung Windows</TTL><BRK/>
<BRK/>
<TXT><RID>AAMA 101</RID>, Type DH- [R 15] [C 20] [HC 40] [[_____] (Optional Performance Class)] or <RID>ASTM D 4099</RID>, Grade [_____].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.4   Horizontal Sliding Windows</TTL><BRK/>
<BRK/>
<TXT><RID>AAMA 101</RID>, Type HS- [R 15] [C 20] [HC 40] [[_____] (Optional Performance Class)] or <RID>ASTM D 4099</RID>, Grade [_____].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.5   Projected Windows</TTL><BRK/>
<BRK/>
<TXT><RID>AAMA 101</RID>, Type P- [R 15] [C 20] [HC 40] [[_____] (Optional Performance Class)] or <RID>ASTM D 4099</RID>, Grade [_____].  
Provide projected windows with concealed four bar friction hinges only.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.6   Fixed Windows</TTL><BRK/>
<BRK/>
<TXT><RID>AAMA 101</RID>, Type F- [R 15] [C 20] [HC 40] [[_____] (Optional Performance Class)] or <RID>ASTM D 4099</RID>, Grade [_____].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.7   Dual Action (Tilt/Turn) Windows</TTL><BRK/>
<BRK/>
<TXT>Dual action windows shall consist of a ventilator which swings into the room from the top for ventilation and 
swings in from the side for cleaning of the outside surface.  When swung from the side, the ventilator shall 
swing in sufficiently to allow safe access to the outside surface.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.3.7.1   Construction</TTL><BRK/>
<BRK/>
<TXT>Ventilators shall have one or more stabilizing arms attached to the frame when ventilator is opened from top.  
When ventilator is in the tilt-open position, stabilizing arms shall provide positive positioning of the ventilator.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.7.2   Hardware</TTL><BRK/>
<BRK/>
<TXT>Equip each ventilator with one handle to provide both tilt and swing operation.  The tilt or swing operation 
shall be individually selected and rendered operable starting only from the closed sash position.  Provide a 
secondary locking device for each ventilator to prevent accidental swing operation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.7.3   Performance Requirements</TTL><BRK/>
<BRK/>
<TXT>Dual action windows shall meet the primary performance requirements specified in <RID>AAMA 101</RID> for Grade and Performance 
Class [R 15] [C 20] [HC 40] [[_____] (Optional Performance Class)] or the performance requirements specified 
in <RID>ASTM D 4099</RID> for Grade [_____].</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>2.4   FABRICATION</TTL><BRK/>
<BRK/>
<TXT>Conform to <RID>AAMA 101</RID> or <RID>ASTM D 4099</RID> and to the requirements specified herein.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.4.1   Subframes, Mullions and Transom Bars</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit and include this paragraph when PVC subframes, mullions and/or transom 
bars are included, otherwise delete.  Specify the design pressure used to specify 
the Performance Class or the Optional Performance Class for the adjoining windows.  
Avoid mullion covers in cold climate installations.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide subframes, transom bars and mullions between multiple window units which meet the design pressure of<MET> 
[72] [96] [192] [_____] kilograms per square meter (kg/sq m)</MET><ENG> [15] [20] [40] [_____] pounds per square foot (psf)</ENG>
.  Fabricate mullions and transom bars in such a manner as to permit expansion and contraction between adjoining 
construction and window units and to form a weathertight joint.  [Provide mullion covers on the interior and 
exterior to completely close exposed joints and recesses between window units and to present a neat appearance.]  
[Provide special covers over structural support at mullions as indicated.]  [Where window cleaner anchors are 
required, reinforce mullions to provide safe and adequate support.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.2   Combination Windows</TTL><BRK/>
<BRK/>
<TXT>Windows provided in combination shall be the same grade and performance class and shall be factory assembled.  
Where factory assembly of individual windows into larger units is limited by transportation considerations, prefabricate, 
match mark, transport, and field assemble.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.3   Frames and Sash</TTL><BRK/>
<BRK/>
<SPT><TTL>2.4.3.1   Corners and Reinforcement</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify mechanically fixed and sealed or welded corners for most applications.  
Specify only welded corners for cold climate applications.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Corners of PVC frames and sashes shall be [mechanically fixed and sealed or welded] [welded].  Reinforce frames 
and sash as necessary to meet the requirements for the performance classes or grades specified herein.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.3.2   Adjustability</TTL><BRK/>
<BRK/>
<TXT>Ventilating sash shall be adjustable vertically and horizontally to ensure smooth operation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.3.3   Drips and Weep Holes</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include the first two sentences when operable windows are included in 
the project, otherwise delete.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Provide continuous drips over heads of top ventilators.  Where fixed windows adjoin ventilators, provide continuous 
drips across tops of fixed windows.]  Provide drips and weep holes as required to return water to the outside.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.3.4   Provisions for Glazing</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify glass thickness in Section 08800, "Glazing."  Inside glazing 
is preferred, especially for windows above first floor and other locations where 
access is difficult. Windows designed for inside glazing may not be available 
in double-hung type.  Check manufacturer's literature.  Where project requires 
insulating glass, show sash members, glazing beads, and hardware of sufficient 
size and weight to receive and support glass of specified thickness.  Allow 
sufficient space between each side of insulating glass and frame for glazing 
compound or glazing gaskets and expansion as well as sufficient space between 
edges of glass and frame.  Drawings should clearly indicate method for securing 
insulating glass in place.  Specify windows which will require glazing beads 
if they are indicated as such; specify vinyl, EPDM or silicone rubber gaskets 
in Section 08800, "Glazing."  Do not use glazing compound, vinyl glazing gaskets 
or exterior glazing beads in cold climates; dry glaze with EPDM or silicone 
rubber gaskets.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Design windows and rabbets suitable for glass thickness shown [or specified].  Design sash for [inside] [outside] 
[single] [double] [triple] glazing and for securing glass with [glazing beads,] [glazing clips,] [glazing channels,] 
[glazing gaskets,] [or glazing compound].</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.4.4   <SUB>Hardware</SUB></TTL><BRK/>
<BRK/>
<TXT>The item, type, and functional characteristics shall be the manufacturer's standard for the particular window 
type.  Provide hardware of suitable design and of sufficient strength to perform the function for which it is 
used.  Equip operating ventilators with a lock or latching device which can be secured from the inside.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.5   <SUB>Weatherstripping</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide for ventilating sections of windows to ensure a weathertight seal meeting the infiltration requirements 
specified in <RID>AAMA 101</RID> or <RID>ASTM D 4099</RID>.  Provide easily replaceable factory-applied weatherstripping.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.6   <SUB>Screens</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide one insect screen for each operable exterior sash or ventilator. Design screens to be rewirable, easily 
removable from inside the building, and to permit easy access to operating hardware.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.7   Color</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Standard PVC window color is white and should be specified for most projects.  
A number of other colors are available, particularly tan (ivory, beige, almond), 
gray and dark brown (architectural bronze), at additional cost.  Colors co-extruded 
to the exterior of the window are especially designed to prevent heat build-up.  
Specify premium colors only after verification of availability, cost and aesthetic 
need.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Window (PVC) color shall be [white] [_____].  Color shall be integral or co-extruded to the PVC to prevent heat 
build-up.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.8   <SUB>Fasteners</SUB></TTL><BRK/>
<TAI OPT="NAVY"><NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer must verify that products meeting the indicated minimum recycled 
content are available, preferably from at least three sources, to ensure adequate 
competition.  If not, write in suitable recycled content values that reflect 
availability and competition.</NPR><BRK/>
<AST/><BRK/></NTE>
</TAI><BRK/>
<TXT>Provide fastener types as standard with the window manufacturer for windows, trim, and accessories.<TAI OPT="NAVY">  Fabricated 
from 100 percent re-melted steel.</TAI></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.9   <SUB>Accessories</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit for accessories to be included.  Check availability of integral 
venetian blinds before specifying.  Indicate windows to receive grills and/or 
integral venetian blinds on the drawings.  If venetian blinds are to be separate 
from the windows, delete the paragraph entitled "Integral Venetian Blinds" and 
specify venetian blinds in Section 12490, "Blinds, Venetian (and Audio Visual)."</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide windows complete with clips, fins, anchors, [grills,] [venetian blinds,] and other appurtenances necessary 
for complete installation and proper operation.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.4.9.1   Anchors</TTL><BRK/>
<BRK/>
<TXT>Provide concealed anchors of the type recommended by the window manufacturer for the specific type of construction.  
Anchors and fasteners shall be compatible with the window and the adjoining construction.  For each jamb<MET> 900 
mm</MET><ENG> 36 inches</ENG> or longer, provide a minimum of three anchors located approximately<MET> 150 mm</MET><ENG> 6 inches</ENG> from each end 
and at midpoint.  For jambs less than<MET> 900 mm</MET><ENG> 36 inches</ENG> long, provide two anchors.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.9.2   Window-Cleaner Anchors</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Show and specify window-cleaner anchors where sills are more than<MET> 1800 
mm</MET><ENG> 6 feet</ENG> above grade, adjoining balconies, or adjoining roofs, unless window 
cleaning methods at the activity make use of anchors unnecessary.  Coordinate 
with using activity in making decision as to need for anchors.  When requested 
by activity, removable or tilting-type sash may be provided instead of anchors.  
Removable or tilting-type sash may be specified as Contractor's option when 
these units are desired by using activity and when economically competitive 
with conventional double-hung sash equipped with window cleaner anchors.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide double head anchors for windows [indicated] [specified].  Anchors shall be stainless steel of size and 
design conforming to <RID>ASME A39.1</RID>.  Provide two anchors for each single window [and each adjacent fixed glass window 
unit].  Fasten anchors<MET> 1120 mm</MET><ENG> 44 inches</ENG> above the window sill in accordance with <RID>ASME A39.1</RID>.  Reinforce frames 
to receive anchors.  Provide wall anchors on backs of frames at points where anchors are located.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.9.3   Grills</TTL><BRK/>
<BRK/>
<TXT>Provide the manufacturer's standard grills for the windows indicated. Grills shall be removable or shall be sealed 
within insulating glass units. Unless otherwise indicated, grill pattern shall be the manufacturer's standard 
design or as approved.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.9.4   Integral Venetian Blinds</TTL><BRK/>
<BRK/>
<TXT>Provide the manufacturer's standard venetian blinds mounted within the window frame for the windows indicated.  
Venetian blinds shall be fully adjustable allowing full angle tilting and stops at any position.  Color of blinds 
shall [be white] [match the color of the PVC].</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Install in accordance with the window manufacturer's printed instructions and details.  Build in windows as work 
progresses or install without forcing into prepared window openings.  Set windows at proper elevation, location, 
and reveal; plumb, square, level, and in alignment; and brace, strut, and stay properly to prevent distortion 
and misalignment.  Bed screws or bolts in sill members, joints at mullions, contacts of windows with sills, built-in 
fins, and subframes in mastic sealant of a type recommended by the window manufacturer.  Install and seal windows 
in a manner that will prevent entrance of water and wind.  [Fasten insect screens securely in place.] Fasten 
hardware to windows.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.1.1   Anchors and Fastenings</TTL><BRK/>
<BRK/>
<TXT>Secure units to each other, to masonry, and to other adjoining construction with clips, fins, screws, or other 
devices recommended by the window manufacturer.  [Where window cleaner anchors are provided, anchor windows and 
mullions to provide safe and adequate support for the window cleaner.]</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.2   ADJUSTING</TTL><BRK/>
<BRK/>
<TXT>After installation of windows and completion of glazing and field painting, adjust ventilators and hardware to 
operate smoothly and to provide weathertight sealing when ventilators are closed and locked.  Lubricate hardware 
and operating parts as necessary.  Verify products are properly installed, connected, and adjusted.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3   CLEANING</TTL><BRK/>
<BRK/>
<TXT>Clean interior and exterior surfaces of window units of mortar, plaster, paint spattering spots, and other foreign 
matter to present a neat appearance, to prevent fouling of weathering surfaces and weatherstripping, and to prevent 
interference with operation of hardware.  Replace stained, discolored, or abraded windows that cannot be restored 
to their original condition with new windows.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4   PROTECTION</TTL><BRK/>
<BRK/>
<TXT>Protect ventilators and operating parts against accumulation of dirt and building materials by keeping ventilators 
tightly closed and locked to frame.</TXT><BRK/></SPT>
<SPT><TTL>3.5   WASTE MANAGEMENT</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Diverting waste from the landfill contributes to the following LEED credit: 
MR2.  Coordinate with Section 01572 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT.  
Designer shall verify that items are able to  be disposed of as specified.  
Army projects include bracketed text only if pursuing this LEED (tm) credit.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Separate <TAI OPT="NAVY">plastic materials, </TAI>corrugated cardboard, and protective materials in accordance with the Waste Management 
Plan and reuse or recycle.  Place materials defined as hazardous or toxic waste in designated containers and 
dispose of properly.  Close and seal tightly all partly used sealant containers and store protected in well ventilated 
fire-safe area at moderate temperature.  Place used sealant tubes and containers in areas designated for hazardous 
materials and dispose of properly.</TXT><BRK/>
<BRK/></SPT>
</PRT>    <END/><BRK/></SEC>