<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"> <MTA NAME="SUBFORMAT" CONTENT="NEW"/><HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA      UFGS-11 72 13 (April 2006)<BRK/>
                                    ------------------------------<BRK/>
Preparing Activity:  <PRA>NAVFAC</PRA>         Replacing without change <BRK/>
                                    UFGS-11702 (August 2001)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 11 72 13</SCN><BRK/>
<BRK/>
<STL>MEDICAL EQUIPMENT, MISCELLANEOUS</STL><BRK/>
<DTE>04/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>miscellaneous medical 
equipment</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  On the drawings, show:</NPR><BRK/>
<BRK/>
<NPR>1.  Location of equipment.</NPR><BRK/>
<BRK/>
<NPR>2.  Height of turntable unit and control switch box above finish floor.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 167</RID><RTL>(1999; R 2004) Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip</RTL><BRK/><BRK/><RID>ASTM A 366/A 366M</RID><RTL>(1997e1) Standard Specification for Commercial Steel, Sheet, Carbon,(0.15 Maximum Percent Cold-Rolled</RTL><BRK/><BRK/><RID>ASTM B 221</RID><RTL>(2008) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes</RTL><BRK/><BRK/><RID>ASTM B 221M</RID><RTL>(2007) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric)</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)</ORG><BRK/><BRK/><RID>NEMA LD 3</RID><RTL>(2005) Standard for High-Pressure Decorative Laminates</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 768</RID><RTL>(2006; Rev thru Mar 2007) Standard for Combination Locks</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   RELATED REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Section <SRF>11 70 00</SRF> GENERAL REQUIREMENTS FOR MEDICAL AND DENTAL EQUIPMENT applies to this section with the additions 
and modifications specified herein.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete items that are not used and add additional items requiring drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
[<ITM><SUB>Specimen cabinet</SUB>, pass thru[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
<ITM><SUB>Autopsy table, tank type</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Autopsy table, L-shape</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Autopsy table, movable system</SUB> with sink[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Narcotic cabinet</SUB>, safe type[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Clock</SUB>, elapsed time, electric[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
[<ITM><SUB>Medicine center</SUB>,<MET> 1200 mm</MET><ENG> 48 inches</ENG> wide[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM>Miscellaneous medical equipment <SUB>items</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit equipment lists and manufacturer's literature for each specified item.  [Include manufacturer's 
standard colors and patterns for laminated plastic items.]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Autopsy table, tank type</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Autopsy table, L-shape</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Autopsy table, movable system</SUB> with sink, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Clock</SUB>, elapsed time, electric, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE DATA.</ITM><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   MATERIALS</TTL><BRK/>
<BRK/>
<TXT>Items not specified otherwise shall conform to the following requirements:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Aluminum alloy:  Equivalent in ultimate tensile, yield, and shear strengths to Alloy 6063-T5 
or 6063-T6; conforming to<MET> <RID>ASTM B 221M</RID></MET><ENG> <RID>ASTM B 221</RID></ENG>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Carbon steel:  <RID>ASTM A 366/A 366M</RID>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Laminated plastic: <RID>NEMA LD 3</RID>; colors and patterns as selected by the Contracting Officer 
from the manufacturer's standard colors and patterns.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Stainless steel:  <RID>ASTM A 167</RID>, Type 301, 302, or 304.  Exposed surfaces shall have a satin 
finish or a minimum No. 3 polished finish.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2   <SUB>ITEMS</SUB></TTL><BRK/>
<BRK/>
<SPT>[<TTL>2.2.1   <SUB>Specimen Cabinet</SUB>, Pass Thru</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include these items for Air Force projects only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Unit for through-the-wall passing of specimen containers from one area to another while preventing viewing between 
rooms through the apparatus. Include the following:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Design:  Cylindrically enclosed turntable with center divider and openings allowing access 
into compartments.  Cylinder mounted in frame housing for installation through wall.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Material:  Fabricate turntable and exposed housing of<MET> 1.2 mm thick</MET><ENG> 18 gage</ENG> stainless steel 
with exposed surfaces and edges ground and polished to a No. 4 finish.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Turntable:  Fabricate<MET> 300 mm</MET><ENG> 12 inches</ENG> in diameter; two compartments; removable and sterilizable.  
Provide with self-lubricating ball bearings, allowing unit to revolve freely with catches to 
prevent uncontrolled rotation.</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Regarding the text below, drawings shall indicate location and height 
of unit above the finished floor.  Unit may be located<MET> 750 to 1050 mm</MET><ENG> 30 to 
42 inches</ENG> above finished floor in walls up to<MET> 175 mm</MET><ENG> 7 inches</ENG> thick.  Do not 
locate unit in a fire-rated partition.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">d.  Housing assembly:  Fabricate assembly compatible with wall thickness as indicated, enclosing 
turntable and incorporating an access door and trim to overlap rough opening.  Locate access 
door on receiving side of assembly.  Overall trim dimensions shall not exceed<MET> 400 by 400 mm</MET><ENG> 
16 by 16 inches</ENG>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Access door:  Fabricate to facilitate removal of turntable; include a key lock.  [Key passboxes 
in project the same.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Keys:  Furnish two keys per passbox.</ITM><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.2.2   <SUB>Autopsy Table, Tank Type</SUB></TTL><BRK/>
<BRK/>
<TXT>Trough-shaped design, approximately<MET> 2500 mm long by 750 mm wide by 900 mm high</MET><ENG> 100 inches long by 30 inches wide 
by 36 inches high</ENG>.  Include the following features:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  General construction:  Fabricate of stainless steel, joints welded and polished smooth, 
exposed surfaces with a satin finish, outer edges rounded, and interior corners coved to approximately<MET>
 10 mm</MET><ENG> 3/8 inch</ENG> radius.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Table top:</ITM><BRK/>
<BRK/>
<ITM>(1)  One-piece construction,<MET> 1.8 mm thick</MET><ENG> 14 gage</ENG> stainless steel, with raised rim edge</ITM><BRK/>
<BRK/>
<ITM>(2)  Top surface sloped to drain and provided with a removable strainer</ITM><BRK/>
<BRK/>
<ITM>(3)  Top edge of table graduated in centimeters.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Sink:  Single compartment,<MET> 300 by 500 by 275 mm</MET><ENG> 12 by 20 by 11 inches</ENG> deep, corners coved, 
provide knee-operated drain control, overflow, hot and cold water mixing valve with wrist blades, 
and gooseneck faucet.</ITM><BRK/>
<BRK/>
<ITM>(1)  Locate faucet between working area of table and sink or to one side of sink.  Faucet on 
outer end of table unacceptable.</ITM><BRK/>
<BRK/>
<ITM>(2)  Manifold sink waste and waste from table shall require only one waste connection.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Base frame:  Tubular legs and braces with adjustable bullet feet. Intersection of legs and 
braces welded and polished smooth.  Sharp edges unacceptable.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Aspirator assembly:  Water-powered, with control valve, built-in vacuum breaker, serrated 
nozzle outlet,<MET> 2400 mm</MET><ENG> 8 feet</ENG> of flexible hose, and suction bottle.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Irrigation assembly:  Dual-controlled hot and cold water flow regulated by a quick-opening, 
knee-operated valve or standard hand control valve; provide with serrated nozzle outlet, at 
least<MET> 2400 mm</MET><ENG> 8 feet</ENG> of flexible hose, and nozzled end piece.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Head rest:  Removable, rubber.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  Body slats:  Not less than<MET> 150 mm</MET><ENG> 6 inches</ENG> wide [, perforated]; provide at least five for 
each table.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">i.  Instrument tray:  With removable rubber cutting board.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">j.  Perimeter table flushing system:  With control valve and vacuum breaker.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">k.  Electrical duplex outlet with ground fault circuit interrupter (GFCI):  120-volt, 60 Hz.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">l.  Waste disposal: <MET> 370 watt</MET><ENG> 1/2 hp</ENG>, with switch and solenoid valve, 120-volt, 60 Hz.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.3   <SUB>Autopsy Table, L-Shape</SUB></TTL><BRK/>
<BRK/>
<TXT>L-shaped design, with enclosed storage areas and instrument drawer; stainless steel;<MET> 100 and 200 mm</MET><ENG> 4 and 8 inch</ENG>
 body supports; rubber headrest; hydro-aspirator with built-in vacuum breaker and table rinse hose;<MET> 175 mm</MET><ENG> 7 
inch</ENG> diameter by<MET> 50 mm</MET><ENG> 2 inch</ENG> deep pump with removable, perforated stainless steel strainer and basket with<MET> 13 
mm</MET><ENG> 1/2 inch</ENG> drain;<MET> 13 mm</MET><ENG> 1/2 inch</ENG> hot and cold water mixing faucet with swinging gooseneck spout, wrist-operated 
handles and hot and cold water inlet control valves for aspirator.  Include the following features:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Stainless steel specimen instrument tray.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b. <MET> 370 watt</MET><ENG> 1/2 hp</ENG> waste disposer with switch, vacuum breaker, solenoid valve, and standpipe; 
120-volt, 60 Hz.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Hard rubber cutting board,<MET> 450 mm wide by 600 mm long by 25 mm</MET><ENG> 18 inches wide by 24 inches 
long by one inch</ENG> thick.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Perforated viscera basket.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Graduated table edge in centimeters.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Autopsy scale with<MET> 325 mm</MET><ENG> 13 inch</ENG> dial.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.4   <SUB>Autopsy Table, Movable System</SUB> With Sink</TTL><BRK/>
<BRK/>
<TXT>Autopsy system utilizing autopsy tables in conjunction with stationary service island equipped with operator 
work facilities; include enclosed storage areas and instrument drawer; stainless steel;<MET> 100 and 200 mm</MET><ENG> 4 and 
8 inch</ENG> body supports; rubber headrest; hydro-aspirator with built-in vacuum breaker and table rinse hose;<MET> 13 
mm</MET><ENG> 1/2 inch</ENG> hot and cold water mixing faucet with swinging gooseneck spout, wrist-operated handles and hot and 
cold water inlet control valves for aspirator.  Include an autopsy table, nominal<MET> 2030 by 815 by 890 mm</MET><ENG> 80 by 
32 by 35 inches</ENG> high, and a service island, nominal<MET> 500 by 815 mm by 890 mm</MET><ENG> 19 5/8 by 32 by 35 inches</ENG> high.  
Stationary service island shall include cabinet unit containing plumbing.  Include the following features:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Stainless steel specimen instrument tray.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b. <MET> 370 watt</MET><ENG> 1/2 hp</ENG> waste disposer with switch, vacuum breaker, solenoid valve, and standpipe; 
120-volt, 60 Hz.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Hard rubber cutting board,<MET> 450 mm wide by 600 mm long by 25 mm</MET><ENG> 18 inches wide by 24 inches 
long by one inch</ENG> thick.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Perforated viscera basket.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Graduated table edge in centimeters.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Autopsy table with<MET> 325 mm</MET><ENG> 13 inch</ENG> dial.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Irrigation hose connection controlled by thermostatic water-mixing valve.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  Duplex electrical outlet with GFCI.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">i.  Sink,<MET> 290 by 500 by 275 mm</MET><ENG> 11 1/2 by 20 by 11 inches</ENG> deep, equipped with faucet swing spout 
and wrist blades.  Specimen basket shall hang inside sink.  Removable swing drain to receive 
mobile table drainage.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.5   <SUB>Narcotic Cabinet</SUB>, Safe Type</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate with fastening details for cabinet.  If fastening has not 
been detailed, include components necessary for tamperproof fastening.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Carbon steel cabinet for storage of controlled substances, with overall dimensions approximately<MET> 600 mm high 
by 600 mm across face by 300 mm</MET><ENG> 24 inches high by 24 inches across face by 12 inches</ENG> front to back.  Include 
the following:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Construction:  Fabricate cabinet body of at least<MET> 1.8 mm thick</MET><ENG> 14 gage</ENG> steel, with door 
and frame fabricated to produce maximum rigidity.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Door:  Fabricated of minimum<MET> 2.5 mm thick</MET><ENG> 12 gage</ENG> steel.  Recess exterior face of door in 
relation to front face of cabinet so that top and bottom of cabinet overhang hinge pin.  Hang 
door on full length piano hinge, with leaves of hinges welded to door and frame and with hinge 
pin fixed to stationary leaf.  Hinge door [on [_____] side].</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Combination lock:  <RID>UL 768</RID>, Group 2.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Indicator light:  Provide red warning light [on face of exterior cabinet] [as indicated] 
that illuminates when door is unlocked.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.6   <SUB>Clock</SUB>, Elapsed Time, Electric</TTL><BRK/>
<BRK/>
<TXT>Electrically powered, round face, dial-type, suitable for use in operating rooms.  Include the following features:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Elapsed time interval displayed in hours, minutes, and seconds.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Flush mounting.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Instantaneous reset.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Time display:  12 hours in Arabic numerals.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Finishes:</ITM><BRK/>
<BRK/>
<ITM>(1)  Case:  [Aluminum] [Enameled metal].</ITM><BRK/>
<BRK/>
<ITM>(2)  Dial face:  White.</ITM><BRK/>
<BRK/>
<ITM>(3)  Sweep second hand:  Red.</ITM><BRK/>
<BRK/>
<ITM>(4)  Minute indicator numerals:  Black.</ITM><BRK/>
<BRK/>
<ITM>(5)  Hour indicator numerals:  Red.</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Height of control switch box for control shall be indicated on the drawings.  
In rooms where explosive anesthetics are anticipated, the bottom of this box 
shall be at least<MET> 1500 mm</MET><ENG> 60 inches</ENG> above finished floor.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">f.  Control panel,<MET> 150 mm</MET><ENG> 6 inches</ENG> square, for installation in a double-gang switch box, completely 
wired and assembled, including the following:</ITM><BRK/>
<BRK/>
<ITM>(1)  Indicator light that illuminates when timer is on.</ITM><BRK/>
<BRK/>
<ITM>(2)  Indicator light that illuminates when timer is in reset mode.</ITM><BRK/>
<BRK/>
<ITM>(3)  Switch:  Start/stop.</ITM><BRK/>
<BRK/>
<ITM>(4)  Switch:  Reset.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.7   Dispenser, Brush, Arm and Foot</TTL><BRK/>
<BRK/>
<TXT>Provide wall-mounted unit, fabricated of<MET> 1.8 mm thick</MET><ENG> 14 gage</ENG> stainless steel, with overall dimensions approximately<MET>
 50 mm deep by 535 mm long by 110 mm</MET><ENG> 2 inches deep by 21 inches long by 4 3/8 inches</ENG> wide.  Include the following 
features:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Dispenser, removable for sterilization.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Arm operator fabricated from<MET> 1.5 mm thick</MET><ENG> 16 gage</ENG> stainless steel with automatic spring 
return.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Foot pedal operator, fabricated from<MET> 1.8 mm thick</MET><ENG> 14 gage</ENG>stainless steel with spring-loaded 
return and<MET> 5 mm</MET><ENG> 3/16 inch</ENG> thick nonslip bottom pad.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Capacity, 12 to 14 brushes of industry standard make and size.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.8   Dispenser, Soap, Foot Operated</TTL><BRK/>
<BRK/>
<TXT>Provide foot-operated, wall-mounted dispenser suitable for dispensing liquid surgical soap.  Include the following 
features:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Dispensing tube assembly, stainless steel, with drip-proof nozzle.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Foot pedal pump with flexible air tubing.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Jar, removable, one-quart capacity, polyethylene.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.9   <SUB>Medicine Center</SUB>,<MET> 1200 mm</MET><ENG> 48 Inches</ENG> Wide</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include these items for Air Force projects only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Self-contained station for storing, preparing, and dispensing medicines;<MET> 525 mm</MET><ENG> 21 inch</ENG> minimum to<MET> 600 mm</MET><ENG> 24 
inch</ENG> maximum width (front to back) by<MET> 1200 mm</MET><ENG> 48 inch</ENG> length (across face) by<MET> 1800 mm</MET><ENG> 72 inch</ENG> minimum to<MET> 2085 
mm</MET><ENG> 82 inch</ENG> maximum height.  Front surface of station in one plane, allowing station to be recessed.  Provide 
station completely assembled, with one service connection for each utility. Include the following features:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Construction:  Fabricate as an integral unit with exposed-to-view metal cabinet surfaces, 
both interior and exterior, of satin-finished or a minimum No. 3 polished finish stainless steel. 
Use heli-arc welding process with precautions taken to ensure noncorrosive condition.  Grind 
smooth and polish exposed welds and edges to match finish, including inside cabinets.  Provide 
countertop full width of cabinet with raised rim edge and integral sink.  Provide removable 
access panel on back wall of utility compartment under sink for access to service connections.  
Assembly shall permit servicing from front without disassembling unit.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Sink:  Stainless steel, minimum<MET> 1.5 mm thick</MET><ENG> 16 gage</ENG>, approximately<MET> 240 by 288 by 150 mm</MET><ENG>
 9 1/2 by 11 1/2 by 6 inches</ENG> deep, equipped with waste strainer and tailpiece.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Faucet:  Gooseneck with hot and cold water fittings with indexed cross handles or wrist 
blade handles.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Illumination:  Provide a recessed fluorescent lighting fixture with bulbs and translucent 
diffusing shield.  Locate switch in splash area above countertop.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Electrical outlet:  Provide 120-volt, 60 Hz duplex electrical outlet with GFCI, located 
in splash area above countertop and accessible without reaching over sink.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Storage Shelves:  Provide stepped shelves directly over countertop.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Door:  Double-pan hinged door at storage cabinets.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  Drawers:  Stainless steel construction, removable, with double-pan front for storage of 
syringe kits.  Extends fully on ball bearings and slides; provide with key lock.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">i.  Medicine card rack:  24-hour.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">j.  Medicine cup dispenser and waste container:  For disposable, one-ounce medicine cups.  Provide 
opening for disposal of used paper cups into a removable waste container concealed in lower 
cabinets.  Provide waste container.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">k.  Narcotic cabinet:  Locate in upper section of cabinet; provide with one pair of successive 
locking doors, each door requiring a separate key.  Insertion of key in outer lock shall automatically 
light a red warning light located [on face of cabinet] [as indicated] that remains on until 
lock is secured and both keys are removed.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">l.  Refrigerator:  Insulated, self-defrosting biological type, with minimum<MET> 0.125 cubic meter</MET><ENG>
 4.5 cubic foot</ENG> capacity.  Provide with three adjustable, moisture-proof shelves designed to 
allow air circulation.  Door to include gaskets, latch, and key lock.  Stainless steel interior 
surfaces.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">m.  Security door:  Provide a roll-type security door with lock to enclose medicine shelves.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">n.  Trim:  Provide stainless steel closure strips for recessed locations.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">o.  Dust cap:  Provide stainless steel sloping dust cap for each nonrecessed unit.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">p.  Keys:  Provide at least two keys for each lock on unit.  Key units separately.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">q.  Service characteristics:</ITM><BRK/>
<BRK/>
<ITM>(1)  Hot and cold water supply: <MET> 13 mm</MET><ENG> 1/2 inch</ENG>.</ITM><BRK/>
<BRK/>
<ITM>(2)  Waste: <MET> 38 mm</MET><ENG> 1 1/2 inches</ENG>.</ITM><BRK/>
<BRK/>
<ITM>(3)  Electrical:  120-volt, 60 Hz.</ITM><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.2.10   Item [_____ - _____]</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Insert identification number, name, and description with salient features 
for item not covered in this guide specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Unit shall be [_____].  Include the following features:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  [_____]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  [_____]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  [_____].</ITM><BRK/>
<BRK/>
]</SPT></SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Install items at locations indicated.  Conform to installation provisions of Section <SRF>11 70 00</SRF> GENERAL REQUIREMENTS 
FOR MEDICAL AND DENTAL EQUIPMENT.  Provide final utility connections and utility service to equipment, including 
waste, under Sections <SRF>23 03 00.00 20</SRF> BASIC MECHANICAL MATERIALS AND METHODS, <SRF>22 00 00</SRF> PLUMBING SYSTEMS, 
<SRF>22 60 70</SRF> GAS AND VACUUM SYSTEMS FOR HEALTHCARE FACILITIES, <SRF>26 00 00.00 20</SRF> BASIC ELECTRICAL MATERIALS AND METHODS, 
and <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   FIELD QUALITY CONTROL</TTL><BRK/>
<BRK/>
<SPT><TTL>3.2.1   Tests</TTL><BRK/>
<BRK/>
<TXT><TST>Test each item to ensure equipment is operational and conforms to specification requirements.</TST></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.2   Inspection</TTL><BRK/>
<BRK/>
<TXT>Examine each item for visual defects and conformance to specifications.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT>    <END/><BRK/></SEC>