<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA   UFGS-21 13 21.00 20 (April 2006)<BRK/>
                                 ------------------------------<BRK/>
Preparing Activity:  <PRA>NAVFAC</PRA>      Replacing without change<BRK/>
                                 UFGS-13957N (September 1999)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATION</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 21 13 21.00 20</SCN><BRK/>
<BRK/>
<STL>FOAM FIRE EXTINGUISHING FOR FUEL TANK PROTECTION</STL><BRK/>
<DTE>04/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>automatic and manual 
tank farm fire extinguishing foam systems</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  It should not be assumed that an automatic system will always be required.  
The NAVFAC Engineering Field Division Fire Protection Engineer will provide 
guidance on whether automatic operation or automatic detection with manual operation 
is required.  Factors to be considered include products stored, proximity to 
Department of Defense Fire Department(s) and facility operations and manning. 
When the type of operation required is determined, carefully edit this guide 
specification to include only those features and elements necessary to provide 
that type of operation.  For truck or rail car loading/unloading rack protection 
use Section 21 13 22.00 20 FOAM FIRE EXTINGUISHING FOR HAZ/FLAM MATERIAL FACILITY.  
Assure that up to date reliable hydraulic data is used in design of the project.  
System requirements must conform to Unified Facilities Criteria (UFC) 3-600-01 
Design: Fire Protection Engineering for Facilities.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: If there are questions concerning type of foam systems required, consult 
the Engineering Field Division, Naval Facilities Engineering Command.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following information shall be shown on the project drawings:</NPR><BRK/>
<BRK/>
<NPR>1.  Location and detail of each foam system supply riser, deluge valve, water 
motor alarm, fire department inlet connection, foam hydrants, hand hose stations, 
water monitor nozzles, foam chambers, and associated electrical connections.</NPR><BRK/>
<BRK/>
<NPR>2.  Point of connection to the existing water distribution system.</NPR><BRK/>
<BRK/>
<NPR>3.  Location of foam system control valves and post indicator valves.</NPR><BRK/>
<BRK/>
<NPR>4.  Area(s) of foam system coverage, with zone designations (if multiple zones).  
Do not show piping layout.</NPR><BRK/>
<BRK/>
<NPR>5.  Capacity, height, and type of fuel tank to be protected.</NPR><BRK/>
<BRK/>
<NPR>6.  For pipe larger than <MET>305 mm</MET> <ENG>12 inches</ENG>, detail methods of anchoring pipe 
including pipe clamps and tie rods.</NPR><BRK/>
<BRK/>
<NPR>7.  Location of foam proportioning equipment and storage tank.</NPR><BRK/>
<BRK/>
<NPR>8.  Show locations of control panel, annunciator(s), alarm devices, manual actuation 
stations, point of connection to the base fire alarm system, remote trouble 
device, point of connection to the incoming power supply and fusible safety 
switch.  Do not show conduit sizes or number of conductors for DC circuits.  
Show mounting details for heat detectors, however, do not show locations of 
detectors.</NPR><BRK/>
<BRK/>
<NPR>9.  Show single line riser diagram for all detection, activation, and alarm 
circuits. Connection of equipment shall be indicated by circuit runs and not 
conduit runs.  Do not indicate number and size of conductors for interconnection 
of fire alarm components.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>AMERICAN WATER WORKS ASSOCIATION (AWWA)</ORG><BRK/><BRK/><RID>AWWA C500</RID><RTL>(2002; R 2003) Metal-Seated Gate Valves for Water Supply Service</RTL><BRK/><BRK/><RID>AWWA C651</RID><RTL>(2005; Errata 2005) Standard for Disinfecting Water Mains</RTL><BRK/><BRK/></REF><REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 53/A 53M</RID><RTL>(2007) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless</RTL><BRK/><BRK/></REF><REF><ORG>FM GLOBAL (FM)</ORG><BRK/><BRK/><RID>FM P7825</RID><RTL>(2005) Approval Guide</RTL><BRK/><BRK/></REF><REF><ORG>FOUNDATION FOR CROSS-CONNECTION CONTROL AND HYDRAULIC RESEARCH (FCCCHR)</ORG><BRK/><BRK/><RID>FCCCHR List</RID><RTL>(continuously updated) List of Approved Backflow Prevention Assemblies</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 11</RID><RTL>(2005; Amendment 1 2006; Amendment 2 2007) Low-, Medium- and High- Expansion Foam Systems</RTL><BRK/><BRK/><RID>NFPA 13</RID><RTL>(2006; Errata 2007; Amendment 1 2008) Installation of Sprinkler Systems</RTL><BRK/><BRK/><RID>NFPA 14</RID><RTL>(2006) Standard for the Installation of Standpipe, Private Hydrants and Hose Systems</RTL><BRK/><BRK/><RID>NFPA 16</RID><RTL>(2006) Installation of Foam-Water Sprinkler and Foam-Water Spray Systems</RTL><BRK/><BRK/><RID>NFPA 24</RID><RTL>(2006) Standard for the Installation of Private Fire Service Mains and Their Appurtenances</RTL><BRK/><BRK/><RID>NFPA 30</RID><RTL>(2007; Errata 2008) Flammable and Combustible Liquids Code</RTL><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/><RID>NFPA 72</RID><RTL>(2006) National Fire Alarm Code</RTL><BRK/><BRK/></REF><REF><ORG>THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)</ORG><BRK/><BRK/><RID>SSPC Paint 22</RID><RTL>(1982; E 2004) Paint Specification No. 22 Epoxy-Polyamide Paints (Primer, Intermediate, and Topcoat)</RTL><BRK/><BRK/><RID>SSPC Paint 25</RID><RTL>(1997; E 2004) Paint Specification No. 25Zinc Oxide, Alkyd, Linseed Oil Primer for Use Over Hand Cleaned Steel Type I and Type II</RTL><BRK/><BRK/><RID>SSPC SP 11</RID><RTL>(1987; E 2004) Power Tool Cleaning to Bare Metal</RTL><BRK/><BRK/><RID>SSPC SP 3</RID><RTL>(2004; E 2004) Power Tool Cleaning</RTL><BRK/><BRK/><RID>SSPC SP 6</RID><RTL>(7) Commercial Blast Cleaning</RTL><BRK/><BRK/></REF><REF><ORG>U.S. DEPARTMENT OF DEFENSE (DOD)</ORG><BRK/><BRK/><RID>MIL-F-24385</RID><RTL>(Rev F; Am 1) Fire Extinguishing Agent, Aqueous Film Forming Foam (AFFF) Liquid Concentrate, for Fresh and Seawater</RTL><BRK/><BRK/><RID>MIL-P-24441</RID><RTL>(Rev C; Supp 1; INT Am 1) Paint, Epoxy-Polyamide</RTL><BRK/><BRK/></REF><REF><ORG>U.S. GENERAL SERVICES ADMINISTRATION (GSA)</ORG><BRK/><BRK/><RID>FS A-A-2962</RID><RTL>(Rev J) Enamel, Alkyd, Gloss, Low VOC Content</RTL><BRK/><BRK/><RID>FS A-A-58092</RID><RTL>(Basic) Tape, Antiseize, Polytetrafluoroethylene</RTL><BRK/><BRK/><RID>FS WW-S-2739</RID><RTL>(Basic) Strainers, Sediment:  Pipeline, Water, Air, Gas, Oil, or Steam</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 262</RID><RTL>(2004) Standard for Gate Valves for Fire-Protection Service</RTL><BRK/><BRK/><RID>UL 789</RID><RTL>(2004; Rev thru Aug 2008) Indicator Posts for Fire-Protection Service</RTL><BRK/><BRK/><RID>UL Fire Prot Dir</RID><RTL>(2008) Fire Protection Equipment Directory</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   DEFINITION</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Year 2000 compliant - means computer controlled facility components that accurately process 
date and time data (including, but not limited to, calculating, comparing, and sequencing) from, 
into, and between the twentieth and twenty-first centuries, and the years 1999 and 2000 and 
leap year calculations.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   RELATED REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Section <SRF>23 03 00.00 20</SRF> BASIC MECHANICAL MATERIALS AND METHODS, applies to this section, with the additions and 
modifications specified herein.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   SYSTEM DESCRIPTION</TTL><BRK/>
<BRK/>
<SPT><TTL>1.4.1   Design Requirements</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Identify the tanks which are to be protected by each system.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include only those NFPA codes applicable to the specific project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Design and [provide a new] [and] [modify an existing] aqueous film forming foam (AFFF) fuel tank protection system 
for [_____].  System shall provide uniform distribution of AFFF solution to provide complete coverage by surface 
application to the tank(s) indicated.  The design, equipment, materials, installation, and workmanship shall 
be in strict accordance with the required and advisory provisions of <RID>NFPA 11</RID>, <RID>NFPA 13</RID>, [<RID>NFPA 14</RID>,] <RID>NFPA 16</RID>, [<RID>NFPA 24</RID>
,] [<RID>NFPA 30</RID>,] <RID>NFPA 70</RID>, and <RID>NFPA 72</RID>, except as modified herein.  [Each] [The] system [shall be designed for earthquakes 
and] shall include all materials, accessories and equipment necessary to provide [each] [the] system complete 
and ready for use.  Design and install [each] [the] system to give full consideration to blind spaces, piping, 
electrical equipment, and all other construction and equipment to provide complete coverage in accordance with 
the drawings to be submitted for approval.  Devices and equipment for fire protection service shall be of a make 
and type listed by the Underwriter's Laboratories Inc. in the <RID>UL Fire Prot Dir</RID>, or approved by the Factory Mutual 
System and listed in <RID>FM P7825</RID>.  In the publications referred to herein, the advisory provisions shall be considered 
to be mandatory, as though the word "shall" had been substituted for "should" wherever it appears; reference 
to the "authority having jurisdiction" shall be interpreted to mean the [[_____] Division, Naval Facilities Engineering 
Command Fire Protection Engineer] [Corps of Engineers Contracting Officer].  Begin work at the point indicated.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.4.1.1   Shop Drawings</TTL><BRK/>
<BRK/>
<TXT>Prepare shop drawings for the <SUB>fire extinguishing system</SUB> in accordance with the requirements for "Plans" as specified 
in <RID>NFPA 11</RID> and "Working Plans" as specified in <RID>NFPA 13</RID>.  Each drawing shall be<MET> A1 841 x 594 mm</MET><ENG> 34 by 22 inches</ENG>
. Do not commence work until the design of [each] [the] system and the various components have been approved.  
Show:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Tank and tank farm area layout and include data essential to the proper installation of 
[each] [the] system.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Foam chambers, discharge nozzles and system piping layout annotated with reference points 
for design calculations.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Field wiring diagrams showing locations of devices and points of connection and terminals 
used for all electrical field connections in the system, with wiring color code scheme.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.1.2   Calculations</TTL><BRK/>
<BRK/>
<TXT>Submit design calculations for the system.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  <SUB>Hydraulic calculations</SUB> showing basis for design in accordance with <RID>NFPA 11</RID> and <RID>NFPA 13</RID>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  <SUB>Pressure discharge graphs or tables</SUB> showing relationship for foam chambers and discharge 
nozzles.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Substantiating <SUB>battery standby power requirements calculations</SUB>showing battery capacity, 
supervisory and alarm power requirements.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.1.3   <SUB>AFFF Containment and Disposal Plan</SUB></TTL><BRK/>
<BRK/>
<TXT>Submit AFFF containment and disposal plan as required under paragraph entitled "Environmental Protection."</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.1.4   <SUB>As-Built Drawings for the Fire Extinguishing System</SUB></TTL><BRK/>
<BRK/>
<TXT>Upon completion, and before final acceptance of the work, submit a complete set of as-built drawings [, including 
complete as-built circuit diagrams,] of each system.  Submit<MET> A1 841 x 594 mm</MET><ENG> 34 by 22 inch</ENG> reproducible as-built 
drawings on mylar film with<MET> 200 by 100 mm</MET><ENG> 8 by 4 inch</ENG> title block similar to contract drawings. Submit as-built 
drawings in addition to the record drawings required by Division 1.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.4.2   System Operation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For automatic operation include bracketed phrase.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Flow of water and AFFF shall be controlled by deluge valves.  Foam proportioning equipment shall activate automatically 
upon tripping of the deluge valve(s) for the corresponding foam system(s).  Valves shall be tripped by remote 
manual release stations [and by activation of the detection system].  No valve will be operated by a building 
fire evacuation alarm system.  Use of motor-operated valves is prohibited.  Once activated, system(s) shall operate 
until shut down manually.  Provide separate circuits from the control panel to each zone of initiating devices. 
Transmission of signals from more than one zone over a common circuit is prohibited.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.4.2.1   Tank System</TTL><BRK/>
<BRK/>
<TXT>Tank system shall be controlled by valves operated by remote manual release stations [and by activation of the 
detection system].</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>1.4.2.2   Monitor System</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where monitors are activated solely by manually opening a value (e.g. 
post indicator valve), show valves on plans.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Monitor nozzles shall be controlled by valves operated [by remote manual release stations separate from those 
used for tank systems or hose systems] [manually].</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>1.4.2.3   Hose System</TTL><BRK/>
<BRK/>
<TXT>Hose reels shall be controlled by valves operated by remote manual release stations, separate from those used 
for tank systems or monitor nozzles.</TXT><BRK/>
<BRK/>
]</SPT></SPT></SPT><SPT><TTL>1.5   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
[<TXT>The fire protection engineer, [_____] Division, Naval Facilities Engineering Command will review any approve 
all submittals in this section requiring Government approval.</TXT>]<BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For projects administered by the Pacific Division, Naval Facilities Engineering 
Command, use the optional "SUBMITTALS" article immediately below and delete 
the general "SUBMITTALS" article above.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
[<TXT>The [_____] Division, Naval Facilities Engineering Command, Fire Protection Engineer delegates the authority 
to the Quality Control (QC) Representative's U.S. Registered Fire Protection Engineer for review and approval 
of submittals required by this section.  Submit to the [_____] Division, Naval Facilities Engineering Command, 
Fire Protection Engineer one set of all approved submittals and drawings immediately after approval but no more 
later than 15 working days prior to final inspection.</TXT>]<BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Fire extinguishing system</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Pipe, fittings, and mechanical couplings</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Deluge valves</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Valves</SUB>, including gate, check, and globe[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Water motor alarms</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Foam chambers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Monitor nozzles</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Hose and nozzles</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Pipe hangers and supports</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Pressure switch</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Fire department inlet connections</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Master fire alarm boxes</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Auxiliary transmitters</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Radio fire alarm transmitters</SUB> [and interface panel][; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Master box location light</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Detection devices</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Storage batteries</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Alarm bells</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Alarm horns</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Annunciator panel</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Foam hydrants</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>AFFF concentrate storage tanks</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Proportioning equipment</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>AFFF concentrate</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
[<ITM><SUB>Strainers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
<ITM><SUB>Manual release stations</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Backflow preventers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Control panel</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Battery charger</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Data which describe more than one type of item shall be clearly marked to indicate which type 
the Contractor intends to provide.  Submit only originals.  Photocopies will not be accepted.  
Partial submittals will not be accepted.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-05 Design Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Hydraulic calculations</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Pressure discharge graphs or tables</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Battery standby power requirements calculations</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM>Hydrostatic testing of the <SUB>diaphragm pressure proportioning tanks</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Preliminary tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Acceptance tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit for all inspections and tests specified under paragraph entitled "Field Quality Control."</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Backflow preventers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Qualifications of installer</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>AFFF containment and disposal plan</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit installers qualifications as required under paragraph entitled "Qualifications of Installer."</ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Deluge valves</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Proportioning equipment</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Control panel</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>AFFF concentrate storage tanks</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Monitor nozzles</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Instructions for operating the <SUB>fire extinguishing system</SUB>, Data Package 4[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE DATA.  Furnish one complete 
set of data prior to the time that final acceptance tests are performed, and furnish the remaining 
sets before the contract is completed.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-11 Closeout Submittals</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>As-built drawings for the fire extinguishing system</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.6.1   <SUB>Qualifications of Installer</SUB></TTL><BRK/>
<BRK/>
<TXT>Prior to commencing work, submit data showing that the Contractor has successfully installed automatic foam fire 
extinguishing systems of the same type and design as specified herein, or that he has a firm contractual agreement 
with a subcontractor having the required experience.  Include the names and locations of at least two installations 
where the Contractor, or the subcontractor referred to above, has installed such systems.  Indicate the type 
and design of each system, and certify that the system has performed satisfactorily for a period of at least 
18 months.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For projects administered by the Pacific Division, Naval Facilities Engineering 
Command, include the following optional paragraph requiring the minimum qualification 
of a NICET Level-III technician for preparation of all fire protection system 
drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Qualifications of System Technician:  Installation drawings, shop drawing and as-built drawings shall be prepared, 
by or under the supervision of, an individual who is experienced with the types of works specified herein, and 
is currently certified by the National Institute for Certification in Engineering Technologies (NICET) as an 
engineering technician with minimum Level-III certification in Special Hazard System program.  Contractor shall 
submit data for approval showing the name and certification of all involved individuals with such qualifications 
at or prior to submittal of drawings.]</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.7   SPARE PARTS</TTL><BRK/>
<BRK/>
<TXT>Furnish the following spare parts:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  2 of each type of detector installed.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  1 of each type of audible and/or visual alarm device installed.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  2 of each type of fuse required by the system.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  5 complete sets of system keys.</ITM><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   DESIGN OF FOAM SYSTEMS</TTL><BRK/>
<BRK/>
<TXT>Design of fuel tank fire extinguishing foam systems shall be by hydraulic calculations for uniform distribution 
of AFFF solution over the protected area and shall conform to the NFPA standards listed above and to the requirements 
as specified herein.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.1   Tankside <SUB>Foam Chambers</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide chamber(s) as required by <RID>NFPA 11</RID>.  Provide each chamber with a manufacturer-approved diaphragm or rupture 
disk to prevent entrance of fuel vapors into system piping.  Upon discharge of AFFF, diaphragm or disk shall 
rupture, allowing foam to flow into the tank.  Chamber shall be air-aspirating type with screened air intake 
and hinged or removable inspection cover.  [Rupture disk or diaphragm is not required for open top, floating 
roof tanks].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   <SUB>Deluge Valves</SUB></TTL><BRK/>
<BRK/>
<TXT>Valves shall be operated by a detection system listed for releasing service and independent of the fire alarm 
system.  [Deluge valve clappers shall incorporate a latching mechanism that will not be affected by changes of 
pressure in the water system.]  If<MET> 150 mm</MET><ENG> 6 inch</ENG> valves are used in<MET> 200 mm</MET><ENG> 8 inch</ENG> risers, provide smoothly tapered 
connections.  In addition to automatic operation, arrange each valve for manual release at the valve.  Provide 
pressure gages and other appurtenances at the deluge valves as required by <RID>NFPA 13</RID>.  Provide a detection device 
at the end of each actuation circuit to test the circuit and mount the device between<MET> 1.80 and 2.40 meters</MET><ENG> 6 
and 8 feet</ENG> above the finish floor or grade.  Label each testing device to indicate the valve it activates.  [Provide 
remote manual releases [at [_____]] [where shown].]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.3   AFFF Solution Distribution</TTL><BRK/>
<BRK/>
<TXT>Distribution shall be essentially uniform from all foam chambers on any single tank.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.4   AFFF Solution Application Density</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Refer to MIL-HDBK-1008 and NFPA 11 governing the particular hazard to 
determine the density required. </NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Size system to provide the specified density when the system is discharging the specified total maximum required 
flow.  Application to tanks being protected shall be [_____]<MET> mL/sec per sq meter</MET><ENG> gallons per minute (gpm) per 
square foot</ENG> over the discharge area [with foam hose stream requirements of [_____]<MET> mL/sec</MET><ENG> gpm</ENG>] [, and with outside 
water hose stream [and monitor nozzle] requirements of [_____]<MET> mL/sec</MET><ENG> gpm</ENG>].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.5   Foam Chamber Discharge Area</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select first bracketed option for fixed roof tanks with or without interior 
floating pans. Select second bracketed option for floating roof tanks.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Area shall be over the [entire liquid surface] [annular ring seal between the tank wall and foam dam] as required 
by <RID>NFPA 11</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.6   Friction Losses</TTL><BRK/>
<BRK/>
<TXT>Calculate losses in pipe in accordance with the Hazen-Williams Formula with 'C' value of 100 for steel pipe, 
150 for copper tube, and 140 for cement lined ductile iron pipe.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.7   Location of Foam Chambers</TTL><BRK/>
<BRK/>
<TXT>Locate chambers on the tank wall just below the roof joint as required by <RID>NFPA 11</RID>.  Where two or more chambers 
are required, they shall be equally spaced around the tank circumference.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.8   Water Supply</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select first option if the water supply is provided directly from the 
base water distribution system and show or specify the point of connection. 
Select second option if the water supply is provided from fire pumps dedicated 
to the AFFF system, which are taking suction from a static water source. Select 
third option if the water supply is provided from booster fire pumps being supplied 
from the base water distribution system, and show or specify the point of connection 
to the base system.  Edit Section 13920, "Fire Pumps" and include as part of 
the project specification when using the second or third option.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Base hydraulic calculations on a static pressure of [_____]<MET> kPa (gage)</MET><ENG> pounds per square inch gage (psig)</ENG> with 
[_____]<MET> L/m</MET><ENG> gpm</ENG> being available at a residual pressure of [_____]<MET> kPa (gage)</MET><ENG> psig</ENG> at the point [indicated] [of 
connection with the base water distribution system].]</TXT><BRK/>
<BRK/>
<TXT>[Base hydraulic calculations on [_____] fire pump(s) running.  Provide fire pumps as specified in Section 
<SRF>21 30 00</SRF> FIRE PUMPS.]</TXT><BRK/>
<BRK/>
<TXT>[Base hydraulic calculations on [_____] fire pump(s) running, with a suction supply having a static pressure 
of [_____]<MET> kPa (gage)</MET><ENG> psig</ENG>with [_____]<MET> L/m</MET><ENG> gpm</ENG> being available at a residual pressure of [_____]<MET> kPa (gage)</MET><ENG> psig</ENG>
 at the point [indicated] [of connection with the base water distribution system].  Provide fire pumps as specified 
in Section <SRF>21 30 00</SRF> FIRE PUMPS.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.9   Duration of Discharge</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For discharge duration, consult NFPA 11 and NFPA 30.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>System shall apply foam solution over the discharge area for a minimum of [_____] minutes [while simultaneously 
discharging foam solution through hose lines for a minimum of [_____] minutes]. Reduction of the discharge duration 
based on a discharge rate higher than the specified minimum is not permitted.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2   <SUB>DETECTION DEVICES</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide electric heat detectors.  All wiring shall be supervised and installed in protective metal conduit or 
tubing.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.1   <SUB>Control Panel</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select either "Class B" or "Class A" supervision ("Style B" or "Style 
D" as defined by NFPA 72).  "Class B" supervision which will normally be used, 
provides a trouble indication when a failure occurs in a circuit.  "Class A" 
supervision provides a trouble indication when a fault occurs in a circuit and 
at the same time allows continued operation of that circuit.  "Class A" supervision 
should be used for strategically critical facilities.  Select first ("Class 
B") or second ("Class A") supervisory option accordingly.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide a remote trouble bell or buzzer in a constantly attended area 
if the control panel is not so located.  Provide a trouble bell at the control 
panel if the panel is located in a high noise area. Coordinate location of remote 
trouble bell and remote annunciator panel when both are provided.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Modular type panel installed in a [flush] [surface] mounted steel cabinet with hinged door and cylinder lock.  
Switches and other controls shall not be accessible without the use of a key.  The control panel shall be a neat, 
compact, factory-wired assembly containing all parts and equipment required to provide specified operating and 
supervisory functions of the system. Panel cabinet shall be finished on the inside and outside with factory-applied 
enamel finish.  Provide main annunciator located on the exterior of the cabinet door or visible through the cabinet 
door.  Provide audible trouble signal.  Provide prominent engraved rigid plastic or metal identification plates, 
or silk-screened labels attached to the rear face of the panel viewing window, for all lamps and switches.  System 
power shall be 120 volts ac service, transformed through a two winding isolation transformer and rectified to 
24 volts dc for operation of all system initiating, actuating, signal sounding, trouble signal and fire alarm 
tripping circuits.  System shall be electrically supervised on all circuits.  [A ground fault condition or a 
single break in any circuit which prevents the required operation of the system shall result in the operation 
of the system trouble signal.]  [A single open or ground fault condition in any detection (initiating) [or signaling] 
circuit shall not result in any loss of system function, but shall cause the actuation of system trouble signals.  
A ground fault condition or single break in any other circuit shall result in the activation of the system trouble 
signals.]  Loss of ac power, a break in the standby battery power circuits, or abnormal ac power or low battery 
voltage shall result in the operation of the system trouble signals.  The abnormal position of any system switch 
in the control panel shall result in the operation of the system trouble signals.  Trouble signals shall operate 
continuously until the system has been restored to normal at the control panel.  [Provide a<MET> 100 mm</MET><ENG> 4 inch</ENG> remote 
system trouble bell [or buzzer], installed [in a constantly attended area] [where shown], arranged to operate 
in conjunction with the integral trouble signals of the panel.  Provide remote bell [or buzzer] with a rigid 
plastic or metal identification sign which reads "FOAM SYSTEM TROUBLE."  Lettering on identification sign shall 
be a minimum of<MET> 25 mm</MET><ENG> one inch</ENG> high.] Control panel, batteries, and battery charger shall be weatherproof type 
or located in an area not subject to water damage.  System control panel shall be UL listed or FM approved for 
extinguishing system control (releasing device service). [Control panel initiating circuits shall be intrinsically 
safe for use with line-type heat detection systems.]  Permanently label all switches. Provide panel with the 
following switches:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Trouble silencing switch which transfers audible trouble signals (including remote trouble 
devices, if provided) to an indicating lamp.  Upon correction of the trouble condition, audible 
signals will again sound until the switch is returned to its normal position, or the trouble 
signal circuit shall be automatically restored to normal upon correction of the trouble condition.  
The silencing switch may be a momentary action, self-resetting type.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Alarm silencing switch which when activated will silence all associated alarm devices without 
resetting the panel, and cause operation of system trouble signals.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Individual zone disconnect switches which when operated will disable only their respective 
initiating circuit and cause operation of the system and zone trouble signals.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Reset switch which when activated will restore the system to normal standby status after 
the cause of the alarm has been corrected, and all activated initiating devices reset.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Lamp test switch.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[f.  City disconnect switch which when activated will disconnect the coded device and cause 
operation of the system trouble signal.]</ITM><BRK/>
<BRK/>
<SPT><TTL>2.2.1.1   Main Annunciator</TTL><BRK/>
<BRK/>
<TXT>Provide integral with the main control panel.  Provide separate alarm and trouble lamps for each zone alarm initiating 
circuit as indicated below, located on the exterior of the cabinet door or visible through the cabinet door.  
Lamps shall be LED (Light Emitting Diode) type.  Supervision will not be required provided a fault in the annunciator 
circuits results only in loss of annunciation and will not affect the normal functional operation of the remainder 
of the system.  Each lamp shall provide specific identification of the [zone] [area] [device] by means of a permanent 
label. In no case shall zone identification consist of the words "Zone 1," "Zone 2," etc., but shall consist 
of the description of the [zone] [area] [device].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.1.2   Initiating Zones</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  List zones from 1 to x, with a brief description of each zone; e.g. "Zone 
1:  Tank No. 123".  Expand this list as necessary to identify all the zones 
required for the project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Shall be arranged as follows:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">Zone 1:  [_____]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">Zone 2:  [_____]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">Zone 3:  [_____]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">Zone x:  [_____]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.1.3   Remote <SUB>Annunciator Panel</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate location of remote trouble bell and remote annunciator panel 
when both are provided.</NPR><BRK/>
<NPR>Locate panel at or near the building entrance to allow fire department quick 
access to panel.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Locate as shown.  Panel shall duplicate all requirements specified for the main control panel annunciator, except 
that in lieu of individual zone trouble lamps a single common system trouble lamp may be provided.  Lamps shall 
be LED (Light Emitting Diode) type, except lamps used in backlit panels shall be LED or neon type.  Panel shall 
have a lamp test switch. Zone identification shall be by means of [permanently attached rigid plastic or metal 
plate(s)] [silk-screened labels attached to the reverse face of backlighted viewing window(s)].  Panel shall 
be of the [interior] [weatherproof] type, [flush] [surface] [pedestal]-mounted.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2.2   Auxiliary Power Supply</TTL><BRK/>
<BRK/>
<SPT><TTL>2.2.2.1   <SUB>Storage Batteries</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Consult the Public Works Department for battery preference.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide [sealed lead calcium,] [or] [sealed lead acid,] [or] [vented wet cell nickel cadmium,] batteries and 
charger.  Drycell batteries are not acceptable.  House batteries in the control panel or in a well constructed 
vented steel cabinet with cylinder lock, non-corrosive base, and louvered vents.  Provide batteries of adequate 
ampere-hour rating to operate the system under supervisory conditions for 60 hours, at the end of which time 
batteries shall be capable of operating the entire system in a full alarm condition for not less than [30] [15] 
minutes.  Provide calculations substantiating the battery capacity.  Provide reliable separation between cells 
to prevent contact between terminals of adjacent cells and between battery terminals and other metal parts.  
Provide batteries with post-and-nut, "L"-blade, or similar terminals.  Slip-on tab type terminals are not acceptable.  
When a separate battery cabinet is used, provide a fuse block for battery leads within the cabinets.  Finish 
the cabinet on the inside and outside with enamel paint.  Locate the top of the battery cabinet not more than<MET>
 1.22 meters</MET><ENG> 4 feet</ENG> above floor level.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.2.2   <SUB>Battery Charger</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide completely automatic high/low charging rate type charger capable of recovery of the batteries from full 
discharge to full charge in 24 hours or less.  Provide an ammeter for recording rate of charge and a voltmeter 
to indicate the state of battery charge under load.  Meters shall be factory installed, or factory-supplied plug-in 
modules.  Field installation of meters other than the panel manufacturer's plug-in modules is prohibited. Provide 
a trouble light to indicate when batteries are manually placed on a high rate of charge as part of the unit assembly 
if a high-rate switch is provided.  House charger in the control panel or battery cabinet.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>2.3   <SUB>MANUAL RELEASE STATIONS</SUB></TTL><BRK/>
<BRK/>
<TXT>Operation of a manual station shall cause the control panel to go into alarm condition and shall cause the valve(s) 
controlling the foam discharge to the corresponding hazard to trip.  Stations shall be of a type not subject 
to operation by jarring or vibration.  Stations shall have a dual action release configuration to prevent accidental 
system discharge. Break-glass-front stations are not permitted; however a pull lever break-glass-rod type is 
acceptable.  Station color shall be red.  Station shall provide positive visible indication of operation.  Restoration 
shall require use of a key or special tool.  Place warning signs at each station indicating that operation of 
the station will cause immediate AFFF discharge.  Where a fire alarm pull station is also mounted in the vicinity 
of a foam release station, separate the stations by at least<MET> one meter</MET><ENG> 3 feet</ENG> horizontally.  Provided permanent 
engraved rigid plastic or metal labels to clearly distinguish foam release stations from fire alarm stations, 
and to indicate the function of each foam release station. Stations shall be weatherproof type.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4   HEAT DETECTORS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the type of heat detector most suited for application or design.  
Do not use rate-of-rise detectors in areas subject to rapid temperature changes.  
Consult the Division Fire Protection Engineer.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.4.1   Spot-Type Heat Detectors</TTL><BRK/>
<BRK/>
<TXT>Designed for detection of fire by [combination fixed temperature rate-of-rise] [rate compensating] principle.  
Space detectors in accordance with their listing by UL or FM but not more than<MET> 15.25 meters</MET><ENG> 50 feet</ENG> apart around 
the tank perimeter.  For fixed roof tanks provide detectors on the tank wall just below the roof joint and at 
the center of the roof.  For floating roof tanks provide detectors on the interior side of the tank wall above 
the highest possible elevation of the roof.  Detectors shall be intermediate temperature rated as defined by <RID>
NFPA 72</RID>.  Detectors, located in hazardous locations as defined by <RID>NFPA 70</RID>, shall be types approved for such locations.  
Provide with terminal screw type connections.  Removal of detector head from its base shall cause activation 
of system trouble signal.  Detectors shall be weatherproof type.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.4.1.1   Combination Fixed Temperature Rate-of-Rise Detectors</TTL><BRK/>
<BRK/>
<TXT>Designed for [surface] [semi-flush] outlet box mounting and supported independently of conduit, tubing or wiring 
connections.  Contacts shall be</TXT><BRK/>
<TXT>self-resetting after response to rate-of-rise actuation.  Operation under fixed temperature actuation shall result 
in an external indication. Detector units located in areas subject to abnormal temperature changes shall operate 
on fixed temperature principle only.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.1.2   Rate Compensating Detector</TTL><BRK/>
<BRK/>
<TXT>Designed for [surface] [flush] [vertical unit] outlet box mounting and supported independently of conduit, tubing 
or wiring connections. Detectors shall be hermetically sealed and automatically resetting type which will operate 
when ambient air temperature reaches detector setting regardless of rate of temperature rise.  Detector operation 
shall not be subject to thermal time lag.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.4.2   Line-Type Heat Detectors</TTL><BRK/>
<BRK/>
<TXT>Provide [thermister] [or] [thermostatic] line-type heat detection cable with weather-resistant outer covering.  
Cable shall be suitable for severe industrial exposure.  Cable shall be UL listed or FM approved, shall be intermediate 
temperature rated as defined by <RID>NFPA 72</RID> and shall operate on fixed temperature only.  Locate on tank perimeter 
and mount as recommended by the manufacturer.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.5   ELECTRICAL WORK</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit Section 26 20 00, INTERIOR DISTRIBUTION SYSTEM and include as part 
of the project specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When project includes requirement for a building fire alarm system, include 
Section 28 31 74.00 20. When project requires only tying into an existing building 
fire alarm system, fire alarm wiring should be specified in this section.  Select 
the first 28 31 74.00 20 Section title when using the basic NAVFAC guide specification 
covering the subject work or select the second title when using the EFD regional 
guide specification covering the subject work.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Electrical work is specified in Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM, except for control [and fire alarm] 
wiring.  [Fire alarm system is specified in Section [<SRF>28 31 74.00 20</SRF> INTERIOR FIRE ALARM SYSTEM] ["Fire Alarm 
and Fire Detecting Systems (Local)"].]</TXT><BRK/>
<BRK/>
<SPT><TTL>2.5.1   Wiring</TTL><BRK/>
<BRK/>
<TXT>Provide control wiring and connections to fire alarm systems, under this section and conforming to <RID>NFPA 70</RID> and <RID>
NFPA 72</RID>.  Wire for 120 volt circuits shall be No. 12 AWG minimum solid conductor.  Wire for low voltage DC circuits 
shall be No. [14] [16] AWG minimum solid conductor [, except wire to remote annunciators, if provided, may be 
18 AWG minimum solid conductor].  All wiring shall be color coded. Wiring, conduit and devices exposed to weather, 
water or foam discharge shall be weatherproof.  Wiring, conduit and devices located in hazardous atmospheres, 
as defined by <RID>NFPA 70</RID> [and as shown], shall be explosion proof.  All conduit shall be minimum<MET> 20 mm</MET><ENG> 3/4 inch</ENG> 
size.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.2   Operating Power</TTL><BRK/>
<BRK/>
<TXT>Power shall be 120 volts AC service, transformed through a two winding isolation type transformer and rectified 
to 24 volts DC for operation of all signal initiating, signal sounding, trouble signal, and actuating (releasing) 
circuits.  Provide secondary DC power supply for operation of system in the event of failure of the AC supply.  
Transfer from normal to emergency power or restoration from emergency to normal power shall be fully automatic 
and shall not cause transmission of a false alarm.  Obtain AC operating power for control panel, and battery 
charger from the line side of the incoming building power source ahead of all building services. Provide independent 
properly fused safety switch, with provisions for locking the cover and operating handle in the "POWER ON" position 
for these connections and locate adjacent to the main distribution panel.  Paint switch box red and suitably 
identify by a lettered designation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.3   Conductor Identification</TTL><BRK/>
<BRK/>
<TXT>Identify circuit conductors within each enclosure where a tap, splice or termination is made.  Identify conductors 
by plastic coated self sticking printed markers or by heat-shrink type sleeves.  Attach the markers in a manner 
that will not permit accidental detachment.  Properly identify control circuit terminations.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.6   SYSTEM ACTIVATION</TTL><BRK/>
<BRK/>
<SPT><TTL>2.6.1   Tank System Activation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Depending on the tank size, more than one riser may be required for each 
tank.  Follow the requirements specified in NFPA 11.  Tank systems and hose 
systems shall be served by separate mains.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Each zone shall encompass one tank.  Upon activation of the tank system manual release station(s), [or the detection 
system], all foam chambers protecting that tank shall discharge foam.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.6.2   Monitor System Activation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where monitors are activated solely by manually opening a value (e.g. 
post indicator valve), delete this paragraph and show valves on plans.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Each zone shall encompass the monitors indicated.  Upon activation of a monitor manual release station, all piping 
to monitors in that zone shall be charged.  Provide a manual release station at each monitor.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.6.3   Hose System Activation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Tank systems and hose systems shall be served by separate mains.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Each] [The] zone shall encompass [all hose stations] [the hose stations indicated].  Hose stations shall be 
activated upon activation of a hose station manual release station.  Provide a manual release station at each 
hose station.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>2.7   ALARMS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.7.1   <SUB>Water Motor Alarms</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide weatherproof and guarded type alarm for each deluge valve.  Alarms shall sound locally on the flow of 
foam solution in each system to which it is connected.  Mount alarms on the outside of the outer walls of each 
building, at locations indicated.  When more than one alarm gong is provided, provide permanent engraved rigid 
plastic or metal signs indicating to which system each gong is connected.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2   Local Alarm</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete if a fire alarm system exists or is being provided under this 
project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide electric [<SUB>alarm horns</SUB>] [<SUB>alarm bells</SUB>] sound locally on operation of any system, regardless of whether 
water flows or not.  When more than one alarm is provided, provide permanent engraved rigid plastic or metal 
signs indicating to which system each alarm is connected.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.3   Fire Alarm</TTL><BRK/>
<BRK/>
<TXT>Provide equipment for the automatic transmittal of an alarm over the facility fire alarm system.  Arrange so 
that the detection system and the flow of solution in each system will actuate the alarm.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.7.3.1   <SUB>Pressure Switch</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide switch with SPDT contacts to automatically transmit alarms upon flow of water or AFFF.  Alarm actuating 
device shall [have mechanical diaphragm controlled retard device adjustable from 10 to 60 seconds and shall] 
instantly recycle.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.7.3.2   <SUB>Master Fire Alarm Boxes</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify master fire alarm boxes for connection to a positive non-interfering 
successive (PNIS) type base fire alarm system and when there is also a need 
for a new exterior coded fire alarm box. In mercantile, manufacturing, and industrial 
districts it shall not be necessary to travel in excess of one block or<MET> 150 
meters</MET><ENG> 500 feet</ENG> to reach an exterior fire alarm box.  Specify local energy tripping 
devices unless approved otherwise by the Division or District Fire Protection 
Engineer.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Master fire alarm boxes shall be of the coded, positive non-interfering type with succession features having 
a local energy type auxiliary tripping device.  Boxes shall be of the prewound, open-door pull-lever type. Mechanism 
shall be housed in a weatherproof cottage shell housing with metallic bronze or nickel-alloy or rigid plastic 
code number plate mounted on the exterior face of the cottage shell.  Operation of the actuating pull-lever shall 
cause the box to transmit four complete rounds of code. Driving springs shall have the capability to transmit 
not less than 8 complete four round groups of code before being rewound.  Boxes shall be designed for operation 
at 100 milliamperes and shall be capable of full operation between 70 and 120 milliamperes DC line current.  
Boxes shall have the ability to transmit signals through ground to overcome an open circuit.  Box mechanism shall 
be capable of transmitting signals at varying rates of speed ranging from electrical impulses at 3 1/4 second 
intervals to 1/4 second intervals and shall be field adjustable to any speed within this range.  Each box shall 
have a manual signaling key, telephone jack, silent test device and box shunt device.  Code wheel shall be metallic. 
Box code shall be as directed by the Contracting Officer.  Box shall be [wall] [pole] [pedestal]-mounted with 
center of box<MET> 1.50 meters</MET><ENG> 5 feet</ENG> above grade.  Mounting bolts, brackets, and fastenings shall be copper alloy 
or cadmium or zinc-coated steel.  Transmitter housing shall be finished in gloss red enamel.  Housing shall have 
a reflective, highly visible label imprinted with the word "FIRE" in minimum<MET> 50 mm</MET><ENG> two inch</ENG> block characters 
on both sides of the box.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.7.3.3   Automatic <SUB>Auxiliary Transmitters</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify automatic auxiliary transmitters for connection to a PNIS type 
base fire alarm system when there is no requirement for a new exterior coded 
fire alarm box.  For connection to a shunt non-interfering (SNI) type base fire 
alarm system, specify automatic auxiliary transmitters in all instances.  Master 
boxes are not manufactured for SNI systems.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Auxiliary transmitters shall be of the coded, [positive non-interfering type with succession features] [shunt 
non-interfering type].  Transmitters shall be [prewound spring mechanism type having a local energy type auxiliary 
tripping device] [or] [solid state electronic type utilizing form "A" or form "C" dry contacts] which, when activated 
by the fire alarm control panel, will transmit four rounds of code.  Driving springs if required shall have the 
capability to transmit not less than 8 complete four-round groups of code before being rewound.  [Electronic 
transmitters shall have a standby battery with the capacity to power the transmitter in a standby status for 
60 hours and then transmit not less than 8 complete four-round groups of code.] Transmitters shall be designed 
for operation at 100 milliamperes and shall be capable of full operation between 70 and 120 milliamperes DC line 
current.  Transmitters shall have the ability to transmit signals through ground to overcome an open circuit.  
Transmitters shall have a device to disconnect the transmitter for maintenance purposes. Code wheel if required 
shall be metallic.  Transmitter code shall be as directed by the Contracting Officer.  The transmitter shall 
be capable of transmitting signals at varying rates of speed ranging from electrical impulses at 3 1/4 second 
intervals to 1/4 second intervals and shall be field adjustable to any speed within this range.  Mechanism shall 
be housed in a wall mounted locked metal cabinet.  Cabinet shall be finished in gloss red enamel.  Provide engraved 
metallic bronze or nickel-alloy or rigid plastic code number plate mounted on face of transmitter housing.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.7.3.4   <SUB>Radio Fire Alarm Transmitters</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify radio fire alarm transmitters for bases having radio fire alarm 
systems.  Transmitters must be obtained from the manufacturer of the base system.  
Provide manufacturer's name, model number, color and frequency or frequencies 
to match the existing system.  Interface panels are required by some manufacturer's 
systems, whereas with other manufacturer's systems all required functions are 
contained within the transmitter enclosure.  Edit accordingly.  A level I Contracting 
Officer must approve use of this paragraph for specifying a proprietary product.  
Reason for specifying a proprietary product is that only the manufacturer of 
the existing system would have a transmitter which would be FM approved or UL 
listed for use with the existing base radio fire alarm system.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide a [_____] model [_____] radio [fire alarm [master box] [auxiliary transmitter]] [fire alarm [master box] 
[auxiliary transmitter] and model [_____] interface panel] [combination auxiliary transmitter and interface panel] 
to be compatible with the existing base system.  Not withstanding any other provisions of this contract, no other 
product will be acceptable. Transmitter shall operate on a frequency of [_____] MHz [AM] [FM]. Transmitter code 
number(s) shall be as specified by the Contracting Officer.  Transmitter [and interface] shall operate on 120 
VAC and shall also be provided with the manufacturer's approved battery charger and standby battery adequate 
to supply standby power for at least 60 hours. Transmitter housing shall be [red] [lime yellow] in color.  Mounting 
shall be [wall] [pole] [pedestal],<MET> 1.50 meters</MET><ENG> 5 feet</ENG> above grade.  [Arrange the transmitter(s) to send a separate 
alarm signal for each zone on the fire alarm control panel as specified in the paragraph entitled "Initiating 
Zones", and a common trouble signal for any trouble condition on the control panel.]  Provide antenna as recommended 
by the transmitter manufacturer.  Provide engraved metallic bronze or nickel-alloy or rigid plastic code number 
plate mounted on face of transmitter housing.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>2.7.4   Trouble Alarm</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete if a fire alarm system exists or is being provided under this 
project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide local [<MET>100 mm</MET><ENG>4 inch</ENG>] electric alarm [bell] [horn] [_____] to indicate trouble [or failure of the detection 
system] and label "Foam System Trouble".</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>2.8   MASTER BOX PEDESTAL</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select master box pedestal for pedestal mounted telegraphic master boxes.  
Select radio master box pedestal for pedestal mounted radio master boxes.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Construct pedestal of galvanized sheet metal with heavy cast iron base, designed to support the fire alarm box 
and light.  The shaft shall be rectangular in cross section with a hollow compartment inside, readily accessible 
and containing facilities for installing cable terminals.  Such facilities shall be capable of mounting no less 
than ten two-point terminals.  The pedestal shall have a suitable red and white finish of the same shades as 
those used for the fire alarm boxes.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.9   RADIO MASTER BOX PEDESTAL</TTL><BRK/>
<BRK/>
<TXT>Pedestal shall have a round aluminum barrel with a bell base, designed to support the radio transmitter, location 
light, and antenna.  The bell base shall contain a compartment with access plate to permit pulling and splicing 
of cables in the base.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.10   [<SUB>MASTER BOX LOCATION LIGHT</SUB>] [RADIO MASTER BOX LOCATION LIGHT]</TTL><BRK/>
<BRK/>
<TXT>Light shall be a vaportight, incandescent type fixture constructed of a cast aluminum housing and unbreakable, 
heat resistant, threaded ruby globe. The light shall be supported with<MET> 15 mm</MET><ENG> 1/2 inch</ENG> galvanized steel conduit 
screwed into the hub on the top of the master box.  Light shall be located approximately one foot above the master 
box.  Light shall be provided with an incandescent 25-watt, 130-volt AC extended service lamp.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11   <SUB>AFFF CONCENTRATE</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select percentage when specifying MIL-F-24385 concentrate.  Consult the 
facility fire department and the Division Fire Protection Engineer. MIL-F-24385 
does not cover alcohol resistant-type concentrate.  Specify UL listed alcohol 
resistant-type concentrate if there is a possibility of alcohol-based liquids 
being present.  When alcohol resistant foam is required, it must be used at 
the UL listed application rate.  Currently 3 percent alcohol resistant-type 
concentrate is not available.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[<RID>MIL-F-24385</RID>, [3] [6] percent] [UL listed alcohol/polar solvent resistant type].</TXT><BRK/>
<BRK/>
<SPT><TTL>2.11.1   Concentrate Fill Pump</TTL><BRK/>
<BRK/>
<TXT>Provide one pump to fill foam system tank.  Pump shall have a minimum flow rate of<MET> 27 L/m</MET><ENG> 7 gpm</ENG>.  Pump shall 
be complete with 115 VAC motor, fused switch, power cord with plug and<MET> 3 meters</MET><ENG> 10 foot</ENG> minimum suction and clear 
discharge hoses.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.12   DIAPHRAGM PRESSURE <SUB>PROPORTIONING EQUIPMENT</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the method of proportioning best suited for the project.</NPR><BRK/>
<BRK/>
<NPR>Diaphragm pressure proportioning systems operate by water pressure, require 
no electrical power, and minimal control circuitry for automatic operation. 
Maintenance requirements are minimal, however refilling the tank is a difficult 
operation requiring the services of a qualified technician to avoid rupturing 
the diaphragm.</NPR><BRK/>
<BRK/>
<NPR>Balanced pressure proportioning systems require reliable electrical power and 
more complex control circuitry for automatic operation.  In some cases an emergency 
generator will be required.  The primary advantage of the non-diaphragm systems 
is the ease in refilling the tanks.  Tanks may be refilled even while the system 
is in operation, if necessary. This feature is valuable when prolonged fire 
fighting operations may be encountered.</NPR><BRK/>
<BRK/>
<NPR>Skid-mounted balanced pressure proportioning systems perform proportioning at 
a central location, avoiding long runs of concentrate lines.  They are well 
suited for systems which have a relative narrow range of flow rates.</NPR><BRK/>
<BRK/>
<NPR>In-line balanced pressure proportioning is useful when there are multiple hazards 
with widely varying discharge rates which are to be supplied from the same proportioning 
system, and any time it is desired to proportion foam remotely at risers or 
discharge devices instead of at the pump room. Their disadvantage is the need 
for much more concentrate piping in the field.</NPR><BRK/>
<BRK/>
<NPR>Line proportioners (venturi type) are fixed-flow rate devices which are useful 
on relatively small systems which have only one set flow rate per proportioner.  
They require no electric power but have limited application, since they require 
high water pressure and low discharge back pressure.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Foam solution shall be produced by introducing AFFF concentrate into the water stream by the balanced pressure 
proportioning method using a diaphragm pressure tank and ratio controller.  [Provide proportioning system and 
storage tanks for hose lines independent of main proportioning system and tanks.]</TXT><BRK/>
<BRK/>
<SPT><TTL>2.12.1   <SUB>Diaphragm Pressure Proportioning Tanks</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When large quantities of AFFF concentrate are required, consider two 
or more tanks in parallel vs one large tank.  (This is in addition to reserve 
tanks.)  Approved diaphragm tanks larger than<MET> 9.50 - 11.40 cu meters</MET><ENG> 2,500 - 
3,000 gallons</ENG>are not readily available.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer must calculate foam tank capacity based on maximum flow for 
maximum duration to determine size of tank and space required.  Do not label 
foam tank capacity on drawing.  Exact tank size (which may be larger) will be 
determined by Contractor's hydraulic calculations.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Tanks shall be cylindrical steel ASME INTERNATIONAL (ASME) pressure vessels with a full Buna-N impregnated nylon 
inner tank or bladder designed to contain AFFF concentrate and to be used in conjunction with the concentrate 
ratio controller.  Tanks shall be designed for working pressure of<MET> [1206 kPa (gage)]</MET><ENG> [175 psig]</ENG> [_____] and hydrostatically 
tested at 1.5 times the working pressure in accordance with ASME standards at the factory.  Tanks shall have 
UL or FM label and ASME stamp affixed to the vessel.  Size tank to provide sufficient AFFF concentrate for the 
time specified when the system is discharging foam solution at total maximum system flow.  Also provide connected 
reserve tanks(s) of equal capacity.  Permanently label each tank with its capacity, type and percentage of concentrate, 
which system(s) it serves, and whether it is a main or reserve tank. Conspicuously post filling instructions 
near each group of tanks.  Provide a gage or unbreakable sight glass to permit visual determination of level 
of tank contents.  Prior to shop painting, abrasive blast clean tank exterior surface in accordance with <RID>SSPC SP 6</RID>
to a surface profile not to exceed<MET> 0.05 mm</MET><ENG> 2.0 mils</ENG> and provide a <RID>MIL-P-24441</RID> or SSPC coating system to the tank 
exterior.  Prime tank exterior with one coat of <RID>MIL-P-24441</RID>/1, Formula 150 or <RID>SSPC Paint 22</RID> primer applied to 
a dry film thickness of<MET> 0.076 mm</MET><ENG> 3 mils</ENG> and topcoat with one coat of <RID>MIL-P-24441</RID>/7 Formula 156 (red) or <RID>SSPC Paint 22</RID>
 topcoat (red) applied to a dry film thickness of<MET> 0.076 mm</MET><ENG> 3 mils</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12.2   Concentrate Ratio Controller</TTL><BRK/>
<BRK/>
<TXT>Ratio controller shall be a modified venturi device with AFFF concentrate feed line from diaphragm tank(s), and 
integral concentrate metering orifice.  Size for specified flow rate(s).</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.13   BALANCED PRESSURE PROPORTIONING SYSTEM</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the method of proportioning best suited for the project.</NPR><BRK/>
<BRK/>
<NPR>Diaphragm pressure proportioning systems operate by water pressure, require 
no electrical power, and minimal control circuitry for automatic operation. 
Maintenance requirements are minimal, however refilling the tank is a difficult 
operation requiring the services of a qualified technician to avoid rupturing 
the diaphragm.</NPR><BRK/>
<BRK/>
<NPR>Balanced pressure proportioning systems require reliable electrical power and 
more complex control circuitry for automatic operation.  In some cases an emergency 
generator will be required.  The primary advantage of the non-diaphragm systems 
is the ease in refilling the tanks.  Tanks may be refilled even while the system 
is in operation, if necessary. This feature is valuable when prolonged fire 
fighting operations may be encountered.</NPR><BRK/>
<BRK/>
<NPR>Skid-mounted balanced pressure proportioning systems perform proportioning at 
a central location, avoiding long runs of concentrate lines.  They are well 
suited for systems which have a relative narrow range of flow rates.</NPR><BRK/>
<BRK/>
<NPR>In-line balanced pressure proportioning is useful when there are multiple hazards 
with widely varying discharge rates which are to be supplied from the same proportioning 
system, and any time it is desired to proportion foam remotely at risers or 
discharge devices instead of at the pump room. Their disadvantage is the need 
for much more concentrate piping in the field.</NPR><BRK/>
<BRK/>
<NPR>Line proportioners (venturi type) are fixed-flow rate devices which are useful 
on relatively small systems which have only one set flow rate per proportioner.  
They require no electric power but have limited application, since they require 
high water pressure and low discharge back pressure.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Foam solution shall be produced by introducing AFFF concentrate into the water stream by the balanced pressure 
proportioning method using a pump and proportioner.  [Provide proportioning system and storage tanks for hose 
lines independent of main proportioning system and tanks.]</TXT><BRK/>
<BRK/>
<SPT>[<TTL>2.13.1   Skid-Mounted Balanced Pressure Proportioning System</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Choose this paragraph or the paragraph below entitled "In-Line Balanced 
Pressure Proportioning System."</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Self-contained, skid-mounted system, fully assembled at the factory and delivered complete and ready for use.  
Field connections shall be limited to water, electrical, and AFFF concentrate inputs, foam solution output, and 
foam concentrate return line to storage tank.  Size system for required flow rate(s).  The concentrate pump and 
all piping, valves, and fittings in contact with foam concentrate shall be of materials resistant to the corrosive 
effects of the AFFF concentrate.  Concentrate pump shall be electric motor driven, drip proof, 240/480 volts, 
60 Hz AC.  Activation and operation of system shall be fully automatic, with manual over-ride and manual shut-down.  
Provide permanent engraved rigid plastic or corrosion resistant metal instruction plate for emergency manual 
operation, along with a similarly constructed label for each control device.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.13.2   In-Line Balanced Pressure Proportioning System</TTL><BRK/>
<BRK/>
<TXT>Size system for required flow rates.  AFFF concentrate pump shall be positive displacement, electric motor driven, 
drip proof, 240/480 volts, 60 Hz AC.  System operation shall be fully automatic, with manual over-ride and manual 
shut-down.  Provide a pressure regulating device in the AFFF concentrate pump return line to maintain constant 
pressure on the concentrate piping system at all AFFF solution flow rates.  Provide an in-line balanced pressure 
proportioning device at each system riser to automatically balance the AFFF concentrate pressure with the water 
pressure at the riser to provide correct proportioning over the range of flow rates calculated for that riser.  
The pump and all piping, valves, and fittings in contact with the foam concentrate shall be of materials resistant 
to the corrosive effects of the AFFF concentrate.  Provide permanent engraved rigid plastic or corrosion-resistant 
metal instruction plate for emergency manual operation, along with a similarly constructed label for each control 
device.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.13.3   <SUB>AFFF Concentrate Storage Tanks</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer must calculate foam tank capacity based on maximum flow for 
maximum duration to determine size of tank and space required.  Do not label 
foam tank capacity on drawing.  Exact tank size (which may be larger) will be 
determined by Contractor's hydraulic calculations.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Consult the Division or District Fire Protection Engineer to determine 
need for reserve tanks.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Tank shall be designed for storage of AFFF concentrate at atmospheric pressure, and shall be [horizontal] [or] 
[vertical] cylindrical, fiberglass or polyethylene construction.  Tank shall have the following:  Drain valve 
located at the lowest point in the tank, connections for concentrate supply and return lines to the proportioners, 
top-mounted fill connections and inspection hatch, and a pressure/vacuum relief vent.  All openings and tank 
connections shall be installed at the factory, no holes shall be made in the tank shell in the field.  Tank shall 
include all necessary supports for free-standing installation.  Provide a gage or unbreakable sight glass to 
permit visual determination of level of tank contents, unless liquid level is clearly visible through shell of 
tank.  Size tank to provide sufficient AFFF concentrate for the time specified when the system is discharging 
foam solution at total maximum system flow.  [Also provide connected reserve tank(s) of equal capacity.]  Permanently 
label each tank with its capacity, type and percentage of concentrate, which system it serves [, and whether 
it is a main or reserve tank].</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.14   LINE PROPORTIONING (VENTURI TYPE) SYSTEM</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the method of proportioning best suited for the project.</NPR><BRK/>
<BRK/>
<NPR>Diaphragm pressure proportioning systems operate by water pressure, require 
no electrical power, and minimal control circuitry for automatic operation. 
Maintenance requirements are minimal, however refilling the tank is a difficult 
operation requiring the services of a qualified technician to avoid rupturing 
the diaphragm.</NPR><BRK/>
<BRK/>
<NPR>Balanced pressure proportioning systems require reliable electrical power and 
more complex control circuitry for automatic operation.  In some cases an emergency 
generator will be required.  The primary advantage of the non-diaphragm systems 
is the ease in refilling the tanks.  Tanks may be refilled even while the system 
is in operation, if necessary. This feature is valuable when prolonged fire 
fighting operations may be encountered.</NPR><BRK/>
<BRK/>
<NPR>Skid-mounted balanced pressure proportioning systems perform proportioning at 
a central location, avoiding long runs of concentrate lines.  They are well 
suited for systems which have a relative narrow range of flow rates.</NPR><BRK/>
<BRK/>
<NPR>In-line balanced pressure proportioning is useful when there are multiple hazards 
with widely varying discharge rates which are to be supplied from the same proportioning 
system, and any time it is desired to proportion foam remotely at risers or 
discharge devices instead of at the pump room. Their disadvantage is the need 
for much more concentrate piping in the field.</NPR><BRK/>
<BRK/>
<NPR>Line proportioners (venturi type) are fixed-flow rate devices which are useful 
on relatively small systems which have only one set flow rate per proportioner.  
They require no electric power but have limited application, since they require 
high water pressure and low discharge back pressure.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Size system for required flow rates.  Provide separate proportioner for each [tank] [,] [riser] [, or] [group 
of discharge devices required to operate simultaneously].  Ensure suction lift of proportioner(s) and system 
back pressure do not exceed limits specified by the proportioner manufacturer.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.14.1   AFFF Concentrate Storage Tank</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer must calculate foam tank capacity based on maximum flow for 
maximum duration to determine size of tank and space required.  Do not label 
foam tank capacity on drawing.  Exact tank size (which may be larger) will be 
determined by Contractor's hydraulic calculations.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Consult the Division or District Fire Protection Engineer to determine 
need for reserve tanks.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Tank shall be designed for storage of AFFF concentrate at atmospheric pressure, and shall be [horizontal] [or] 
[vertical] cylindrical, fiberglass or polyethylene construction.  Tank shall have the following:  Drain valve 
located at the lowest point in the tank, connections for concentrate supply and return lines to the proportioners, 
top-mounted fill connections and inspection hatch, and a pressure/vacuum relief vent.  All openings and tank 
connections shall be installed at the factory, no holes shall be made in the tank shell in the field.  Tank shall 
include all necessary supports for free-standing installation.  Provide a gage or unbreakable sight glass to 
permit visual determination of level of tank contents, unless liquid level is clearly visible through shell of 
tank.  Size tank to provide sufficient AFFF concentrate for the time specified when the system is discharging 
foam solution at total maximum system flow.  [Also provide connected reserve tank(s) of equal capacity.]  Permanently 
label each tank with its capacity, type and percentage of concentrate, which system it serves [, and whether 
it is a main or reserve tank].</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>2.15   WATER <SUB>MONITOR NOZZLES</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Refer to MIL-HDBK-1008 to determine the density required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Manually operated, [free standing] [hydrant mounted] type with<MET> 6.30 radian</MET><ENG> 360 degree</ENG> rotation and capable of 
being locked at any position.  Nozzle shall be adjustable while in operation from<MET> 0.35 radian</MET><ENG> 20 degrees</ENG> below 
to <MET>1.40 radian</MET> <ENG>80 degrees</ENG> above horizontal, with lock or latching mechanism.  [Nozzle shall be adjustable while 
in operation from straight stream to spray.]  Nozzle shall produce a straight stream of<MET> 46 meters</MET><ENG> 150 feet</ENG> at<MET>
 [1920 L/m]</MET> <ENG>[500 gpm]</ENG> [_____] and<MET> [690 kPa (gage)]</MET><ENG> [100 psig]</ENG> [_____].  Provide [post indicator] [0S&amp;Y gate] 
[quarter-turn indicating] valve in water supply line at each monitor location.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.16   HAND HOSE LINES</TTL><BRK/>
<BRK/>
<TXT>At each hose station, provide [flow-through reel with<MET> 40 mm</MET><ENG> 1 1/2 inch</ENG> hard rubber] [automatic hose rack in cabinet 
with<MET> 40 mm</MET><ENG> 1 1/2 inch</ENG> lined, double jacket] <SUB>hose and nozzles</SUB>.  Provide minimum [_____]<MET> meter</MET><ENG> feet</ENG> of hose.  Nozzle 
shall have pistol-grip ball shutoff valve.  Nozzle shall be [non aspirating] [air aspirating] type.  Provide 
normally closed quarter-turn valve in supply line at each hose station.  Nozzle flow rate shall be<MET> [139 L/m]</MET><ENG> 
[50 gpm]</ENG> [_____] minimum.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.17   <SUB>FOAM HYDRANTS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide foam hydrants for testing of proportioners or where additional 
foam hand hose lines are required.  Determine number of outlet connections based 
upon a ratio of one outlet for each<MET> 948 L/m</MET><ENG> 250 gpm</ENG> of design flow, up to a 
maximum of 8 outlets.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide [single] [dual] outlet connections with integral gate valves and locate about<MET> one meter</MET><ENG> 3 feet</ENG> above 
grade.  Provide each outlet with<MET> 65 mm</MET><ENG> 2 1/2 inch</ENG> male National Standard hose threads with<MET> 65 to 40 mm</MET><ENG> 2 1/2 
to 1 1/2 inch</ENG> reducer with cap and chain.  Provide wall escutcheon plate with "FOAM HYDRANT" in raised letters 
cast in plate.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.18   ABOVEGROUND PIPING SYSTEMS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.18.1   <SUB>Pipe, Fittings, and Mechanical Couplings</SUB></TTL><BRK/>
<BRK/>
<TXT><RID>NFPA 11</RID>, except steel piping shall be Schedule 40 for sizes smaller than<MET> 200 mm</MET><ENG> 8 inches</ENG>, and Schedule 30 or 
40 for sizes<MET> 200 mm</MET><ENG> 8 inches</ENG> and larger.  All steel piping shall be zinc-coated.  Pipe nipples<MET> 150 mm</MET><ENG> 6 inches</ENG>
 long and shorter shall be Schedule 80 steel pipe.  Water motor alarm piping shall be zinc-coated steel pipe 
and fittings.  Rubber gasketed grooved-end pipe and fittings with mechanical couplings shall only be permitted 
in pipe sizes<MET> 40 mm</MET><ENG> 1 1/2 inches</ENG> and larger.  Rubber gaskets shall be UL listed for use in dry-pipe sprinkler 
systems.  Gasketed fittings are not permitted inside the diked area.  Use of restriction orifices, reducing flanges, 
and plain-end fittings with mechanical couplings (which utilize steel gripping devices to bite into the pipe 
when pressure is applied) are not permitted. Pipe and fittings in contact with AFFF concentrate shall be [material 
resistant to the corrosive effects of AFFF concentrate as approved by the manufacturer of the proportioning system] 
[stainless steel].  [Fittings on concentrate lines shall be flanged or welded only.  Screwed or mechanical fittings 
will not be permitted.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.18.2   Jointing Material</TTL><BRK/>
<BRK/>
<TXT><RID>FS A-A-58092</RID>, Polytetrafluoroethylene (PTFE) tape.  Pipe joint compound (pipe dope) is not acceptable.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.18.3   Duplex Basket <SUB>Strainers</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include for systems with high volume flow, and for untreated water supply.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>FS WW-S-2739</RID>, Style Y (Y pattern).  Provide duplex basket strainers with removable screens having standard perforations,<MET>
 3 mm</MET><ENG> 0.125 inch</ENG> in diameter in the riser beneath the deluge valves.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.18.4   <SUB>Pipe Hangers and Supports</SUB></TTL><BRK/>
<BRK/>
<TXT><RID>NFPA 11</RID> and <RID>NFPA 13</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.18.5   <SUB>Valves</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide valves as required by <RID>NFPA 11</RID> and <RID>NFPA 13</RID> and of types approved for fire service.  Gate valves shall 
open by counterclockwise rotation.  Check valves shall be flanged clear opening swing check type with flanged 
inspection and access cover plate for sizes<MET> 100 mm</MET><ENG> 4 inches</ENG> and larger.  Provide an OS&amp;Y valve beneath each 
deluge valve in each riser, when more than one valve is supplied from the same water supply pipe. Butterfly valves 
are not acceptable.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.18.6   Identification Signs</TTL><BRK/>
<BRK/>
<TXT>Attach properly lettered approved metal signs conforming to <RID>NFPA 13</RID> to each valve and alarm device.  Permanently 
affix design data nameplates to the riser of each system.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.18.7   Main Drains</TTL><BRK/>
<BRK/>
<TXT>Provide drain piping to discharge at safe points outside each building or to sight cones attached to drains of 
adequate size to readily receive the full flow from each drain under maximum pressure.  Provide auxiliary drains 
as required by <RID>NFPA 11</RID> and <RID>NFPA 13</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.18.8   Pipe Sleeves</TTL><BRK/>
<BRK/>
<TXT>Provide where piping passes through walls, floors, roofs, and partitions. Secure sleeves in proper position and 
location during construction. Provide sleeves of sufficient length to pass through entire thickness of walls, 
floors, roofs, and partitions.  Provide not less than<MET> 6.50 mm</MET><ENG> 1/4 inch</ENG> space between exterior of piping and interior 
of sleeve.  Firmly pack space with insulation and calk at both ends of the sleeve with plastic waterproof cement.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.18.8.1   Sleeves in Masonry and Concrete Walls, Floors, Roofs</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM A 53/A 53M</RID>, schedule 40 or standard weight, zinc-coated steel pipe sleeves.  Extend sleeves in floor slabs<MET>
 80 mm</MET><ENG> 3 inches</ENG> above the finished floor.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.18.8.2   Sleeves in Partitions</TTL><BRK/>
<BRK/>
<TXT>Provide zinc-coated steel sheet having a nominal weight of not less than<MET> 4.40 kg per sq meter</MET><ENG> 0.90 pounds per 
square foot</ENG>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.18.9   Escutcheon Plates</TTL><BRK/>
<BRK/>
<TXT>Provide one piece or split hinge type plates for piping passing through floors, walls and ceilings, in both exposed 
and concealed areas.  Provide chromium plated metal plates where pipe passes through finished ceilings. Provide 
other plates of steel or cast iron with aluminum paint finish. Securely anchor plates in place.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.18.10   <SUB>Fire Department Inlet Connections</SUB></TTL><BRK/>
<BRK/>
<TXT>[Two] [Three] way type with<MET> 65 mm</MET><ENG> 2 1/2 inch</ENG> National Standard female hose threads with plug, chain, and identifying 
fire department connection escutcheon plate.  Provide inlet connections about<MET> one meter</MET><ENG> 3 feet</ENG> above grade.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.18.11   <SUB>Backflow Preventers</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When the water supply for the AFFF system is non-potable water delete 
this paragraph.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Reduced pressure principle type.  Proof shall be furnished that each make, model/design, and size of backflow 
preventer being furnished for the project is approved by and has a current "Certificate of Approval" from the <RID>
FCCCHR List</RID>.  Listing of the particular make, model/design, and size in the current <RID>FCCCHR List</RID> will be acceptable 
as the required proof.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.19   BURIED PIPING SYSTEMS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.19.1   Pipe and Fittings</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For pipe sizes larger than<MET> 305 mm</MET><ENG> 12 inches</ENG>, method for pipe anchorage 
including pipe clamps and the rods shall be shown on the drawings.  Avoid velocities 
greater than<MET> 4.50 meters per second</MET><ENG> 15 ft./sec</ENG>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select first bracketed phrase for connection to an existing water distribution 
system located a short distance from the work.  Select second bracketed phrase 
when a new water distribution line is being provided as part of this project.  
For new water distribution system, select Section 33 11 00 WATER DISTRIBUTION, 
edit the appropriate guide specification and include as part of the project 
specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NFPA 24</RID>, outside coated cement lined ductile iron pipe and fittings for piping under the building and to a point<MET>
 1.50 meters</MET><ENG> 5 feet</ENG> outside the building walls.  Anchor the joints in accordance with <RID>NFPA 24</RID> using pipe clamps 
and steel rods.  Minimum pipe size shall be<MET> 150 mm</MET><ENG> 6 inches</ENG>.  Minimum depth of cover shall be [_____]<MET> [one meter]</MET><ENG>
 [3 feet]</ENG>.  Piping more than<MET> 1.50 meters</MET><ENG> 5 feet</ENG> outside the building walls shall be [outside coated cement lined 
ductile iron pipe and fittings conforming to <RID>NFPA 24</RID>] [provided under Section <SRF>33 11 00</SRF> WATER DISTRIBUTION].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.19.2   Valves</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If Section 33 11 00 WATER DISTRIBUTION is included as part of the project 
specification, requirements for buried gate valves, post indicator valves, and 
valve boxes may be deleted here and specified in Section 33 11 00.  Careful 
coordination is required to insure that materials rated for fire service are 
specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide as required by <RID>NFPA 24</RID> for fire service.  Gate valves shall conform to <RID>AWWA C500</RID> or <RID>UL 262</RID> with cast 
iron body and bronze trim, and shall open by counterclockwise rotation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.19.3   Post Indicator Valves</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If Section 33 11 00 WATER DISTRIBUTION is included as part of the project 
specification, requirements for buried gate valves, post indicator valves, and 
valve boxes may be deleted here and specified in Section 33 11 00.  Careful 
coordination is required to insure that materials rated for fire service are 
specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide with operating nut located about<MET> one meter</MET><ENG> 3 feet</ENG> above grade.  Gate valves for use with indicator post 
shall conform to <RID>UL 262</RID>.  Indicator posts shall conform to <RID>UL 789</RID>.  Paint each indicator post with one coat of 
primer and two coats of red enamel paint.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.19.4   Valve Boxes</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If Section 33 11 00 WATER DISTRIBUTION is included as part of the project 
specification, requirements for buried gate valves, post indicator valves, and 
valve boxes may be deleted here and specified in Section 33 11 00.  Careful 
coordination is required to insure that materials rated for fire service are 
specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Except where indicator posts are provided, provide each gate valve in buried piping with an adjustable cast-iron 
valve box of a size suitable for the valve on which it is to be used.  Boxes outside of paved areas may be of 
Acrylonitrile-Butadiene- Styrene (ABS) plastic or of inorganic fiber reinforced black polyolefin plastic.  The 
head shall be round and the lid shall have the word WATER cast on it.  The least diameter of the shaft of the 
box shall be<MET> 133 mm</MET><ENG> 5 1/4 inches</ENG>.  Coat each cast-iron box with bituminous paint.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.19.5   Buried Utility Warning and Identification Tape</TTL><BRK/>
<BRK/>
<TXT>Provide detectable aluminum foil plastic-backed tape or detectable magnetic plastic tape manufactured specifically 
for warning and identification of buried piping.  Tape shall be detectable by an electronic detection instrument.  
Provide tape in rolls,<MET> 80 mm</MET><ENG> 3 inches</ENG> minimum width, color coded for the utility involved, with warning and identification 
imprinted in bold black letters continuously and repeatedly over entire tape length.  Warning and identification 
shall be CAUTION BURIED WATER PIPING BELOW or similar.  Use permanent code and letter coloring unaffected by 
moisture and other substances contained in trench backfill material.  Bury tape with the printed side up at a 
depth of<MET> 305 mm</MET><ENG> 12 inches</ENG> below the top surface of earth or the top surface of the subgrade under pavements.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   EXCAVATION, BACKFILLING, AND COMPACTING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Sectect and edit Section 02302, "Excavation, Backfilling, and Compacting 
for Utilities" and include as part of the project specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide under this section as specified in Section <SRF>31 00 00</SRF> EARTHWORK.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   CONNECTIONS TO EXISTING WATER SUPPLY SYSTEMS</TTL><BRK/>
<BRK/>
<TXT>Use tapping or drilling machine valve and mechanical joint type sleeves for connections to be made under pressure.  
Bolt sleeves around the mains; bolt valve conforming to <RID>AWWA C500</RID> or <RID>UL 262</RID> to the branch.  Open valve, attach 
drilling machine, make tap, close valve, and remove drilling machine, all without interruption of service.  Notify 
the Contracting Officer in writing at least [_____] [15] calendar days prior to the date the connections are 
required; approval shall be received before any service is interrupted.  Furnish all material required to make 
connections into the existing water supply systems, and perform all excavating, backfilling, and other incidental 
labor as required.  [Furnish] [Government will furnish only] the labor and the tapping or drilling machine for 
making the actual connections to the existing systems.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3   AFFF SYSTEM INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Equipment, materials, installation, workmanship, fabrication, assembly, erection, examination, inspection, and 
testing shall be in accordance with the NFPA standards referenced herein.  Install piping straight and true to 
bear evenly on hangers and supports.  Piping shall be inspected, tested and approved before being concealed.  
Provide fittings for changes in direction of piping and for all connections.  Make changes in piping sizes through 
standard reducing pipe fittings; do not use bushings.  Cut pipe accurately and work into place without springing 
or forcing.  Ream pipe ends and free pipe and fittings from burrs.  Clean with solvent to remove all varnish 
and cutting oil prior to assembly.  Make screw joints with PTFE tape applied to male thread only.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4   DISINFECTION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When the water supply for the AFFF system is non-potable water delete 
this paragraph.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Disinfect new water piping from the system control valve to the point of connection at the water main and existing 
water piping affected by the Contractor's operation in accordance with <RID>AWWA C651</RID>.  Fill piping systems with solution 
containing minimum of 50<MET> mg/kg</MET><ENG> parts per million (ppm)</ENG> of free available chlorine and allow solution to stand 
for minimum of 24 hours. Flush solution from systems with clean water until maximum residual chlorine content 
is not greater than 0.2<MET> mg/kg</MET><ENG> ppm</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5   FIELD PAINTING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For facilities located in a marine environment specify SSPC SP 11 cleaning 
and specify a second topcoat.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Clean, prime, and paint new foam systems including valves, piping, conduit, hangers, miscellaneous metal work, 
and accessories.  Apply coatings to clean dry surfaces using clean brushes.  Clean the surfaces in accordance 
with [<RID>SSPC SP 3</RID>] [<RID>SSPC SP 11</RID>].  Immediately after cleaning, prime the metal surfaces with one coat of <RID>SSPC Paint 25</RID>
 or <RID>SSPC Paint 25</RID>primer applied to a minimum dry film thickness of<MET> 0.04 mm</MET><ENG> 1.5 mils</ENG>.  Exercise care to avoid 
the painting of operating devices.  Upon completion of painting, remove materials which were used to protect 
operating devices while painting is in process.  Remove operating devices which have been inadvertently painted 
and provide new clean operating devices of the proper type.  Finish primed surfaces as follows:</TXT><BRK/>
<BRK/>
<SPT><TTL>3.5.1   Foam Systems in Unfinished Areas</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For facilities located in a marine environment specify SSPC SP 11 cleaning 
and specify a second topcoat.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Unfinished areas are defined as locations exposed to weather, attic spaces, spaces above suspended ceilings, 
crawl spaces, foam rooms, pump rooms, pipe chases, and other spaces where ceilings are not painted or not constructed 
of a prefinished material.  Paint primed surfaces with [one] [two] coat[s] of <RID>FS A-A-2962</RID> red enamel applied 
to a minimum dry film thickness of <MET>0.04 mm</MET> <ENG>1.5 mils</ENG>.  Paint surfaces exposed to weather with two coats of red 
enamel as specified herein.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.2   Foam Systems in All Other Areas</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For facilities located in a marine environment specify SSPC SP 11 cleaning 
and specify a second topcoat.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Paint primed surfaces with two coats of paint to match adjacent surfaces, except paint valves and operating accessories 
with [one] [two] coat[s] of <RID>FS A-A-2962</RID> red enamel applied to a minimum dry film thickness of<MET> 0.04 mm</MET><ENG> 1.5 mils</ENG>
.  Provide piping with<MET> 50 mm</MET><ENG> 2 inch</ENG> wide red bands spaced at maximum<MET> 6 meters</MET><ENG> 20 foot</ENG> intervals throughout the 
piping systems.  Bands shall be red enamel or self adhering red plastic tape.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.3   Piping Labels</TTL><BRK/>
<BRK/>
<TXT>Provide permanent labels in foam rooms, spaced at<MET> 6 meters</MET><ENG> 20 foot</ENG> maximum intervals along pipe, indicating "WATER", 
"FOAM CONCENTRATE", and "FOAM SOLUTION" on corresponding piping.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.4   Field Touch-Up</TTL><BRK/>
<BRK/>
<TXT>Clean damaged areas of shop coated tanks in accordance with <RID>SSPC SP 11</RID> and coat cleaned areas with the same materials 
used for the shop applied coating system.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.6   ELECTRICAL WORK</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit Section 26 20 00, INTERIOR DISTRIBUTION SYSTEM and include as part 
of the project specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When project includes requirement for a building fire alarm system, include 
Section 28 31 74.00 20 in the project specification.  When project requires 
only tying into an existing building fire alarm system, fire alarm wiring should 
be specified in this section.  Select the first 28 31 74.00 20 Section title 
when using the basic NAVFAC guide specification covering the subject work or 
select the second title when using the EFD regional guide specification covering 
the subject work.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Electrical work is specified in Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM except for control [and fire alarm] 
wiring.  [Fire alarm system is specified in Section [<SRF>28 31 74.00 20</SRF> INTERIOR FIRE ALARM SYSTEM] ["Fire Alarm 
and Fire Detecting Systems (Local)"]].</TXT><BRK/>
<BRK/>
<SPT><TTL>3.6.1   Wiring</TTL><BRK/>
<BRK/>
<TXT>Provide control wiring and connections, to fire alarm systems, under this section in accordance with <RID>NFPA 70</RID> 
and <RID>NFPA 72</RID>.  Provide wiring in rigid metal conduit or intermediate metal conduit, except electrical metallic 
tubing may be used in dry locations not enclosed in concrete or where not subject to mechanical damage.  Do not 
run low voltage DC circuits in the same conduit with AC circuits.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.7   FLUSHING</TTL><BRK/>
<BRK/>
<TXT>Flush the piping system with potable water in accordance with <RID>NFPA 13</RID>. Continue flushing operation until water 
is clear, but for not less than 10 minutes.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8   FIELD QUALITY CONTROL</TTL><BRK/>
<BRK/>
<TXT>Prior to initial operation, inspect equipment and piping systems for compliance with drawings, specifications, 
and manufacturer's submittals. Perform tests in the presence of the Contracting Officer to determine conformance 
with the specified requirements.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.8.1   <SUB>Preliminary Tests</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify hydrostatic test not less than<MET> 1379 kPa or 345 kPa</MET><ENG> 200 psi or 
50 psi</ENG> above the maximum working pressure when the maximum working pressure 
is greater than<MET> 1034 kPa</MET><ENG> 150 psi</ENG>.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><TST>Each piping system shall be hydrostatically tested at<MET> [1379 kPa (gage)]</MET><ENG> [200 psig]</ENG> [_____] in accordance with <RID>
NFPA 11</RID> and <RID>NFPA 13</RID> and shall show no leakage or reduction in gage pressure after 2 hours.  The Contractor shall 
conduct complete preliminary tests, which shall encompass all aspects of system operation.  Individually test 
all detectors, manual actuation stations, alarms, control panels, and all other components and accessories to 
demonstrate proper functioning.  Test water flow alarms by flowing water. When tests have been completed and 
all necessary corrections made, submit to the Contracting Officer a signed and dated certificate, similar to 
that specified in <RID>NFPA 13</RID>, attesting to the satisfactory completion of all testing and stating that the system 
is in operating condition.  Also include a written request for a formal inspection and test.</TST></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.2   Formal Inspection and Tests (<SUB>Acceptance Tests</SUB>)</TTL><BRK/>
<BRK/>
<TXT>The [_____] Division, Naval Facilities Engineering Command Fire Protection Engineer, will witness formal tests 
and approve all systems before they are accepted.  The system shall be considered ready for such testing only 
after all necessary preliminary tests have been made and all deficiencies found have been corrected to the satisfaction 
of the equipment manufacturer's technical representative and written certification to this effect is received 
by the Division Fire Protection Engineer.  Submit the request for formal inspection at least 15 working days 
prior to the date the inspection is to take place.  The control panel(s) and detection system(s) shall be in 
continuous service for a "break-in" period of at least 15 consecutive days prior to the formal inspection.  Experienced 
technicians regularly employed by the Contractor in the installation of both the mechanical and electrical portions 
of such systems shall be present during the inspection and shall conduct the testing.  All AFFF concentrate, 
instruments, personnel, appliances and equipment for testing shall be furnished by the Contractor.  All necessary 
tests encompassing all aspects of system operation shall be made including the following, and any deficiency 
found shall be corrected and the system retested at no cost to the Government.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.8.2.1   Systems and Device Testing</TTL><BRK/>
<BRK/>
<TST><TXT>The entire initiating, alarm, actuation systems shall be operated.  As a minimum, operation and supervision of 
the following functions and devices shall be demonstrated:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  All operational and supervisory functions of the control and annunciator panels.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Each manual actuation station and associated circuit(s).</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  All detectors and associated circuits.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  All alarms and associated circuits.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  All actuator circuits and system control valve(s) (without foam discharge).</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Activation of the fire alarm system.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Activation of the Base fire alarm system (receipt of fire alarm at alarm office).</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  All of the above tests shall then be repeated with the system on battery power only.</ITM></TST><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.2.2   AFFF Discharge and Concentration Testing</TTL><BRK/>
<BRK/>
<TST><TXT>When all of the initiating, alarm, actuation, and supervisory functions of the system operate to the satisfaction 
of the system manufacturer's technical representative and the Division Fire Protection Engineer, a complete discharge 
test of each system shall be performed to demonstrate satisfactory performance, proper AFFF concentration, mechanical 
operation and operation of valves, release devices, alarms, and interlocks which control the protected areas.  
These tests shall be conducted by experienced personnel according to the equipment and AFFF manufacturers' recommendations.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Test each system by full flow of foam solution from the individual systems or combination 
of systems to achieve maximum design flow rate for at least 60 seconds.  Test tank-side foam 
chambers by turning chambers and flowing foam solution down outside of tank.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Test all hose lines by full flow of foam solution for at least 60 seconds.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[c.  Test monitor nozzles by full flow of water.]</ITM><BRK/>
<BRK/>
<TXT>The manufacturer's representative shall test samples of foam solution taken from each system to ensure proper 
AFFF concentration.  Provide protection for all electrical fixtures and equipment exposed to possible damage 
during tests and take necessary steps to prevent soil erosion [and contain runoff] during testing.</TXT></TST><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.2.3   Flushing and Rinsing</TTL><BRK/>
<BRK/>
<TXT>After completion of tests flush all piping carrying AFFF concentrate and solution with fresh water.  Piping normally 
containing AFFF concentrate when the system is in standby mode need not be flushed.  Rinse with fresh water all 
equipment and surfaces exposed to AFFF discharge.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.8.3   Environmental Protection</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Consult facility and the Division or District environmental officials 
to determine local requirements for containment and disposal of discharged AFFF.  
In sufficient concentrations, AFFF may cause disruption of processes in sewage 
treatment plants and damage to fisheries.  Edit the paragraph as appropriate.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide temporary measures to prevent AFFF from entering storm drains, [sanitary sewers,] drainage ditches, streams 
and water courses.  [Do not allow AFFF concentrate or solution to come in contact with earth.  Contain all discharged 
AFFF on paved surfaces or in tanks.]  [Collect all discharged AFFF and rinse and flushing water and dispose of 
it in an EPA - approved waste-water treatment facility which provides secondary (biological) treatment].  At 
least 15 days prior to the date flow testing is to take place, submit written plan for AFFF containment [and 
disposal] methods(s) to the Contracting Officer for approval.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.4   Additional Tests</TTL><BRK/>
<BRK/>
<TXT><TST>When deficiencies, defects or malfunctions develop during the tests required, all further testing of the system 
shall be suspended until proper adjustments, corrections or revisions have been made to assure proper performance 
of the system.  If these revisions require more than a nominal delay, the Contracting Officer shall be notified 
when the additional work has been completed, to arrange a new inspection and test of the system. All tests required 
shall be repeated prior to final acceptance, unless directed otherwise.</TST></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.5   AFFF Concentrate Storage Tanks Fill-Up</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Consult facility to determine whether the Government or the Contractor 
will furnish the initial fill-up of AFFF concentrate.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Fill storage tanks including reserve tanks and piping normally containing concentrate when the system is in standby 
mode with [Contractor] [Government] furnished AFFF concentrate after acceptance of the system.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.6   Manufacturer's Representative</TTL><BRK/>
<BRK/>
<TXT>Provide the services of representatives or technicians from the manufacturers of the foam system and control 
panel, experienced in the installation and operation of the type of system being provided, to supervise installation, 
adjustment, preliminary testing, and final testing of the system and to provide instruction to Government personnel.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.9   OPERATING INSTRUCTIONS</TTL><BRK/>
<BRK/>
<TXT>Provide operating instructions at control equipment and at each remote control station.  Instructions shall clearly 
indicate all necessary steps for the operation of the system.  Submit the proposed legend for operating instructions 
for approval prior to installation.  Instructions shall be in engraved white letters on red rigid plastic or 
red enameled steel backgrounds and shall be of adequate size to permit them to be easily read.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.10   TRAINING REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Prior to final acceptance, the Contractor shall provide two sessions of 4 hours each of operation and maintenance 
training to the Base Fire Department and [Public Works] [Civil Engineering] personnel on two different days to 
accommodate both shifts of the Base Fire Department. Each training session shall include emergency procedures, 
and unique maintenance and safety requirements.  Training areas will be provided by the Government.  The training 
conducted shall use operation and maintenance manuals specified in paragraph entitled "Operations and Maintenance 
Manuals." Dates and times of the training period shall be coordinated through the Contracting Officer not less 
than two weeks prior to the session.</TXT><BRK/>
<BRK/></SPT>
<MET><SPT><TTL>3.11   SCHEDULE</TTL><BRK/>
<BRK/>
<TXT>Some metric measurements in this section are based on mathematical conversion of inch-pound measurements, and 
not on metric measurements commonly agreed on by the manufacturers or other parties.  The inch-pound and metric 
measurements shown are as follows:</TXT><BRK/>
<TBL><THD><BRK/>
      <HL1>Products</HL1>                       <HL1>Inch-Pound</HL1>           <HL1>Metric</HL1><BRK/></THD>
<BRK/>
   a.  Alarm Bells<BRK/>
         Diameter                    = 4 inches           = 100 mm<BRK/>
<BRK/>
   b.  AFFF Concentrate Fill Pumps<BRK/>
         Minimum Flow Rate           = 7 gpm              = 27 L/m<BRK/>
<BRK/>
   c.  Diaphragm Pressure<BRK/>
         Proportioning Tanks<BRK/>
         Working Pressure             = 175 psig          = 1206 kPa (gage)<BRK/>
<BRK/>
   d.  Buried Warning and<BRK/>
<BRK/>
         Identification Tapes<BRK/>
         Width                        = 3 inches          = 80 mm<BRK/></TBL>
</SPT></MET><BRK/></PRT>
    <END/><BRK/></SEC>