<SCN>SECTION 26 05 33</SCN><BRK/>
<BRK/>
<STL>DOCKSIDE POWER CONNECTION STATIONS  </STL><BRK/>
<DTE>01/07</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers <SCP>600 V and 15 kV dockside power connection 
stations for use in 480 V, 4160 V, and 13.8 kV ship service and 480 V industrial 
service electrical distribution systems</SCP> meeting the requirements of UFC 4-150-02 
DESIGN: DOCKSIDE UTILITIES FOR SHIP SERVICE.  This specification section shall 
be referenced in Ssection 26 11 16 SECONDARY UNIT SUBSTATIONSand Section26 11 
13.00 20 PRIMARY UNIT SUBSTATIONwhen the power connection stations are to be 
included as an auxiliary compartment of the switchgear associated with a secondary 
or primary unit substation being provided for electrical ship service.<BRK/>
<BRK/>
Use the following related guide specification for associated power distribution equipment:<BRK/>
<BRK/>
--Section <SRF>26 08 00</SRF> APPARATUS INSPECTION AND TESTING<BRK/>
--Section <SRF>26 12 19.10</SRF> THREE-PHASE PAD-MOUNTED TRANSFORMERS<BRK/>
--Section <SRF>33 71 02.00 20</SRF> UNDERGROUND ELECTRICAL DISTRIBUTION<BRK/>
<BRK/>
--Section <SRF>26 11 16</SRF> SECONDARY UNIT SUBSTATIONS<BRK/>
<BRK/>
26 11 13 00.00 20 PRIMARY UNIT SUBSTATION<BRK/>
--Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM<BRK/>
 <BRK/>
Before preparing plans and specifications for a specific project, consult Unified 
Facilities Criteria UFC 4-150-02 DESIGN: DOCKSIDE UTILITIES FOR SHIP SERVICE 
demand and service requirements.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This section contains the following ACAD files (Graphics) which are available 
in metric (SI) and U.S. Customary (IP) system dimensions.  Use files to develop 
project specific drawings.  Files may be modified as mecessary.  <BRK/>
<BRK/>
File Name                            TITLE<BRK/>
<BRK/>
26 05 33-Layout 1 (SI)     600 V Ship Service Power<BRK/>
                        Connection Station<BRK/>
<BRK/>
26 05 33-Layout 1 (IP)     600 V Ship Service Power<BRK/>
                        Connection Station<BRK/>
<BRK/>
26 05 33-Layout 2 (SI)     600 V Industrial Service<BRK/>
                        Power Connection Station<BRK/>
<BRK/>
26 05 33-Layout 2 (IP)     600 V Industrial Service<BRK/>
                        Power Connection Station<BRK/>
<BRK/>
26 05 33-Layout 3 (SI)     15 kV Power Connection<BRK/>
                        Station<BRK/>
<BRK/>
26 05 33-Layout 3 (IP)     15 kV Power Connection<BRK/>
                        Station</NPR><BRK/>
<BRK/>
<NPR>NOTE:  Do not include this index in project specification.</NPR><BRK/>
<BRK/>
<NPR>NOTE: TO DOWNLOAD UFGS GRAPHICS<BRK/>
<BRK/>
Go to <URL HREF="http://www.wbdg.org/ccb/NAVGRAPH/graphtoc.pdf">http://www.wbdg.org/ccb/NAVGRAPH/graphtoc.pdf</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This section contains links to the following Shore Power Cable and Connector 
requirement documents in pdf form.  Use these <BRK/>
files to develop procurement specifications for components required in OPNAVINST 
11310.2B, Operation and Maintenance Policy for Shore-to Ship Power and UFC 4-150-02, 
Dockside Utilities.  Do not include this index in project specifications. <BRK/>
<BRK/>
File (Package) Name       TITLE<BRK/>
<BRK/>
26 05 33 Pkg 1            Enhanced Low Voltage<BRK/>
                   Portable Power Cables, 600V<BRK/>
<BRK/>
26 05 33 Pkg 2            Enhanced Plus Low Voltage<BRK/>
                   Portable Power Cables, 600V<BRK/>
<BRK/>
26 05 33 Pkg 3            Medium Voltage Portable<BRK/>
                   Power Cables, 350 KCMIL, 8KV<BRK/>
<BRK/>
26 05 33 Pkg 4            Medium Voltage Portable<BRK/>
                   Power Cables, 500 KCMIL, 8KV<BRK/>
<BRK/>
26 05 33 Pkg 5            Medium Voltage Portable<BRK/>
                   Power Cables, 350 KCMIL, 15KV<BRK/>
<BRK/>
26 05 33 Pkg 6            Medium Voltage Portable<BRK/>
                   Power Cables, 500 KCMIL, 15KV <BRK/>
<BRK/>
26 05 33 Pkg 7            Single Pole Inline<BRK/>
                   Connectors, 600V<BRK/>
<BRK/>
26 05 33 Pkg 8            Cable Couplers, 15KV <BRK/>
<BRK/></NPR>
<BRK/>
<NPR>NOTE: TO DOWNLOAD UFGS GRAPHICS AND PACKAGES<BRK/>
<BRK/>
Go to <URL HREF="http://www.wbdg.org/ccb/NAVGRAPH/graphtoc.pdf">http://www.wbdg.org/ccb/NAVGRAPH/graphtoc.pdf</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following information should be indicated on the project drawings 
or specified in the project specifications.<BRK/>
<BRK/>
1.  Site Plan showing location, space available, and desired arrangement of 
power connection station.<BRK/>
<BRK/>
2.  Single-line diagram showing number and configuration of power connection 
stations; type, number, and size of conductors for each circuit; metering; and 
power cable terminations.<BRK/>
<BRK/>
3.  Floor plan, and elevation and section views of power connection stations 
as necessary indicating the number and configuration of receptacles, auxiliary 
devices, and metering accessories.<BRK/>
<BRK/>
4.  Control diagrams showing operation of circuit breakers, emergency trip pushbuttons, 
shunt trip pushbuttons, electric interlock switches, and control cabling between 
power connection stations, emergency trip panels, and associated unit substation 
switchgear.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
<BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
<BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 167</RID><RTL>(1999; R 2004) Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip</RTL><BRK/><BRK/><RID>ASTM B 33</RID><RTL>(2004) Standard Specification for Tinned Soft or Annealed Copper Wire for Electrical Purposes</RTL><BRK/><BRK/><RID>ASTM D 1535</RID><RTL>(2008) Specifying Color by the Munsell System</RTL><BRK/><BRK/><RID>ASTM D 2240</RID><RTL>(2005) Standard Test Method for Rubber Property - Durometer Hardness</RTL><BRK/><BRK/><RID>ASTM D 709</RID><RTL>(2001; R 2007) Laminated Thermosetting Materials</RTL><BRK/><BRK/></REF><REF><ORG>INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)</ORG><BRK/><BRK/><RID>IEEE C2</RID><RTL>(2007; Errata 2007; INT 2008) National Electrical Safety Code</RTL><BRK/><BRK/><RID>IEEE C57.12.28</RID><RTL>(2005) Standard for Pad-Mounted Equipment - Enclosure Integrity</RTL><BRK/><BRK/><RID>IEEE C57.13</RID><RTL>(2008) Standard Requirements for Instrument Transformers</RTL><BRK/><BRK/><RID>IEEE Std 100</RID><RTL>(2000) The Authoritative Dictionary of IEEE Standards Terms</RTL><BRK/><BRK/><RID>IEEE Std 386</RID><RTL>(2006) Standard for Separable Insulated Connector Systems for Power Distribution Systems Above 600V</RTL><BRK/><BRK/></REF><REF><ORG>INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)</ORG><BRK/><BRK/><RID>NETA ATS</RID><RTL>(2003) Acceptance Testing Specifications</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)</ORG><BRK/><BRK/><RID>NEMA C12.1</RID><RTL>(2008) Electric Meters; Code for Electricity Metering</RTL><BRK/><BRK/><RID>NEMA C12.7</RID><RTL>(2005) Requirements for Watthour Meter Sockets</RTL><BRK/><BRK/><RID>NEMA WC 58</RID><RTL>(2008) Portable and Power Feeder Cables for Use in Mines and Similar Applications-ICEA No. S-75-381</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/></REF><REF><ORG>U.S. DEPARTMENT OF DEFENSE (DOD)</ORG><BRK/><BRK/><RID>MIL-C-24368/1</RID><RTL>(Rev B) Connector Assemblies; Plug, Power Transfer, Shore to Ship and Ship to Ship, 500 Volts, 500 Amperes, 60 Hertz, Symbol Number 1160</RTL><BRK/><BRK/><RID>MIL-C-24368/2</RID><RTL>(Rev B) Connector Assemblies; Receptacle, and Receptacle-Cabled, Power Transfer, Shore to Ship and Ship to Ship, 500 Volts, 500 Amperes, 60 Hertz, Symbol Number 1161</RTL><BRK/><BRK/><RID>MIL-DTL-24643/3</RID><RTL>(Rev D; Notice 1) Cable, Electrical, 600 Volts, Types LSSHOF, LSDHOF, LSTHOF, and LSFHOF</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 489</RID><RTL>(2002; Rev thru Jun 2006) Standard for Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures</RTL><BRK/><BRK/><RID>UL 50</RID><RTL>(2007) Standard for Enclosures for Electrical Equipment</RTL><BRK/><BRK/><RID>UL 94</RID><RTL>(1996; Rev thru Jun 2006) Tests for Flammability of Plastic Materials for Parts in Devices and Appliances</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   RELATED REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Section <SRF>26 08 00</SRF> APPARATUS INSPECTION AND TESTING applies to this section, with the additions and modifications 
specified herein.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   DEFINITIONS</TTL><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, 
and on the drawings, shall be as defined in <RID>IEEE Std 100</RID>.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Submittals must be limited to those necessary for adequate quality control.  
The importance of an item in the project should be one of the primary factors 
in determining if a submittal for the item should be required.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy projects.<BRK/>
<BRK/>
Submittal items not designated with a "G" are considered as being for information 
only for Army projects and for Contractor Quality Control approval for Navy 
projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Revise or amplify these paragraphs where necessary to cover project requirements.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM><SUB>600 V Power Connection Station</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>15 kV Power Connection Station</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Ship Service Emergency Trip Panel</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Include wiring diagrams and installation details of equipment indicating layout and arrangement, 
control panels, accessories, and other items that must be shown to ensure a coordinated installation.  
Wiring diagrams shall identify circuit terminals and indicate the internal wiring for each item 
of equipment and the interconnection between each item of equipment.  Drawings shall indicate 
adequate clearance for operation, maintenance, and replacement of operating equipment devices.  
Submittals shall include the nameplate data, size, and capacity.  Submittals shall also include 
applicable federal, military, industry, and technical society publication references.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>600 V Single Pole Connectors</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Industrial Service Auxiliary Devices</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Metering Accessories</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>15 kV Cable Couplers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Deadbreak Junctions</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>High-Voltage Connectors</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Flexible Power Cable</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Paint Coating System</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>600 V Single Pole Connector Compatibility Tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>600 V Single Pole Connector Torque Test</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Power Receptacle and Plug Assembly Tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>15 kV Cable Coupler Design Tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Acceptance Checks and Tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>600 V Power Connection Station</SUB>, data package 5[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>15 kV Power Connection Station</SUB>, data package 5[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Ship Service Emergency Trip Panel</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.5.1   Drawings</TTL><BRK/>
<BRK/>
<TXT>Furnish drawings that include, but are not limited to, the following:</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  One-line diagram including breakers, fuses, current transformers, and meters.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Outline drawings including front elevation, section views, footprint, and overall dimensions.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Markings and NEMA nameplate data, including fuse information (manufacturer's name, catalog number, 
and ratings).</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">d.  Circuit breaker type, interrupting rating, and trip devices, including available settings.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">e.  Three-line diagrams and elementary diagrams and wiring diagrams with terminals identified, and indicating 
prewired interconnections between items of equipment and the interconnection between the items.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">f.  Manufacturer's instruction manuals and published time-current curves (on full size logarithmic paper) 
of the main secondary breaker and largest secondary feeder device.  These shall be used by the designer 
of record to provide breaker settings that will insure protection and coordination are achieved.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5.2   Regulatory Requirements</TTL><BRK/>
<BRK/>
<TXT>In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the 
word, "shall" had been substituted for "should" wherever it appears.  Interpret references in these publications 
to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer.  Equipment, 
materials, installation, and workmanship shall be in accordance with the mandatory and advisory provisions of <RID>
NFPA 70</RID> unless more stringent requirements are specified or indicated.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5.3   Standard Products</TTL><BRK/>
<BRK/>
<TXT>Provide materials and equipment that are products of manufacturers regularly engaged in the production of such 
products which are of equal material, design and workmanship.  Products shall have been in satisfactory commercial 
or industrial use for 2 years prior to bid opening.  The 2-year period shall include applications of equipment 
and materials under similar circumstances and of similar size.  The product shall have been on sale on the commercial 
market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.  Where two or 
more items of the same class of equipment are required, these items shall be products of a single manufacturer 
and the component parts of the item shall be the products of the same manufacturer.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.5.3.1   Alternative Qualifications</TTL><BRK/>
<BRK/>
<TXT>Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory 
field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is 
furnished.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5.3.2   Material and Equipment Manufacturing Date</TTL><BRK/>
<BRK/>
<TXT>Products manufactured more than 3 years prior to date of delivery to site shall not be used, unless specified 
otherwise.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>1.6   WARRANTY</TTL><BRK/>
<BRK/>
<TXT>The equipment items shall be supported by service organizations which are reasonably convenient to the equipment 
installation in order to render satisfactory service to the equipment on a regular and emergency basis during 
the warranty period of the contract.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.7   MAINTENANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.7.1   Operation and Maintenance Data</TTL><BRK/>
<BRK/>
<TXT>Submit Operation and Maintenance Manuals in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE DATA.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   <SUB>600 V POWER CONNECTION STATION</SUB></TTL><BRK/>
<BRK/>
<TXT>Ship service and industrial service power connection station assemblies shall include enclosure, power receptacles, 
auxiliary devices, metering accessories, and related wiring.  Each power connection station shall have the number 
of circuits indicated and each circuit shall provide three-phase, three-wire service.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.1   Enclosure Integrity</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where exposed to physical damage from vehicular traffic, provide suitable 
guards.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Enclosure shall be <RID>UL 50</RID> listed, type 3R, fabricated entirely of <RID>ASTM A 167</RID> type 304 or 304L stainless steel.  
All interior and exterior covers and doors shall be minimum 12 gauge stainless steel sheets.  Unit shall have 
fixed top and open bottom.  Side covers shall be bolt-on and removable.  Rear covers shall be hinged.  Optional 
doors shall have full height continuous hinge and door stop to allow door to be secured open at 90 degrees.  
Ventilating or similar openings in equipment shall be designed so that foreign objects inserted through these 
openings are deflected from energized parts.  Paint enclosure <RID>ASTM D 1535</RID> light grey No. 61.  Paint coating system 
shall comply with <RID>IEEE C57.12.28</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   <SUB>600 V Single Pole Connectors</SUB></TTL><BRK/>
<BRK/>
<TXT>Insulated connectors shall be rated for 600 volts, 690 amperes, 60 hertz, single pole, continuous duty operation.  
Connectors shall be compatible with Leviton and Duraline cam-type positive latching ball nose connectors.  Insulation 
and protective caps shall be ethylene propylene thermoplastic rubber (EPTR) colored black phase A, white phase 
B, and red phase C, conforming to the following:</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Constant Service Temperature Range: -60°C to + 135°C (-81°F to +275°F)</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Flammability: <RID>UL 94</RID> HB Rated</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Electrical: UL Relative Thermal Index (RTI): 100°C (212°F) minimum</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">d.  Durometer Hardness: <RID>ASTM D 2240</RID>, 55 - 65A</LST><BRK/>
<BRK/>
<SPT><TTL>2.1.2.1   Panel Mount Connectors</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  (1) Provide auxiliary switches with receptacles to be used for supplying 
industrial service and where required by the activity utility department with 
receptacles to be used for supplying ship service.  (2) When electric interlock 
switches are required, indicate circuiting to effect opening of breakers and 
disabling of closing of breakers via the interlock switches when a connector 
plug is removed from the associated receptacle.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide 15 degree angled, panel mount female connectors (receptacles) with threaded stud terminations.  Each 
receptacle shall be provided with a protective cap attached via wirelon.[  Panel Mount Connectors (receptacles) 
indicated to have electric interlock switches shall have a thru-center plunger that engages a single-pole double-throw, 
water-tight aluminum housed "roller lever actuated" switch upon insertion of a connector plug.  UL listed switch 
shall be electrically rated for 100,000 cycles at 10 amps, 125/250 VAC, and mechanically rated for 20,000,000 
cycles.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2.2   Cable Mount In-Line Connectors</TTL><BRK/>
<BRK/>
<TXT>Male and female cable mount in-line connectors (plugs) shall be designed for terminating on 500 kcmil cables 
with a crimp-type connection.  The connectors shall lock together so that they can not twist or turn loose unless 
a push button release mechanism is engaged.  The insulated sleeve shall be mechanically secured to the connector 
contacts to give a minimum of <MET> 3100N (700 pounds)</MET><ENG> 700 pounds</ENG> shear force.[  Provide a mating male cable mount 
in-line connector (plug) for each panel mount connector to be turned over to the contracting officer.][  Provide 
[___] male and [___] female cable mount in-line connectors[ terminated as indicated][ to be turned over to the 
contracting officer].]</TXT><BRK/>
<BRK/></SPT>
</SPT>[<SPT><TTL>2.1.3   600 V Power Receptacle</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the following paragraph only for repair projects where the existing 
MIL-C-24368/2 power receptacles are being replaced in the existing enclosure.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Rated for 500 volts, 500 amperes, 60 hertz, three-pole, continuous duty operation.  Power receptacle assembly 
shall conform to <RID>MIL-C-24368/2</RID>.  Provide receptacle assembly with factory potted cable pigtails.  Cable pigtails 
shall be a minimum of<MET> 1220 mm(4 feet)</MET><ENG> 4 feet</ENG> in length and 3-1/c Type LSSHOF-500 cables conforming to <RID>MIL-DTL-24643/3</RID>
.  Provide each receptacle with provisions for interlocking the receptacle with its respective feeder circuit 
breaker so that breaker will trip automatically if an attempt is made to remove the plug from the receptacle 
and when the receptacle cover is opened. </TXT><BRK/>
<BRK/></SPT>
]<SPT>[<TTL>2.1.4   <SUB>Industrial Service Auxiliary Devices</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide circuit breaker overcurrent protection of each service circuit.  
When the over current protection for the industrial service circuits is located 
within the associated industrial power connection station, include the paragraphs 
for "fusing," "Circuit Breakers," and "Circuit Breaker Operating Mechanism."  
When the overcurrent protection is located in a remote panelboard, include the 
paragraph for "Shunt Trip Pushbutton Control" and indicate conduit and wiring 
from the industrial power connection station shunt trip pushbutton control to 
the circuit breaker shunt trip.  Also indicate circuiting to effect opening 
of breakers via the shunt trip pushbutton control (in conjunction with the interlock 
switches).</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide the following auxiliary devices for each industrial service power connection station circuit.</TXT><BRK/>
<BRK/>
<SPT>[<TTL>2.1.4.1   Shunt Trip Pushbutton Control</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Indicate desired location (side cover or rear flange) of pushbutton control 
on drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide NEMA Q600 rated, 30 millimeter, heavy duty industrial type, normally-open, momentary, red pushbutton 
behind a spring return cover, each circuited to shunt trip one circuit breaker.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.4.2   Fusing</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include "fusing" when metering is provided.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide a fuse block mounted in the enclosure containing one fuse per phase to protect the voltage input to the[ 
watt hour meter][ and][ circuit breaker shunt trip].</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.4.3   Circuit Breaker</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide 200 kA, non-fused, current limiting circuit breakers when the 
service transformer is rated 1000 kVA and greater.  When the overcurrent protection 
is located in a remote panelboard, indicate the required circuit breaker ratings 
on the "Panelboard Schedule."</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>UL 489</RID>.  100% rated,[ non-fused, current limiting,] molded case circuit breaker, 480 VAC, 400 amperes, 3-pole, 
[200][____] kaic short circuit current interrupting rating, with a 480 V shunt trip.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.1.4.4   Circuit Breaker Operating Mechanism</TTL><BRK/>
<BRK/>
<TXT>Provide flexible cable mechanism with flange mounted disconnect handle for each circuit breaker as indicated.</TXT><BRK/>
<BRK/></SPT>
]</SPT><SPT>[<TTL>2.1.5   <SUB>Metering Accessories</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When metering is required by the activity and the industrial power connection 
stations are to be directly connected to the industrial power transformer secondary, 
the industrial power connection stations shall include the following metering 
accessories.  Where a panelboard is to be provided for industrial loads, provide 
a separate watt-hour meter/current transformer cabinet.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide watt-hour meter and current transformers for each industrial service power connection station circuit.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.5.1   Watt-hour Meter</TTL><BRK/>
<BRK/>
<TXT>Provide a socket-mounted, electronic programmable outdoor watt-hour meter mounted on door of cabinet.  Meter 
shall either be programmed at the factory or shall be programmed in the field.  When field programming is performed, 
turn field programming device over to the Contracting Officer at completion of project.  Meter shall be coordinated 
to system requirements and conform to <RID>NEMA C12.1</RID>.</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Design:  Provide watt-hour meter for use on a three-phase, 3-wire, 480 volt system with 3 current 
transformers.  Include necessary KYZ pulse initiation hardware for Energy Monitoring and Control System 
(EMCS).</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Class: 20; Form: 45S, accuracy: +/- 1.0 percent; Finish: Class II</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Cover:  Polycarbonate and lockable to prevent tampering and unauthorized removal.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">d.  Kilowatt-hour Register:  Five digit electronic programmable type</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">e.  Demand Register:</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Provide solid state.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  Meter reading multiplier:  Indicate multiplier on the meter face.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Demand interval length:  Shall be programmed for 15 minutes with rolling demand up to six 
subintervals per interval.</ITM><BRK/>
<BRK/>
<LST INDENT="-0.33">f.  Socket:  <RID>NEMA C12.7</RID>.  Provide NEMA Type 3R, box-mounted socket, ringless, having manual circuit-closing 
bypass and having jaws compatible with requirements of the meter.  Cover unused hub openings with blank 
hub plates.  Provide manufacturers standard enclosure color unless otherwise indicated.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.5.2   Current Transformers</TTL><BRK/>
<BRK/>
<TXT><RID>IEEE C57.13</RID>.  Provide butyl-molded window type current transformers with 600 volt insulation, 10 kV BIL.  Provide 
three current transformers with characteristics listed in the following table.</TXT><BRK/>
<BRK/>
<TBL><THD>      <HL1>CT Ratio</HL1>          <HL1> RF </HL1>           <HL1>Meter Accuracy Class</HL1><BRK/>
<BRK/></THD>
       400/5            4.0             0.3 thru B-0.2</TBL><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.1.5.3   Watt-hour Meter/Current Transformer Cabinet</TTL><BRK/>
<BRK/>
<TXT>Cabinet shall be NEMA 3R fabricated of 12 gauge stainless steel and shall have hinged front door with vault handle.  
Paint enclosure <RID>ASTM D 1535</RID> light grey No. 61.  Paint coating system shall comply with <RID>IEEE C57.12.28</RID>.</TXT><BRK/>
<BRK/>
]</SPT>]</SPT><SPT><TTL>2.1.6   Enclosure Configurations</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Ship Service Power Stations shall consist of multiple sections, with 
each section having a maximum of four vertically arranged receptacle circuits.  
Provide pad lockable doors to restrict access to unused energized receptacles 
where ship service circuits are connected in parallel to multiple stations.  
See Layout 1 for typical enclosure design.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">a.  Enclosures for ship service stations shall be configured as indicated.  All three receptacles of 
the same circuit shall be mounted on a common plate.  Each plate shall have handles on both ends and 
shall be bolted to the front cover so that it can be removed from the front without disconnecting the 
incoming circuit power cables.  Each section shall include a full width ground bus.[  Each section shall 
have a hinged pad lockable door.]  Provide nameplates to identify each phase designation and each circuit 
number as indicated.</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Industrial Power Stations shall consist of multiple sections, with each 
section having a maximum of two vertically arranged receptacle circuits.  Include 
information concerning circuit breakers, current transformers, fusing, shunt 
trip pushbuttons, and watt-hours meters when auxiliary devices and metering 
accessories are specified. Indicate desired side for mounting external ground 
bus and shunt trip.  See Layout 2 for typical enclosure design.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">b.  Enclosures for industrial service stations shall be configured as indicated.  All three receptacles 
of the same circuit shall be mounted on a common plate.  Each plate shall have handles on both ends and 
shall be bolted to the front cover so that it can be removed from the front without disconnecting the 
power cable.  Include a full width internal ground bus and a ground bus with four NEMA spaced lug mounting 
holes on the exterior as indicated.[  Mount the[ circuit breakers,][ and][ current transformers] on inside 
of enclosure.][  The handle for the circuit breaker operating mechanism shall be located on the rear 
flange.][  Mount watt-hour meters on rear hinged covers.][  Mount shunt trip pushbuttons on side cover 
as indicated.]</LST><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2   <SUB>15 KV POWER CONNECTION STATION</SUB></TTL><BRK/>
<BRK/>
<TXT>15 kV power connection station assemblies shall include enclosure, 15 kV power receptacles, dead-front high-voltage 
deadbreak junctions, and insulated high-voltage connectors.  Each power connection station shall have the number 
of circuits indicated and each circuit shall provide three-phase, three-wire service.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.1   Enclosure Integrity</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where exposed to physical damage from vehicular traffic, provide suitable 
guards.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>IEEE C57.12.28</RID> fabricated entirely of <RID>ASTM A 167</RID> type 304 or 304L stainless steel.  All interior and exterior 
covers and doors shall be minimum 12 gauge stainless steel sheets.  Unit shall have fixed top and open bottom 
with padlockable two-door front and removable center post.  Side and rear covers shall be bolt-on.  Doors shall 
be<MET> 915mm (36 inch)</MET><ENG> 36 inch</ENG> wide with full height continuous hinge and door stops to allow doors to be secured 
open at 90 degrees.  Paint enclosure <RID>ASTM D 1535</RID> light grey No. 61.  Paint coating system shall comply with <RID>IEEE C57.12.28</RID>
.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.2   <SUB>15 kV Cable Couplers</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  (1) High voltage cable couplers are used predominately in the mining 
and tunneling industries. There currently is no industry standard for these 
products and therefore, couplers from different manufactures may not be compatible.  
Once the use of a particular model coupler has been established at an activity, 
it may be necessary to request proprietary procurement of future couplers to 
ensure compatibility.  (2) When couplers are requested by station to have a 
mechanical interlock feature, coordinate keys with existing or new interlock 
scheme.  (3) The interlock design when required for new installations shall 
be as follows:  The circuit breakers associated with the receptacles of a respective 
power connection station shall be electrically locked open via a common electric 
reset multi-contact auxiliary relay that is controlled by a key-operated selector 
switch.  Placing the selector switch in the key-release position shall effect 
electrically locking open the circuit breakers.  This same key will then be 
used for unlocking/locking the associated couplers.  Inserting the key into 
the selector switch will allow return to the “close” position, unlocking the 
circuit breakers.<BRK/></NPR>
<BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide high voltage cable couplers rated for 15,000 volts, 500 amperes, 60 hertz, three-phase, continuous duty 
operation, and configured with three insulated phase contacts, one ground contact, and one isolated ground check 
contact.  Couplers shall be aluminum with epoxy powder coating and include hypalon gaskets and seals, all stainless 
steel hardware and[ three-bolt quick flip][ or][ 90 degree turn] connection feature.  Receptacles shall be equipment 
mount type with provisions for terminating<MET> [____] mm</MET><ENG> [____] inch</ENG> diameter [350][___] kcmil cables and include 
Live End Covers.[  Provide one cable mount type plug with weatherproof cover and provisions for terminating<MET> [____] 
mm</MET><ENG> [____] inch</ENG> diameter [350][___] kcmil cables for each receptacle.  Turn plugs over to the contracting officer.]  
Coupler pairs shall[ have provisions for padlocking][ have a mechanical interlock that allows key release only 
after the coupler pair is locked].</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Voltage ratings:  Withstand voltages shall comply with <RID>IEEE Std 386</RID> voltage ratings and characteristics 
of connectors rated 14.4 kV rms phase-to-phase.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Current ratings:  Short-time current ratings shall comply with <RID>IEEE Std 386</RID> current ratings and characteristics 
of 600 A connectors.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.3   Separable Insulated Connectors and Accessories</TTL><BRK/>
<BRK/>
<TXT><RID>IEEE Std 386</RID>.  15 kV, 95 kV BIL.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.3.1   <SUB>Deadbreak Junctions</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide 600 A deadbreak junctions with two interfaces.  Brackets shall be stainless steel.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.3.2   Insulated <SUB>High-Voltage Connectors</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide 600 Ampere deadbreak connectors.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2.4   <SUB>Flexible Power Cable</SUB></TTL><BRK/>
<BRK/>
<TXT><RID>ASTM B 33</RID>, <RID>NEMA WC 58</RID>.  Flexible power cable Type SH, 15 kV single conductor.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.5   Enclosure Configuration</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  See Layout 3 for typical enclosure design.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Enclosures shall be configured as indicated.  Include a full width ground bus.  A power cable terminated with 
a 600-ampere deadbreak connector shall connect each phase of each receptacle to one of the 600-ampere one-piece 
deadbreak apparatus bushings of a deadbreak junction.  The remaining apparatus bushing for each deadbreak junction  
shall be used for connection of the incoming circuit power cables terminated with 600-ampere deadbreak connectors.  
Provide nameplates to identify each phase designation and each circuit number.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>2.3   <SUB>SHIP SERVICE EMERGENCY TRIP PANEL</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide an emergency trip pushbutton circuited to trip all (480 V, 5 
kV, and 15 kV) circuit breakers that provide ship service to a respective berth.  
Locate the emergency trip box where it can be readily accessed by ships force.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide a stainless steel NEMA 3R cabinet sized as necessary with a color red pushbutton cover mounted behind 
the front door.  Pushbutton shall be rated for 10 amperes continuous at 600 volts, heavy duty, watertight, momentary 
contact, marked "SHIP SERVICE EMERGENCY TRIP".</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.4   MANUFACTURER'S NAMEPLATE</TTL><BRK/>
<BRK/>
<TXT>Each item of equipment shall have a nameplate bearing the manufacturer's name, address, model number, and serial 
number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5   FIELD FABRICATED NAMEPLATES</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM D 709</RID>.  Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as 
specified or as indicated on the drawings.  Each nameplate inscription shall identify the function and, when 
applicable, the position.  Nameplates shall be melamine plastic,<MET> 3 mm (0.125 inch)</MET><ENG> 0.125 inch</ENG> thick, white with 
[black][_____] center core.  Surface shall be matte finish.  Corners shall be square.  Accurately align lettering 
and engrave into the core.  Minimum size of nameplates shall be<MET> 25 by 65 mm (one by 2.5 inches)</MET><ENG> one by 2.5 inches</ENG>
.  Lettering shall be a minimum of<MET> 6.35 mm (0.25 inch)</MET><ENG> 0.25 inch</ENG> high normal block style.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6   WARNING SIGNS</TTL><BRK/>
<BRK/>
<TXT>Provide warning signs for the enclosures of electrical equipment having a nominal rating exceeding 600 volts.</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  When the enclosure integrity of such equipment is specified to be in accordance with <RID>IEEE C57.12.28</RID>
, provide self-adhesive warning signs on the outside of the high voltage compartment door(s).  Sign shall 
be a decal and shall have nominal dimensions of<MET> 178 by 255 mm (7 by 10 inches)</MET><ENG> 7 by 10 inches</ENG> with the 
legend "DANGER HIGH VOLTAGE" printed in two lines of nominal<MET> 50 mm (2 inch)</MET><ENG> 2 inch</ENG> high letters.  The 
word "DANGER" shall be in white letters on a red background and the words "HIGH VOLTAGE" shall be in 
black letters on a white background.  Decal shall be Panduit No. PPSO710D72 or approved equal.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7   SOURCE QUALITY CONTROL</TTL><BRK/>
<BRK/>
<SPT><TTL>2.7.1   <SUB>Paint Coating System</SUB></TTL><BRK/>
<BRK/>
<TXT>Submit <RID>IEEE C57.12.28</RID> paint coating system performance requirement tests.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2   <SUB>600 V Single Pole Connector Compatibility Tests</SUB></TTL><BRK/>
<BRK/>
<TXT>Conduct the following tests in the sequence noted on a male in-line connector mated with a Leviton or Duraline 
female in-line connector and a female in-line connector mated with a Leviton or Duraline male in-line connector 
with each connector terminated on a bare 500 kcmil copper conductor.  After completion of the tests, inspect 
assemblies.  There shall be no evidence of damage to the connectors.  Assemblies shall be satisfactory for immediate 
return to service at full ratings without maintenance or repair.[  Contracting Officer or his designated representative 
will witness the tests.][  A factory-certified report of the specified tests previously performed on identical 
units of each rating will be acceptable.]</TXT><BRK/>
<BRK/>
<SPT><TTL>2.7.2.1   Impact Test</TTL><BRK/>
<BRK/>
<TXT>Drop each mated connector set in a horizontal position from a height of 36-inches onto a concrete floor 50 times.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2.2   Pull Strain Test</TTL><BRK/>
<BRK/>
<TXT>Apply a 500-lb straight pull on each mated connector set for a duration of 5-minutes.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2.3   Shear Test</TTL><BRK/>
<BRK/>
<TXT>Apply a 100-lb perpendicular pull on each mated connector set for a duration of 5-minutes.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2.4   Torque Test</TTL><BRK/>
<BRK/>
<TXT>Apply a 100 ft-lb torque on each mated connector set for a duration of 5-minutes.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2.5   Heat Rise Test</TTL><BRK/>
<BRK/>
<TXT>Apply 400 amperes through each mated connector set for duration of 30-minutes.  Record temperature rise at surface 
of each mated connector set via infrared scanning equipment.  Temperature rise shall be less than 45 degree C.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2.6   Moisture Resistance Test</TTL><BRK/>
<BRK/>
<TXT>Subject the mated connectors to a water spray maintained at 5-psi, with a collection rate of 18-in/hr, at a distance 
of 5-feet, for one hour.  Verify that no water penetrated the connection.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2.7   Dielectric Voltage Withstand Test</TTL><BRK/>
<BRK/>
<TXT>Wrap the mated connectors in conductive foil and apply a test potential of 2200 VAC between the conductor and 
the foil for a period of 5-minutes.  Dielectric breakdown shall constitute a failed test.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2.8   Insulation Resistance Test</TTL><BRK/>
<BRK/>
<TXT>Wrap the mated connectors in conductive foil and using a Megger insulation resistance tester with an open circuit 
output of 500 VDC, measure the insulation resistance between the conductor and foil.  Resistance measurement 
shall be greater than 100 Megohms.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.7.3   <SUB>600 V Single Pole Connector Torque Test</SUB></TTL><BRK/>
<BRK/>
<TXT>Conduct a torque test on three male and three female cable mount in-line connectors as follows:  With the metal 
connector part rigidly secured, apply a rotating (twisting) force of 700 lbs on the insulating sleeve.  The insulating 
sleeve shall not break free and spin around the connector metal part.[  Contracting Officer or his designated 
representative will witness the tests.][  A factory-certified report of the specified tests previously performed 
on identical units of each rating will be acceptable.]</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.7.4   <SUB>Power Receptacle and Plug Assembly Tests</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the following paragraph only when providing MIL-C-24368/2 receptacles.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Conduct design, production, and quality assurance tests, as required by <RID>MIL-C-24368/1</RID> and <RID>MIL-C-24368/2</RID>, at the 
manufacturer's plant during fabrication and assembly of power receptacle and plug assemblies.  After completion 
of tests, inspect assemblies.  There shall be no evidence of damage to the receptacle or plug assembly.  Assemblies 
shall be satisfactory for immediate return to service at full ratings without maintenance or repair.[  Contracting 
Officer or his designated representative will witness the tests.][  A factory-certified report of the specified 
tests previously performed on identical units of each rating will be acceptable.]</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.7.5   <SUB>15 kV Cable Coupler Design Tests</SUB></TTL><BRK/>
<BRK/>
<TXT>Furnish reports which include results of AC withstand voltage, DC withstand voltage, impulse withstand voltage, 
short time current, and current cycling design tests performed in accordance with <RID>IEEE Std 386</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Electrical installations shall conform to <RID>IEEE C2</RID>, <RID>NFPA 70</RID>, and to the requirements specified herein.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   POWER CONNECTION STATION GROUNDING</TTL><BRK/>
<BRK/>
<TXT>Ground in accordance with <RID>NFPA 70</RID>.  Maximum resistance from assembly to ground shall be 3 ohms.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3   FIELD APPLIED PAINTING</TTL><BRK/>
<BRK/>
<TXT>Paint electrical equipment as required to match finish of adjacent surfaces or to meet the indicated or specified 
safety criteria.  Painting shall be as specified in Section <SRF>09 90 00</SRF> PAINTS AND COATINGS.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4   FIELD FABRICATED NAMEPLATE MOUNTING</TTL><BRK/>
<BRK/>
<TXT>Provide number, location, and letter designation of nameplates as indicated.  Fasten nameplates to the device 
with a minimum of two sheet-metal screws or two rivets.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5   WARNING SIGN MOUNTING</TTL><BRK/>
<BRK/>
<TXT>Provide the number of signs required to be readable from each accessible side, but space the signs a maximum 
of<MET> 9 meters (30 feet)</MET><ENG> 30 feet</ENG> apart.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6   FIELD QUALITY CONTROL</TTL><BRK/>
<BRK/>
<SPT><TTL>3.6.1   Performance of <SUB>Acceptance Checks and Tests</SUB></TTL><BRK/>
<BRK/>
<TXT>Perform in accordance with the manufacturer's recommendations and include the following visual and mechanical 
inspections and electrical tests, performed in accordance with <RID>NETA ATS</RID>.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.6.1.1   Power Connection Stations and Control Panels</TTL><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Visual and mechanical inspection performed in accordance with inspection and test procedures for 
Switchgear and Switchboard Assemblies.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  System function tests.</LST><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.6.1.2   Current Transformers</TTL><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Visual and mechanical inspection in accordance with inspection and test procedures for Instrument 
Transformers.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Electrical tests in accordance with inspection and test procedures for Instrument Transformers.</LST><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.6.1.3   Watt-hour Meters</TTL><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Visual and mechanical inspection in accordance with inspection and test procedures for Metering Devices.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Electrical tests in accordance with inspection and test procedures for Metering Devices.</LST><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.6.1.4   Circuit Breakers</TTL><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Visual and mechanical inspection in accordance with inspection and test procedures for Circuit Breakers, 
Air, Insulated-Case/Molded-Case.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Perform Electrical tests in accordance with inspection and test procedures for Circuit Breakers, 
Air, Insulated-Case/Molded-Case.</LST><BRK/>
<BRK/>
]</SPT></SPT></SPT><SPT><TTL>3.7   DEMONSTRATION</TTL><BRK/>
<BRK/>
<TXT>Upon completion of the work and at a time approved by the Contracting Officer, the Contractor shall provide instructions 
by a qualified instructor to the Government personnel in the proper operation and maintenance of the equipment.  
[_____] Government personnel shall receive training comparable to the equipment manufacturer's factory training.  
The duration of instruction shall be for not less than one 8 hour working day for instruction of operating and 
maintenance personnel.</TXT><BRK/>
<BRK/></SPT>