<SCN>SECTION 23 05 48</SCN><BRK/>
<BRK/>
<STL>VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT</STL><BRK/>
<DTE>08/08</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This specification covers the requirements for <SCP>vibration-isolation systems 
for air-conditioning equipment</SCP>.</NPR><BRK/>
<BRK/>
<NPR>Provisions of the following specifications should be coordinated with equipment 
selection, specifications, and the drawings.</NPR><BRK/>
<BRK/>
<NPR>For equipment speeds under 250 revolutions per minute (rpm), special consideration 
is required.</NPR><BRK/>
<BRK/>
<NPR>This specification is arranged to be used in either of the following two ways:</NPR><BRK/>
<BRK/>
<NPR>The part entitled, "Vibration-Isolation Systems Application," and selected or 
rewritten text thereunder may be published as part of the bound specification.  
Drawing schedules shall include applicable data listed under Part 2.</NPR><BRK/>
<BRK/>
<NPR>Or, the part entitled, "Vibration Isolation-Systems Application," may be deleted 
when required applicable content is scheduled on the drawings.</NPR><BRK/>
<BRK/>
<NPR>Drawing schedules shall include the following data:  equipment number; mass 
of inertia block if different from that specified or if not specified; minimum 
number of isolators for complex applications; lowest equipment rpm; impeller 
size; power; isolation provisions in the form of "C-CIB-1.75" which includes 
mounting, base, and minimum deflection in<MET> millimeter</MET><ENG> inches</ENG>.  This method is 
recommended in view of anticipated need to rewrite or supplement this basic 
specification to ensure suitability of provisions for specific project applications.</NPR><BRK/>
<BRK/>
<NPR>Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.</NPR><BRK/>
<BRK/>
<NPR>Remove information and requirements not required in respective project, whether 
or not brackets are present.</NPR><BRK/>
<BRK/>
<NPR>Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.</NPR><BRK/>
<BRK/>
<NPR>Recommended changes to a UFGS should be submitted as a <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.</NPR><BRK/>
<BRK/>
<NPR>Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.</NPR><BRK/>
<BRK/>
<NPR>References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ACOUSTICAL SOCIETY OF AMERICA (ASA)</ORG><BRK/><BRK/><RID>ASA S2.40</RID><RTL>(1984; R 2001) Mechanical Vibration of Rotating and Reciprocating Machinery - Requirements for Instruments for Measuring Vibration Severity</RTL><BRK/><BRK/><RID>ASA S2.71</RID><RTL>(1983; R 2006) Guide to the Evaluation of Human Exposure to Vibration in Buildings</RTL><BRK/><BRK/></REF><REF><ORG>AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING ENGINEERS (ASHRAE)</ORG><BRK/><BRK/><RID>ASHRAE HVAC APP IP HDBK</RID><RTL>(2007) HVAC Applications Handbook, I-P Edition</RTL><BRK/><BRK/><RID>ASHRAE HVAC APP SI HDBK</RID><RTL>(2007) HVAC Applications Handbook, SI Edition</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB)</ORG><BRK/><BRK/><RID>NEBB PROCEDURAL STANDARDS</RID><RTL>(2005) Procedural Standards for TAB (Testing, Adjusting and Balancing) Environmental Systems</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   GENERAL REQUIREMENTS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If Sections <SRF>23 00 00</SRF> AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST 
SYSTEMS and Section <SRF>23 05 15</SRF> COMMON PIPING FOR HVAC are not included in the 
project specification, applicable requirements therefrom should be inserted 
and the following paragraphs deleted.  Vibration isolation considerations for 
systems other than A/C equipment should be addressed in each respective section.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Section <SRF>23 00 00</SRF> AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS applies to work specified in this 
section to the extent applicable.</TXT><BRK/>
<BRK/>
<TXT>Section <SRF>23 05 15</SRF> COMMON PIPING FOR HVAC applies to work specified in this section to the extent applicable.</TXT><BRK/>
<BRK/>
<TXT>All vibration-control apparatus must be the product of a single manufacturing source, where possible.  Human 
exposure levels should be considered using <RID>ASA S2.71</RID> and <RID>NEBB PROCEDURAL STANDARDS</RID>.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the following paragraphs if text under "Vibration-Isolation Systems 
Application" is deleted and required isolation provisions are scheduled on the 
drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Scheduled isolation mounting is in<MET> millimeter</MET><ENG> inches</ENG> and is a minimum static deflection.</TXT><BRK/>
<BRK/>
<TXT>Spans referred to in Part 2, "Vibration-Isolation Systems Application," must mean longest bay dimension.</TXT><BRK/>
<BRK/>
<TXT>Determine exact mounting sizes and number of isolators by the isolator manufacturer based on equipment that will 
be installed.  Check equipment revolutions per minute (rpm) and spring deflections to verify that resonance cannot 
occur.</TXT><BRK/>
<BRK/>
<TXT><SUB>Installation Drawings</SUB> for vibration isolator systems must include equipment and performance requirements.</TXT><BRK/>
<BRK/>
<TXT>Indicate within <SUB>Outline Drawings</SUB> for vibration isolator systems overall physical features, dimensions, ratings, 
service requirements, and weights of equipment.</TXT><BRK/>
<BRK/>
<TXT><SUB>Equipment and Performance Data</SUB> for vibration isolator systems must include equipment base design; inertia-block 
mass relative to support equipment weight; spring loads and free, operating, and solid heights of spring; spring 
diameters; nonmetallic isolator loading and deflection; disturbing frequency; natural frequency of mounts; deflection 
of working member; and anticipated amount of physical movement at the reference points.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review Submittal Description (SD) definitions in Section <SRF>01 33 00</SRF> SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.</NPR><BRK/>
<BRK/>
<NPR>A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.</NPR><BRK/>
<BRK/>
<NPR>For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.</NPR><BRK/>
<BRK/>
<NPR>Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  Submit the following 
in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM>Submit <SUB>Installation Drawings</SUB> and <SUB>Outline Drawings</SUB> in accordance with paragraph entitled, "General 
Requirements," of this section.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM>Submit <SUB>Equipment and Performance Data</SUB> in accordance with paragraph entitled, "General Requirements," 
of this section.</ITM><BRK/>
<BRK/>
<ITM>Submit Manufacturer's catalog data for the following items:</ITM><BRK/>
<BRK/>
<ITM><SUB>Mountings</SUB></ITM><BRK/>
<ITM><SUB>Bases</SUB></ITM><BRK/>
<ITM><SUB>Isolators</SUB></ITM><BRK/>
<ITM><SUB>Floor-Mounted Piping</SUB></ITM><BRK/>
<ITM><SUB>Vertical Piping</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM>Submit test reports for deflection tests in accordance with the paragraph entitled, "Type of 
Vibration-Isolation Provisions," of this section.  Include within reports the following information:</ITM><BRK/>
<BRK/>
<ITM><SUB>Type of Isolator</SUB></ITM><BRK/>
<ITM><SUB>Type of Base</SUB></ITM><BRK/>
<ITM><SUB>Allowable Deflection</SUB></ITM><BRK/>
<ITM><SUB>Measured Deflection</SUB></ITM><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   TYPE OF VIBRATION-ISOLATION PROVISIONS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use only those standards as necessary.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Design for vibration isolation using [<RID>NEBB PROCEDURAL STANDARDS</RID>] [<MET><RID>ASHRAE HVAC APP SI HDBK</RID>, </MET><ENG><RID>ASHRAE HVAC APP IP HDBK</RID>
, </ENG>Chapter 37,] as applicable to the following sections.</TXT><BRK/>
<BRK/>
<TXT>Test reports for testing vibration isolation must be submitted for each <SUB>Type of Isolator</SUB> and each <SUB>Type of Base</SUB>
, and meet referenced standards contained within this section.  Include in test reports <SUB>Allowable Deflection</SUB>and <SUB>
Measured Deflection</SUB> also meeting referenced standards within this section.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.1   Materials</TTL><BRK/>
<BRK/>
<TXT>Rubber must be natural rubber.  Elastomer must be chloroprene.  Shore A durometer measurement of both materials 
and range between 40 and 60.</TXT><BRK/>
<BRK/>
<TXT>Inorganic materials such as precompressed, high-density, fibrous glass encased in a resilient moisture-impervious 
membrane may be used in lieu of specified natural rubber and elastomers.  Where this substitution is made, specified 
deflections must be modified by the manufacturing source to accommodate physical characteristics of inorganic 
materials and to provide equal or better vibration isolation.</TXT><BRK/>
<BRK/>
<TXT>Weather-exposed metal vibration-isolator parts must be corrosion protected.  Chloroprene coat springs.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   <SUB>Mountings</SUB></TTL><BRK/>
<BRK/>
<TXT>Mountings must be:</TXT><BRK/>
<BRK/>
<LST>[Type A:  Composite pad, with<MET> 6.3 millimeter</MET><ENG> 0.25-inch</ENG> thick elastomer top and bottom layers, molded 
to contain a pattern with nonslip characteristics in all horizontal directions.  Elastomer loading must 
not exceed<MET> 275 kilopascal</MET><ENG> 40 pounds per square inch (psi)</ENG>.  Minimum overall thickness must be<MET> 25 millimeter</MET><ENG>
 1 inch</ENG>.  Maximum deflections up to<MET> 6.3 millimeter</MET><ENG> 0.25-inch</ENG> are allowed.]</LST><BRK/>
<BRK/>
<LST>[Type B:  Double [rubber-in-shear] [elastomer-in-shear] with molded-in steel reinforcement in top and 
bottom.  Maximum deflections up to<MET> 12.7 millimeter</MET><ENG> 0.50 inch</ENG> are allowed.]</LST><BRK/>
<BRK/>
<LST>[Type C:  Free-standing laterally stable open-spring type for deflections over<MET> 12.7 millimeter</MET><ENG> 0.50 inch</ENG>
, with built-in bearing and leveling provisions,<MET> 6.3 millimeter</MET><ENG> 0.25-inch</ENG> thick Type A base elastomer 
pads, and accessories.  Outside diameter of each spring must be equal to or greater than 0.9 times the 
operating height of the spring under rated load.]</LST><BRK/>
<BRK/>
<LST>[Type D:  Partially housed type, containing one or more vertically restrained springs with at least<MET> 12.7 
millimeter</MET><ENG> 0.50 inch</ENG> clearance maintained around springs, with adjustable limit stops,<MET> 6.3 millimeter</MET><ENG>
 0.25-inch</ENG> thick Type A base elastomer pads, and accessories.]</LST><BRK/>
<BRK/>
<LST>[Type E:  Pendulum-suspension configuration with free-standing stable spring with resilient horizontal 
and vertical restraints to allow maximum movements of<MET> 6.3 millimeter</MET><ENG> 0.25 inch</ENG> in each direction,<MET> 6.3 
millimeter</MET><ENG> 0.25-inch</ENG> thick Type A base elastomer pads.]</LST><BRK/>
<BRK/>
<LST>[Type F:  Combination [spring and rubber-in-shear] [elastomer-in-shear] steel framed for hanger-rod mounting.  
Minimum total static deflection must be<MET> 25 millimeter</MET><ENG> 1 inch</ENG>.]</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use air springs where springs are not practical.  Consider use where 
spring deflection exceeds<MET> 89 millimeter</MET><ENG> 3.5 inches</ENG>.  Mount equipment on type 
base with "outrigger" brackets.  Detail dependable air supply and connection 
provisions including hose connections where necessary.</NPR><BRK/>
<BRK/>
<NPR>Servo-controlled air spring isolators with natural frequencies for most applications 
can be provided. System loads can range from<MET> 227 to 226,796 kilogram</MET><ENG> 500 to 
500,000 pounds</ENG>.  Servo-mechanisms will maintain height of isolated mass within<MET>
 0.13 millimeter</MET><ENG> 0.005 inch.</ENG></NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Type G:  Air spring with body constructed of reinforced elastomer specifically suitable for application environment.  
Select air spring to provide a natural frequency equal to<MET> 127 millimeter</MET><ENG> 5 inches</ENG> of deflection of conventional 
specified steel springs.  Provide facilities for dead-level adjustment and height-control of supported equipment.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.3   <SUB>Bases</SUB></TTL><BRK/>
<BRK/>
<TXT>Bases must be:</TXT><BRK/>
<BRK/>
<LST>[Type U:  Unit isolators without rails, structural-steel bases, or inertia blocks.]</LST><BRK/>
<BRK/>
<LST>[Type R:  Rails, [connected] [disconnected] mill-rolled structural steel, of sufficient dimension to 
preclude deflection at midpoint of unsupported span in excess of 1/1,440th of the span between isolators, 
power transmission, component misalignment, and any overhung weight.  Where Type R bases are specified 
and the equipment proposed requires additional base support, use a Type S base.]</LST><BRK/>
<BRK/>
<LST>[Type S:  Structural-steel bases common to a supported assembly, made from welded-joint mill-rolled structural 
steel with closed-perimeter configuration, isolators attached to outrigger supports.]</LST><BRK/>
<BRK/>
<LST>Height of steel members must be sufficient to provide stiffness required to maintain equipment manufacturer's 
recommended alignment and duty efficiency of power-transmission components.  Height of steel member must 
not result in member deflection at midpoint of unsupported span of more than 1/1,440th of the span between 
isolators.  Minimum height must be<MET> 127 millimeter</MET><ENG> 5 inches</ENG>.</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following concrete inertia-block thickness and mass criteria are 
of necessity, general in scope and should be reviewed for each application and 
rewritten to reflect specific job conditions.</NPR><BRK/>
<BRK/>
<NPR>Mass of inertia block may range from one to three times the weight of supported 
equipment.  Usually a 1 to 1 ratio is satisfactory and 1-1/2 to 1 ratio is not 
unusual.  It is very difficult to achieve an equal weight between equipment 
and inertia base on air-handling units, especially where they may be large size.</NPR><BRK/>
<BRK/>
<NPR>Due to more complex forming and isolator construction required, blocks with 
recessed isolator-mounting provisions are more expensive and should be specified 
only to eliminate hazard to personnel.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST>[Type CIB:  Concrete inertia blocks must be common to the entire assembly, and have welded-joint construction, 
mill-rolled structural-steel perimeters, welded-in No. 4 reinforcing bars<MET> 200 millimeter</MET><ENG> 8 inches</ENG> on 
center each way near the bottom of the block, outrigger-isolator mounting provisions, anchor bolts, and 
be filled with<MET> 20.68 Megapascal</MET><ENG> 3,000 psi</ENG> cured-strength concrete.]</LST><BRK/>
<BRK/>
<LST>Configuration of inertia bases must be rectangular to accommodate equipment supported.</LST><BRK/>
<BRK/>
<LST>Minimum thickness of inertia base, in addition to providing suitable mass, must be sufficient to provide 
stiffness to maintain equipment manufacturer's recommended alignment and duty efficiency of power-transmission 
components.  Minimum thickness must be sufficient to result in base deflection at midpoint of unsupported 
span of not more than 1/1,440th of the span between isolators.  Minimum thickness, the preceding requirements 
not withstanding, must be 8 percent of the longest base dimension.</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Pump bases should be as stiff as practical. <MET> 300 millimeter</MET><ENG> 12-inch</ENG> thick 
bases are common.  To attain stiffness, mass to 1-1/2 times weight of assembly 
may be considered.  Modify thickness in the following paragraph as required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Pumps with flexible couplings must not have inertia bases less than<MET> 200 millimeter</MET><ENG> 8 inches</ENG> thick.</TXT><BRK/>
<BRK/>
<TXT>Minimum mass of concrete inertia block must be equal in weight to supported equipment.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2   VIBRATION-ISOLATION SYSTEMS APPLICATION</TTL><BRK/>
<BRK/>
<TXT>Vibration isolation design per [<RID>NEBB PROCEDURAL STANDARDS</RID>] [<MET> <RID>ASHRAE HVAC APP SI HDBK</RID>,</MET><ENG><RID>ASHRAE HVAC APP IP HDBK</RID>,</ENG>
 Chapter 37,] [<RID>ASA S2.40</RID>].</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following empirical recommendations are based on floors<MET> 102 to 152 
millimeter</MET><ENG> 4 to 6 inches</ENG> thick and without subbase or "housekeeping" pad.  Spring 
deflections may be reduced for floors which are<MET> 200 millimeter</MET><ENG> 8 inches</ENG> thick.  
"Basement below grade" is considered as on "undisturbed earth."  "On grade" 
is considered as on some fill.</NPR><BRK/>
<BRK/>
<NPR>Review "provisions" for each application.</NPR><BRK/>
<BRK/>
<NPR>Where isolator deflection is specified for inside locations and project equipment 
application is roof-mounted and weather-exposed; add<MET> 13 millimeter</MET><ENG> 1/2 inch</ENG> 
to specific deflection, use Type D isolators and type U, R, or S bases.</NPR><BRK/>
<BRK/>
<NPR>Reciprocating compressor-condenser (rcc) criteria are for inside location, with 
water-cooled condenser integrally mounted.</NPR><BRK/>
<BRK/>
<NPR>Extreme care should be used in isolating field-erected cooling-tower mechanical-equipment 
supports.  Too much mechanical-equipment support movement may reduce propeller 
to fan ring clearance, normally about<MET> 13 millimeter</MET><ENG> 1/2 inch</ENG>, to 0.  Type U 
isolators cannot be used on certain units because construction may be such that 
adequately spaced support points are not available.  Recommendations specified 
are for package units only.  Review all structural-steel supports and vibration-isolation 
provisions with cooling-tower and vibration-isolator manufacturers for field-erected 
cooling towers with mountings to be applied as follows:</NPR><BRK/>
<BRK/>
<NPR>Type A under basin alone which may suffice in 50 percent of cases</NPR><BRK/>
<BRK/>
<NPR>Type D the under basin or structural-steel supports only, with deflections similar 
to those specified for package tower springs</NPR><BRK/>
<BRK/>
<NPR>Type E under mechanical-equipment supports with Type A under basin<MET> 75 to 100 
millimeter</MET><ENG> 3 to 4 inch</ENG> Type E deflection</NPR><BRK/>
<BRK/>
<NPR>Wherever practical, avoid putting pumps on vibration isolators.</NPR><BRK/>
<BRK/>
<NPR>Where deflections exceed<MET> 90 millimeter</MET><ENG> 3.5 inches</ENG>, consider air springs</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.2.1   Centrifugal Water Chiller Package Locations</TTL><BRK/>
<MET><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    6096 MM     9144 MM     12192 MM<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Hermetic    A-U-6.3     B-U-13      D-S-44.5    D-S-63<BRK/>
<BRK/>
            Open Type   B-U-9.7     D-U-25      D-CIB-44.5  D-CIB-63<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN MILLIMETER<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    20-FOOT     30-FOOT     40-FOOT<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Hermetic    A-U-0.25    B-U-0.50    D-S-1.75    D-S-2.5<BRK/>
<BRK/>
            Open Type   B-U-0.38    D-U-1.0     D-CIB-1.75  D-CIB-2.5<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES<BRK/></TBL>
</ENG><BRK/></SPT>
<SPT><TTL>2.2.2   Reciprocating Water Chiller Package Locations</TTL><BRK/>
<MET><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    6096 MM     9144 MM     12192 MM<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            500 to<BRK/>
            750 rpm     D-U-25      D-U-38      D-S-63      D-CIB-69<BRK/>
<BRK/>
            750 rpm<BRK/>
            and over    D-U-25      D-U-25      D-R-50      D-CIB-63<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN MILLIMETER<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    20-FOOT     30-FOOT     40-FOOT<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            500 to<BRK/>
            750 rpm     D-U-1.0     D-U-1.5     D-S-2.5     D-CIB-2.75<BRK/>
<BRK/>
            750 rpm<BRK/>
            and over    D-U-1.0     D-U-1.0     D-R-2.0     D-CIB-2.5<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES<BRK/></TBL>
</ENG><BRK/></SPT>
<SPT><TTL>2.2.3   Absorption Water Chiller Package Locations</TTL><BRK/>
<MET><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    6096 MM     9144 MM     12192 MM<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Standard    A-U-6       D-U-25      D-U-38      D-U-69<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN MILLIMETER<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    20-FOOT     30-FOOT     40-FOOT<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Standard    A-U-0.25    D-U-1.0     D-U-1.5     D-U-2.75<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES<BRK/></TBL>
</ENG><BRK/></SPT>
<SPT><TTL>2.2.4   Reciprocating Compressor/Condenser Locations</TTL><BRK/>
<MET><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    6096 MM     9144 MM     12192 MM<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            500 to<BRK/>
            750 rpm     D-U-25      D-U-38      D-U-63      D-CIB-69<BRK/>
<BRK/>
            750 to<BRK/>
            and over    D-U-25      D-U-25      D-U-50      D-CIB-63<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN MILLIMETER<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    20-FOOT     30-FOOT     40-FOOT<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            500 to<BRK/>
            750 rpm     D-U-1.0     D-U-1.5     D-U-2.5     D-CIB-2.75<BRK/>
<BRK/>
            750 to<BRK/>
            and over    D-U-1.0     D-U-1.0     D-U-2.0     D-CIB-2.5<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES<BRK/></TBL>
</ENG><BRK/></SPT>
<SPT><TTL>2.2.5   Reciprocating Refrigeration Compressor Locations</TTL><BRK/>
<MET><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    6096 MM     9144 MM     12192 MM<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            500 to<BRK/>
            750 rpm     C-U-25      C-U-38      C-U-63      C-CIB-69<BRK/>
<BRK/>
            750 rpm<BRK/>
            and over    C-U-25      C-U-25      C-U-50      C-CIB-63<BRK/>
<BRK/>
           *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN MILLIMETER<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    20-FOOT     30-FOOT     40-FOOT<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            500 to<BRK/>
            750 rpm     C-U-1.0     C-U-1.5     C-U-2.5     C-CIB-2.75<BRK/>
<BRK/>
            750 rpm<BRK/>
            and over    C-U-1.0     C-U-1.0     C-U-2.0     C-CIB-2.5<BRK/>
<BRK/>
           *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES<BRK/></TBL>
</ENG><BRK/></SPT>
<SPT><TTL>2.2.6   Centrifugal Pump Locations</TTL><BRK/>
<MET><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    6096 MM     9144 MM     12192 MM<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Close-<BRK/>
            couple<BRK/>
            through<BRK/>
            3728 watt   None        -R-8.9      C-S-25      C-S-25<BRK/>
<BRK/>
            Bedplate-<BRK/>
            mounted<BRK/>
            through<BRK/>
            3728 watt   None        C-CIB-25    C-CIB-38    C-CIB-44.5<BRK/>
<BRK/>
            5592 watt   None        C-CIB-25    C-CIB-44.5  C-CIB-44.5<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN MILLIMETER<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    20-FOOT     30-FOOT     40-FOOT<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Close-<BRK/>
            couple<BRK/>
            through<BRK/>
            5 hp        None        -R-0.35     C-S-1.0     C-S-1.0<BRK/>
<BRK/>
            Bedplate-<BRK/>
            mounted<BRK/>
            through<BRK/>
            5 hp        None        C-CIB-1.0   C-CIB-1.5   C-CIB-1.75<BRK/>
<BRK/>
            7-1/2 hp    None        C-CIB-1.0   C-CIB-1.75  C-CIB-2.5<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES<BRK/></TBL>
</ENG><BRK/></SPT>
<SPT><TTL>2.2.7   Air-Cooled Condensing Unit Locations</TTL><BRK/>
<MET><TBL><THD><BRK/>
                             6096 MM       9144 MM       12192 MM<BRK/>
                             ROOF-SPAN     ROOF-SPAN     ROOF-SPAN<BRK/>
            <HL1>TYPE EQUIPMENT</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Through 5 hp<BRK/>
            over 900 rpm       B-U-13        D-U-25        D-U-44.5<BRK/>
<BRK/>
            Over 5 hp<BRK/>
            to 500 rpm         B-U-13        D-U-44.5      D-U-63<BRK/>
<BRK/>
            500 rpm and over   B-U-13        D-U-25        D-U-44.5<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN MILLIMETER<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
                             20-FOOT       30-FOOT       40-FOOT<BRK/>
                             ROOF-SPAN     ROOF-SPAN     ROOF-SPAN<BRK/>
            <HL1>TYPE EQUIPMENT</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
<BRK/>
            Through 5 hp<BRK/>
            over 900 rpm       B-U-0.5       D-U-1.0       D-U-1.75<BRK/>
<BRK/>
            Over 5 hp<BRK/>
            to 500 rpm         B-U-0.5       D-U-1.75      D-U-2.5<BRK/>
<BRK/>
            500 rpm and over   B-U-0.5       D-U-1.0       D-U-1.75<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES<BRK/></TBL>
</ENG><BRK/></SPT>
<SPT><TTL>2.2.8   Low-Pressure Suspended Air-Handling Unit (AHU) Locations</TTL><BRK/>
<BRK/>
<TXT>Vibration-isolation provisions apply to ceiling-suspended Air Moving and Conditioning Association Class A packaged 
central-station units.</TXT><BRK/>
<MET><TBL><THD><BRK/>
                             6096 MM       9144 MM       12192 MM<BRK/>
                             ROOF-SPAN     ROOF-SPAN     ROOF-SPAN<BRK/>
            <HL1>TYPE EQUIPMENT</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
           Through 3728 watt   F-U-25        F-U-25        F-U-25<BRK/>
<BRK/>
           5592 watt and over<BRK/>
           250 to 500 rpm      F-U-44.5      F-U-44.5      F-U-44.5<BRK/>
<BRK/>
           500 rpm and over    F-U-25        F-U-31.8      F-U-39.4<BRK/>
<BRK/>
           *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN MILLIMETER<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
                             20-FOOT       30-FOOT       40-FOOT<BRK/>
                             ROOF-SPAN     ROOF-SPAN     ROOF-SPAN<BRK/>
            <HL1>TYPE EQUIPMENT</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Through 5 hp       F-U-1.0       F-U-1.0       F-U-1.0<BRK/>
<BRK/>
            7-1/2 hp and over<BRK/>
            250 to 500 rpm     F-U-1.75      F-U-1.75      F-U-1.75<BRK/>
<BRK/>
            500 rpm and over   F-U-1.0       F-U-1.25      F-U-1.55<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES<BRK/></TBL>
</ENG><BRK/></SPT>
<SPT><TTL>2.2.9   Low-Pressure AHU Locations</TTL><BRK/>
<BRK/>
<TXT>Vibration-isolation provisions apply to floor-mounted Air Moving and Conditioning Association Class A packaged 
central-station units.</TXT><BRK/>
<MET><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    6096 MM     9144 MM     12192 MM<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Through<BRK/>
            3728 watt   B-U-8.9     C-U-25      C-U-25      C-U-25<BRK/>
<BRK/>
            5592 watt<BRK/>
            and over<BRK/>
            250 to<BRK/>
            500 rpm     B-U-8.9     C-U-44.5    C-U-44.5    C-U-44.5<BRK/>
<BRK/>
            500 rpm     B-U-8.9     C-U-25      C-U-38<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN MILLIMETER<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    20-FOOT     30-FOOT     40-FOOT<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Through<BRK/>
            5 hp        B-U-0.35    C-U-1.0     C-U-1.0     C-U-1.0<BRK/>
<BRK/>
            7-1/2 hp<BRK/>
            and over<BRK/>
            250 to<BRK/>
            500 rpm     B-U-0.35    C-U-1.75    C-U-1.75    C-U-1.75<BRK/>
<BRK/>
            500 rpm     B-U-0.35    C-U-1.0     C-U-1.5<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES<BRK/></TBL>
</ENG><BRK/></SPT>
<SPT><TTL>2.2.10   Medium- And High-Pressure Ahu Locations</TTL><BRK/>
<BRK/>
<TXT>Vibration-isolation provisions apply to floor-mounted Air Moving and Conditioning Association Classes B and C 
packaged central-station units.</TXT><BRK/>
<ENG><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    20-FOOT     30-FOOT     40-FOOT<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Through<BRK/>
            20 hp<BRK/>
            250 to<BRK/>
            300 rpm     B-U-0.35    C-U-2.5     C-U-2.5     C-U-3.5<BRK/>
<BRK/>
            300 to<BRK/>
            500 rpm     B-U-0.35    C-U-1.75    C-U-1.75    C-U-2.5<BRK/>
<BRK/>
            500 rpm<BRK/>
            and over    B-U-0.35    C-U-1.0     C-U-1.0     C-U-1.75<BRK/>
<BRK/>
            Over 20 hp<BRK/>
            250 to<BRK/>
            300 rpm     B-U-0.35    C-U-2.5     C-CIB-3.5   C-CIB-3.5<BRK/>
<BRK/>
            300 to<BRK/>
            500 rpm     B-U-0.35    C-U-2.5     C-CIB-2.5   C-CIB-3.5<BRK/>
<BRK/>
            500 rpm<BRK/>
            and over    B-U-0.35    C-U-1.0     C-CIB-1.75  C-CIB-2.5<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES<BRK/></TBL>
</ENG><BRK/></SPT>
<SPT><TTL>2.2.11   Air-Moving Device Locations</TTL><BRK/>
<BRK/>
<TXT>Vibration-isolation provisions apply to [housed] [unhoused] free-standing fans of any pressure rating, located 
in [field-erected [field-] [factory-] fabricated central-station units] [unhoused [return-air] [supply-air] service].</TXT><BRK/>
<MET><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    6096 MM     9144 MM     12192 MM<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Through<BRK/>
            14.9<BRK/>
            kilowatt<BRK/>
            250 to<BRK/>
            300 rpm     B-U-8.9     C-U-63      C-U-63      C-U-89<BRK/>
<BRK/>
            300 to<BRK/>
            500 rpm     B-U-8.9     C-U-44.5    C-U-44.5    C-U-63<BRK/>
<BRK/>
            500 rpm<BRK/>
            and over    B-U-8.9     C-U-25      C-U-25      C-U-44.5<BRK/>
<BRK/>
            Over 14.9<BRK/>
            kilowatt<BRK/>
            250 to<BRK/>
            300 rpm     B-U-8.9     C-U-63      C-CIB-89    C-CIB-89<BRK/>
<BRK/>
            300 to<BRK/>
            500 rpm     B-U-8.9     C-U-63      C-CIB-63    C-CIB-89<BRK/>
<BRK/>
            500 rpm<BRK/>
            and over    B-U-8.9     C-U-25      C-CIB-44.5  C-CIB-63<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN MILLIMETER<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    20-FOOT     30-FOOT     40-FOOT<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Through<BRK/>
            20 hp<BRK/>
            200 to<BRK/>
            300 rpm     B-U-0.35    C-S-2.5     C-S-2.5     C-S-3.5<BRK/>
<BRK/>
            300 to<BRK/>
            500 rpm     B-U-0.35    C-S-1.75    C-S-1.75    C-S-2.5<BRK/>
<BRK/>
            500 rpm<BRK/>
            and over    B-U-0.35    C-S-1.0     C-S-1.5     C-S-1.75<BRK/>
<BRK/>
            Over 20 hp<BRK/>
            250 to<BRK/>
            300 rpm     B-U-0.35    C-S-2.75    C-CIB-3.5   C-CIB-5.0<BRK/>
<BRK/>
            300 to<BRK/>
            500 rpm     B-U-0.35    C-S-1.75    C-CIB-2.5   C-CIB-3.5<BRK/>
<BRK/>
            500 rpm<BRK/>
            and over    B-U-0.35    C-S-1.0     C-CIB-1.75  C-CIB-2.5<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES<BRK/></TBL>
</ENG><MET><TBL><THD><BRK/>
                                  ON GRADE    ON GRADE    ON GRADE<BRK/>
                      BASEMENT    6096 MM     9144 MM     12192 MM<BRK/>
              TYPE    BELOW-GRADE FLOOR-SPAN  FLOOR-SPAN  FLOOR-SPAN<BRK/>
            <HL1>EQUIPMENT</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1> <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Through<BRK/>
            14.9<BRK/>
            kilowatt<BRK/>
            200 to<BRK/>
            300 rpm     B-U-8.9     C-S-63      C-S-63      C-S-89<BRK/>
<BRK/>
            300 to<BRK/>
            500 rpm     B-U-8.9     C-S-44.5    C-S-44.5    C-S-63<BRK/>
<BRK/>
            500 rpm<BRK/>
            and over    B-U-8.9     C-S-250     C-S-38      C-S-44.5<BRK/>
<BRK/>
            Over 14.9<BRK/>
            kilowatt<BRK/>
            250 to<BRK/>
            300 rpm     B-U-8.9     C-S-69.9    C-CIB-89    C-CIB-127<BRK/>
<BRK/>
            300 to<BRK/>
            500 rpm     B-U-8.9     C-S-44.5    C-CIB-63    C-CIB-89<BRK/>
<BRK/>
            500 rpm<BRK/>
            and over    B-U-8.9     C-S-25      C-CIB-44.5  C-CIB-63<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN MILLIMETER<BRK/></TBL>
</MET><BRK/></SPT>
<SPT><TTL>2.2.12   Cross-Flow Cooling Tower Locations</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For blank spaces see notes at beginning of paragraph entitled, "Vibration-Isolation 
Systems Application.  Design vibration isolators capable of supporting towers 
exposed to wind loading of<ENG> 30 pounds per square foot</ENG><MET> 1437 pascal</MET>.</NPR><BRK/>
<AST/><BRK/></NTE>
<MET><TBL><THD><BRK/>
                             6096 MM       9144 MM       12192 MM<BRK/>
                             ROOF-SPAN     ROOF-SPAN     ROOF-SPAN<BRK/>
            <HL1>TYPE EQUIPMENT</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Package under<BRK/>
            tower base<BRK/>
            to 500 rpm         B-U-8.9       D-U-50        D-U-63<BRK/>
<BRK/>
            500 rpm and over   B-U-8.9       D-U-25        D-U-44.5<BRK/>
<BRK/>
            Field erected<BRK/>
            under tower<BRK/>
            base; all rpm<BRK/>
<BRK/>
            Under mechanical-<BRK/>
            equipment<BRK/>
            supporting<BRK/>
            frame to 500 rpm<BRK/>
<BRK/>
            500 rpm and over<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN MILLIMETER<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
                             20-FOOT       30-FOOT       40-FOOT<BRK/>
                             ROOF-SPAN     ROOF-SPAN     ROOF-SPAN<BRK/>
            <HL1>TYPE EQUIPMENT</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Package under<BRK/>
            tower base<BRK/>
            to 500 rpm         B-U-0.35      D-U-2.0       D-U-2.5<BRK/>
<BRK/>
            500 rpm and over   B-U-0.35      D-U-1.0       D-U-1.75<BRK/>
<BRK/>
            Field erected<BRK/>
            under tower<BRK/>
            base; all rpm<BRK/>
<BRK/>
            Under mechanical-<BRK/>
            equipment<BRK/>
            supporting<BRK/>
            frame to 500 rpm<BRK/>
<BRK/>
            500 rpm and over<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES<BRK/></TBL>
</ENG><BRK/></SPT>
<SPT><TTL>2.2.13   Blow-Through Cooling Tower Locations</TTL><BRK/>
<MET><TBL><THD><BRK/>
                             6096 MM       9144 MM       12192 MM<BRK/>
                             ROOF-SPAN     ROOF-SPAN     ROOF-SPAN<BRK/>
            <HL1>TYPE EQUIPMENT</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Under tower base<BRK/>
            to 500 rpm         B-U-8.9       C-S-63        C-S-89<BRK/>
<BRK/>
            500 rpm and over   B-U-8.9       C-S-25        C-S-44.5<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN MILLIMETER<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
                             20-FOOT       30-FOOT       40-FOOT<BRK/>
                             ROOF-SPAN     ROOF-SPAN     ROOF-SPAN<BRK/>
            <HL1>TYPE EQUIPMENT</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1>   <HL1>PROVISIONS*</HL1><BRK/></THD>
<BRK/>
            Under tower base<BRK/>
            to 500 rpm         B-U-0.35      C-S-2.5       C-S-3.5<BRK/>
<BRK/>
            500 rpm and over   B-U-0.35      C-S-1.0       C-S-1.75<BRK/>
<BRK/>
            *TYPE OF MOUNTING, BASE, AND MINIMUM DEFLECTION IN INCHES<BRK/></TBL>
</ENG><BRK/></SPT>
</SPT><SPT><TTL>2.3   PIPE AND DUCT VIBRATION ISOLATION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Drawings should show pipe and duct isolation required by project conditions.</NPR><BRK/>
<BRK/>
<NPR>Hanger-rod length should be long enough to dissipate conducted heat which might 
be detrimental to elastomers.</NPR><BRK/>
<BRK/>
<NPR>Drawings should show type and spacing of pipe isolators in accordance with the 
following guide:</NPR><BRK/>
<MET><BRK/>
<NPR>Pipe Size (DN)   Distance To       Maximum Spacing<BRK/>
Millimeter       Be Isolated      Between Isolators<BRK/>
<HL1>Inclusive</HL1>        <HL1>Millimeter</HL1>          <HL1>Millimeter</HL1><BRK/>
<BRK/>
   25               3048                3048<BRK/>
<BRK/>
   50               4572                3048<BRK/>
<BRK/>
   75               6096                3048<BRK/>
 <BRK/>
   100              7620                3048<BRK/>
 <BRK/>
   150              9144                3048<BRK/>
<BRK/>
   200             12192                3048<BRK/>
<BRK/>
   250             13716                3048<BRK/>
<BRK/>
   300             15240                3048<BRK/>
<BRK/>
   406             18288                3048</NPR><BRK/></MET>
<ENG><BRK/>
<NPR>Pipe Size      Distance To       Maximum Spacing<BRK/>
Inches         Be Isolated      Between Isolators<BRK/>
<HL1>Inclusive</HL1>         <HL1>Feet</HL1>               <HL1>Feet</HL1><BRK/>
<BRK/>
   1               10                 10<BRK/>
<BRK/>
   2               15                 10<BRK/>
<BRK/>
   3               20                 10<BRK/>
<BRK/>
   4               25                 10<BRK/>
<BRK/>
   6               30                 10<BRK/>
<BRK/>
   8               40                 10<BRK/>
<BRK/>
   10              45                 10<BRK/>
<BRK/>
   12              50                 10<BRK/>
<BRK/>
   16              60                 10</NPR><BRK/></ENG>
<BRK/>
<NPR>Coordinate duct and piping drawings and specifications with respect to connected 
vibration-isolated equipment deflections, expansion joints, and other flexible 
equipment connections.</NPR><BRK/>
<BRK/>
<NPR>In addition to springs and rubber, high-density fibrous-glass segment pipe saddles 
may be used for vibration isolation.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Type G:  Isolators must be devices with in-series contained steel springs and preformed fibrous-glass or chloroprene-elastomer 
elements for connecting to building-structure attachments.  Load devices by supported system during operating 
conditions to produce a minimum spring and elastomer static deflection of<MET> 25 millimeter and 10 millimeter</MET><ENG> 1 inch 
and 3/8 inch</ENG>, respectively.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use Type H and Type J isolators where necessary to support pipe beyond 
tabulated distance.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Type H:  <SUB>Isolators</SUB> must be devices with contained chloroprene-elastomer elements for connecting to building-structure 
attachments.  Load devices by supported system during operating conditions to produce a minimum elastomer static 
deflection of<MET> 10 millimeter</MET><ENG> 3/8 inch</ENG>.</TXT><BRK/>
<BRK/>
<TXT>Type J:  Isolators must be devices with elastomers mounted on floor-supported columns or directly on the floor.  
Load devices by supported system during operating conditions to produce a minimum elastomer static deflection 
of<MET> 10 millimeter</MET><ENG> 3/8 inch</ENG>.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.3.1   <SUB>Floor-Mounted Piping</SUB></TTL><BRK/>
<BRK/>
<TXT>Type K:  Isolators must be devices with springs mounted on floor-supported columns or directly on the floor.  
Load devices by supported system during operating conditions to produce a minimum spring static deflection of<MET>
 25 millimeter</MET><ENG> 1 inch</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.2   <SUB>Vertical Piping</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For pipe approximately<MET> DN100</MET><ENG> 4 inches</ENG> and larger.</NPR><BRK/>
<BRK/>
<NPR>Do not use Type l typical vertical pipe attachments on vibration-isolated pipe.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Type L:  Isolators must be pipe base-support devices with one or more contained steel springs.  Load devices 
by supported system during operating conditions to produce a minimum static deflection of<MET> 25 millimeter</MET><ENG> 1 inch</ENG>
.  Equip devices with precompression and vertical-limit features, as well as a minimum<MET> 6.4 millimeter</MET><ENG> 1/4-inch</ENG>
 thick elastomer sound pad and isolation washers, for mounting to floor.</TXT><BRK/>
<BRK/>
<TXT>Type M:  Isolators must be elastomer mounted baseplate and riser pipe-guide devices.  Elastomer elements must 
be contained double acting, and elastomers under rated load must have a minimum static deflection of<MET> 10 millimeter</MET><ENG>
 3/8 inch</ENG>.  Size isolator to accommodate thermal insulation within the stationary guide ring.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Install equipment in accordance with manufacturer's recommendations.</TXT><BRK/>
<BRK/>
<TXT>[Rails, structural steel bases, and concrete inertia blocks must be raised not less than<MET> 25 millimeter</MET><ENG> 1 inch</ENG>
 above the floor and be level when equipment supported is under operating load.]</TXT><BRK/>
<BRK/>
<TXT>[Vibration-isolation installation and deflection testing after equipment start-up must be directed by a competent 
representative of the manufacturer.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   TESTS AND REPORTS</TTL><BRK/>
<BRK/>
<TXT>[<TST>Vibration-isolation devices must be deflection tested.</TST>  Submit test reports in accordance with paragraph entitled, 
"Submittal Procedures," substantiating that all equipment has been isolated as specified and that <NED/>minimum specified 
deflections have been met.  Make all measurements in the presence of the Contracting Officer.]</TXT><BRK/>
<BRK/></SPT>
</PRT>    <END/><BRK/></SEC>