<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA   UFGS-26 12 19.20 (April 2006)<BRK/>
                                 -------------------------------<BRK/>
Preparing Activity:  <PRA>NAVFAC</PRA>      Replacing without change <BRK/>
                                 UFGS-16273 (January 2006)<BRK/>
                                           <BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 26 12 19.20</SCN><BRK/>
<BRK/>
<STL>SINGLE-PHASE PAD-MOUNTED TRANSFORMERS</STL><BRK/>
<DTE>04/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>single-phase clam 
shell type and two-compartment type pad-mounted transformers of the dead-front 
type for exterior applications</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>Use the following related guide specifications for power distribution equipment:</NPR><BRK/>
<NPR>--Section <SRF>26 08 00</SRF> APPARATUS INSPECTION AND TESTING</NPR><BRK/>
<NPR>--Section <SRF>26 12 19.10</SRF> THREE-PHASE PAD-MOUNTED TRANSFORMERS</NPR><BRK/>
<NPR>--Section <SRF>33 71 01</SRF> OVERHEAD TRANSMISSION AND DISTRIBUTION</NPR><BRK/>
<NPR>--Section <SRF>26 13 00.00 20</SRF> SF6 INSULATED PAD-MOUNTED SWITCHGEAR</NPR><BRK/>
<NPR>--Section <SRF>26 11 16</SRF> SECONDARY UNIT SUBSTATIONS</NPR><BRK/>
<NPR>--Section <SRF>26 11 13.00 20</SRF> PRIMARY UNIT SUBSTATION</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: TO DOWNLOAD UFGS GRAPHICS<BRK/>
<BRK/>
Go to <URL HREF="http://www.wbdg.org/ccb/NAVGRAPH/graphtoc.pdf">http://www.wbdg.org/ccb/NAVGRAPH/graphtoc.pdf</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This section uses the following energy cost and loss value tables, found 
on CCB following the directions above.</NPR><BRK/>
<BRK/>
<NPR>Do not include list of tables, or tables themselves, in project specifications.  
Use tables to obtain values required in Part 2 of the specification.</NPR><BRK/>
<BRK/>
<NPR>For SOUTHNAVFACENGCOM facilities use table SPPM-2.</NPR><BRK/>
<BRK/>
<TBL><THD>  <HL1>TABLE NUMBER</HL1>                           <HL1>TITLE</HL1><BRK/>
<BRK/></THD>
    SPPM-1           Single Phase Pad-Mounted Transformer Loss<BRK/>
                     &amp; Impedance Data - for Energy Cost (EC)<BRK/>
                     Less Than or Equal to $0.04  (1 page)<BRK/>
<BRK/>
    SPPM-2           Single Phase Pad-Mounted Transformer Loss<BRK/>
                     &amp; Impedance Data - for Energy Cost (EC)<BRK/>
                     Greater Than $0.04 and Less Than or Equal<BRK/>
                     to $0.08  (1 page)<BRK/>
<BRK/>
    SPPM-3           Single Phase Pad-Mounted Transformer Loss<BRK/>
                     &amp; Impedance Data - for Energy Cost (EC)<BRK/>
                     Greater Than $0.08 and Less Than or Equal<BRK/>
                     to $0.12  (1 page)<BRK/>
<BRK/>
     EC-1            Energy costs at LANTNAVFACENGCOM Activities<BRK/>
                     (2 pages)</TBL><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  On drawings, show:</NPR><BRK/>
<BRK/>
<NPR>1.  Single-line diagram showing pad-mounted transformer connectors, inserts, 
surge arresters, switches, fuses, current transformers with ratings, and meters 
as applicable.</NPR><BRK/>
<BRK/>
<NPR>2.  Grounding plan.</NPR><BRK/>
<BRK/>
<NPR>3.  Type and number of cables, and size of conductors for each power circuit.</NPR><BRK/>
<BRK/>
<NPR>4.  Transformer primary and secondary voltages.  (Use IEEE C57.12.00, Table 
11(a), "Designation of voltage ratings of single-phase windings").  State the 
primary voltage (nominal) actually in service and not the voltage class.</NPR><BRK/>
<BRK/>
<NPR>5.  Special conditions, such as altitude, temperature, and humidity; exposure 
to fumes, vapors, dust, and gases; and seismic requirements.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
<BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
<BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)</ORG><BRK/><BRK/><RID>ANSI C12.7</RID><RTL>(2005) Requirements for Watthour Meter Sockets</RTL><BRK/><BRK/></REF><REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 167</RID><RTL>(1999; R 2004) Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip</RTL><BRK/><BRK/><RID>ASTM D 117</RID><RTL>(2002) Standard Guide for Sampling, Test Methods, Specifications and Guide for Electrical Insulating Oils of Petroleum Origin</RTL><BRK/><BRK/><RID>ASTM D 1535</RID><RTL>(2008) Specifying Color by the Munsell System</RTL><BRK/><BRK/><RID>ASTM D 3487</RID><RTL>(2008) Standard Specification for Mineral Insulating Oil Used in Electrical Apparatus</RTL><BRK/><BRK/><RID>ASTM D 877</RID><RTL>(2002; R 2007) Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes</RTL><BRK/><BRK/><RID>ASTM D 92</RID><RTL>(2005a) Standard Test Method for Flash and Fire Points by Cleveland Open Cup Tester</RTL><BRK/><BRK/><RID>ASTM D 97</RID><RTL>(2008) Pour Point of Petroleum Products</RTL><BRK/><BRK/></REF><REF><ORG>FM GLOBAL (FM)</ORG><BRK/><BRK/><RID>FM P7825</RID><RTL>(2005) Approval Guide</RTL><BRK/><BRK/></REF><REF><ORG>INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)</ORG><BRK/><BRK/><RID>IEEE C2</RID><RTL>(2007; Errata 2007; INT 2008) National Electrical Safety Code</RTL><BRK/><BRK/><RID>IEEE C37.47</RID><RTL>(1981) Distribution Fuse Disconnecting Switches, Fuse Supports, and Current-Limiting Fuses**</RTL><BRK/><BRK/><RID>IEEE C57.12.00</RID><RTL>(2006) Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers</RTL><BRK/><BRK/><RID>IEEE C57.12.25</RID><RTL>(1990) Standard for Transformers - Pad-Mounted, Compartmental-Type, Self-Cooled, Single-Phase Distribution Transformers with Separable Insulated High-Voltage Connectors; High Voltage (34 500-Grd Y/19 920 Volts and Below; Low Voltage, 240/120 Volts; 167 kVA and Smaller - Requirements)</RTL><BRK/><BRK/><RID>IEEE C57.12.28</RID><RTL>(2005) Standard for Pad-Mounted Equipment - Enclosure Integrity</RTL><BRK/><BRK/><RID>IEEE C57.12.80</RID><RTL>(2002) Standard Terminology for Power and Distribution Transformers</RTL><BRK/><BRK/><RID>IEEE C57.12.90</RID><RTL>(2006) Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers</RTL><BRK/><BRK/><RID>IEEE C57.13</RID><RTL>(2008) Standard Requirements for Instrument Transformers</RTL><BRK/><BRK/><RID>IEEE C57.98</RID><RTL>(1993; R 1999) Guide for Transformer Impulse Tests</RTL><BRK/><BRK/><RID>IEEE C62.11</RID><RTL>(2005; Amendment A 2008) Standard for Metal-Oxide Surge Arresters for Alternating Current Power Circuits (&gt;1kV)</RTL><BRK/><BRK/><RID>IEEE Std 100</RID><RTL>(2000) The Authoritative Dictionary of IEEE Standards Terms</RTL><BRK/><BRK/><RID>IEEE Std 386</RID><RTL>(2006) Standard for Separable Insulated Connector Systems for Power Distribution Systems Above 600V</RTL><BRK/><BRK/></REF><REF><ORG>INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)</ORG><BRK/><BRK/><RID>NETA ATS</RID><RTL>(2003) Acceptance Testing Specifications</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)</ORG><BRK/><BRK/><RID>NEMA C12.1</RID><RTL>(2008) Electric Meters; Code for Electricity Metering</RTL><BRK/><BRK/><RID>NEMA C12.10</RID><RTL>(2004) Physical Aspects of Watthour Meters</RTL><BRK/><BRK/><RID>NEMA C12.4</RID><RTL>(1984; R 2002) Mechanical Demand Registers</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/></REF><REF><ORG>ORGANISATION FOR ECONOMIC CO-OPERATION AND DEVELOPMENT (OECD)</ORG><BRK/><BRK/><RID>OECD Test 203</RID><RTL>(1992) Fish Acute Toxicity Test</RTL><BRK/><BRK/></REF><REF><ORG>U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)</ORG><BRK/><BRK/><RID>EPA 600/4-90/027F</RID><RTL>(1993) Methods for Measuring the Acute Toxicity of Effluents and Receiving Waters to Freshwater and Marine Organisms</RTL><BRK/><BRK/><RID>EPA 712-C-98-075</RID><RTL>(1996) Fate, Transport and Transformation Test Guidelines - OPPTS 835.3100- "Aerobic Aquatic Biodegradation"</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 467</RID><RTL>(2007) Standard for Grounding and Bonding Equipment</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   RELATED REQUIREMENTS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include Section 26 08 00 APPARATUS INSPECTION AND TESTING on all projects 
involving medium voltage and specialized power distribution equipment.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Section <SRF>26 08 00</SRF> APPARATUS INSPECTION AND TESTING applies to this section, with the additions and modifications 
specified herein.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   DEFINITIONS</TTL><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, 
and on the drawings, shall be as defined in <RID>IEEE Std 100</RID>.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Submittals must be limited to those necessary for adequate quality control.  
The importance of an item in the project should be one of the primary factors 
in determining if a submittal for the item should be required.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy projects.<BRK/>
<BRK/>
Submittal items not designated with a "G" are considered as being for information 
only for Army projects and for Contractor Quality Control approval for Navy 
projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include the bracketed option on "CIEE and 074 review" for NAVFAC Atlantic 
and SOUTHNAVFACENGCOM projects respectively.  For other projects, submittal 
review shall be performed by the designer of record;  If submittal review by 
NAVFAC Atlantic or SOUTHNAVFACENGCOM is specifically desired, the responsible 
Government agency must coordinate with the respective Code CIEE or 074 during 
the design process.  Add appropriate information in Section 01 33 00 "Submittal 
Procedures" to coordinate with the special requirements.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[[Code CIEE, NAVFAC Atlantic][Code 074, Southern Division, Naval Facilities Engineering Command] will review 
and approve submittals in this section requiring Government approval.]  As an exception to this paragraph, transformers 
manufactured by ABB in Jefferson City, MO; by Cooper Power Systems in Waukesha, WI; by ERMCO in Dyersburg, TN; 
or by Howard Industries in Laurel, MS need not submit the entire submittal package requirements of this contract.  
Instead, the following items shall be submitted:</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  A certification, from the manufacturer, that the technical requirements of this specification shall 
be met.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  An outline drawing of the transformer with devices identified (paragraph entitled "Pad-Mounted Transformer 
Drawings," item a).</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  ANSI nameplate data of the transformer (paragraph entitled "Pad-Mounted Transformer Drawings," item 
b).</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use "will" on SOUTHNAVFACENGCOM projects.  Coordinate with paragraph 
entitled "Source Quality Control."</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">d.  Routine and other tests (paragraph entitled "Routine and Other Tests"), shall be conducted by the 
manufacturer and [may][will] be witnessed by the Government (paragraph entitled "Source Quality Control").  
Provide transformer test schedule required by submittal item "SD-11 Closeout Submittals".  Provide certified 
copies of the tests.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">e.  Provide acceptance test reports required by submittal item "SD-06 Test Reports".</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">f.  Provide operation and maintenance manuals required by submittal item "SD-10 Operation and Maintenance 
Data".</LST><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Pad-mounted transformer drawings</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Single-phase pad-mounted transformers (dead-front)</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Submittal shall include manufacturer's information for each component, device, and accessory 
provided with the transformer.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Acceptance checks and tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Transformer losses</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Submit certification from the manufacturer indicating conformance with the paragraph entitled 
"Specified Transformer Losses."</ITM><BRK/>
<BRK/>
<LST><SUB>SD-09 Manufacturer's Field Reports</SUB></LST><BRK/>
<BRK/>
<ITM>Pad-mounted transformer <SUB>design tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Pad-mounted transformer <SUB>routine and other tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Transformer(s)</SUB>, Data Package 5[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE DATA.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-11 Closeout Submittals</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Transformer test schedule</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.5.1   <SUB>Pad-Mounted Transformer Drawings</SUB></TTL><BRK/>
<BRK/>
<TXT>Drawings shall indicate, but not be limited to the following:</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  An outline drawing, including front, top, and side views.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  ANSI nameplate data.</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Navy policy requires that facilities be metered.  If exception is taken, 
coordinate with paragraphs entitled "Additions to Operation and Maintenance 
Manuals" and "Metering."  On "Clam Shells," coordinate with optional metering 
paragraph.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">[c.  Elementary diagrams and wiring diagrams with terminals identified of meter and current transformers.]</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">d.  One-line diagram, including switch(es)[, current transformers, meters,] and fuses.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">e.  Manufacturer's published time-current curves (on full size logarithmic paper) of the transformer 
high side fuse.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5.2   Regulatory Requirements</TTL><BRK/>
<BRK/>
<TXT>In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the 
word, "shall" had been substituted for "should" wherever it appears.  Interpret references in these publications 
to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer.  Equipment, 
materials, installation, and workmanship shall be in accordance with the mandatory and advisory provisions of <RID>
NFPA 70</RID> unless more stringent requirements are specified or indicated.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5.3   Standard Products</TTL><BRK/>
<BRK/>
<TXT>Provide materials and equipment that are products of manufacturers regularly engaged in the production of such 
products which are of equal material, design and workmanship.  Products shall have been in satisfactory commercial 
or industrial use for 2 years prior to bid opening.  The 2-year period shall include applications of equipment 
and materials under similar circumstances and of similar size.  The product shall have been on sale on the commercial 
market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.  Where two or 
more items of the same class of equipment are required, these items shall be products of a single manufacturer; 
however, the component parts of the item need not be the products of the same manufacturer unless stated in this 
section.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.5.3.1   Alternative Qualifications</TTL><BRK/>
<BRK/>
<TXT>Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory 
field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is 
furnished.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5.3.2   Material and Equipment Manufacturing Date</TTL><BRK/>
<BRK/>
<TXT>Products manufactured more than 3 years prior to date of delivery to site shall not be used, unless specified 
otherwise.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>1.6   MAINTENANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.6.1   <SUB>Transformer(s)</SUB> Operation and Maintenance Data</TTL><BRK/>
<BRK/>
<TXT>Submit operation and maintenance data in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE DATA and 
as specified herein.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.6.1.1   Additions to Operation and Maintenance Data</TTL><BRK/>
<BRK/>
<TXT>In addition to requirements of Data Package 5, include the following on the actual transformer(s) provided:</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  An instruction manual with pertinent items and information highlighted</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  An outline drawing, including front, top, and side views</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Prices for spare parts and supply list</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">d.  Routine and field acceptance test reports</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">e.  Fuse curves for primary fuses</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use the following bracketed option for two-compartment type transformers 
and when providing a demand meter in a clam shell type transformer.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">[f.  Information on meter, CT's, and fuse block]</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">g.  Actual nameplate diagram</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">h.  Date of purchase</LST><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>1.7   WARRANTY</TTL><BRK/>
<BRK/>
<TXT>The equipment items shall be supported by service organizations which are reasonably convenient to the equipment 
installation in order to render satisfactory service to the equipment on a regular and emergency basis during 
the warranty period of the contract.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   PRODUCT COORDINATION</TTL><BRK/>
<BRK/>
<TXT>Products and materials not considered to be pad-mounted transformers and related accessories are specified in 
[Section <SRF>33 71 01</SRF> OVERHEAD TRANSMISSION AND DISTRIBUTION,] [Section <SRF>33 71 02.00 20</SRF> UNDERGROUND ELECTRICAL DISTRIBUTION,] 
[and] [Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2   <SUB>SINGLE-PHASE PAD-MOUNTED TRANSFORMERS (DEAD-FRONT)</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  According to IEEE Std 386, 200 ampere separable insulated connectors 
normally used on dead-front pad-mounted transformers have both a fault closure 
and a short-time current rating of 10,000 amperes.  Therefore, from a safety 
standpoint, dead-front configurations which utilize these connectors should 
only be used at system locations which have available fault currents of less 
than 10,000 rms symmetrical amperes.</NPR><BRK/>
<BRK/>
<NPR>Portions of the 4.16 kV system at Dam Neck, VA and all of the 11.5 kV system 
at Norfolk Naval Shipyard, VA have a fault capability in excess of 10,000 amps.  
Therefore, 200 amp separable insulated connectors and load-break switches can 
not be used on pad-mounted transformers in these locations.  In these locations 
use 600 amp separable insulated connectors with a short time rating of 25,000 
rms symmetrical amperes.</NPR><BRK/>
<BRK/>
<NPR>Normally use single compartment (clam shell) transformers.  If two-compartment 
transformers are required, their use shall be approved by the cognizant EFD 
or EFA.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>IEEE C57.12.25</RID>, <RID>IEEE C57.12.28</RID> and as specified herein.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.1   Compartment Construction</TTL><BRK/>
<BRK/>
<LST INDENT="-0.33">[a.  Single compartment:  Shall be Type 1 as defined by <RID>IEEE C57.12.25</RID> with combination high- and low-voltage 
compartment.  Compartment shall be of the clam shell type with lockable (having pad-locking provisions) 
hinged cover and single-point latching.]</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">[b.  Two compartment:  The high- and low-voltage compartments shall be separated by steel isolating barriers 
extending the full height and depth of the compartments.  Compartment doors:  hinged lift-off type with 
stop in open position and three-point latching.]</LST><BRK/>
<BRK/>
<SPT><TTL>2.2.1.1   High Voltage</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Current policy is to use oil-immersed fuses in series with current limiting 
fuses to achieve better protection and obtain life cycle cost benefits.  Do 
not use dry-well canister fuses.</NPR><BRK/>
<BRK/>
<NPR>Do not provide standoff bushings unless this transformer is the only dead-front 
transformer on the base.  Public works normally carries standoff bushings in 
their vehicles.  Provide protective caps when providing standoff bushings and 
to cover unused bushing well inserts when not providing surge arresters.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use two bushing wells for phase-to-neutral systems and four bushing wells 
for phase-to-phase systems.  Coordinate with transformer voltage designations 
in paragraph entitled "Transformer Type and Ratings."  If feed through applications 
are required, special transformer compartment sizing may be necessary.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>High-voltage portion shall contain the incoming line, insulated high-voltage load-break connectors, bushing well 
inserts,[ feed-through inserts,] [two][four] high-voltage bushing wells configured for loop feed application, 
access to oil-immersed fuses,[ dead-front surge arresters,] tap changer handle, connector parking stands[ with 
insulated standoff bushings,][ protective caps,] and ground pad.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following paragraph is based on 200 ampere connectors.  If transformer 
primary load current is greater than 200 amperes or if primary cable size is 
greater than No. 4/0 AWG, designer shall determine the appropriate connector 
system.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">a.  Insulated high-voltage load-break connectors:  <RID>IEEE Std 386</RID>, rated [15][_____] kV, [95][_____] kV 
BIL.  Current rating:  200 amperes rms continuous.  Short time rating:  10,000 amperes rms symmetrical 
for a time duration of 0.17 seconds.  Connectors and inserts shall be the product of a single manufacturer.  
Connector shall have a steel reinforced hook-stick eye, grounding eye, test point, and arc-quenching 
contact material.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Bushing well inserts[ and feed-through inserts]:  <RID>IEEE Std 386</RID>, 200 amperes, [15][_____] kV class.  
Provide a bushing well insert for each bushing well unless indicated otherwise.[  Provide feed-through 
inserts as indicated.]</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Provide bayonet oil-immersed, expulsion fuses in series with oil-immersed, partial-range, current-limiting 
fuses.  Bayonet fuse links shall sense both high currents and high oil temperature in order to provide 
thermal protection to the transformer.  Coordinate transformer protection with expulsion fuse clearing 
low-current faults and current-limiting fuse clearing high-current faults beyond the interrupting rating 
of the expulsion fuse.  In order to eliminate or minimize oil spills, the bayonet fuse assembly shall 
include an oil retention valve inside the housing which closes when the fuse holder is removed and an 
external drip shield.  Warning shall be conspicuously displayed adjacent to the bayonet fuse(s) cautioning 
against removing or inserting fuses unless the transformer has been de-energized and the tank pressure 
has been released.</LST><BRK/>
<BRK/>
<LST>Bayonet fuse assembly:  150 kV BIL.</LST><BRK/>
<BRK/>
<LST>Oil-immersed current-limiting fuses:  <RID>IEEE C37.47</RID>; 50,000 rms amperes symmetrical interrupting rating 
at the system voltage specified.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">[d.  Surge arresters:  <RID>IEEE C62.11</RID>, rated [3][6][9][10][12][15][_____] kV, fully shielded, dead-front 
metal-oxide-varistor, elbow type with resistance-graded gap suitable for plugging into inserts as indicated.]</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">e.  Parking stands:  Provide a parking stand near each bushing well.[  Provide insulated standoff bushings 
for parking of energized load-break connectors on parking stands.]</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">[f.  Protective caps:  <RID>IEEE Std 386</RID>, 200 amperes, [15][25][_____] kV class.  Provide insulated protective 
caps (not shipping caps) for insulating and sealing out moisture from unused bushing well inserts[ and 
insulated standoff bushings].]</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.1.2   Low Voltage</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Installation of circuit breakers in the transformer is not recognized 
by ANSI standards, and limits accessibility by covering lugs, gages, and accessories.  
Do not use.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Low-voltage portion shall contain low-voltage bushings with NEMA spade terminals, accessories,[ metering,] stainless 
steel or laser-etched anodized aluminum diagrammatic transformer nameplate, and ground pad.</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Accessories shall include drain plug, fill plug, pressure relief device and a liquid level sight 
gage.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">[b.  Metering</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For single compartment (clam shell type) transformers, provide self-contained 
meter base at corresponding facility, such as individual housing unit or lift 
station, and specify in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM.  If requested 
by the activity, provide kilowatt demand meter within the transformer.</NPR><BRK/>
<BRK/>
<NPR>For two-compartment type transformers, use watthour meters.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">[1.  <RID>NEMA C12.10</RID>.  Metering for single compartment transformers:  Provide an electronic kilowatt 
demand meter mounted in the low-voltage portion of the pad-mounted transformer as indicated.</ITM><BRK/>
<BRK/>
<ITM>(a)  Meter:  Provide kilowatt demand meter coordinated to ratios of current transformers and 
transformer secondary voltage.  Meter shall indicate the highest demand load over a 15-minute 
interval conforming to <RID>NEMA C12.4</RID>.  Meter accuracy shall be within plus or minus one percent.  
Provide correct multiplier on face of meter.</ITM><BRK/>
<BRK/>
<ITM>(b)  Meter fusing:  Provide a fuse block mounted in the secondary side containing one fuse per 
phase to protect the voltage input to the meter.  Size fuses as recommended by the meter manufacturer.</ITM><BRK/>
<BRK/>
<ITM>(c)  Metering assembly:  Provide complete system including all devices required.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[2.  <RID>NEMA C12.10</RID>.  Metering for two-compartment transformers:  Provide a socket-mounted electronic 
programmable outdoor watthour meter, surface mounted flush against the side of the low-voltage 
compartment as indicated.  Meter shall either be programmed at the factory or shall be programmed 
in the field.  When field programming is performed, turn field programming device over to the 
Contracting Officer at completion of project.  Meter shall be coordinated to system requirements.</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When Section 23 09 54.00 20, "Direct Digital Control Systems" is used, 
coordinate meter requirements.  Form 4S, in text below, is for single-phase, 
three-wire systems, for other system configurations, designer shall determine 
the appropriate form designation.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM>(a)  Design:  Provide meter designed for use on a single-phase, three-wire, [240/120][480/240] 
volt system with two current transformers.  Include necessary KYZ pulse initiation hardware 
for energy monitoring and control system (EMCS)[ as specified in Section <SRF>23 09 23</SRF> DIRECT DIGITAL 
CONTROL FOR HVAC AND OTHER BUILDING SYSTEMS].</ITM><BRK/>
<BRK/>
<ITM>(b)  Coordination:  Provide meter coordinated with ratios of current transformers and transformer 
secondary voltage.</ITM><BRK/>
<BRK/>
<ITM>(c)  Class:  20<BRK/>
Form:  4S, accuracy:  plus or minus 1.0 percent<BRK/>
Finish:  Class II</ITM><BRK/>
<BRK/>
<ITM>(d)  Cover:  Polycarbonate and lockable to prevent tampering and unauthorized removal.</ITM><BRK/>
<BRK/>
<ITM>(e)  Kilowatt-hour register:  five digit electronic programmable type</ITM><BRK/>
<BRK/>
<ITM>(f)  Demand register</ITM><BRK/>
<BRK/>
<ITM>    (1)  Provide solid state</ITM><BRK/>
<BRK/>
<ITM>    (2)  Meter reading multiplier:  Indicate multiplier on the meter face.</ITM><BRK/>
<BRK/>
<ITM>    (3)  Demand interval length:  shall be programmed for [15][30][60] minutes with rolling 
demand up to six subintervals per interval.</ITM><BRK/>
<BRK/>
<ITM>(g)  Meter fusing:  Provide a fuse block mounted in the secondary side containing one fuse per 
phase to protect the voltage input to the meter.  Size fuses as recommended by the meter manufacturer.</ITM><BRK/>
<BRK/>
<ITM>(h)  Socket:  <RID>ANSI C12.7</RID>.  Provide NEMA Type 3R, box-mounted socket having automatic circuit-closing 
bypass and having jaws compatible with requirements of the meter.  Cover unused hub openings 
with blank hub plates.  Paint box Munsell 7GY3.29/1.5 green to match the pad-mounted transformer 
to which the box-mounted socket is attached.  The Munsell color notation is specified in <RID>ASTM D 1535</RID>
.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Current transformers <RID>IEEE C57.13</RID>.  Provide butyl-molded window type current transformers 
with 600-volt insulation, 10 kV BIL and mount on the low-voltage bushings.  Route current transformer 
leads in a location as remote as possible from the power transformer secondary cables to permit 
current measurements to be taken with hook-on-ammeters.  Provide two current transformers per 
power transformer with characteristics listed in the following table.</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following guidelines for specifying current transformers are based 
on the standard current transformer primary rating which is just below the full 
load current of the power transformer.</NPR><BRK/>
<BRK/>
<NPR>1.  Select the appropriate current transformer (CT) ratio, continuous-thermal-current 
rating factor (RF) at 30 degrees C and ANSI metering accuracy class values based 
on transformer kVA size and secondary voltage.  Example:  for a 50 kVA transformer 
at 240 volts - select 200/5, 4.0, 0.3 through B-0.1.</NPR><BRK/>
<BRK/>
<TBL><THD>       |--------------------------(VOLTS)--------------------------|<BRK/>
       |             240             |            480              |<BRK/>
       |-----------------------------|-----------------------------|<BRK/>
       |   CT  |    |     Meter      |   CT  |    |      Meter     |<BRK/>
  kVA  | Ratio | RF |     Class      | Ratio | RF |      Class     |<BRK/>
|------|-----------------------------|-----------------------------|<BRK/>
<BRK/></THD>
|   10 | 200/5, 4.0,  0.3 thru B-0.1 | 200/5, 4.0,  0.3 thru B-0.1 |<BRK/>
|   15 | 200/5, 4.0,  0.3 thru B-0.1 | 200/5, 4.0,  0.3 thru B-0.1 |<BRK/>
|   25 | 200/5, 4.0,  0.3 thru B-0.1 | 200/5, 4.0,  0.3 thru B-0.1 |<BRK/>
| 37.5 | 200/5, 4.0,  0.3 thru B-0.1 | 200/5, 4.0,  0.3 thru B-0.1 |<BRK/>
|   50 | 200/5, 4.0,  0.3 thru B-0.1 | 200/5, 4.0,  0.3 thru B-0.1 |<BRK/>
|   75 | 300/5, 3.0,  0.3 thru B-0.2 | 200/5, 4.0,  0.3 thru B-0.1 |<BRK/>
|  100 | 400/5, 4.0,  0.3 thru B-0.2 | 200/5, 4.0,  0.3 thru B-0.1 |<BRK/>
|  167 | 600/5, 3.0,  0.3 thru B-0.5 | 300/5, 3.0,  0.3 thru B-0.2 |<BRK/>
|------------------------------------------------------------------|</TBL><BRK/>
<BRK/>
<NPR>2.  Incorporate the appropriate values in table.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TBL><THD>  NAME   KVA      SEC. VOLT     CT RATIO    RF       METER ACC. CLASS<BRK/>
<BRK/></THD>
  [T1]   [50]     [240]         [200/5]     [4.0]    [0.3 thru B-0.1]<BRK/>
  [T2]   [75]     [480]         [200/5]     [4.0]    [0.3 thru B-0.1]]</TBL><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2.2   Transformer Type and Ratings</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use the following guidelines for specifying transformers.</NPR><BRK/>
<BRK/>
<NPR>1.  Previously the use of mineral oil filled transformers were recommended wherever 
possible.  The recent availability of biodegradable electrical insulating and 
cooling liquids may have altered that recommendation.  For NAVFAC Atlantic, 
choose less-flammable transformer liquids as specified below for all projects 
unless there is a specific requirement to do otherwise.  Where adequate distance 
from structures cannot be attained, consult NAVFAC design manuals and UFC 3-600-01, 
"Design: Fire Protection Engineering for Facilities."  Silicon-filled and R-temp 
filled transformers shall not be used for less-flammable requirements.</NPR><BRK/>
<BRK/>
<NPR>2.  Use IEEE C57.12.00, Table 11(a), voltage designations, such as "4160 V - 
240/120 V" for transformers connected phase-phase on the primary side, or "4160GrdY/2400 
V - 240/120 V" for transformers connected phase-neutral on the primary side.  
Coordinate the number of bushing wells (either two or four depending on phase-to-neutral, 
or phase-to-phase systems) with the primary voltage.</NPR><BRK/>
<BRK/>
<NPR>3.  Tap ratings may vary from those indicated, especially in lower kVA ratings.</NPR><BRK/>
<BRK/>
<NPR>4.  Specify the following transformer information under the appropriate column 
headers in the table below:  Name, Location, kVA Rating, BIL(kV) Rating (coordinate 
with primary voltage), Minimum Tested Impedance and Audible Sound Level.</NPR><BRK/>
<BRK/>
<NPR>5.  Select impedance value in accordance with technical note under paragraph 
entitled "Specified Transformer Losses.</NPR><BRK/>
<BRK/>
<NPR>6.  Determine the appropriate audible sound level from the following information.</NPR><BRK/>
<BRK/>
<TBL><THD>               <HL1>kVA</HL1>           <HL1>DECIBELS (MAX)</HL1><BRK/>
<BRK/></THD>
               10                  48<BRK/>
               15                  48<BRK/>
               25                  48<BRK/>
               37.5                48<BRK/>
               50                  48<BRK/>
               75                  51<BRK/>
               100                 51<BRK/>
               167                 55</TBL><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">a.  [Oil-insulated][Less flammable liquid-insulated], two winding, 60 hertz, 65 degrees C rise above 
a 30 degrees C average ambient, self-cooled type.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Transformer voltage ratings:  [_____] V - [240/120][480/240] V.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Tap changer shall be externally operated, manual type for changing tap setting when the transformer 
is de-energized.  Provide four 2.5 percent full capacity taps, two above and two below rated primary 
voltage.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">d.  Transformer(s) shall have characteristics per the following table:</LST><BRK/>
<BRK/>
<TBL><THD>                                      MIN TESTED IMP<BRK/>
                              BIL     (Percent at     DB<BRK/>
  NAME     LOCATION      KVA  (KV)    85 Degree C)   (MAX)<BRK/>
<BRK/></THD>
  [T1]   [AMTC Site 1]   [50] [60]      [___]         [48]<BRK/>
  [T2]   [AMTC Site 2]   [75] [60]      [___]         [51]</TBL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use "lifting lugs" on two-compartment  and "recessed stainless steel 
lifting provisions" on clam shell type transformers.  Delete the "access handhole" 
on clam shell type transformers.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">e.  Transformer shall include[ lifting lugs and provisions for jacking under base][ recessed stainless 
steel lifting provisions].  The transformer base construction shall be suitable for using rollers or 
skidding in any direction.[  Provide transformer top with an access handhole.][  Transformer shall have 
its kVA rating conspicuously displayed on its enclosure.]  The transformer shall have an insulated low-voltage 
neutral bushing with NEMA spade terminal, and with removable ground strap.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.3   Specified <SUB>Transformer Losses</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Steps to specifying transformer losses.</NPR><BRK/>
<BRK/>
<NPR>1.  Print Tables SPPM-1, SPPM-2, SPPM-3, and EC-1 as applicable (directions 
included at the front of this specification).</NPR><BRK/>
<BRK/>
<NPR>2.  Obtain energy cost for the specific activity from the cognizant EFD or PWC.  
Energy costs should be based on the cost of energy without the demand charge 
factors scaled in.  Use Table EC-1 for energy costs at the NAVFAC Atlantic activities 
indicated.  Use Table SPPM-2 for energy costs at all SOUTHNAVFACENGCOM activities.  
(Additional tables will be added for other EFD's as the information becomes 
available.</NPR><BRK/>
<BRK/>
<NPR>3.  Use Tables SPPM-1, SSPM-2, and SSPM-3 to specify losses and impedances for 
transformers based on energy cost range, and transformer primary and secondary 
voltages.</NPR><BRK/>
<BRK/>
<NPR>4.  Perform fault current calculations to verify that distribution equipment 
is coordinated with impedance specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>No-load losses (NLL) in watts at 20 degrees C, and load losses (LL) in watts at 85 degrees C, shall be as follows:</TXT><BRK/>
<BRK/>
<TBL><THD>     <HL1>NAME</HL1>        <HL1>KVA</HL1>         <HL1>"NLL"</HL1>        <HL1>"LL"</HL1><BRK/>
<BRK/></THD>
     [T1]      [     ]      [     ]      [     ]<BRK/>
     [T2]      [     ]      [     ]      [     ]</TBL><BRK/>
<BRK/>
<TXT>The values for the specified losses shall be used for comparison with the losses determined during the routine 
tests.  If the routine test values for no-load losses exceed the specified no-load losses by more than 10 percent, 
or the total losses exceed the specified total losses (sum of no-load and load losses) by more than 6 percent, 
the transformer is unacceptable.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.3   INSULATING LIQUID</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For NAVFAC Atlantic, choose less-flammable transformer liquids for all 
projects unless there is a specific requirement to do otherwise.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">[a.  Mineral oil:  <RID>ASTM D 3487</RID>, Type II, tested in accordance with <RID>ASTM D 117</RID>.  Provide identification 
of transformer as non-PCB and Type II mineral oil on the nameplate.]</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">[b.  Less-flammable transformer liquids:  <RID>NFPA 70</RID> and <RID>FM P7825</RID> for less-flammable liquids having a fire 
point not less than 300 degrees C tested per <RID>ASTM D 92</RID> and a dielectric strength not less than 33 kV 
tested per <RID>ASTM D 877</RID>.  Provide identification of transformer as "non-PCB" and "manufacturer's name and 
type of fluid" on the nameplate.</LST><BRK/>
<BRK/>
<LST>The fluid shall be a biodegradable electrical insulating and cooling liquid classified by UL and approved 
by FM as "less flammable" fluids.  The fluid shall meet the following fluid properties:</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Pour point:  <RID>ASTM D 97</RID>, less than -15 degree C</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  Aquatic biodegradation:  <RID>EPA 712-C-98-075</RID>, 100%</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Trout toxicity:  <RID>OECD Test 203</RID>, zero mortality of <RID>EPA 600/4-90/027F</RID>, pass]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4   LIQUID-FILLED TRANSFORMER NAMEPLATES</TTL><BRK/>
<BRK/>
<TXT>Distribution transformers shall be provided with nameplate information in accordance with <RID>IEEE C57.12.00</RID> and 
as modified or supplemented by this section.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5   CORROSION PROTECTION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use stainless steel bases and cabinets for most applications.  In hostile 
environments, the additional cost of totally stainless steel tanks and metering 
may be justified.  Manufacturer's standard construction material is acceptable 
only in noncoastal and noncorrosive environments.  Modifications are required 
to the specification when either of the above conditions apply.  Choose the 
second main bracketed option for hostile environments.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[[Front sill, hood, and tank base of single compartment transformers shall be corrosion resistant and shall be 
stainless steel, no less than No. 13 U.S. gage, conforming to <RID>ASTM A 167</RID>, Type 304 or 304L.  Base shall include 
any part of pad-mounted transformer that is within<MET> 37.5 mm</MET><ENG> 1.5 inches</ENG> of concrete pad.  ][Base and cabinets of 
two compartment transformers shall be corrosion resistant and shall be stainless steel, conforming to <RID>ASTM A 167</RID>
, Type 304 or 304L.  Base shall include any part of pad-mounted transformer that is within<MET> 75 mm</MET><ENG> 3 inches</ENG> of 
concrete pad.  ]Paint bases, cabinets, and tanks Munsell 7GY3.29/1.5 green.  Paint coating system shall comply 
with <RID>IEEE C57.12.28</RID>.  The Munsell color notation is specified in <RID>ASTM D 1535</RID>.  ][Entire transformer assembly, 
including tank and radiator, base, enclosure, and metering enclosure shall be fabricated of stainless steel conforming 
to <RID>ASTM A 167</RID>, Type 304 or 304L.  Form enclosure of stainless steel sheets.  Paint entire transformer assembly 
Munsell 7GY3.29/1.5 green.  Paint coating system shall comply with <RID>IEEE C57.12.28</RID>.  The Munsell color notation 
is specified in <RID>ASTM D 1535</RID>.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6   WARNING SIGNS</TTL><BRK/>
<BRK/>
<TXT>Provide warning signs for the enclosures of pad-mounted transformers having a nominal rating exceeding 600 volts.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  When the enclosure integrity of such equipment is specified to be in accordance with <RID>IEEE C57.12.28</RID>
, such as for pad-mounted transformers, provide self-adhesive warning signs on the outside of 
the high voltage compartment door(s).  Sign shall be a decal and shall have nominal dimensions 
of<MET> 178 by 255 mm</MET><ENG> 7 by 10 inches</ENG> with the legend "DANGER HIGH VOLTAGE" printed in two lines of 
nominal<MET> 50 mm</MET><ENG> 2 inch</ENG> high letters.  The word "DANGER" shall be in white letters on a red background 
and the words "HIGH VOLTAGE" shall be in black letters on a white background.  Decal shall be 
Panduit No. PPSO710D72 or approved equal.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  When such equipment is guarded by a fence, mount signs on the fence.  Provide metal signs 
having nominal dimensions of<MET> 355 by 255 mm</MET><ENG> 14 by 10 inches</ENG> with the legend "DANGER HIGH VOLTAGE 
KEEP OUT" printed in three lines of nominal<MET> 75 mm</MET><ENG> 3 inch</ENG> high white letters on a red and black 
field.]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7   SOURCE QUALITY CONTROL</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use "reserves the right to" on all projects, except those for SOUTHNAVFACENGCOM.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.7.1   <SUB>Transformer Test Schedule</SUB></TTL><BRK/>
<BRK/>
<TXT>The Government [reserves the right to][will] witness tests.  Provide transformer test schedule for tests to be 
performed at the manufacturer's test facility.  Submit required test schedule and location, and notify the Contracting 
Officer 30 calendar days before scheduled test date.  Notify Contracting Officer 15 calendar days in advance 
of changes to scheduled date.</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Test Instrument Calibration</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  The manufacturer shall have a calibration program which assures that all applicable test 
instruments are maintained within rated accuracy.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  The accuracy shall be directly traceable to the National Institute of Standards and Technology.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Instrument calibration frequency schedule shall not exceed 12 months for both test floor 
instruments and leased specialty equipment.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">4.  Dated calibration labels shall be visible on all test equipment.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">5.  Calibrating standard shall be of higher accuracy than that of the instrument tested.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">6.  Keep up-to-date records that indicate dates and test results of instruments calibrated or 
tested.  For instruments calibrated by the manufacturer on a routine basis, in lieu of third 
party calibration, include the following:</ITM><BRK/>
<BRK/>
<ITM>(a)  Maintain up-to-date instrument calibration instructions and procedures for each test instrument.</ITM><BRK/>
<BRK/>
<ITM>(b)  Identify the third party/laboratory calibrated instrument to verify that calibrating standard 
is met.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2   <SUB>Design Tests</SUB></TTL><BRK/>
<BRK/>
<TXT><RID>IEEE C57.12.00</RID>, and <RID>IEEE C57.12.90</RID>.  Section 5.1.2 in <RID>IEEE C57.12.80</RID> states that "design tests are made only 
on representative apparatus of basically the same design."  Submit design test reports (complete with test data, 
explanations, formulas, and results), in the same submittal package as the catalog data and drawings for[ each 
of] the specified transformer(s).  Design tests shall have been performed prior to the award of this contract.</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Tests shall be certified and signed by a registered professional engineer.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Temperature rise:  "Basically the same design" for the temperature rise test means a pad-mounted 
transformer with the same coil construction (such as wire wound primary and sheet wound secondary), the 
same kVA, the same cooling type (ONAN), the same temperature rise rating, and the same insulating liquid 
as the transformer specified.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Lightning impulse:  "Basically the same design" for the lightning impulse dielectric test means a 
pad-mounted transformer with the same BIL, the same coil construction (such as wire wound primary and 
sheet wound secondary), and a tap changer, if specified.  Design lightning impulse tests shall include 
the primary windings only of that transformer.</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  <RID>IEEE C57.12.90</RID>, paragraph 10.3 entitled "Lightning Impulse Test Procedures," and <RID>IEEE C57.98</RID>
.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  State test voltage levels.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Provide photographs of oscilloscope display waveforms or plots of digitized waveforms with 
test report.</ITM><BRK/>
<BRK/>
<LST INDENT="-0.33">d.  Lifting and moving devices:  "Basically the same design" requirement for the lifting and moving devices 
test means a test report confirming that the lifting device being used is capable of handling the weight 
of the specified transformer in accordance with <RID>IEEE C57.12.25</RID>.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">e.  Pressure:  "Basically the same design" for the pressure test means a pad-mounted transformer with 
a tank volume within 30 percent of the tank volume of the transformer specified.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.3   <SUB>Routine and Other Tests</SUB></TTL><BRK/>
<BRK/>
<TXT><RID>IEEE C57.12.00</RID>.  Routine and other tests shall be performed by the manufacturer on[ each of] the actual transformer(s) 
prepared for this project to ensure that the design performance is maintained in production.  Submit test reports, 
by serial number and receive approval before delivery of equipment to the project site.  Required tests shall 
be as follows:</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Cold resistance measurements (provide reference temperature)</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Polarity</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Ratio</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">d.  No-load losses (NLL) and excitation current</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">e.  Load losses (LL) and impedance voltage</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">f.  Dielectric</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Impulse</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  Applied voltage</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Induced voltage</ITM><BRK/>
<BRK/>
<LST INDENT="-0.33">g.  Leak</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">h.  Dissolved gas analysis (DGA)</LST><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Electrical installations shall conform to <RID>IEEE C2</RID>, <RID>NFPA 70</RID>, and to requirements specified herein.  Provide new 
equipment and materials unless indicated or specified otherwise.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   GROUNDING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For SOUTHNAVFACENGCOM projects, delete this paragraph and its subparagraphs, 
and use optional paragraph entitled "Transformer Grounding" instead.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where rock or other soil conditions prevent obtaining a specified ground 
value, other methods of grounding should be specified.  Where it is impractical 
to obtain the indicated ground resistance values, make every effort within reason 
to obtain ground resistance values as near as possible to the indicated values.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NFPA 70</RID> and <RID>IEEE C2</RID>, except that grounding systems shall have a resistance to solid earth ground not exceeding 
5 ohms.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.2.1   Grounding Electrodes</TTL><BRK/>
<BRK/>
<TXT>Provide driven ground rods as specified in Section <SRF>33 71 02.00 20</SRF> UNDERGROUND ELECTRICAL DISTRIBUTION.  Connect 
ground conductors to the upper end of ground rods by exothermic weld or compression connector.  Provide compression 
connectors at equipment end of ground conductors.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.2   Pad-Mounted Transformer Grounding</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Ensure plans show the secondary neutral grounding conductor sized in 
accordance with NFPA 70 and the primary neutral grounding conductor when required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide separate copper grounding conductors and connect them to the ground loop as indicated.  When work in 
addition to that indicated or specified is required to obtain the specified ground resistance, the provision 
of the contract covering "Changes" shall apply.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.3   Connections</TTL><BRK/>
<BRK/>
<TXT>Make joints in grounding conductors and loops by exothermic weld or compression connector.  Exothermic welds 
and compression connectors shall be installed as specified in Section <SRF>33 71 02.00 20</SRF> UNDERGROUND ELECTRICAL DISTRIBUTION.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.4   Grounding and Bonding Equipment</TTL><BRK/>
<BRK/>
<TXT><RID>UL 467</RID>, except as indicated or specified otherwise.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>3.3   TRANSFORMER GROUNDING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For SOUTHNAVFACENGCOM projects, use this paragraph in lieu of the previous 
paragraph entitled "GROUNDING."</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide a 1/0 bare copper-ground girdle around transformer.  Girdle shall be buried<MET> 305 mm</MET><ENG> one foot</ENG> deep and 
placed<MET> 915 mm</MET><ENG> 3 feet</ENG> laterally from the transformer enclosure.  Connect girdle to enclosure at two opposite places 
using 1/0 copper.  Exothermically weld joints.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.4   INSTALLATION OF EQUIPMENT AND ASSEMBLIES</TTL><BRK/>
<BRK/>
<TXT>Install and connect pad-mounted transformers furnished under this section as indicated on project drawings, the 
approved shop drawings, and as specified herein.</TXT><BRK/>
<BRK/>
<SPT>[<TTL>3.4.1   Meters and Current Transformers</TTL><BRK/>
<BRK/>
<TXT><RID>NEMA C12.1</RID>.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.5   FIELD APPLIED PAINTING</TTL><BRK/>
<BRK/>
<TXT>Where field painting of enclosures is required to correct damage to the manufacturer's factory applied coatings, 
provide manufacturer's recommended coatings and apply in accordance with manufacturer's instructions.</TXT><BRK/>
<BRK/></SPT>
[<SPT><TTL>3.6   WARNING SIGN MOUNTING</TTL><BRK/>
<BRK/>
<TXT>Provide the number of signs required to be readable from each accessible side, but space the signs a maximum 
of<MET> 9 meters</MET><ENG> 30 feet</ENG> apart.</TXT><BRK/>
<BRK/></SPT>
]<SPT><TTL>3.7   FOUNDATION FOR EQUIPMENT AND ASSEMBLIES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Mounting slab connections may have to be given in detail depending on 
the requirements for the seismic zone in which the requirement is located.  
Include construction requirements for concrete slab only if slab is not detailed 
in drawings.  At some activities, curbs or raised edges may also be required 
around liquid filled transformer.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Mount transformer on concrete slab.  Unless otherwise indicated, the slab shall be at least<MET> 200 mm</MET><ENG> 8 inches</ENG> thick, 
reinforced with a<MET> 152 by 152 mm MW19 by MW19</MET><ENG> 6 by 6 inches - W2.9 by W2.9</ENG> mesh placed uniformly<MET> 100 mm</MET><ENG> 4 inches</ENG>
 from the top of the slab.  Slab shall be placed on a<MET> 150 mm</MET><ENG> 6 inch</ENG> thick, well-compacted gravel base.  Top of 
concrete slab shall be approximately<MET> 100 mm</MET><ENG> 4 inches</ENG> above the finished grade.  Edges above grade shall have<MET> 
15 mm</MET><ENG> 1/2 inch</ENG> chamfer.  Slab shall be of adequate size to project at least<MET> 200 mm</MET><ENG> 8 inches</ENG> beyond the equipment.</TXT><BRK/>
<BRK/>
<TXT>Stub up conduits, with bushings, <MET>50 mm</MET><ENG>2 inches</ENG> into cable wells in the concrete pad.  Coordinate dimensions of 
cable wells with transformer cable training areas.  Concrete work shall be as specified in Section <SRF>03 30 00</SRF> CAST-IN-PLACE 
CONCRETE.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8   FIELD QUALITY CONTROL</TTL><BRK/>
<BRK/>
<SPT><TTL>3.8.1   Performance of <SUB>Acceptance Checks and Tests</SUB></TTL><BRK/>
<BRK/>
<TXT><TST>Perform in accordance with the manufacturer's recommendations, and include the following visual and mechanical 
inspections and electrical tests, performed in accordance with <RID>NETA ATS</RID>.</TST></TXT><BRK/>
<BRK/>
<SPT><TTL>3.8.1.1   Pad-Mounted Transformers</TTL><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Visual and mechanical inspection</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Compare equipment nameplate information with specifications and approved shop drawings.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  Inspect physical and mechanical condition.  Check for damaged or cracked insulators and 
leaks. </ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Inspect all bolted electrical connections for high resistance using low-resistance ohmmeter, 
verifying tightness of accessible bolted electrical connections by calibrated torque-wrench 
method, or performing thermographic survey.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">4.  Verify correct liquid level in tanks.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">5.  Perform specific inspections and mechanical tests as recommended by manufacturer.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">6.  Verify correct equipment grounding.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">7.  Verify the presence of transformer surge arresters.</ITM><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Electrical tests</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Perform resistance measurements through all bolted connections with low-resistance ohmmeter.</ITM><BRK/>
<BRK/>
 <ITM INDENT="-0.33">2.  Verify that the tap-changer is set at specified ratio.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Verify proper secondary voltage phase-to-phase and phase-to-neutral after energization and 
prior to loading.</ITM><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.8.1.2   Current Transformers</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate use of current transformers and meter testing paragraphs with 
equipment specified in PART 2.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">a.  Visual and mechanical inspection</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Compare equipment nameplate data with specifications and approved shop drawings. </ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  Inspect physical and mechanical condition.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Verify correct connection.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">4.  Verify that adequate clearances exist between primary circuits and secondary circuit.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">5.  Inspect all bolted electrical connections for high resistance using low-resistance ohmmeter, 
verifying tightness of accessible bolted electrical connections by calibrated torque-wrench 
method, or performing thermographic survey.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">6.  Verify that required grounding and shorting connections provide good contact.</ITM><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Electrical tests</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Perform resistance measurements through all bolted connections with low-resistance ohmmeter, 
if applicable.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  Perform insulation-resistance test.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Perform a polarity test.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">4.  Perform a ratio-verification test.</ITM><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.8.1.3   [Kilowatt Demand Meter][Watthour Meter]</TTL><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Visual and mechanical inspection</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Compare equipment nameplate data with specifications and approved shop drawings.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  Inspect physical and mechanical condition.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Verify tightness of electrical connections.</ITM><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Electrical tests</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">[1.  Calibrate watthour meters according to manufacturer's published data.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  Verify that correct multiplier has been placed on face of meter, where applicable.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Verify that current transformer secondary circuits are intact.</ITM><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.8.1.4   Grounding System</TTL><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Visual and mechanical inspection</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Inspect ground system for compliance with contract plans and specifications.</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete "Electrical tests" below for SOUTHNAVFACENGCOM projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">b.  Electrical tests</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Perform ground-impedance measurements utilizing the fall-of-potential method.  On systems 
consisting of interconnected ground rods, perform tests after interconnections are complete.  
On systems consisting of a single ground rod perform tests before any wire is connected.  Take 
measurements in normally dry weather, not less than 48 hours after rainfall.  Use a portable 
ground testing megger in accordance with manufacturer's instructions to test each ground or 
group of grounds.  The instrument shall be equipped with a meter reading directly in ohms or 
fractions thereof to indicate the ground value of the ground rod or grounding systems under 
test.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  Submit the measured ground resistance of each ground rod and grounding system, indicating 
the location of the rod and grounding system.  Include the test method and test setup (i.e., 
pin location) used to determine ground resistance and soil conditions at the time the measurements 
were made.</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.8.2   Follow-Up Verification</TTL><BRK/>
<BRK/>
<TXT><TST>Upon completion of acceptance checks and tests, the Contractor shall show by demonstration in service that circuits 
and devices are in good operating condition and properly performing the intended function.</TST>  As an exception to 
requirements stated elsewhere in the contract, the Contracting Officer shall be given 5 working days advance 
notice of the dates and times of checking and testing.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT>    <END/><BRK/></SEC>