<SCN>SECTION 08 56 46.10 20</SCN><BRK/>
<BRK/>
<STL>RADIO FREQUENCY SHIELDED ENCLOSURES, DEMOUNTABLE TYPE</STL><BRK/>
<DTE>04/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>radio frequency 
shielded enclosures, demountable Type</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for radio frequency 
shielded enclosures, demountable Type, in sizes under<MET> 50 square meter</MET><ENG> 500 square 
feet</ENG>.  For larger enclosures and for High Altitude Electromagnetic Pulse (HEMP) 
protected enclosures, contact NAVFAC Engineering Innovation and Criteria Office 
(Code EICO) before beginning design.  Do not design HEMP enclosures utilizing 
demountable shield construction.  The electrical designer should refer to MIL-HDBK-419 
Volumes I and II for special grounding and bonding requirements for EMI enclosures 
and to NACSIM 5203 for TEMPEST enclosures.  All metallic electrical conduits 
which penetrate a TEMPEST shield must be isolated within<MET> 50 mm</MET><ENG> 2 inches</ENG> of the 
exterior of the shield by a nonmetallic conduit section at least<MET> 150 mm</MET><ENG> 6 inches</ENG>
 long to prevent conduction of information from the shielded enclosure.  Although 
not addressed in this specification, it is recognized that fiber optic cable 
has gained acceptance as an effective method of transmitting data across the 
boundary of shielded enclosures without filtering.  If fiber optic cable is 
used, describe the penetration of the shield in detail.  For a discussion of 
the advantages and disadvantages of fiber optic systems see NAVFAC DM-12.02.  
Designer should consult these documents and other appropriate sources before 
applying this guide specification to large scale EMI enclosures to HEMP and 
to TEMPEST Projects.  The potential requirement for thermal expansion joints 
inherent to large scale enclosures is not addressed in this guide specification.  
The extent and location of the work to be accomplished and wiring, equipment, 
and accessories necessary for a complete installation should be indicated on 
the project drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following information shall be shown on the project drawings:</NPR><BRK/>
<BRK/>
<NPR>1.  Assembly details;</NPR><BRK/>
<BRK/>
<NPR>2.  Penetration details;</NPR><BRK/>
<BRK/>
<NPR>3.  Location and method of mounting shielded enclosure within building;</NPR><BRK/>
<BRK/>
<NPR>4.  Location of mechanical and electrical equipment within shielded enclosure;</NPR><BRK/>
<BRK/>
<NPR>5.  Interior wall finish;</NPR><BRK/>
<BRK/>
<NPR>6.  Suspended ceiling; and</NPR><BRK/>
<BRK/>
<NPR>7.  Raised computer floor.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL (AMCA)</ORG><BRK/><BRK/><RID>AMCA 210</RID><RTL>(2007) Laboratory Methods of Testing Fans for Aerodynamic Performance Rating</RTL><BRK/><BRK/></REF><REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 653/A 653M</RID><RTL>(2008) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process</RTL><BRK/><BRK/><RID>ASTM B 194</RID><RTL>(2008) Standard Specification for Copper-Beryllium Alloy Plate, Sheet, Strip, and Rolled Bar</RTL><BRK/><BRK/><RID>ASTM E 84</RID><RTL>(2008a) Standard Test Method for Surface Burning Characteristics of Building Materials</RTL><BRK/><BRK/><RID>ASTM E 90</RID><RTL>(2004) Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements</RTL><BRK/><BRK/><RID>ASTM F 1066</RID><RTL>(2004) Standard Specification for Vinyl Composition Floor Tile</RTL><BRK/><BRK/></REF><REF><ORG>INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)</ORG><BRK/><BRK/><RID>IEEE Std 299</RID><RTL>(2006) Standard Method for Measuring the Effectiveness of Electromagnetic Shielding Enclosures</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/></REF><REF><ORG>U.S. DEPARTMENT OF COMMERCE (DOC)</ORG><BRK/><BRK/><RID>DOC FED PS51</RID><RTL>(1971; R 1972) Hardwood and Decorative Plywood</RTL><BRK/><BRK/><RID>DOC FED PS58</RID><RTL>(1974) Basic Hardboard</RTL><BRK/><BRK/></REF><REF><ORG>U.S. DEPARTMENT OF DEFENSE (DOD)</ORG><BRK/><BRK/><RID>MIL-PRF-15733</RID><RTL>(Rev H; Supp 1; Am 1; Am 2; Am 3) Filters and Capacitors, Radio Frequency Interference</RTL><BRK/><BRK/><RID>MIL-STD-220</RID><RTL>(Rev B; Notice 1) Method of Insertion-Loss Measurement</RTL><BRK/><BRK/><RID>MIL-STD-461</RID><RTL>(Rev F) Requirements for the Control of Electromagnetic Interference Characteristics of Subsystems and Equipment</RTL><BRK/><BRK/></REF><REF><ORG>U.S. GENERAL SERVICES ADMINISTRATION (GSA)</ORG><BRK/><BRK/><RID>FS A-A-50032</RID><RTL>(Rev B) Fans, Ventilating, Propeller</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   GENERAL REQUIREMENTS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Insert additional details describing the specific project for which this 
specification is being used.  Projects involving military communications equipment 
must be designed to incorporate the applicable requirements of MIL-STD-188-124, 
"Grounding, Bonding and Shielding for Common Long Haul/Tactical Communication 
Systems."  Be aware that standard manufactured shielded doors are not designed 
for exposure to weather.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Section <SRF>26 00 00.00 20</SRF> BASIC ELECTRICAL MATERIALS AND METHODS, applies to this section, with the additions and 
modifications specified herein.  The enclosure[s] shall be capable of being erected, disassembled, and reerected 
entirely from its interior without special tools [, except where RF enclosure ceiling is specified as being supported 
by the structural ceiling above].  Provide enclosure[s] complete with [power line filters,] [telephone/signal 
line filters,] [RF air vents,] [penetrations for compressed air lines, water lines and _____,] [coaxial cables,] 
[lighting fixtures,] [workbenches with convenience outlets,] and door assembly. Provide each item with fittings 
and hardware necessary for a complete and operable RF shielded enclosure.  Where two or more units of the same 
type, class, and size of equipment are required, these units shall be products of a single manufacturer.  Provide 
means of completely isolating the structure electrically from the building in which it is to be installed.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.2.1   Mechanical Work</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Modify or delete these paragraphs as required for each project.  Additional 
items such as raised computer floors may be specified in the same manner.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Insert appropriate Section number and title in blank below using format 
per UFC 1-300-02.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide complete shielded enclosure[s] including work specified in [_____] [and [_____]].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.2.2   Electrical Work</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Modify or delete these paragraphs as required for each project.  Additional 
items such as raised computer floors may be specified in the same manner.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Insert appropriate Section number and title in blank below using format 
per UFC 1-300-02.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Conform to the requirements of the <RID>NFPA 70</RID>, National Electrical Code. Provide a complete shielded enclosure[s] 
including work specified in [_____] [and [_____]].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.2.3   Acoustical Ceiling System</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Modify or delete these paragraphs as required for each project.  Additional 
items such as raised computer floors may be specified in the same manner.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide as specified in Section <SRF>09 51 00</SRF> ACOUSTICAL CEILINGS.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.3   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM>Radio frequency <SUB>shielded enclosure</SUB></ITM><BRK/>
<BRK/>
<ITM>  Include penetration details.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM>Telephone and signal <SUB>line filters</SUB></ITM><BRK/>
<BRK/>
<ITM>Shielded <SUB>air vents</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Lighting</SUB> fixtures</ITM><BRK/>
<BRK/>
<ITM><SUB>Exhaust fan</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Door assemblies</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When specifying nonlatching doors, delete door static load and sag tests 
and cycle test for door latches.  Retain cycle test for door hinges.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM>Door <SUB>static load test</SUB></ITM><BRK/>
<BRK/>
<ITM>Door <SUB>sag test</SUB></ITM><BRK/>
<BRK/>
<ITM>Swinging door <SUB>closure test</SUB></ITM><BRK/>
<BRK/>
<ITM>EMI tests for <SUB>line filters</SUB></ITM><BRK/>
<BRK/>
<ITM>  Submit final report to Resident Officer in Charge of Construction within 30 days following 
completion.</ITM><BRK/>
<BRK/>
<ITM><SUB>Attenuation testing</SUB></ITM><BRK/>
<BRK/>
<ITM>Seam <SUB>leak detection testing</SUB></ITM><BRK/>
<BRK/>
<ITM>  The results of EMI testing shall be submitted to the Contracting Officer on a daily basis 
and test results incorporated into a EMI Shielding Test Final Report. Submit final reports within 
30 days following completion of tests.  List location of the permanent SELDS test leads.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Performance</SUB> test plan</ITM><BRK/>
<BRK/>
<ITM>Qualifications of <SUB>installation supervision</SUB> personnel</ITM><BRK/>
<BRK/>
<ITM>Qualifications of <SUB>testing agency</SUB></ITM><BRK/>
<BRK/>
<ITM>Certification of <SUB>test equipment</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Components</SUB> of shielded enclosure individually and as a system, meet specified attenuation requirements.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Shielded enclosure</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE DATA.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   RELIABILITY</TTL><BRK/>
<BRK/>
<TXT>Reliability to maintain high shielding effectiveness for long term usage with minimum maintenance shall be stressed 
throughout the design, construction, and erection of the specified shielded enclosure.  Particular attention 
shall be paid to the total project so that corrosion and the installation of electrical service, power line filters, 
ventilation, and connector panels do not derate the required shielding effectiveness.  The enclosures will be 
subject to varying moveable live floor loads and continuous use of the ventilation system and ac power line filters.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5   DELIVERY AND STORAGE</TTL><BRK/>
<BRK/>
<TXT>Deliver materials to the job site in undamaged condition.  Store material to ensure proper alignment, and protect 
material against dampness and accumulated moisture before and after delivery.  Store materials under cover in 
a well-ventilated enclosure, and do not allow materials to be exposed to extreme changes in temperature and humidity.  
Do not store materials in the building until concrete and masonry are dry.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.6.1   Certificates</TTL><BRK/>
<BRK/>
<SPT><TTL>1.6.1.1   <SUB>Performance</SUB> Test Plan</TTL><BRK/>
<BRK/>
<TXT>Submit a performance test plan for SELDS and <RID>IEEE Std 299</RID> testing of the facility.  The test plan shall include 
tester qualifications, equipment listings (including calibration dates and antenna factors), and proposed test 
report format.  The plan shall also address specific dates and durations that testing will be conducted during 
the overall construction period so that the expert Government witness may be scheduled to observe the testing 
and so that repairs may be made to the shield and retests conducted before the building finish materials are 
installed.  Finally, the test plan shall indicate the proposed dates and duration of the lowest and the highest 
frequency tests following installation of the building finish materials [so that an expert Government witness 
may be available for these final acceptance tests].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6.1.2   Qualifications of <SUB>Testing Agency</SUB></TTL><BRK/>
<BRK/>
<TXT>Submit the experience and qualifications of an independent testing agency for review and approval.  The testing 
agency shall have recent experience in Shielded Enclosure Leak Detection System (SELDS) and <RID>IEEE Std 299</RID> shielded 
enclosure testing and shall list where and when the experience was obtained.  Submit with the performance test 
plan.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6.1.3   Certification of <SUB>Test Equipment</SUB></TTL><BRK/>
<BRK/>
<TXT>Certify that test equipment for the attenuation testing has been calibrated within last 12 months.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>1.7   MAINTENANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.7.1   Contents</TTL><BRK/>
<BRK/>
<TXT>In addition, the manual shall contain the following information:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  A complete set of assembly and disassembly drawings;</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  A schedule of recommended maintenance and adjustment procedures to ensure continuous shielding 
effectiveness;</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Allowable loads on top of room and on shelves mounted on walls, including permissible weights 
of equipment that can be mounted on walls; and</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Prescribed method of handling panels, cleaning of seams and contact fingers, bonding jumpers, 
installing metallic items penetrating the shielding material without decreasing the attenuation 
characteristics.</ITM><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   <SUB>SHIELDED ENCLOSURE</SUB> CHARACTERISTICS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1.1   Radio Frequency Interference Attenuation</TTL><BRK/>
<BRK/>
<TXT>The attenuation and shielding effectiveness requirements apply to the finished shielded enclosure[s] and enclosure's <SUB>
components</SUB> when all power line filters are installed and carrying current, ventilation systems are operating, 
[the coaxial connector panels capped,] and shielded door[s] are in normal operation position.  The specified 
shielded effectiveness shall be achieved without using conductive tapes, gaskets, or cement materials.  Provide 
enclosure[s] having the following minimum magnetic, electric, and plane wave attenuation:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">Magnetic - [60] [_____] dB at 14kHz increasing linearly to [100] [_____] dB at 200 kHz</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">Electric - [100] [_____] dB from 1.0 kHz to 50 MHz</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">Plane Wave - [100] [_____] dB between 50 MHz and 10 GHz</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   Sound Transmission Class (STC)</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  STC 30 provides only minimum sound transmission loss.  For greater sound 
control, more detailed acoustical design requirements must be incorporated into 
the specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide enclosure[s] having an STC of [30] [_____] dB minimum when tested according to <RID>ASTM E 90</RID> [not including 
sound transmission loss of surrounding building construction].</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2   PANELS CONSTRUCTION</TTL><BRK/>
<BRK/>
<TXT>Flat steel sheet laminated to each side of a<MET> 20 mm</MET><ENG> 3/4 inch</ENG> structural core of either plywood or hardboard.  
[Panels shall have a flame spread rating of less than 25 when tested according to <RID>ASTM E 84</RID>.]</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.1   Flat Steel Sheet</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM A 653/A 653M</RID> with<MET> Z180</MET><ENG> G-60</ENG> coating, minimum 24 gage, phosphatized.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.2   Plywood</TTL><BRK/>
<BRK/>
<TXT><RID>DOC FED PS51</RID> for exterior, sound grade hardwood, Type I.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.3   Hardboard</TTL><BRK/>
<BRK/>
<TXT><RID>DOC FED PS58</RID> for standard type hardboard.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.4   Adhesive for Laminating Steel Sheets to Structural Core</TTL><BRK/>
<BRK/>
<TXT>Waterproof type which maintains a permanent bond for the lifetime of the enclosure.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.5   Floor Finish</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Indicate or specify whether other flooring is to be provided or higher 
floor loads are required. This is most critical when raised floors are required.  
Allowances must be made for elevated door thresholds.  Vinyl composition 1 is 
asbestos-free and should be specified for all projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Vinyl-composition tile, <RID>ASTM F 1066</RID>, Type IV, composition 1,<MET> 300 by 300 mm, 3 mm</MET><ENG> 12 by 12 inches, 1/8 inch</ENG>, thick.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.3   FRAMING-JOINING SYSTEM</TTL><BRK/>
<BRK/>
<TXT>The panels shall be joined and supported by specially designed members that clamp the edges of the panels and 
provide continuous, uniform, and constant pressure contact against the shielding elements of the panels.  The 
walls shall be self-supporting from floor to ceiling with no bracing.  Deflection of walls under a static load 
of<MET> 35 kg</MET><ENG> 75 pounds</ENG> applied normal to the wall surface at any point along the framing members shall not exceed 
1/250 of the span between supports.  [Ceilings shall be self-supporting from wall to wall.]  [Ceilings shall 
be supported by adjustable, nonconducting, isolated hangers from the structural ceiling above.] Ceilings shall 
be designed to have a deflection under total weight, including ceiling finish, of not more than 1/270 of the 
span.  At corner intersections of walls, floor, or ceiling, provide a one-piece factory prewelded corner section 
or trihedral corner framed with brass machined cast corner cap assemblies consisting of inner and outer parts.  
The modular enclosure shall be designed for ease of erection, disassembly, and re-assembly.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.3.1   Channels</TTL><BRK/>
<BRK/>
<TXT>The framing-joining system members shall consist of<MET> 3 mm</MET><ENG> 1/8 inch</ENG>zinc-plated steel channels having minimum<MET> 16 
mm</MET><ENG> 5/8 inch</ENG> overlap along each side of the contacting surface.  Screw fasteners shall be spaced at<MET> 75 or 100 
mm</MET><ENG> 3 or 4 inch</ENG> intervals.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.2   Screw Fasteners</TTL><BRK/>
<BRK/>
<TXT>Screw fasteners shall be either zinc-plated or cadmium-plated steel, minimum size<MET> 6 mm</MET><ENG> 1/4 inch</ENG> - 20 with pan 
or flat Phillips heads.  Fasteners shall be heat treated and hardened with minimum tensile strength of<MET> 930 MPa</MET><ENG>
 135,000 psi</ENG>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.4   <SUB>DOOR ASSEMBLIES</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Do not accept doors that deviate from this specification without consulting 
NAVFAC 15C.  Probable deviations include:  magnetic and electromagnetic doors, 
other non-finger stock type doors, adhesive mounted finger stock, and requests 
to approve doors tested to less than 10,000 open close cycles, among others.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The enclosure door shall be nonsagging and nonwarping and shall afford shielded effectiveness equal to the rest 
of the enclosure when the door is closed.  The shielded door shall be provided with [multiple rows] [at least 
one row] of RF finger stock around the door or its frame.  The fingers that form a contact between the door and 
its frame shall be protected from damage due to physical contact and shall be concealed within the door and frame 
assemblies.  The door shall have a clear opening of<MET> [900 mm]</MET><ENG> [36 inches]</ENG> [_____] wide and<MET> [2100 mm]</MET><ENG> [84 inch]</ENG>
 [_____] high.  Door assembly shall be the same manufacture as the enclosure.  Doors shall be reinforced steel 
or laminated type.  Laminated type shall be the same construction as enclosure panels, except the steel faces 
shall be electrically and mechanically joined by channels or overlapping seams, both of which shall be continuously 
seam welded along all joined surfaces.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.4.1   Finger Stock</TTL><BRK/>
<BRK/>
<TXT>Contacts for doors shall be copper beryllium conforming to <RID>ASTM B 194</RID>, Condition HT.  The finger stock shall 
be secured to the door or frame without using special tools or soldering or adhesives and shall have a minimum 
overlap of<MET> 50 mm</MET><ENG> 2 inches</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.2   [Latching Type</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the applicable paragraph(s) from the following:</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specially designed door for electrical or pneumatic operation may be 
specified; however, these special doors are not compatible with all demountable 
enclosures.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The door shall be lever controlled with roller cam action requiring not more than<MET> 90 N</MET><ENG> 20 pounds</ENG> of operating 
force on the handle for both opening and closing.  The door shall be equipped with a two or three-point latching 
mechanism that provides proper compressive force for the RF seal.  The mechanism shall be operable from both 
sides of the door and shall have permanently-lubricated ball bearings at points of pivot and rotation.  The door 
latches and hinges shall be rated for a minimum of 10,000 cycles without loss of attenuation and without adjustments.]</TXT><BRK/>
<BRK/>
<TXT>[Nonlatching Type</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Nonlatching doors may be used for enclosures having many daily open-close 
operations; however, they may not retain as high an attenuation over the long 
term compared with doors having three-point latching mechanisms.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The door shall be equipped with three heavy-duty ball bearing hinges and a door pull.  Door shall open and close 
with a force not to exceed<MET> 20 N</MET><ENG> 5 pounds</ENG>.]</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.5   <SUB>LINE FILTERS</SUB></TTL><BRK/>
<BRK/>
<SPT><TTL>2.5.1   Power Line Filters</TTL><BRK/>
<BRK/>
<TXT>Shall conform to the requirements of Section <SRF>26 35 46.00 20</SRF> RADIO FREQUENCY INTERFERENCE POWER LINE FILTERS and 
shall have current and voltage ratings as [indicated] [specified].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.2   Telephone and Signal Line Filters</TTL><BRK/>
<BRK/>
<TXT><RID>MIL-PRF-15733</RID>.  Filters shall have an insertion loss of 100 decibels in the frequency range of 14 kHz to 10 GHz 
measured according to <RID>MIL-STD-220</RID>, full load condition.  Filters shall have a pass band of [_____] kHz to [_____] 
kHz with a characteristic impedance of [_____] ohms.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.6   WAVEGUIDE-TYPE <SUB>AIR VENTS</SUB></TTL><BRK/>
<BRK/>
<TXT>Honeycomb-type air vents shall have cores fabricated of brass or steel, and each guide shall be electrically 
and mechanically bonded to all adjacent guides.  Air vents shall be a permanent part of the shielded enclosure 
and shall have a shielding effectiveness equal to that of the total enclosure. Static pressure drop through the 
vents shall not exceed<MET> 5 Pa</MET><ENG> 0.02 inch</ENG> water gage at an air velocity of<MET> 3 m/s</MET><ENG> 600 feet per minute</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7   GROUNDING STUD</TTL><BRK/>
<BRK/>
<TXT>Enclosure shall have a permanently installed, solid brass or bronze grounding stud complete with hardware and 
jamb nuts located in the entrance plate [unless otherwise specified or indicated].  The stud shall be <MET> 13 mm</MET><ENG> 
1/2 inch</ENG> diameter double-threaded bolt which allows a full <MET> 50 mm</MET><ENG> 2 inch</ENG> running thread inside and outside of 
the shielded enclosure.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.8   SERVICE ENTRANCE PLATES (SET-UP PANELS)</TTL><BRK/>
<BRK/>
<TXT>Shall be minimum<MET> 3 mm</MET><ENG> 1/8 inch</ENG> thick steel, sized<MET> [300 by 300 mm]</MET><ENG> [12 by 12 inches]</ENG> [_____] and shall have a<MET> 
6 mm</MET><ENG> 1/4 inch</ENG> extruded brass frame for mounting to shielded enclosure wall panel.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9   NAMEPLATES</TTL><BRK/>
<BRK/>
<TXT>Major components of equipment shall have manufacturer's name, address, catalog number, model, style, and type 
on a plate securely and conspicuously attached to each item of equipment.  Nameplates for electrical apparatus 
shall conform to NEMA Standards.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.10   <SUB>LIGHTING</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  In shielded enclosures where electronic equipment is very sensitive to 
EMI, specify a dual lighting system so that fluorescent lighting can be turned 
off and incandescent lighting left on during sensitive tests or operations.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide lighting fixtures as indicated [and as specified in Section <SRF>26 51 00</SRF> INTERIOR LIGHTING].  Fluorescent 
lighting fixtures shall meet the requirements of <RID>MIL-STD-461</RID>, Class C3, Group I for both conducted and radiated 
interference.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11   <SUB>EXHAUST FAN</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph cites only minimum requirements.  Design calculations 
are necessary to size HVAC to suit room size and equipment/personnel contained 
within.  Exhaust fan motors located inside shielded enclosure must meet MIL-STD-461, 
Class C3, Group I.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>FS A-A-50032</RID>, Type I, Class 1 for direct drive, Class 2 for belt drive, Style A for wall or window mounting, 
Style B for roof or ceiling mounting, except that fans shall be centrifugal type with aluminum housing and wheel. 
Additionally exhaust fans shall meet the electromagnetic compatibility requirements of <RID>FS A-A-50032</RID>.  Motors 
shall be completely shielded from the air stream.  Provide exhaust opening and gravity closing type automatic 
louvers.  Provide exhaust which can supply 15 room air changes per hour. Capacity of fans shall be certified 
in accordance with <RID>AMCA 210</RID>, and shall be not greater than 110 percent of the indicated capacity at indicated 
pressure drop.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12   COAXIAL CABLE PENETRATIONS</TTL><BRK/>
<BRK/>
<TXT>For each coaxial cable entering the shielded enclosure, provide RF waveguide threaded insert with cap and chain 
on shielded room side of enclosure.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.13   SOURCE QUALITY CONTROL</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When specifying nonlatching doors, delete door static load and sag tests 
and cycle test for door latches.  Retain cycle test for door hinges.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.13.1   Door <SUB>Static Load Test</SUB></TTL><BRK/>
<BRK/>
<TXT>The door shall be mounted and latched to its frame, then set down in a horizontal position such that the door 
will open downward and only the frame is rigidly and continuously supported from the bottom.  A load of <MET> 2kPa</MET><ENG>
 40 psf</ENG> shall be applied uniformly over the entire surface of the door for at least 10 minutes.  The door will 
not be considered acceptable if this load causes breakage, failure, or permanent deformation which varies the 
clearance between door leaf and stops to vary more than<MET> 2 mm</MET><ENG> 1/16 inch</ENG> from the original dimension.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.13.2   Door <SUB>Sag Test</SUB></TTL><BRK/>
<BRK/>
<TXT>The door and its frame shall be installed normally and opened 90 degrees. Two<MET> 23 kg</MET><ENG> 50 pound</ENG> weights, one on 
each side of the door, shall be suspended from the door within<MET> 125 mm</MET><ENG> 5 inches</ENG> of the outer edge for at least 
10 minutes.  The door will not be considered acceptable if this test causes breakage, failure, or permanent deformation 
which varies the clearance between the door leaf and floor frame more than<MET> 2 mm</MET><ENG> 1/16 inch</ENG> from its original dimension.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.13.3   Swinging Door <SUB>Closure Test</SUB></TTL><BRK/>
<BRK/>
<TXT>Door shall be operated 5000 complete open-close cycles.  The door will not be acceptable if the closure test 
causes any breakage, failure, or permanent deformation that causes the clearance between door and frame to vary 
more than<MET> 2 mm</MET><ENG> 1/16 inch</ENG> from the original dimension.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   INSTALLATION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1.1   <SUB>Installation Supervision</SUB></TTL><BRK/>
<BRK/>
<TXT>Furnish the services of a qualified installation engineer or technician regularly employed by the shielding manufacturer/fabricator 
for a minimum of three 8 hours working days to instruct Contractor personnel in the installation of the RFI shield.  
A qualified installation technician is acceptable in lieu of a qualified installation engineer.  <TST>After the shielded 
enclosure has been completely installed including RF filters, vents, and exhaust fans, furnish the services of 
the engineer or technician described herein to inspect the installation for compliance with the specifications.  
The inspection shall be made before any finishes or the concrete topping coat are installed.</TST></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.2   Panel Installation</TTL><BRK/>
<BRK/>
<TXT>Lay panels in a straight line with true, level, and even surfaces and with the joints in alignment; install them 
in accordance with the shielding manufacturer's recommendations.  Exercise care while handling and installing 
metal shielding panels to ensure that panels are not damaged. Clean exposed surfaces of all dirt, finger marks, 
and foreign matter resulting from manufacturing processes, handling, or installation.  Inside the enclosure, 
mount items including boxes, conduits, fixtures, and switches directly to the RF panels with<MET> 16 mm</MET><ENG> 5/8 inch</ENG> long, 
zinc-plated, self-tapping screws.  Keep electrical conduits as close to RF shielding as possible.  Do not use 
framing-joining system bolts to mount material and equipment.  If material and equipment penetrate shielded enclosure, 
seam weld or solder materials and equipment to both shielding surfaces.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.3   Surface Preparation</TTL><BRK/>
<BRK/>
<TXT>Clean and buff surfaces to ensure good electrical contact with shielding surface.  Remove paint or other coverings 
on mating surfaces of special boxes such as for fire alarm systems, buzzers, and signal lights, including areas 
between box and cover, box and wall, and box and conduit.  Remove insulating material to maintain a low-resistance 
ground system and to ensure firm mating of metal surfaces.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.4   Floor Panel Setting</TTL><BRK/>
<BRK/>
<TXT>Place a polyethylene film of 6-mil thickness over the structural floor of the parent room before any other work 
is set thereon.  Provide a<MET> 3 mm</MET><ENG> 1/8 inch</ENG> thick layer of hardboard over this film with joints loosely butted.  
Over this layer provide an additional layer of similar filler material of equal thickness as the projection of 
the framing-joining member from the bottom surface of the floor panel leaving no more than<MET> 6 mm</MET><ENG> 1/4 inch</ENG> space 
between the hardboard and the framing-joining member.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.2   FRAMING-JOINING SYSTEM</TTL><BRK/>
<BRK/>
<TXT>Tighten screws with a calibrated adjustable torque wrench so that equal torque can be set on each screw.  (Proper 
torque values will be approximately<MET> 9 Nm</MET><ENG> 80 inch pounds</ENG>, but may vary somewhat depending on the manufacturer).</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3   DOOR ASSEMBLIES</TTL><BRK/>
<BRK/>
<TXT>Mount so that the clearance between the door edges and frame shall not vary more than<MET> 2 mm</MET><ENG> 1/16 inch</ENG> and the 
innerface of the door periphery does not vary more than<MET> 2 mm</MET><ENG> 1/16 inch</ENG> from the plane of the face of the stop.  
Through-bolt hinges to the door and the frame.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4   LINE FILTERS</TTL><BRK/>
<BRK/>
<TXT>Provide filters for incoming electrical power lines [, including neutrals,] and for incoming telephone and signal 
lines.  Support filters independently of the shielding.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5   WAVEGUIDE-TYPE AIR VENTS</TTL><BRK/>
<BRK/>
<TXT>[Provide each inlet and return air duct with the number and size of waveguide-type air vents at each location 
where the ducts enter the shielded enclosure.]  [As a minimum, provide each enclosure with one <MET> 300 mm</MET><ENG> 12 inch</ENG>
 square and one<MET> 300 mm</MET><ENG> 12 inch</ENG> square return waveguide-type air vent.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6   EXHAUST FAN</TTL><BRK/>
<BRK/>
<TXT>Mount on [wall] [or] [ceiling] over the exhaust vent on the exterior surface of shielded enclosure.  Provide 
power from electrical source exterior to the shielded enclosure.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7   CONDUCTOR INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Provide filtered conductors in conduit, except for coaxial cables, from filter to shielding and penetrate the 
enclosure through threaded rigid steel conduits.  [Twist conductors leading from the filters and conductors inside 
the shielded enclosure approximately 10 turns per foot in the conduit.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8   GROUNDING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If not specified in Division 16, "Electrical," the following sentence 
shall be added: "Wires inside the enclosure and for a distance of at least<MET> 15 
meters</MET><ENG> 50 feet</ENG> outside of the enclosure shall be enclosed in a grounded, threaded 
rigid steel conduit system."</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Extend the grounding stud through and [bolt] [weld] it to the electrical power panel with a minimum No. 4 AWG 
insulated stranded copper conductor to effectively serve as a single grounding point for the completely assembled 
shielded enclosure, both internally and externally.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.9   SERVICE ENTRANCE PLATE</TTL><BRK/>
<BRK/>
<TXT>Install RF connectors for coaxial cable and other RF shielded cable on entrance plate.  Soft solder connectors 
to the plate.  If location of plate is not indicated, mount plate in wall panel adjacent to power line filters.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.10   FIELD TESTS</TTL><BRK/>
<BRK/>
<SPT><TTL>3.10.1   Seam <SUB>Leak Detection Testing</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  SELDS testing the seams in the floor shielding is usually very difficult 
because you cannot "sniff" on both sides (assuming the shield is on the ground 
level).  To circumvent this problem SELDS loops may be positioned beneath the 
floor shield for SELDS testing.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><TST>Continuously test seams during fabrication using the SELDS, commonly known as a "sniffer."  Upon completion of 
the basic shielded enclosure, before applying any metal primer or installing any accessories, test the entire 
shielded enclosure with the SELDS.  Install terminal points on the shielding exterior and permanently attach 
test leads on two sets of diagonally opposing corners during construction for use with the SELDS. Continuously 
probe seams with the test receiver set to detect abrupt change of shielding level greater than 10 dB on the "shielding 
unit" scale. Clearly mark points having change greater than 10 dB and repair the seam to meet the specified requirement.</TST>
  Retest each repaired point until there are no points on seams which fail test.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.10.2   <SUB>Attenuation Testing</SUB></TTL><BRK/>
<BRK/>
<TXT>[Furnish the services of an independent testing laboratory, approved by the Contracting Officer, to test the 
shielded enclosure.  Certify that laboratory is equipped and staffed to perform field tests of RF shielded enclosures 
and performs the tests as a normal service.]  [Final acceptance testing will be by the Government.]  <TST>Conduct 
the final shielding acceptance test after penetrations have been completed, specifically including electrical 
and other utility penetrations.  In addition, the Contractor may schedule a complete or abbreviated test to verify 
that the shielding assembly is adequate prior to conducting final shielding acceptance test.</TST></TXT><BRK/>
<BRK/>
<SPT><TTL>3.10.2.1   Test Method</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Expert Government witness should be present for all final acceptance 
testing.  Note that IEEE Std 299 requires one magnetic field test (150 kHz), 
three electric field tests (200 kHz, 1 MHz, 18 MHz), and one plane wave test 
(400 MHz).  Also, note that IEEE Std 299 and NSA 65-6 differ on positioning 
of source and receiver.   IEEE Std 299 requires source outside and receiver 
inside the shield, while NSA 65-6 requires source inside and receiver outside 
(to simulate TEMPEST conditions).  For TEMPEST shielding effectiveness testing, 
continuous sweeping of seams at one or more plane wave frequencies should also 
be specified, in addition to testing around all door panels, filters, air duct 
penetrations and all other penetrations of the shielding at all test frequencies.  
If enclosure is designed specifically for attenuating microwave frequencies, 
specify additional test frequencies above 1 GHz.  Such testing is expensive 
and should only be used when a firm requirement exists (e.g., NSA-65-6).</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><TST>The test procedure, frequencies, and equipment shall be as specified in <RID>IEEE Std 299</RID> [plus the additional frequencies 
specified in the contract].  Perform the test as soon as possible after completion of the shielded enclosure, 
including installation of services, power/telephone/signal lines, RF filters, and waveguide vents.  Conduct tests 
with doors closed and the filters under normal load conditions.</TST></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.10.2.2   Additional Test Points</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use this paragraph if design includes strict tolerances, high attenuation 
requirements, and many penetrations.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><TST>Measure additional test points beyond those specified in <RID>IEEE Std 299</RID>. Test points include the periphery of doors 
and covers, handles, latches, power filter penetrations, air vent filters, telephone and control line filter 
penetrations, and points of penetration by pipes, tubes, and bolts.</TST></TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.10.3   Final In Service Testing</TTL><BRK/>
<BRK/>
<TXT><TST>Upon completion of acceptance checks, settings, and tests, show by demonstration in service that equipment and 
devices are in operating condition and performing the intended function.</TST>  Give the Contracting Officer five working 
days advance notice of the dates and times for checks and tests.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT>    <END/><BRK/></SEC>