<SCN>SECTION 28 16 00.00 20</SCN><BRK/>
<BRK/>
<STL>BASIC INTRUSION DETECTION SYSTEMS (IDS)</STL><BRK/>
<DTE>04/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This specification covers <SCP>basic intrusion detection systems (IDS) consisting 
of commercial equipment which is limited to a full range of interior point protection 
devices, duress sensors, volumetric (space) protection sensors, alarm signal 
data communications media, and alarm reporting and monitoring systems.</SCP> System 
requirements shall conform to NAVFAC DM-13.02, "Commercial Intrusion Detection 
Systems (IDS).  For higher security IDS, CCTV, and access control systems, use 
Section 13703, "Commercial Intrusion Detection Systems (IDS)."  If there are 
questions concerning system design, the Engineering Field Division (EFD), Naval 
Facilities Engineering Command, should be consulted.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following information shall be shown on the project drawings:</NPR><BRK/>
<BRK/>
<NPR>1.  Floor Plans:  Location of security devices, control units, alarm display 
equipment, and electrical power cabinets.</NPR><BRK/>
<BRK/>
<NPR>2.  Site Plan:  Exterior devices and routing of conductors and conduit into 
building.</NPR><BRK/>
<BRK/>
<NPR>3.  Single line type system riser diagram.  Label zones on riser diagrams.  
Connection of equipment should be indicated for typical system chosen for cost 
estimating purposes.</NPR><BRK/>
<BRK/>
<NPR>4.  Single line type electrical riser diagram.</NPR><BRK/>
<BRK/>
<NPR>5.  Mounting:  Details for each device required for complete installation.  
Include device height and installation of wiring.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
<BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
<BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 123/A 123M</RID><RTL>(2008) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products</RTL><BRK/><BRK/><RID>ASTM B 32</RID><RTL>(2008) Standard Specification for Solder Metal</RTL><BRK/><BRK/><RID>ASTM D 709</RID><RTL>(2001; R 2007) Laminated Thermosetting Materials</RTL><BRK/><BRK/></REF><REF><ORG>INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)</ORG><BRK/><BRK/><RID>IEEE Std 100</RID><RTL>(2000) The Authoritative Dictionary of IEEE Standards Terms</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)</ORG><BRK/><BRK/><RID>NEMA ICS 2</RID><RTL>(2000; Errata 2002; R 2005; Errata 2006) Standard for Industrial Control and Systems:  Controllers, Contractors, and Overload Relays Rated Not More than 2000 Volts AC or 750 Volts DC: Part 8 - Disconnect Devices for Use in Industrial Control Equipment</RTL><BRK/><BRK/><RID>NEMA ICS 6</RID><RTL>(1993; R 2006) Standard for Industrial Controls and Systems Enclosures</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/></REF><REF><ORG>U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)</ORG><BRK/><BRK/><RID>47 CFR 15</RID><RTL>Radio Frequency Devices</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 1076</RID><RTL>(1995; Rev thru Mar 2005) Standard for Safety Proprietary Burglar Alarm Units and Systems</RTL><BRK/><BRK/><RID>UL 1610</RID><RTL>(1998; Rev thru Aug 2005) Central-Station Burglar-Alarm Units</RTL><BRK/><BRK/><RID>UL 1635</RID><RTL>(1996; Rev thru Aug 2005) Digital Alarm Communicator System Units</RTL><BRK/><BRK/><RID>UL 1638</RID><RTL>(2001; Rev thru Oct 2008) Visual Signaling Appliances - Private Mode Emergency and General Utility Signaling</RTL><BRK/><BRK/><RID>UL 464</RID><RTL>(2003; Rev thru Feb 2008) Standard for Audible Signal Appliances</RTL><BRK/><BRK/><RID>UL 609</RID><RTL>(1996; Rev thru Mar 2005) Local Burglar Alarm Units and Systems</RTL><BRK/><BRK/><RID>UL 634</RID><RTL>(2007) Connectors and Switches for Use with Burglar-Alarm Systems</RTL><BRK/><BRK/><RID>UL 639</RID><RTL>(2007) Intrusion Detection Units</RTL><BRK/><BRK/><RID>UL 681</RID><RTL>(1999; Rev thru Jan 2001) Installation and Classification of Burglar and Holdup Alarm Systems</RTL><BRK/><BRK/><RID>UL 796</RID><RTL>(2006; Rev thru Feb 2008) Printed-Wiring Boards</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   STANDARD PRODUCTS</TTL><BRK/>
<BRK/>
<TXT>Material and equipment shall be the standard products of a manufacturer regularly engaged in the manufacture 
of such products.  Items of equipment shall essentially duplicate equipment that have been in satisfactory use 
at least 2 years prior to bid opening.  Equipment shall be supported by a service organization that is, in the 
opinion of the Contracting Officer, reasonably convenient to the site.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   DEFINITIONS</TTL><BRK/>
<BRK/>
<TXT>Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on 
the drawings, shall be as defined in <RID>IEEE Std 100</RID>.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Active mode:  That in which some type of signal is continuously sent across the link, resulting 
in simple link breaks being readily detected.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Element:  Constituent part of a complex signal such as AC or DC voltage or current, AC phase, 
or frequency duration.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Fail-safe:  Capability to monitor for system functions and to report an alarm when a failure 
is detected in a critical system function.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Installer:  Either the Contractor or a subcontractor with whom the Contractor has a firm 
contractual agreement.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Intruder:  Animate object at least<MET> 1220 mm</MET><ENG> 48 inches</ENG> in height,<MET> 34 kg</MET><ENG> 75 pounds</ENG> in weight 
and<MET> 0.113 cubic meter</MET><ENG> 4 cubic feet</ENG> in volume, moving through protected zones or portals at a 
velocity of<MET> 30 to 3050 mm per second</MET><ENG> 0.1 to 10 feet per second</ENG>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Sensor zone:  Geographic position for which an intrusion must be identified and displayed 
and may be the combination of multiple detection devices.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   SYSTEM DESCRIPTION</TTL><BRK/>
<BRK/>
<TXT>[Provide new] [and or] [modify existing] basic intrusion detection system (IDS), including associated equipment 
and appurtenances.  Provision of IDS shall include [supervising installation of rigid or flexible conduit for 
IDS during site preparation,] running system wires and cables, and system component installation, component testing, 
and system checkout.  Each system shall be complete and ready for operation.  Equipment, materials, installation, 
workmanship, inspection, and testing shall be as specified herein.  [Existing system was manufactured by [_____], 
and new equipment shall be compatible with and shall operate accurately and reliably with existing system.]  
Include materials not furnished by the manufacturer with IDS equipment as specified in Section <SRF>26 20 00</SRF> INTERIOR 
DISTRIBUTION SYSTEM.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Submittals must be limited to those necessary for adequate quality control.  
The importance of an item in the project should be one of the primary factors 
in determining if a submittal for the item should be required.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy projects.<BRK/>
<BRK/>
Submittal items not designated with a "G" are considered as being for information 
only for Army projects and for Contractor Quality Control approval for Navy 
projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<TXT>[The [_____] will review and] [_____] Division, Naval Facilities Engineering Command will approve submittals 
requiring special review in this section.  Drawings and descriptive data shall be approved prior to procurement, 
fabrication, and installation.  A schedule of required submittals shall be prepared to be integrated with the 
overall construction management schedule to ensure adequate review and necessary corrective work before installation.</TXT><BRK/>
<BRK/>
<TXT>Include wiring diagrams and installation details of equipment indicating proposed location, layout and arrangement, 
control panels, accessories, piping, ductwork, and other items that must be shown to ensure a coordinated installation.  
Wiring diagrams shall identify circuit terminals and indicate the internal wiring for each item of equipment 
and the interconnection between each item of equipment.  Drawings shall indicate adequate clearance for operation, 
maintenance, and replacement of operating equipment devices.  Submittals shall include the nameplate data, size, 
and capacity.  Submittals shall also include applicable federal, military, industry, and technical society publication 
references.</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>IDS components</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Overall system schematic</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Interior point sensors</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Interior volumetric (space) sensors</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Control communicators</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Duress alarms</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Keypad</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Communication <SUB>cables</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Radio frequency link</SUB> communications systems[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
<ITM><SUB>Communications interface devices</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Central station receiver/printer</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
<ITM><SUB>[Bell] [Siren]</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Batteries</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Tamper switches</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Strobes</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>IDS operational test plan</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>IDS operational test plan</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Installer's qualifications</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Instructor's qualifications</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>IDS equipment</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>IDS</SUB>, Data Package 5[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE DATA.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-11 Closeout Submittals</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>As-Built drawings</SUB> for IDS[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Posted operating instructions</SUB> for IDS[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.6.1   Drawings</TTL><BRK/>
<BRK/>
<SPT><TTL>1.6.1.1   <SUB>IDS Components</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide drawings that clearly and completely indicate the function of each component of the IDS.  Indicate termination 
points of devices and indicate interconnections required for operation of the system.  Indicate interconnection 
between modules and devices.  In addition, provide a layout drawing which shows spacing of components, location, 
and details of mounting and positioning.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6.1.2   <SUB>Overall System Schematic</SUB></TTL><BRK/>
<BRK/>
<TXT>The overall system schematic shall indicate the sequence of operation, the relationship of integrated components 
on one diagram, and show power source, system controls, impedance matches, plus number, size, identification, 
and maximum lengths of interconnecting wires.  Drawings shall not be less than<MET> [420 by 297 mm] [_____] mm</MET><ENG> [11 
by 17 inches] [_____] inches</ENG>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.6.2   Experience and Qualifications</TTL><BRK/>
<BRK/>
<SPT><TTL>1.6.2.1   <SUB>Installer's Qualifications</SUB></TTL><BRK/>
<BRK/>
<TXT>Prior to installation, submit data for approval by the [_____] Division, Naval Facilities Engineering Command, 
of the installer's experience and certified qualifications.  Show that the installer who will perform the work 
has a minimum of [3] [_____] years' experience successfully installing IDS of the same type and design as specified 
herein.  Include names, locations, and points of contact of at least five installations of the same type and 
design as specified herein where the installer has installed such systems.  Indicate the type of each system 
and certify that each system has performed satisfactorily in the manner intended for a period of not less than 
[1] [_____] year(s).</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6.2.2   <SUB>Instructor's Qualifications</SUB></TTL><BRK/>
<BRK/>
<TXT>Prior to installation, submit data of the instructor's experience and certified qualifications.  Show that the 
instructor, who will train operating and maintenance personnel, has received a minimum of 24 hours of IDS training 
from a technical organization such as the National Burglar and Fire Alarm Association, and has 2 years' experience 
installing IDS of the type specified.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.6.3   <SUB>IDS Operational Test Plan</SUB></TTL><BRK/>
<BRK/>
<TXT>Submit for approval at least 30 days prior to commencement of formal operational testing.  Include detailed procedures 
for operational testing of each IDS component and subsystem, and for performance of an integrated system test.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6.4   <SUB>IDS Equipment</SUB></TTL><BRK/>
<BRK/>
<TXT>Submit manufacturer's certification of UL listing.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6.5   Regulatory Requirements</TTL><BRK/>
<BRK/>
<TXT>In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the 
word, "shall" had been substituted for "should" wherever it appears.  Interpret references in these publications 
to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer.  Equipment, 
materials, installation, and workmanship shall be in accordance with the mandatory and advisory provisions of 
NFPA 70 unless more stringent requirements are specified or indicated.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.6.5.1   Reference Standard Compliance</TTL><BRK/>
<BRK/>
<TXT>Where equipment or materials are specified to conform to industry and technical society reference standards of 
the organizations such as American National Standards Institute (ANSI), American Society for Testing and Materials 
(ASTM), National Electrical Manufacturers Association (NEMA), Underwriters Laboratories (UL), and Association 
of Edison Illuminating Companies (AEIC), submit proof of such compliance.  The label or listing by the specified 
organization will be acceptable evidence of compliance</TXT></SPT><BRK/>
<BRK/>
<SPT><TTL>1.6.5.2   Independent Testing Organization Certificate</TTL><BRK/>
<BRK/>
<TXT>In lieu of the label or listing, submit a certificate from an independent testing organization, competent to 
perform testing, and approved by the Contracting Officer.  The certificate shall state that the item has been 
tested in accordance with the specified organization's test methods and that the item complies with the specified 
organization's reference standard<BRK/>
Provide only UL listed ESS equipment  for Both exterior and interior ESS sensors, access control, and closed-circuit 
television (CCTV) components.</TXT></SPT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6.6   Standard Products</TTL><BRK/>
<BRK/>
<TXT>Provide materials and equipment that are products of manufacturers regularly engaged in the production of such 
products which are of equal material, design and workmanship.  Products shall have been in satisfactory commercial 
or industrial use for 2 years prior to bid opening.  The 2-year period shall include applications of equipment 
and materials under similar circumstances and of similar size.  The product shall have been on sale on the commercial 
market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.  Where two or 
more items of the same class of equipment are required, these items shall be products of a single manufacturer; 
however, the component parts of the item need not be the products of the same manufacturer unless stated in this 
section</TXT><BRK/>
<BRK/>
<SPT><TTL>1.6.6.1   Alternative Qualifications</TTL><BRK/>
<BRK/>
<TXT>Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory 
field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is 
furnished</TXT></SPT><BRK/>
<BRK/>
<SPT><TTL>1.6.6.2   Material and Equipment Manufacturing Date</TTL><BRK/>
<BRK/>
<TXT>Products manufactured more than 3 years prior to date of delivery to site shall not be used, unless specified 
otherwise.</TXT></SPT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.7   WARRANTY</TTL><BRK/>
<BRK/>
<TXT>The equipment items shall be supported by service organizations which are reasonably convenient to the equipment 
installation in order to render satisfactory service to the equipment on a regular and emergency basis during 
the warranty period of the contract</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   IDS SUBSYSTEMS</TTL><BRK/>
<BRK/>
<TXT>Provide a complete integrated <SUB>IDS</SUB> consisting of the following major subsystems:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Detection</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Arm/disarm multiple function keypad</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Communications</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Assessment</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Alarm reporting</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Power</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2   INTEGRATED SYSTEM FUNCTIONAL REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Ensure that the IDS is fully integrated with the physical security and other elements of the overall facility 
security system.  Except for multiple function keypads, other subsystems may be housed in a single enclosure.  
Specific subsystem functional requirements are as follows:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Detection subsystem:  Subsystem shall consist of sensors to detect intrusion attempts [and 
provide means to indicate a duress condition].</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Arm/disarm multiple function keypad:  Subsystem shall consist of electronic digital keypads 
to monitor and control personnel movement through normal access routes in and out of the facility 
[and between protected areas within the facility].</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Communications subsystem:  Subsystem shall consist of elements required to ensure that pertinent 
data is transferred from the point of origin to the point where appropriate actions can be taken.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Assessment subsystem:  Subsystem shall consist of electronic devices required to visually 
and audibly verify the validity of IDS alarms [at two separate locations].</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Alarm reporting subsystem:  Subsystem shall consist of electronic devices to control, process, 
integrate, and annunciate IDS data [at [two] [_____] separate locations].</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Power subsystem:  Subsystem shall consist of components required to ensure continuous operation 
of the entire IDS.</ITM><BRK/>
<BRK/>
<SPT>[<TTL>2.2.1   Intrinsically Safe</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Do not locate control communicator within a hazardous area.  If point 
sensors and volumetric sensors are required in hazardous areas, clearly identify 
their location on the plans.  Delete this paragraph if no hazardous areas exist 
in this project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>System components located in areas where fire or explosion hazards may exist due to flammable gases or vapors, 
flammable liquids, combustible dust, or ignitable fibers or flyings shall be rated and installed according to 
Chapter 5 of <RID>NFPA 70</RID>.  Classification of area and corresponding equipment ratings and installation procedures 
shall be as defined and specified in Chapter 5 of <RID>NFPA 70</RID>.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>2.3   INTEGRATED SYSTEM PERFORMANCE REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>The installed and operating IDS shall be integrated into the overall facility to detect intrusion and shall perform 
as an entity, as specified below.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.3.1   Detection Coverage</TTL><BRK/>
<BRK/>
<TXT>Provide and adjust sensors so that coverage is [overlapping and] maximized without mutual interference.  [IDS 
coverage shall include [the facility perimeter] [and] critical spaces within the facility.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.2   Detection Resolution (Sensitivity)</TTL><BRK/>
<BRK/>
<TXT>Sensitivity shall be capable of the following:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Locating intrusions at individually protected assets or at an individual portal;</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Locating intrusions within volume/areas to within the coverage on any single volumetric 
sensor; and</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Locating failures or tampering at individual sensors.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.3   Detection Alarm and Reporting Capacity</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select system capacity parameters based on specific facility design requirements.  
Include a 25 percent expansion factor to accommodate changes in design caused 
by reconfiguration of equipment within interior spaces or renovation.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The IDS shall have the capacity to collect, communicate, and display a minimum of [8] [_____] programmable sensor 
zone alarms [and to enable control of one or more response devices in each of the sensor zones].  [When a sensor 
zone includes a combination of multiple detection devices, the system shall maintain the capability to identify 
individual detection devices in an alarm state.]  A single alarm shall be annunciated within approximately 2 
seconds after sensor transducer or other detection device activation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.4   Alarms</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For a wireless transmission system delete "d. Line Fault."</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Alarm shall include, but not be limited to, the following:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Intrusion detection</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Tamper</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Fail-safe</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Line fault</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  AC power loss</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Low battery in control communicator.</ITM><BRK/>
<BRK/>
<SPT><TTL>2.3.4.1   Intrusion Detection</TTL><BRK/>
<BRK/>
<TXT>Sense and respond with visible and audible signals the activation of detection sensors.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.4.2   Tamper</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Each tamper loop requires a dedicated sensor zone in the control communicator.  
Do not use one tamper loop for an entire building since it would be difficult 
to trace the violated device or box.  Instead, zone tamper loops by areas to 
more conveniently locate a violated device or box.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Tamper protection can be physical protection, line supervision, encryption, and tamper alarming of enclosures 
and components.  All intrusion detection, access control, assessment systems and their associated data transmission 
media must be protected commensurate with the classification of asset being protected.  All intrusion detection 
sensors and access control readers must have tamper resistant enclosures and integral tamper protection switches.  
All enclosures, cabinets, housings, and boxes, having hinged doors or removable covers that contain processors 
or connections must have tamper protection switches. All tamper alarm signals must be monitored continuously 
whether the system is in the access or secure mode of operation.  Tamper alarms shall be annunciated to be clearly 
distinguishable from intrusion detection alarms.  Tamper switches on doors which must be opened to make normal 
maintenance adjustments to the system and to service the power supplies shall be of the push/pull-set, automatic-reset 
type.  Tamper switches shall have the following features:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Inaccessibility until the switch is activated;</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Under electrical supervision at all times, irrespective of the protection mode in which 
the circuit is operating;</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Spring-loaded and held in the closed position by the door or cover protected; and</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Wired to break the circuit when the door or cover is disturbed.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.4.3   Fail-Safe</TTL><BRK/>
<BRK/>
<TXT>Provide a fail-safe capability in critical elements of the IDS, including, but not be limited to, the capability 
to monitor communication link integrity and to provide self-test.  When diminished functional capabilities are 
detected, the system shall provide annunciation of the fault.  Fail-safe alarms shall be annunciated to be clearly 
distinguishable from other types of alarms.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.4.4   Line Fault</TTL><BRK/>
<BRK/>
<TXT>As a minimum, fault isolation at the systems level shall have the same geographic resolution as provided for 
intrusion detection.  Communication links of the IDS shall have an active mode for line fault detection.  The 
system shall be either a static system or a dynamic system.  In a static system, the "no-alarm" condition shall 
always be represented by the same signal, which shall be different than the signal originally transmitted.  The 
dynamic system shall represent "no-alarm" with a signal which continually changes with time.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.4.5   Power Loss</TTL><BRK/>
<BRK/>
<TXT>Provide the capability to detect when a critical component of the system experiences temporary or permanent loss 
of power and to declare an alarm. The alarm shall be annunciated to clearly identify the component experiencing 
power loss.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.3.5   Electrical Power</TTL><BRK/>
<BRK/>
<TXT>Electrical power shall be obtained by the normal commercial or base electrical distribution system.  Power shall 
be continuously monitored and, if interrupted, automatic switching from primary to emergency backup sources shall 
be accomplished without interruption or degradation of critical system function.  Intrusion alarms shall not 
be generated by power switching; however, an indication of power switching and on-line source shall be provided 
at the alarm monitor.  Upon restoration of prime power, the system shall automatically switch back to the primary 
source.  Low voltage condition of an on-line battery and battery charger circuit failure shall be detected and 
reported as a fault condition.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.3.5.1   Primary Power</TTL><BRK/>
<BRK/>
<TXT>Furnish [120] [_____] volt AC service, transformed through a two-winding isolation transformer and rectified 
to low-voltage DC for system operation.  Obtain primary power [from the line side of incoming facility power] 
[at the location indicated].  [Provide a separate, lockable, circuit breaker [adjacent to the power distribution 
panel] [at the location indicated].]  [Provide a circuit dedicated to power IDS from a panelboard at the location 
indicated.  Label the circuit breaker in that panelboard: "Alarm System Do Not Turn Off."]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.5.2   Backup Power</TTL><BRK/>
<BRK/>
<TXT>Provide backup power to the primary power by dedicated batteries in remotely located system elements such as 
individual sensors and in <SUB>control communicators</SUB>.  [When radio frequency (RF) operation is required, batteries 
shall be an integral part of dispersed system elements.]  Batteries shall be capable of operation in any position 
and shall be protected against venting caustic chemicals or fumes within an equipment cabinet. <SUB>Batteries</SUB> shall 
also be capable of continuous operation for up to [8] [_____] hours without recharge or replacement.  If the 
sensors power requirements exceed the allowable UL rated capacity of the control communicator battery, provide 
the number of separate power supplies required to power the sensors.  Provide each power supply with its own 
rechargeable battery and charger.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>2.4   SYSTEM PERFORMANCE REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Provide commercial of the shelf (COTS)system components to operate as described herein within the context of 
the integrated system performance previously described.  Where inconsistencies occur between the following component 
performance requirements and integrated system level performance descriptions, integrated system performance 
descriptions shall take precedence.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.4.1   Modularity</TTL><BRK/>
<BRK/>
<TXT>Provide system components to facilitate modular subassembly and part replacement.  Electronic components of the 
system shall be of the solid-state type, mounted on printed circuit boards conforming to <RID>UL 796</RID>.  Circuitry shall 
not be so densely placed as to impede maintenance.  Power-dissipating components shall incorporate safety margins 
of not less than 25 percent with respect to dissipation ratings, maximum voltages, and current-carrying capacity.  
Light duty relays and similar switching devices shall be solid-state or hermetically sealed electromechanical 
type.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.2   Reliability</TTL><BRK/>
<BRK/>
<TXT>Provide only components in current manufacturing production.  Components shall be manufactured to meet requirements 
specified herein and shall be free from characteristics and defects which affect appearance or serviceability 
or which render equipment unsuitable for the intended purpose.  Provide components designed for continuous operation 
at specified conditions.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.3   Maintainability</TTL><BRK/>
<BRK/>
<TXT>Components shall be capable of being maintained using commercially available standard tools and equipment.  Components 
shall be arranged and assembled to be readily accessible to maintenance personnel without compromising the defeat 
resistance of the IDS.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.4   Environmental Conditions</TTL><BRK/>
<BRK/>
<SPT><TTL>2.4.4.1   Interior Conditions</TTL><BRK/>
<BRK/>
<TXT>Equipment installed in environmentally protected interior areas shall meet performance requirements specified 
by UL for the specific equipment or device.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.4.2   Exterior Conditions</TTL><BRK/>
<BRK/>
<TXT>Components mounted in locations exposed to weather shall be housed in corrosion-resistant enclosures with appropriate 
environmental protection. Component performance shall not degrade because of improper housing design. Components 
in enclosures shall meet performance requirements when exposed to ambient conditions specified by UL for the 
specific equipment or device.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.4.3   Transient voltage surge suppression</TTL><BRK/>
<BRK/>
<TXT>Intrusion detection and communication circuits shall be protected at both ends against transient voltage surges.  
Transient voltage surge suppressors (TVSS) or surge protection devices (SPD) are required for the protection, 
within specified limits, of AC electrical circuits and electronic equipment from the effects of lightning induced 
voltages, external switching transients and internally generated switching transients. Individual suppressors 
shall be installed where shown on the drawings.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Line Items a thru e should be part of building construction UFGS specifications.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">a.  Main service and distribution equipment suppressors: The AC voltage SPD's shall be a high 
speed, high current device designed to protect electrical systems and electronic equipment from 
transient over-voltage. The SPD shall provide continuous bi-polar, bi-directional, non-interrupting 
protection and be capable of instant reset with no degradation in protection. Gas tubes are 
not acceptable. The SPD shall utilize SAD or MOV technology. It shall start to suppress at a 
minimum of 115% of the peak voltage of the sine wave. At maximum surge current dissipation, 
the device shall not exceed the maximum voltage protection level. The SPD shall be installed 
in parallel with the service main disconnect, distribution or branch panel main lugs as shown 
on drawings. Connect SPD to over current protection sized as shown with an AIC rating equal 
to panel rating. The suppressor shall have status indicator lights, dry contacts with remote 
alarm capabilities and an audible alarm. Suppressors shall be assembled as modular units to 
permit quick, easy replacement of failed components.</ITM>   <BRK/>
<BRK/>
    <ITM>(1) Electrical Service <BRK/>
  <BRK/>
(a) Voltage shall be as indicated on drawings. <BRK/>
(b) Frequency    --  50/60 Hz<BRK/>
(C) Phases   --   3 phase<BRK/>
(d) Wiring configuration  --  as indicated</ITM><BRK/>
<BRK/>
    <ITM>(2) IEEE 62.41 Categories unless otherwise indicated on drawings:<BRK/>
Service entrance sizes<BRK/>
&lt;600A                           B3/C1<BRK/>
1.2KA                          C3<BRK/>
Distribution or sub-panels      B2</ITM><BRK/>
<BRK/>
    <ITM>(3) Electrical Performance<BRK/>
Response time            &lt; 5 nanoseconds<BRK/>
MCOV            115% minimum<BRK/>
Shortwave test- surge current<BRK/>
(6kv, 1.2/50usec; 3ka 8/20µsec)   5000 surges<BRK/>
Minimum surge current:<BRK/>
<BRK/>
(a) Service Entrance   410,000 Amps/Phase <BRK/>
(b) Distribution and Sub-panels   210,000 Amps/Phase</ITM><BRK/>
<BRK/>
 <ITM>(4) Suppression system protected modes shall be L-N, L-G, N-G for Wye Systems and L-L, L-G for 
ungrounded Delta Systems.</ITM><BRK/>
<BRK/>
<ITM>(5) Power on indicators and failure detection: A lighted panel on the cover shall provide indication 
that the suppressor is properly activated and shall also indicate mode failure. If the suppressor 
fails, an isolated contact shall close. In addition, an audible alarm shall be provided with 
manual reset.</ITM><BRK/>
<BRK/>
<ITM>(6) Failure mode - SPD's shall be designed to fail shorted. Any fuses in series with the SPD's 
shall not open during a surge event.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Disconnect:  Main service suppressors shall be provided with an integral fused disconnect 
switch or dedicated circuit breaker as shown or required by UL.  Breakers and suppressors shall 
have an AIC fault withstand rating equal or greater than the AIC rating of the equipment to 
which it is connected.  The length of wiring from the tap at the service conductors to the suppressor 
being protected, however, shall not exceed the maximum length permitted by manufacturer, to 
maintain the maximum voltage protection level.  Suppressors may be installed within switchgear 
or panel boards where UL label or listing is not affected, suppressors are completely and easily 
accessible, indicator lights are visible and audible alarm can be easily heard.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Enclosures: Enclosures for main service suppressors shall be as follows;<BRK/>
<BRK/></ITM>
<ITM>(1)  Minimum, 14 gauge painted steel or suitable enclosure to meet the NEMA selected requirements 
as listed.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Operation Status Indicator: Audible Remote Signaling and Visual Systems </ITM><BRK/>
<BRK/>
    <ITM>(1)  Visual System<BRK/>
(a)  Protection: Suppressor Working - Green LED's<BRK/>
(b)  Warning/Fault: Suppressor Failure - Red LED's<BRK/>
(c)  LED's shall be field replaceable<BRK/>
(d)  Other visual indicators where approved.</ITM><BRK/>
<BRK/>
    <ITM>(2)  Remote Signaling<BRK/>
(a)  Relay with Auxiliary for C contacts:  Two sets @ 2 ampere, 120 volts each.  1 Set N.O. 
and 1 set N.C. to operate upon failure of suppression module, blown fuse or tripped circuit 
breaker in suppressor module or in disconnect switch for alarm connection to remote location.</ITM><BRK/>
<BRK/>
    <ITM>(3)  Audible <BRK/>
(a)  The audible alarm shall activate upon a fault condition within the suppressor.  An alarm 
silence/reset switch and push-to-test switch shall be provided.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Bonding and Grounding Conductors and Materials for Main Service Suppressors:</ITM><BRK/>
<BRK/>
    <ITM>(1)  Size:  Conductors utilized for surge suppressor connections to service conductors shall 
be a minimum of #6 AWG stranded insulated copper unless otherwise specified.</ITM><BRK/>
<BRK/>
    <ITM>(2)  Bus:  Ground bus or strip material where used shall be copper, a minimum of Ľ inch thickness 
and two inches wide unless otherwise specified.  Bus materials shall be secured to surfaces 
with appropriate insulators and mechanical fasteners.  Bus connections shall be bolted and reinforced 
as necessary to provide a permanent and secure connection.</ITM><BRK/>
<BRK/>
    <ITM>(3)  Connections Compliance:  Connectors, splices, and other fitting used to interconnect grounding 
conductors, bonding to equipment or ground bars, shall comply with requirements of the National 
Electric Code and be accepted by Underwriters' Laboratories for the purpose.</ITM><BRK/>
<BRK/>
   <ITM>(4)  Connectors:  Connectors and fitting for grounding and bonding conductors shall be of the 
compression type in above grade locations. Connections below grade shall be exothermically welded.</ITM><BRK/>
<BRK/>
  <ITM>(5)  Dissimilar Materials:  Bonding connections between electrically dissimilar metals shall 
be made using exothermic welds or using bi-metal connectors designed to prevent galvanic corrosion.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Communication Lines:  The following standard for separately mounted telephone and signal 
line suppressors shall apply.  All protectors shall be securely mounted at protected equipment 
location.  All suppressors shall provide common (L-G) mode protection on all lines..  Suppressors 
shall be tested in accordance with IEEE C62.36-1994 as a minimum.  Protective interfacing with 
the telephone wire pairs shall be listed to UL 497A.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Data Line Protection:  Solid state, silicon avalanche diode or metal oxide varistor circuitry 
for protection from over voltages on long cable runs employing standard RS-232, RS422, or RS485. 
Appropriate connectors shall be utilized to interface a remote station with a host CPU.</ITM>  <BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  Signal Line Protection: Solid state, silicon avalanche diode and metal oxide varistor hybrid 
circuitry for protection from over voltages on 2 or 4 wire signal lines such as balanced pair 
telephone, metallic pair telephone, buried and overhead field cable, remote radio equipment, 
and control systems.  Unit shall have an LED diagnostic lamp that lights if unit needs replacement.  
Unit shall be listed UL497B.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">i.  Modular, Twisted Pair Protection: Solid state, silicon avalanche diode or metal oxide varistor 
circuitry for protection from over voltages on twisted pair data or audio lines.  Protectors 
shall clip mount on 66 punch down blocks furnished with grounding bar or studs and shall be 
totally enclosed.  Units shall be securely mounted at terminal locations where shown and shall 
be grounded to the main building ground with a minimum No.12 stranded copper green insulated 
ground conductor kept as short as possible.  Ground terminals shall be screw insertion lug type.  
No crimp, fork or ring type permitted.  Unit shall have a multi-function diagnostic LED that 
shows continuity, ground present, unit function and line status.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">j.  Coaxial Cable Protectors: Solid state, silicon avalanche diode, metal oxide varistor and/or 
gas tube circuitry for non-interrupting over voltage protection of coaxial cable.  Unit shall 
be provided with one female input connector and one female output connector. Securely mount 
adjacent to protection equipment and ground to equipment or local building ground if an equipment 
ground is not available.</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.4.5   Electromagnetic Interference (EMI)</TTL><BRK/>
<BRK/>
<TXT>IDS components employing electromagnetic radiation shall be designed and constructed to provide maximum practical 
invulnerability to electronic countermeasures.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.6   Electromagnetic Radiation (EMR)</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  National Post Telephone and Telegraph are normally the approving authority 
for EMR components overseas.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide only IDS components which are [FCC] [_____] licensed and approved. Provide system components which are 
electromagnetically compatible.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.7   Interchangeability</TTL><BRK/>
<BRK/>
<TXT>Like components shall be physically and functionally interchangeable as complete items, without modification 
of either the original items or of other components with which the items are used.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.8   Safety</TTL><BRK/>
<BRK/>
<TXT>IDS components shall conform to application rules and requirements of <RID>NFPA 70</RID> and applicable Underwriters Laboratories 
publications.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.9   Human Engineering</TTL><BRK/>
<BRK/>
<TXT>Aural considerations shall include location of annunciators, tone pitch, quality, and intensity.  The number 
of different audible signals shall not exceed four.  Component design shall provide for ease of accessibility 
for maintenance.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.4.9.1   Visual Annunciators</TTL><BRK/>
<BRK/>
<TXT>Annunciators shall be either liquid crystal displays (LCDs) or light emitting diodes (LEDs).  Annunciators shall 
be so connected in the circuit that failure of the annunciator, socket, or protective circuitry shall not result 
in an improper or indeterminate signal.  LCDs and LEDs shall be compatible with standby power supplies.  LEDs 
shall be brightly lit and visible from a distance of<MET> 9150 mm</MET><ENG> 30 feet</ENG> in an area illuminated at<MET> 807 lx</MET><ENG> 75 footcandles</ENG>
.  LEDs shall be used in outdoor applications or in the presence of sunlight.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.9.2   Controls</TTL><BRK/>
<BRK/>
<TXT>Provide to ensure ease of operation of specified characteristics.  Where applicable, clockwise rotation of controls 
shall result in an increasing function.  Controls, switches, visual signals, and indicating devices, input and 
output connectors, terminals, and test points shall be clearly marked or labeled on hardware to permit quick 
identification, intended use, and location.  Terminal markings and labels shall be of a permanent and legible 
type and located to be visible when the associated system wiring is in place.  Identification markings shall 
be associated with each adjustment device or item requiring periodic maintenance.  Safety warning or cautions 
shall be marked in conspicuous red letters.  Control and indicator identifications that are exposed outside enclosures 
shall be permanent, machine-engraved letters, and painted to contrast with the background color.  Controls not 
required for operation of the system shall be inaccessible to the system operator.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.4.10   Test Points</TTL><BRK/>
<BRK/>
<TXT>Test points, controls, and other adjustments inside enclosures shall be readily visible and accessible with minimum 
disassembly of equipment.  Test points and other maintenance controls shall not be readily accessible to operator 
personnel.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.11   Component Enclosures</TTL><BRK/>
<BRK/>
<TXT>Annunciator housings, power supply enclosures, sensor control and terminal cabinets, control communicators, wiring 
gutters, and other component housings, collectively referred to as enclosures, shall be formed and assembled 
to be sturdy and rigid.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.4.11.1   Metal Thickness</TTL><BRK/>
<BRK/>
<TXT>Thicknesses of metal in cast and sheet metal enclosures of all types shall not be less than those in Tables 8.1, 
8.2, and 8.3 of <RID>UL 1610</RID> for alarm components, and <RID>NEMA ICS 2</RID> and <RID>NEMA ICS 6</RID> for other enclosures.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.11.2   Doors and Covers</TTL><BRK/>
<BRK/>
<TXT>Doors and covers shall be flanged.  Where doors are mounted on hinges with exposed pins, hinges shall be of the 
tight-pin type, or ends of hinge pins shall be tack welded to prevent ready removal.  Provide doors having a 
latch edge length of less than<MET> 610 mm</MET><ENG> 24 inches</ENG> with a single lock.  Where the latch edge of a hinged door is<MET>
 610 mm</MET><ENG> 24 inches</ENG> or more in length, provide the door with a three-point latching device with lock; or alternatively 
with two locks, one located near each end.  Covers of junction boxes provided to facilitate initial installation 
of the system shall be held in place by tack welding, brazing, or one-way screws.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.11.3   Ventilation</TTL><BRK/>
<BRK/>
<TXT>Ventilation openings in enclosures and cabinets shall conform to the requirements of <RID>UL 1610</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.11.4   Mounting</TTL><BRK/>
<BRK/>
<TXT>Unless otherwise indicated, sheet metal enclosures shall be designed for wall mounting with top hole slotted.  
Mounting holes shall be in positions which remain accessible when major operating components are in place and 
the door is open, but shall be inaccessible when the door is closed.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.11.5   Enclosure Locks</TTL><BRK/>
<BRK/>
<TXT>Locks and key-lock-operated switches required to be installed on component enclosures shall be UL listed, round-key 
type with three dual, one mushroom, and three plain pin tumblers, or shall have a pick resistance equal to a 
lock having a combination of five cylinder pin and five-point three-position side bar in the same lock.  Keys 
shall be stamped "U.S. GOVT.  DO NOT DUP."  Key-lock-operated switches shall be keyed differently and shall be 
two-position, with the key retractable from either position. Furnish two keys for each switch.  Maintenance locks 
shall be of the one-way key-pull type arranged so that the key can be withdrawn only when the lock is in the 
locked position.  Locks on components for maintenance access shall be keyed alike; furnish only two keys for 
such locks.  Deliver keys, tagged with metal tags, accompanied by a manufacturer's certificate which records 
the number of each key made.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.4.12   Detection Sensors</TTL><BRK/>
<BRK/>
<TXT>Sensors shall detect penetration of the facility perimeter and protected zones by unauthorized personnel or intruders, 
and shall conform to <RID>UL 634</RID> or <RID>UL 639</RID>, as applicable.  Unless otherwise specified, required sensor power shall 
be plus 12 volts DC.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.4.12.1   <SUB>Interior Point Sensors</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If a high level of security is required such as DCID , specify balanced 
magnetic switches (BMS) in Section 13703, "Commercial Intrusion Detection Systems."</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">a.  Door and window open detection</ITM><BRK/>
<BRK/>
<ITM>(1)  Magnetic Switches:  Magnetic switches shall be [surface mounted] [recessed] [______].  
Magnetic switches shall have a magnetic field with a high probability of alarm if an external 
magnet is introduced in defeat attempts.  Provide each magnetic switch with an overcurrent protective 
device, rated to limit current to 80 percent of switch capacity. The magnetic switch housing 
shall be protected from unauthorized access by encapsulating reed switches in a polyurethane 
potting compound. The magnetic switch shall have a tamper resistan enclosure and integral tamper 
switch.  Magnetic switch shall be rated for a minimum lifetime of one million operations. House 
magnetic switch components in enclosures made of nonferrous materials.</ITM><BRK/>
<BRK/>
<ITM>[(2)  Surface mounted magnetic switches:  House components used in outdoor applications in weatherproof 
enclosures.  The switch mechanism shall have a minimum gap of<MET> [10] [19] mm</MET><ENG> [3/8] [3/4] inch</ENG> 
and a maximum gap of<MET> [31.75] [63.5] mm</MET><ENG> [1 1/4] [2 1/2] inches</ENG> without internal adjustment.  
The housing for surface mounted magnetic switches, if made of cast aluminum, shall be secured 
by stainless steel screws. The magnetic switch shall have a tamper resistan enclosure and integral 
tamper switch. Conductors running from the door to alarm circuits shall be jumpered within a 
flexible armored cord constructed from corrosion-resistant metal.  Each end of the armored cord 
shall terminate in a junction box or other enclosure.  Armored cord ends shall be mechanically 
secured to junction boxes by clamps or bushings.  Conductors within the armored cord shall be 
provided with lug terminals at each end.  Jumpered conductors and the armored cord shall experience 
no mechanical strain as the door is removed from fully open to closed.  The switch circuit shall 
initiate an alarm if a short circuit is applied to the door cord.]</ITM><BRK/>
<BRK/>
<ITM>[(3)  Recessed magnetic switches:  The recessed magnetic switches shall have a gap up to<MET> 12.7 
mm (9.5 mm in steel)</MET><ENG> (1/2 inch (3/8 inch in steel)</ENG>.  Field adjustments in the fixed space between 
magnet and switch housing shall not be possible. [Ball bearing door trips shall be mounted within 
vault door headers such that when the locking mechanism is secured, the door bolt engages an 
actuator, mechanically closing the switch.  The door bolt locking mechanism shall be completely 
engaged before the ball bearing door trip is activated.  The magnetic switch shall have a tamper 
resistan enclosure and integral tamper switch. Provide circuit jumpers from the door.]]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Glass breakage detection</ITM><BRK/>
<BRK/>
<ITM>(1)  Glass breakage sensors:  Sensors shall detect window breakage by responding to sonic or 
vibration frequencies that accompany breaking glass.  Sensors shall selectively filter input 
to detect only frequency of breaking glass and to minimize false alarms from sources such as 
jangling keys, ringing phones, and slamming doors.  Glass breakage sensors shall initiate alarm 
when the glass they protect is cracked or broken.  Sensors shall provide positive detection 
of breakage of plate, safety, laminated, and tempered glass.  Sensor shall have a sensitivity 
adjustment controlling the output voltage from the detecting element which triggers a solid-state 
latching device.  Provide the sensor with an LED for adjusting the sensitivity.  [Sensor shall 
be contained in a fire-resistant ABS plastic housing and shall be mounted in contact with the 
window.  Supply the sensor with a two-sided polyurethane tape with acrylic adhesive.  Provide 
the sensor with an exterior label to protect the tape from direct sunlight.]  [Sensor shall 
be contained in a fire-resistant ABS plastic housing and shall be ceiling or wall mounted, as 
indicated.  Sensor shall provide coverage of large glass areas up to<MET> 10 675 mm</MET><ENG> 35 feet</ENG> wide.  
Sensor housing shall be tamper resistant and designed for screw mounting.]  Sensor shall not 
initiate alarm in response to seismic vibrations or other ambient stimuli. The sensor shall 
have a tamper resistan enclosure and integral tamper switch.</ITM><BRK/>
<BRK/>
<ITM>(2)  Dual technology glassbreak sensor: Sensor shall detect window breakage by responding to 
acoustic frequencies that accompany breaking glass.  The sensor shall be combined with a passive 
infrared motion detector (PIR) for the purpose of eliminating occupant-generated false alarms.  
It will extend coverage to occupied areas, allowing the sensors to be armed while people are 
present. The sensor shall have a tamper resistan enclosure and integral tamper switch.</ITM><BRK/>
<BRK/>
<ITM>(3)  Recessed glassbreak sensor:  A recessed glassbreak sensor is to be used when appearance 
is a consideration. Recessed models can be mounted directly to the wall or ceiling or can be 
installed on a signle gang box. The sensor shall employ pattern recognition technology that 
listens for the actual pattern of breaking glass.  The sensor shall be able to detect the difference 
from breaking glass and normal room sounds by listening across the glassbreak frequency spectrum. 
The sensor shall provide a <ENG>25 feet</ENG><MET> 7.6 meters</MET> 360 degree coverage of the area to be protected. 
The sensor shall have a tamper resistan enclosure and integral tamper switch.</ITM><BRK/>
<BRK/>
<ITM>(4)  Screening:  Construct security screens from a maximum of 26 AWG insulated hard-drawn copper.  
Connect screens to an alarm circuitry by means of flexible armored cords.  Security screen circuitry 
shall provide end-of-line resistors in series or equivalent methods ensuring alarm activation 
if short-circuiting of the screen is attempted.  [If screen corners are not installed as a breakwire 
sensor (wire traps), provide tamper switches.  Provide tamper switches in frames as required 
with not less than one switch on each side if dimensions are<MET> 610 mm</MET><ENG> 2 feet</ENG> square or less, and 
two switches if dimensions exceed<MET> 610 mm</MET><ENG> 2 feet</ENG> square.  Tamper switches shall be corrosion 
resistant, spring operated, and shall initiate an alarm with a movement of<MET> 50 mm</MET><ENG> 2 inches</ENG> or 
less and before access to the switch is possible.  Electrical characteristics of the switch 
shall match alarm system requirements.] The sensor shall have a tamper resistan enclosure and 
integral tamper switch.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Object protection</ITM><BRK/>
<BRK/>
<ITM>(1)  Capacitance proximity sensor:  Capacitance proximity sensor shall detect changes in the 
established capacitance to ground of a protected object. When the protected object is touched  
and a ± 20 pf - (variable) change in the capacitance is detected an alarm shall be generated. 
Circuits measure the ratio between the charging current and the resultant rate of change of 
voltage with time. Sensor shall protect objects up to a [50,000] [_____] picofarad capacitive 
load.  The system shall provide means of indicating an alarm condition at the protected objects 
during installation and calibration.  Provide the indicator with a disabling device within a 
tamperproof enclosure.  The number of objects protected by a single capacitance detector shall 
not exceed the unit's maximum capacitance at the desired sensitivity.  Protected objects shall 
be insulated from ground by insulating pads which shall have a dielectric constant such as glass 
or thermoplastic materials.  [If screen grids or radiators are employed as antennas, insulate 
from ground. Wires used for grids shall be larger than No. 14 AWG, 30 percent copper-clad steel 
covered with a minimum of <MET> 0.397 mm</MET><ENG> 1/32 inch</ENG> vinyl coating.  Space grid elements at<MET> 150 mm</MET><ENG> 
6 inches</ENG> maximum, and construct in a symmetrical manner.]  Provide sensor with sensitivity controls 
inaccessible to operating personnel.  Sensor shall be insensitive to human body movements in 
excess of<MET> 915 mm</MET><ENG> 36 inches</ENG> from the antenna circuit.  Sensor sensitivity to alarm-producing 
stimuli shall be readily adjustable from contact to <MET>915 mm </MET><ENG>36 inches </ENG>with a heavily gloved hand.  
Sensor shall not initiate nuisance alarms in response to normal ambient conditions.  [Provide 
sensors with tamper switches. Interconnecting lines and tamper switches shall remain under constant 
supervision, even when the system is set for authorized access.]  Sensor shall not reset upon 
restoration of SECURE mode if the antennas were altered during authorized entry to disable detection 
capability.</ITM><BRK/>
<BRK/>
<ITM>(2)Vibration vault sensor:  Sensor shall sense short duration, large amplitude signals like 
those produced in attacks from explosions, hammering or chiseling.  It shall also detect long 
duration, small amplitude signals like those prduced in attacks from torches, thermic lances, 
drills, grinders or cutting discs.  The sensor enclosure base shall be constructed of die-cast 
aluminum with a stamped 22 guage steel cover.The sensor shall have a tamper resistan enclosure 
and integral tamper switch.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Floor, wall, and ceiling protection</ITM><BRK/>
<BRK/>
<ITM>(1)  Vibration sensors:  Sensors shall sense and selectively amplify signals generated by forced 
penetration of a protective structure.  Sensors shall initiate alarms upon detecting drilling, 
cutting, or blasting through walls, or other methods of forced entry through a structure.  Mount 
vibration sensors directly contacting the surface to be protected.  Sensors shall be designed 
to give peak response to structurally conveyed vibrations associated with forcible attack on 
the protected surface.  Provide at least one sensor on each monolithic slab or wall section, 
even though spacing closer than that required for midrange sensitivity may result. House sensors 
in protective mountings and fasten to the surface with concealed mounting screws or an epoxy.  
[Provide sensors with tamper switches.]  Removal of a sensor from the surface shall initiate 
an alarm.  An adjustable alarm discriminator shall function to prevent incidental vibrations 
which may occur from triggering the alarm circuit.  Adjust the discriminator on the job to the 
precise needs of the application.  Connect sensors to an electronic control unit by means of 
wiring or fiber optics cable run in [rigid steel conduit] [EMT].  Sensor sensitivity shall be 
individually adjustable unless sensor is designed to accommodate vibration ranges of the specific 
surface type on which it will be mounted.  Sensitivity adjustments shall not be accessible without 
removing the cover on the sensor.  Sensor shall not be responsive to airborne sound.</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Utility inlet openings are protected in a variety of methods, the correct 
one being dependent on two variables:  the nature of the intrusion threat (e.g., 
physical penetration, electrical, electro-optical) and the characteristics of 
the utility inlet opening (e.g., discharge water from a nuclear plant, office 
air duct, electric conduit). Subsequent to such analysis, almost any of the 
intrusion detection sensors described herein could provide the necessary protection.  
Normally a breakwire trap sensor is used for this application.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM>(2)  Protection of utility inlet openings:  Provide protection by a sensor of the [breakwire] 
[wire trap] type consisting of up to 26 AWG hard-drawn copper wire with a tensile strength of <MET>
 17.8 N</MET><ENG> 4 pounds</ENG> maximum interlaced throughout the opening such that no opening between wires 
shall be larger than<MET> 100 mm</MET><ENG> 4 inches</ENG> on center. Terminate sensor so that attempts to cut the 
wire or otherwise enlarge openings between wires shall cause an alarm.  Sensor termination shall 
be [concealed] [tamper protected].</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.12.2   <SUB>Interior Volumetric (Space) Sensors</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include a schedule of sensors on the plans when the size of areas and 
pattern coverage is different from one sensor to another.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">a.  Passive infrared (PIR) sensors:  Sensors shall detect intruder presence by monitoring the 
level of infrared energy emitted by objects within a protected zone.  Sensor shall initiate 
an alarm upon observing increased or fluctuating infrared energy caused by the presence and 
motion of an intruder whose temperature is as little as<MET> 1.6 degrees C</MET><ENG> 3 degrees F</ENG> different 
from the background temperature.  Sensor shall be passive in nature; no transmitted energy shall 
be required for detection.  Sensor shall be sensitive to infrared energy emitted at wavelengths 
corresponding to the human body and other objects at ambient temperatures.  Detection pattern 
for wall-mounted sensors shall be<MET> 15 m by 15 m</MET><ENG> 50 ft by 50 ft</ENG>, unless otherwise indicated[, 
and] [shall be housed in a tamper-alarmed enclosure].  Detection pattern for ceiling-mounted 
sensors shall be<MET> 6.28 rad</MET><ENG> 360 degrees</ENG>, unless otherwise indicated[, and] have a tamper resistan 
enclosure and integral tamper switch..  Sensor shall provide some means of indicating an alarm 
condition during installation and calibration.  A means of disabling the indication shall be 
provided within the sensor enclosure.  Sensor shall alarm if an intruder moves within the area 
of protection more than<MET> 1525 mm</MET><ENG> 5 feet</ENG> at a velocity of<MET> 30 mm per second</MET><ENG> 0.1 foot per second</ENG>
, and one step per second, assuming<MET> 150 mm</MET><ENG> 6 inches</ENG> per step.  Detection sensitivity shall be 
irrespective of the direction of motion.  Sensor shall also alarm at velocities faster than<MET> 
30 mm per second</MET><ENG> 0.1 foot per second</ENG>, up to<MET> 3050 mm per second</MET><ENG> 10 feet per second</ENG>.  Sensor optimum 
detection range shall be [a minimum of<MET> 10675 mm</MET><ENG> 35 feet</ENG>] [as indicated].  Sensor shall not alarm 
in response to general area thermal variations.  Sensor shall have RFI and white light immunity.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Dual technology sensors:  Provide sensor combining passive infrared and microwave sensors 
designed and manufactured specifically to be mounted in a single enclosure.</ITM><BRK/>
<BRK/>
<ITM>(1)  Passive infrared (PIR) sensor section:  Sensor shall detect intruder presence by monitoring 
the level of infrared energy emitted by objects within a protected zone.  Sensor shall initiate 
an alarm upon observing increased or fluctuating infrared energy caused by the presence and 
motion of an intruder whose temperature is as little as<MET> 1.6 degrees C</MET><ENG> 3 degrees F</ENG> different 
from the background temperature.  Sensor shall be passive in nature; no transmitting energy 
shall be required for detection.  Sensor shall be sensitive to infrared energy emitted at wavelengths 
corresponding to the human body or other objects at ambient temperatures.  Sensor detection 
pattern shall be<MET> 15 m by 15 m</MET><ENG> 50 ft by 50 ft</ENG>, unless otherwise indicated.  Sensor shall come 
with clip-on mirror inserts that allow the choice of deferent coverage patterns: [full] [90°], 
[45° left], [45° right] [center curtain] [_____].Sensor shall have RFI and white light immunity. 
The sensor shall have a tamper resistan enclosure and integral tamper switch.</ITM><BRK/>
<BRK/>
<ITM>(2)  Microwave sensor section:  Sensor shall detect intruder presence by transmitting electromagnetic 
energy into a protected zone, receiving direct and reflected energy, and monitoring frequency 
shift between transmitted and received signals.  If more than one device is used in an area, 
devices shall operate on different frequencies.  Provide for selective filtering by sensor to 
minimize nuisance alarms due to moving metal objects such as fan blades and venetian blinds, 
interference from radar, or other sources of electronic interference.  Transceivers shall consist 
of a combined transmit/receive antenna and an adjustable-gain preamplifier in a single housing.  
Provide transceivers with sensitivity adjustments.  Transceiver controls shall permit adjustment 
of transmission range and alarm signal threshold.  Sensitivity controls shall be inaccessible 
to operating personnel.  Sensitivity requirements shall be met with sensitivity controls set 
approximately at midrange. The sensor shall have a tamper resistan enclosure and integral tamper 
switch.</ITM><BRK/>
<BRK/>
<ITM>(3)  Additional dual technology sensor requirements:  The enclosure containing two sensor sections 
shall be tamper alarmed.  Both microwave and PIR sections shall activate simultaneously to generate 
an alarm.  Only an intrusion characterized by volumetric motion and radiant body heat shall 
be detected.  Sensor shall provide some means of indicating an alarm condition during installation 
and calibration.  A means of disabling the indicator shall be provided within the sensor enclosure.  
Sensor shall alarm if an intruder moves within the area of protection more than<MET> 1525 mm</MET><ENG> 5 feet</ENG>
 at a velocity of<MET> 30 mm per second</MET><ENG> 0.1 foot per second</ENG>, and one step per second, assuming<MET> 150 
mm</MET><ENG> 6 inches</ENG> per step.  Detection sensitivity shall be irrespective of the direction of motion.  
Sensor shall also alarm at velocities faster than<MET> 30 mm per second</MET><ENG> 0.1 foot per second</ENG>, up to<MET>
 3050 mm per second</MET><ENG> 10 feet per second</ENG>.  Sensor shall not alarm in response to general area 
thermal variations.  Mount sensors [near the ceiling on vibration-free surfaces] [as indicated].  
Electronic circuitry shall be solid state and mounted on printed circuit boards.  Sensor elements 
shall contain circuitry for transmitter drive, signal processing, tamper circuitry, and power 
supplies.  Circuitry shall provide an alarm relay with Form C contacts capable of carrying 2 
amperes at 100 volts DC minimum. The sensor shall have a tamper resistan enclosure and integral 
tamper switch.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Audio sensors:  Sensors shall consist of microphones which detect audio information and 
transmit signals to an audio amplifier in a central control unit.  Multiple units may be connected 
to a central control unit.  Audio sensors shall be designed to be especially sensitive to generic 
audio intrusion signature of [breaking glass] [splintering wood] [fracturing of cement block] 
[normal voice conversation].  Sensors shall have sensitivity adjustments which shall be inaccessible 
to operating personnel.  Sensitivity adjustment shall permit operating ranges up to a maximum 
of <MET> [465] [_____] square meters</MET><ENG> [5000] [_____] square feet</ENG>.  Sensors shall have a detection 
sensitivity of [unidirectional design] [omnidirectional design].  [Audio assessment capability 
shall be provided.]  Sensors shall be capable of installation in a concealed configuration and 
shall be inherently self-protecting.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Photoelectric sensors:  Sensors shall detect intruder presence by establishing a series 
of infrared beams and detecting beam disruptions.  Transmitters shall be dual beam type and 
shall be designed to emit [no perceptible] light.  The beam may be reflected by one or more 
mirrors before being received and amplified.  Disruption of the beam by an opaque body shall 
initiate an alarm.  The transmitted beam shall be uniquely modulated to prohibit an intruder 
from shining another light source into the receiver to escape detection.  Provide some means 
of local alarm indication on the sensor for use at the protected zone during installation and 
calibration.  Provide with an indicator disabling device within the sensor enclosure.  Sensor 
shall consist of modulating transmitter, focusing lenses, mirrors, demodulating receiver, power 
supply, and interconnecting lines.  House elements in tamper-alarmed enclosure.  The receiver 
unit shall provide an alarm relay with contacts capable of carrying 2 amperes at 120 volts AC 
minimum.  The protective beam shall be focused in a straight line.  The installed beam distance 
from transmitter to receiver shall not exceed 80 percent of the manufacturer's maximum recommended 
rating.  Mirrors may be used to extend the beam or to establish a network of beams.  Each mirror 
used shall derate the maximum system range by no more than 50 percent.  Mirrors and photoelectric 
sources used in outdoor applications shall have self-heating capability to eliminate condensation 
and shall be housed in weatherproof enclosures.  The system shall utilize automatic gain control 
or be provided with sensitivity adjustments to allow for various beam lengths.  Controls shall 
be inaccessible to operating personnel.  With controls set at approximately midrange, the system 
shall initiate an alarm whenever the beam is interrupted.  Test the system by walking through 
the beam.  Systems that use multiple beams to establish a fence shall be tested by attempting 
to crawl under and jump through and over the beams.  Systems shall provide cutoffs of at least 
[90] [_____] percent to handle a high percentage of light cutoff prior to initiating an alarm.  
Sensor shall have RFI immunity.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.12.3   <SUB>Duress Alarms</SUB></TTL><BRK/>
<BRK/>
<TXT><RID>UL 639</RID>.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Hardwire duress alarms:  Install at points within the protected area as indicated.  Alarms 
shall be capable of being secretly activated by the foot or hand of an average adult in both 
standing and seated positions.  Alarms shall not be visible or audible from the sensor.  The 
alarm signal shall lock-in upon activation until manually reset with a key or similar device 
and shall be readily identifiable by the IDS.  Sensors shall be easy to operate and designed 
to minimize the possibility of accidental activation. Hardwire duress alarms shall be rated 
for a minimum lifetime of 50,000 operations.  Securely mount sensors in rugged, corrosion-resistant 
housing.  Duress alarms shall be [annunciated to be clearly distinguishable from other intrusion 
detection alarms at the control communicator] [silent at the reporting location and clearly 
distinguishable from intrusion detection alarms at the central monitoring station].</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Radio frequency duress alarms:  Duress alarms shall consist of a compact and lightweight 
transmitter enclosed in a case that can be easily worn at the waist on a belt.  Transmitter 
shall have a unique identification code.  Transmitter shall be capable of transmitting 2 watts 
of RF power.  Transmitter shall transmit up to [500] [_____] times on the power provided by 
internal batteries.  A small, flexible PVC-encased antenna shall be mounted<MET> 12.7 mm</MET><ENG> 1/2 inch</ENG>
 away from the transmitter to ensure reliable propagation of the alarm signal and rotation of<MET>
 6.28 rad</MET><ENG> 360 degrees</ENG> without damage to the sensor.  Provide transmitter in a corrosion-resistant 
case.  Transmitter shall be available in both VHF and UHF radio bands.  Transmitter shall be 
FM modulated to ensure reception and decoding of the alarm signal.  The signal transmitted shall 
readily interface with the IDS communications subsystem as specified in paragraph entitled "Radio 
Frequency Link." Activation of the sensor shall be by hand-operated switch protected from accidental 
activation, yet easily activated by hand when worn at the waist on a belt.  [Sensor activation 
shall be automatic when mounted on a belt and when the wearer is in a horizontal position for 
an adjustable time interval of longer than [1] [5] [15] [_____] minutes.  Adjustment of time 
interval activation shall not be accessible to operations personnel.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Keypad activated duress alarms: Duress alarms shall consist of programmable keypad activated 
push buttons [and] [or] a keypad activated Duress code, a user code programmed as a Duress code. 
Dedicated keys on the keypad shall be individually enabled via programming to initiate an alarm 
signal. Each programmed key shall also have the capability to initiate an auxiliary output for 
additional alarm signaling.  </ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.4.13   Communications</TTL><BRK/>
<BRK/>
<TXT>Communications shall link together the subsystems of the IDS.  IDS communications links shall be via hardwire 
(cable)[, or radio frequency]. Communications links shall be supervised.  Common <SUB>communications interface devices</SUB>
 shall be provided throughout the IDS.  Sensor to Premise Control Unit (PCU) interface shall be by dry relay 
contact normally open or normally closed, except as specified otherwise.  PCU to central alarm reporting Digital 
Receiver shall be digital, asynchronousor multiplexed data.  The system shall be capable of communication using 
the IBM Synchronous Data Link Control format, and at least two other standard industry formats. The system shall 
be capable of supporting Network communication with digital dialer backup, existing Ethernet or token ring data 
networks, satellite communication, fiber optic networks, local area networks, wide area networks, cellular communication, 
and retail data networks. The PCU shall be capable of asynchronous network communication with a retry time between 
3 and 15 seconds for a total of one (1) minute.  If communication is unsuccessful the PCU shall be capable of 
attempting backup communication through any of the available communication methods to the same receiver or a 
backup receiver.  Network communication between the PCU and the receiver shall be in a proprietary communication 
format.  The PCU shall be capable of supporting Dynamic Host Communication Protocol (DHCP) Internet Protocol 
(IP) addressing.  Underwriters Laboratories (UL) shall list network communication by the PCU for Grade AA High-Line 
Security. The PCU shall be capable of two-way network communication using standard Ethernet 10BaseT in a LAN, 
WAN, or Internet configuration.  The PCU shall be capable of communication by means of a 128 Bit AES Rijndael 
Encryption process certified by NIST (National Institute of Standards and Technology) to a Digital receiver with 
a built-in Encryption Alarm Router. The PCU shall be capable of meeting DCID 6/9 and UL 2050 standards. The PCU 
shall be capable of having communication set to Network operation.  When a trap is set in Remote Link, the software 
shall be capable of sending a panel trap message with the panel account number to the Digital receiver. The digital 
receiver shall store the trap and monitor the PCU for the next message.  When the PCU sends its next message, 
the receiver shall then send a message to the PCU to contact Remote Link at the IP address contained in the original 
trap message. The trap message shall be stored in the digital receiver for up to four hours.  If the trap message 
is not sent to the PCU within the four-hour window, the PCU trap message shall be discarded and a new trap message 
must be sent from Remote Link.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.4.13.1   Sensor to PCU Link Supervision</TTL><BRK/>
<BRK/>
<TXT>Provide hardwire direct current line supervision for sensor to PCU links which are within the IDS protected area.  
Circuit shall be supervised by monitoring changes in the current that flows through the detection circuit and 
a terminating resistor of at least [1.0] [__] kohm.  Supervision circuitry shall initiate an alarm in response 
to opening, closing, shorting, or grounding of the conductors by employing Class C, Standard Line Security.  
Class C circuit supervisor units shall provide an alarm response in the annunciator in not more than one second 
as a result of the following changes in normal transmission line current:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Five percent or more in normal line signal when it consists of direct current from 0.5 milliamperes 
through 30 milliamperes.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Ten percent or more in normal line signal when it consists of direct current from 10 microamperes 
to 0.5 milliamperes.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Five percent or more of any element or elements of a complex signal upon which security 
integrity of the system is dependent.  This tolerance will be applied for frequencies up to 
100 Hz.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Fifteen percent or more of any element or elements of a complex signal upon which security 
integrity of the system is dependent.  This tolerance will be applicable for frequencies above 
100 Hz.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.13.2   Control Communicator Hardwire Link</TTL><BRK/>
<BRK/>
<TXT>The control communicator to central alarm reporting processor communications link shall operate over a maximum 
of [2] [4] [_____] standard voice grade telephone leased or proprietary lines.  Digital communicator shall conform 
to <RID>UL 1635</RID>.  The link shall be capable of operating half duplex over a Type 3002 data transmission pair and shall 
be capable of modular expansion.  Telephone lines will be provided by the Government.  Coordinate and check out 
system operation.  General characteristics and telephone line service shall be as follows:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Connections:  Two- or four-wire</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Impedance at 1000 Hz:  600 ohms</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Transmitting level:  0 to 12 dBm</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Transmitting level adjustment:  3 dB increments</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Type:  Data</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Direction:  Two-way alternate (half duplex)</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Maximum speed:  [1.2] [5.12] [10.24] [_____] kilobaud</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  Maximum loss at 1000 Hz:  33 dB.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.13.3   <SUB>Radio Frequency Link</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Radio frequency links may not be allowed on some Government facilities.  
Recommended usage for RF links is as backup to hardwire links or at a remote 
location lacking telephone lines.  OPNAV Instruction 2400.20E requires that 
funds shall not be obligated for procurement of radio equipment until frequency 
allocation authority has been obtained.  As soon as possible, but no later than 
schematic design, the designer shall contact the area radio frequency coordinator 
(usually the base radio officer) to determine the availability of radio frequencies 
and to ensure that the using activity submits a DD Form 1494, Application for 
Frequency Allocation, for a Stage 1 ("Conceptual Development") allocation (see 
DD Form 1494 Preparation Guide).  Stage 1 allocation authority (i.e., approval) 
must be obtained prior to advertisement of the contract.</NPR><BRK/>
<BRK/>
<NPR>The 138 to 150.8 MHz band is the preferred range since specific frequencies 
in this range are reserved for DOD use.  Frequencies in the 162 to 174 MHz and 
450 to 470 MHz bands are shared with other users on a first-come, first-serve 
basis.  To avoid potential contract delays, the frequency assignment should 
be included in the specification when possible.  For additional information, 
contact the base radio officer or the Naval Electromagnetic Spectrum Center 
at (202) 433-0689.  OPNAVINST 2400.20E is issued by OPNAV Code N60 (previous 
Code OP941), telephone (703) 695-7284.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The system shall be a full duplex, supervised RF polling specifically designed for alarm data communications 
with components manufactured by one manufacturer.  The system shall operate in the very high frequency (VHF), 
[134 to 154]  [_____ to _____] MHz band.  The system shall interface directly with the IDS hardwire data link 
from control communicator to the central alarm reporting location.  The system shall also translate (reduce) 
the data rate for RF transmission, modulate and demodulate the data signal, and transmit and receive IDS data.  
Provide a factory-tested complete RF link which both automatically and upon operator command transmits a signal 
with a unique identification from the central alarm monitoring location to control communicator locations.  Message 
receipt at control communicator location shall be ignored by other control communicators except the addressee.  
The communicator with the correct address shall decode the interrogation signal and respond to interrogation 
with status of reporting sensors.  If the addressee fails to respond, reinterrogate.  Failure to respond a second 
time shall cause a line supervision alarm.  Remote units in the RF system shall be individually polled in turn.  
Polling response time and transmission data rate, data error rate, and equipment reliability shall ensure that 
overall IDS alarm annunciation time reliability is not degraded.  Provide RF transmitters, receivers, or transceivers 
in sufficient quantities to meet specified requirements.  RF link transmissions shall be on one or more of the 
frequencies within the specified band as required to meet the specified requirements and shall neither interfere 
with other IDS components nor facility electronic components.  Provide transmitters which are in accordance with 
applicable requirements of <RID>47 CFR 15</RID>.  Message types and content shall be identical to those transmitted by other 
portions of the IDS data communications subsystem.  IDS alarms sent by RF link shall not fail to be transmitted 
by RF link due to events occurring in "off air" periods.  The RF link shall provide message transmission priority 
in the following order:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Intrusion alarms</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Tamper alarms</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Access denial alarms</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Other alarms on a first-in, first-out basis including loss of communication signal, fail-safe, 
low battery, and power loss.</ITM><BRK/>
<BRK/>
<TXT>Provide [omnidirectional, coaxial, half-wave dipole] [_____] antennas for alarm transmitters and transceivers 
with a driving point impedance to match transmission output.  Antennas and antenna mounts shall be corrosion 
resistant and designed to withstand wind velocities of<MET> [161] [_____] km/h</MET><ENG> [100] [_____] mph</ENG> and physical damage 
caused by vandalism.  Antennas shall not be mounted to any portion of the facility fence or roofing system.  
Antennas shall be furnished from the same manufacturer as the rest of the RF link.  Provide coaxial cable in 
lengths as required.  Cable shall use PL-type fittings or connectors, properly protected against moisture.  Cables 
shall match the output impedance of the transmitters.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.4.14   Premise Control Unit (PCU)</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Locate  in secure, indoor, dry location.  To determine the number of 
zones required for a specific project, consider the following as a minimum:  
one zone for entry/exit doors, one zone for window switches and doors that are 
not entry/exit type, one zone for motion sensors, one zone for glass break sensors, 
one or more zones for tamper, and one zone for duress alarm (if used).  Increase 
the number of zones as the size of the building/area increases.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>PCU shall include a command processor installed in an attack and tamper resistant enclosure. The PCU shall be 
packaged and include a power transformer, battery(s), network connection cable, keypad(s), keypad connection 
cable(s) and addtional components as required. All system electronic components shall be solid-state type, mounted 
on printed circuit boards. Light duty relays and similar switching devices shall be solid-state type or electromechanical. 
The PCU shall have an over current notification LED that lights when devices connected to the Keypad Bus or communication 
Bus(es) draw more current than the PCU is rated for. When the over current LED lights, the communications Bus(es) 
and Keypad bus are to shut down. The PCU shall provide at a minimum but not limited to, the following capabilities;</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  The PCU areas and zones shall be programmable, and the system shall store, log, display, 
and transmit specific custom designations for system areas, zones, and user names.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  The PCU, user interfaces, zone input devices, relay output devices, and the signal receiving 
equipment shall be engineered, manufactured, assembled, and must be distributed from a location 
within the United States of America.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  The system shall support user interaction by way of a keypad, web browser, system software, 
key switch, or radio frequency wireless control, using integrated or auxiliary devices provided 
by the system manufacturer.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  The PCU shall support zone input connections, system keypads, system zone expansion modules, 
and wireless zone input modules, and must support zone input connections by way of at least 
two competitive products.  The system shall offer a seamless integrated compatibility with hard-wire 
and/ or wireless zone expansion equipment for at least [200] [___] wireless zones and/ or a 
maximum of [574] [___] hardwired zones.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  The PCU shall be capable of offering at least [5] [__] zone expansion buses, each of which 
can support the connection of up to [15,000] [____] feet of four-wire cable.  Zone expansion 
and keypad data buses that exceed [2,500] [____] feet of cable must include splitter/repeater 
modules to boost data voltage and maintain data integrity.</ITM>  <BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  The PCU shall provide a seamless capability to provide a minimum of [500] [___] addressable 
relays, which can be located at any connection location upon a zone expansion bus.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  PCU relay outputs shall have the capability of being triggered as a result of a command 
from the user interface, changes in system status, changes in zone status, or by a programmable 
schedule.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  PCU relay output states shall be programmable for momentary, maintained, pulsed, or must 
follow the state of an associated zone input.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">i.  The PCU shall be completely programmable either locally from a keypad or remotely through 
a standard dial-up, and network connections by way of a LAN, WAN, and/or by way of the Internet. 
Remote configuration or control is not premissable for installation that must conform to DCID 
6/9 requirements.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">j.  The PCU shall be completely programmable remotely using remote annunciators, and/ or using 
upload/ download software that communicates using SDLC 300 baud, 2400 baud, or IP Addressed 
data network.  On-site programming from a personal computer shall also be permitted. Remote 
configuration or control is not premissable for installation that must conform to DCID 6/9 requirements.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">k.  The PCU shall be equipped with an anti-reversing circuit breaker to prevent damage due to 
accidental reversal of battery leads.</ITM><BRK/>
<BRK/>
<SPT><TTL>2.4.14.1   Input/Output Capacity</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  The PCU shall be capable of monitoring a maximum of 574 individual zones and controlling 
a maximum of 502 output relays.</ITM>  <BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  The PCU shall have, as an integral part of the assembly, 2 SPDT Form C relays rated at 1 
Amp at 30 VDC and four open collector 12 VDC outputs rated at 50mA each.  It shall also have 
the capacity of a maximum of 125 output expander modules with 500 switched ground, open collector 
outputs, 50mA maximum and 502 auxiliary relays (Form C rated at 1.0 Amp at 30 VDC).</ITM>  <BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  The PCU shall also provide 100 programmable output schedules, and include an integral bell 
alarm circuit providing at least 1.5 Amps of steady, pulsed, or temporal bell output.  Output 
type shall be programmable by zone type.  Relays and voltage outputs shall be capable of being 
independently programmed to turn on and/or off at selected times each day.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.14.2   User/Authorization Level Capacity</TTL><BRK/>
<BRK/>
<TXT>The system shall be capable of operation by [10,000] [____] unique Personal Identification Number (PIN) codes 
with each code having one [1] [__] of ninety-nine [99] [__] custom user profiles.  This allows for limitation 
of certain functions to authorized users.  The operation of all keypads shall be limited to authorized users.</TXT> <BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.14.3   <SUB>Keypad</SUB></TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  The PCU shall support a maximum of sixteen [16] [__] keypads with alphanumeric display.  
Each keypad shall be capable of arming and disarming any system area based on a pass code or 
Proximity key authorization.  The keypad alphanumeric display shall provide complete prompt 
messages during all stages of operation and system programming and display all relevant operating 
and test data.</ITM>  <BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Communication between the PCU and all keypads and zone expanders shall be multiplexed over 
a non-shielded multi-conductor cable, as recommended by the manufacturer.  This cable shall 
also provide the power to all keypads, zone expanders, output expanders, and other power consuming 
detection devices.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  If at any time a keypad does not detect polling, the alphanumeric display shall indicate 
"SYSTEM TROUBLE".  If at any time two devices are programmed for the same address, the alphanumeric 
keypad shall display "4 WIRE BUS TROUBLE".  If at any time a keypad detects polling but not 
for its particular address, the alphanumeric display shall indicate "NON POLLED ADDR".  The 
system shall display all system troubles at selected keypads with distinct alphanumeric messages.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  The keypad shall include self-test diagnostics enabling the installer to test all keypad 
functions: display test, key test, zone test, LED test, relay test, tone test, and address test.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  The keypad shall provide an easy-to-read English text display.  The text shall exactly match 
the text seen in all software reports, keypad displays, and central station reports.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  The keypad user interface shall be a simple-to-use, menu-driven help system that is completely 
user friendly.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  The PCU shall support sub-control keypads with four [4] [__] built-in zones and capable 
of functioning in the following modes:</ITM><BRK/>
<BRK/>
<ITM>(1)  Monitors all four [4] [__] keypad zones independently with a maximum of [125] [__] keypads 
attached to the PCU. <BRK/>
<BRK/>
(2)  PCU assigns one [1] [__] zone to each keypad and monitors all keypad zones as a single 
zone with a maximum of [500] [__] keypads attached to the PCU.<BRK/>
<BRK/>
(3)  Stand-alone mode allowing keypad to operate as a self-contained security system independent 
of the PCU.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.14.4   Zone Configuration</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  A minimum of [4] [__] Class B ungrounded zones shall be available at each keypad or zone 
expander on the system.  The system shall have the capacity for a maximum of sixteen [16] [__] 
keypads and a maximum of [125] [___] four (4) zone expanders or [500] [___] single zone expanders.  
It shall also have the capacity of a maximum of [125] [___] supervised relay output expanders.  
All Class B zones shall be 2-wire, 22 AWG minimum, supervised by an end-of-line (EOL) device 
and shall be able to detect open and short conditions in excess of 500ms duration.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Each zone shall function in any of the following configurations: Night, Day, Exit, Fire, 
Supervisory, Emergency, Panic, Auxiliary 1, Auxiliary 2, Fire Verification, Cross Zone, Priority, 
and Key Switch Arming.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  The digital SLCs and the annunciator/keypad bus shall be able to operate at a maximum wiring 
distance of [2500] [___] feet from the control panel on unshielded, non-twisted cable.  This 
distance may be extended to a total of [15,000] [_____] feet when bus repeater modules are installed.</ITM><BRK/>
  <BRK/>
<ITM INDENT="-0.33">d.  The PCU shall have the capability to incorporate up to [200] [___] zone expander points.</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.4.15   <SUB>[Bell] [Siren]</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Choose one of the following options.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">[a.  Bell:  Provide UL listed<MET> 255 mm</MET><ENG> 10 inch</ENG> bell rated for 6 to 12 volts DC and having a sound 
output of [84], [__] dB minimum.  Bell shall conform to <RID>UL 464</RID> and <RID>UL 609</RID>, as applicable.  Provide 
bell in steel enclosed, weather-resistant box having tamper switches on front cover and on back 
of box.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Siren:  Provide 30 watt, 8 ohm speaker and siren driver rated for 6 to 12 volts DC and 
having two distinct sound outputs.  Siren shall produce a sound level output of [103 to 106], 
[____] dB at<MET> 3050 mm</MET><ENG> 10 feet</ENG>.  Siren shall conform to <RID>UL 464</RID> and <RID>UL 609</RID>, as applicable.  Provide 
siren in metal enclosed, weather-resistant box having tamper switches on front cover and on 
back of box.]</ITM><BRK/>
<ITM INDENT="-0.33">c. Chime: Provide for keypad audible indication of a device activation. Audible chime shall 
sound when select devices activate in order to alert personnel of access into an area during 
normal access times. The audible chime may be activated when a magnetic switch is activated 
at a main entrance leading into a un-secured area during working hours.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.16   <SUB>Strobes</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide for visual indication of alarm activation.  Strobe shall flash simultaneously with [siren] [bell] and 
shall be 75 candela minimum with flash rate of 60 per minute.  Strobe shall be designed to operate on 12 volts 
DC and shall conform to <RID>UL 1638</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.17   <SUB>Central Station Receiver/Printer</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide a microprocessor based digital alarm receiver conforming to <RID>UL 1610</RID> to receive and display information 
transmitted by alarm control panels/communicators over the standard telephone network.  Receiver shall be capable 
of handling Ademco low or high speed, Sescoa, Radionics, and BFSK formats with either three- or four-digit subscriber 
identification and four plus two formats on the same line card.  [Receiver shall also interface to derived channel 
telephone company networks.]  Receiver shall have built-in battery backup and shall be able to monitor a minimum 
of 999 accounts.  Telephone connection shall be RJ31X jack.  AC input shall have built-in MOV surge protection.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.4.17.1   Printer</TTL><BRK/>
<BRK/>
<TXT>Printer shall conform to <RID>UL 1610</RID> and shall provide a hard copy record of incoming information including time, 
date, account number, and code number.  Printer shall have built-in battery backup and built-in MOV surge protection 
on AC input.  Clock shall be 24-hour real time.  Calendar shall be 100 year with leap years built in.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.17.2   Operation</TTL><BRK/>
<BRK/>
<TXT>When the receiver receives a transmission over standard telephone network lines from a remote communicator, the 
receiver shall immediately answer the incoming call and acknowledge the call by returning a tone signal (handshake) 
to the communicator.  Upon receipt of the handshake, the communicator shall transmit one or two rounds of coded 
pulses which are the account and code numbers.  When a valid statement of data is received from the communicator, 
the receiver's internal audible signal shall sound to alert the monitoring person that a valid round of data 
is on line.  The receiver shall also alert the printer and shall display on the receiver's front panel the account 
number and code number of the communicator.  When the receiver has received the communicator's data, the receiver 
shall send a signal to the communicator causing the communicator to hang up (kiss off).  The receiver shall then 
automatically shut itself down within 10 seconds.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Standalone Electronic Door Access shall be an integral function of the 
PCU. Access assignment shall be configured at the PCU via the PCU keypad or 
direct PC workstation communications.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/></SPT>
</SPT><SPT><TTL>2.4.18   Standalone Electronic Door Access</TTL><BRK/>
<BRK/>
<TXT>The PCU shall be capable of integrating area access control capability where specified into the same PCU with 
the ability to have up to [10,000] [___] user credentials.  User access is limited to custom profiles and/or 
schedules.  Anti-passback shall be available.  Networked version shall support a Two-Man Rule feature.  The system 
shall support up to sixteen [16] [___] access doors, connected to the system using a manufacturer-approved interface 
module. Access Control equipment shall communicate to the system by way of the PCU keypad bus.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.5   FIELD FABRICATED NAMEPLATES</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM D 709</RID>.  Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as 
specified or as indicated on the drawings.  Each nameplate inscription shall identify the function and, when 
applicable, the position.  Nameplates shall be melamine plastic,3 mm (0.125 inch) 0.125 inch thick, white with 
[black] [_____] center core.  Surface shall be matte finish.  Corners shall be square.  Accurately align lettering 
and engrave into the core.  Minimum size of nameplates shall be 25 by 65 mm (one by 2.5 inches) one by 2.5 inches.  
Lettering shall be a minimum of 6.35 mm (0.25 inch) 0.25 inch high normal block style.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.5.1   Manufacturer's Nameplate</TTL><BRK/>
<BRK/>
<TXT>Each item of equipment shall have a nameplate bearing the manufacturer's name, address, model number, and serial 
number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.6   FACTORY APPLIED FINISH</TTL><BRK/>
<BRK/>
<TXT>Electrical equipment shall have factory-applied painting systems which shall, as a minimum, meet the requirements 
of NEMA 250 corrosion-resistance test.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   EQUIPMENT INSTALLATION</TTL><BRK/>
<BRK/>
<TXT><RID>UL 609</RID>, <RID>UL 639</RID>, <RID>UL 681</RID> <RID>UL 1076</RID> and <RID>UL 1610</RID>, and the appropriate installation manual for each equipment type.  
Components within the system shall be configured with appropriate "service points" to pinpoint system trouble 
in less than 20 minutes.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.1.1   Cable/Wire Runs</TTL><BRK/>
<BRK/>
<TXT><RID>NFPA 70</RID>; Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM, and as specified herein.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.2   Soldering</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM B 32</RID>.  For soldering electrical connections, use composition Sn60, for general purposes; use composition 
Sn62 or Sn63, for special purposes.  Flux shall conform to <RID>ASTM B 32</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.3   Galvanizing</TTL><BRK/>
<BRK/>
<TXT>Ferrous metal shall be hot-dip galvanized in accordance with <RID>ASTM A 123/A 123M</RID>.  Screws, bolts, nuts, and other 
fastenings and supports shall be corrosion resistant.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.4   <SUB>Tamper Switches</SUB></TTL><BRK/>
<BRK/>
<TXT>Tamper switches shall be an integral part of all intrusion sensor devices. An initiation of an alarm signal will 
occur when the door or cover is moved as little as<MET> 6.35 mm</MET><ENG> 1/4 inch</ENG> from the normally closed position.  Tamper 
switches shall also be Located within enclosures, cabinets, housings, boxes, raceways, and fittings to prevent 
direct line of sight to any internal components and to prevent tampering with switch or circuitry.  Conceal tamper 
switch mounting hardware so that the location of the switch within the enclosure cannot be determined from the 
exterior.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.5   Fungus Treatment</TTL><BRK/>
<BRK/>
<TXT>Completely treat system components for fungus resistance.  Treating materials containing mercury-bearing fungicide 
shall not be used.  Treating materials shall not increase the flammability of the material or surface being treated 
nor cause skin irritation or other personnel injury during fabrication, transportation, operation, or maintenance 
of the equipment, or during use of the finished items when used for the purpose intended.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.6   Conduit</TTL><BRK/>
<BRK/>
<TXT>Install in accordance with <RID>NFPA 70</RID> and Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.7   Underground Cable Installation</TTL><BRK/>
<BRK/>
<TXT>Underground conductors connecting protected structures and objects to the central alarm updating and display 
unit shall be run direct burial or in conduit as specified in Section <SRF>33 71 02.00 20</SRF> UNDERGROUND UNDERGROUND 
TRANSMISSION AND DISTRIBUTION.  Coaxial cable shall not be spliced.  If permitted, <SUB>cables</SUB> connecting protected 
structures and objects to the security control console shall be sized such that initially only approximately 
60 percent of the circuit pairs will be used.  Cable pairs not used shall be reserved for future use of additional 
detection circuits.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.2   FIELD QUALITY CONTROL</TTL><BRK/>
<BRK/>
<SPT><TTL>3.2.1   <SUB>IDS Operational Test Plan</SUB></TTL><BRK/>
<BRK/>
<TXT><TST>Test shall ensure that the requisite degree of intrusion detection is provided.  Initially, test each sensor 
and subsystem component individually.  [Test glass breakage sensors by using test units supplied by the manufacturer 
which simulate glass breakage.]  When the function of each component within a particular subsystem, such as each 
sensor within a particular zone, is verified, certify that subsystem of the entire IDS has satisfactorily met 
the specifications.  Test each subsystem similarly until each detection zone has been certified.  When subsystem 
certification is complete, test the entire integrated system to ensure that subsystem elements are compatible 
and function as a complete system.  The integrated system test shall be accomplished in linear fashion, end-to-end, 
and shall verify that each simulated intrusion performed within each detection zone produces an appropriate alarm 
or signal, and that alarm is correctly annunciated at the keypad [and central station receiver].</TST>   Provide for 
approval, not later than 30 days prior to formal inspection and test, a detailed operational test plan of how 
each component, subsystem, and entire IDS will be tested.  When tests are complete and corrections made, submit 
a signed and dated certificate with a request for formal inspection and tests.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.2   System Acceptance Test</TTL><BRK/>
<BRK/>
<SPT><TTL>3.2.2.1   <SUB>Posted Operating Instructions</SUB></TTL><BRK/>
<BRK/>
<TXT>System Acceptance testing shall be performed as follows;</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  The NAVFAC and NAVFAC Engineer will conduct final acceptance testing of the system.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Prior to the final acceptance test, security contractor shall conduct a complete test of 
the entire IDS system and provide the NAVFAC and NAVFAC Engineer with a written report.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Following completion of the initial testing and correction of any noted deficiencies, conduct 
a five-day burn-in test,  intent of the burn-in test shall be to prove the IDS by placing it 
in near real operating conditions. During this period the IDS shall be fully functional and 
programmed such that all points, interfaces, controls, reports, messages, prompts, etc. can 
be exercised and validated. Record and correct any system anomaly, deficiency, or failure noted 
during this period. Scheduling of the final acceptance test shall be based on a review of the 
results of this burn-in test.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Deliver a report describing the results of the functional tests, burn-in tests, diagnostics, 
calibrations, corrections, and repairs including written certification to the NAVFAC and NAVFAC 
Engineer that the installed complete IDS has been calibrated, tested, and is fully functional 
as specified herein.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Prior to the final acceptance test, complete all clean-up and patch work requirements. Security 
equipment closets and similar areas shall be free of accumulation of waste materials or rubbish<BRK/>
caused by operations under the Contract At completion of the Work, remove all waste materials, 
rubbish, contractor tools, construction equipment, machinery and all surplus materials.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Upon written notification from the Contractor that the IDS is completely installed, integrated 
and operational, and the burn-in testing completed, the NAVFAC and NAVFAC Engineer will conduct 
a final acceptance test of the entire system at a mutually acceptable time.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  During the final acceptance test, no adjustments, repairs or modifications to the system 
shall be conducted without the permission of the NAVFAC. </ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  During the course of the final acceptance test by the NAVFAC and NAVFAC Engineer, the Contractor 
shall be responsible for demonstrating that, without exception, the completed and integrated 
IDS complies with the contract requirements. Physical and functional requirements of the project 
shall be demonstrated and shown. This demonstration will begin by comparing <SUB>as-built drawings</SUB>
 conditions of the IDS to requirements outlined in this Section, item by item. Following the 
Section compliance review, IDS and SCCd equipment will be evaluated.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">i.  The functionality of the various interfaces between systems will be tested.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">j.  The installation of all field devices will be inspected. This field inspection will weigh 
heavily on the general neatness and quality of installation, complete functionality of each 
device, and compliance with mounting, back box and conduit requirements.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">k.  All equipment shall be on and fully operational during any and all testing procedures. Provide 
personnel, equipment, and supplies necessary to perform all site testing. Provide a minimum 
of two Contractor employees familiar with the IDS for the final acceptance test. One contractor 
employee shall be responsible for monitoring and verifying alarms while the other will be required 
to demonstrate the function of each device. Supply at least two radios or portable telephones 
for use during the test.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">l.  The NAVFAC and NAVFAC Engineer retain the right to suspend, terminate or reschedule testing 
at any time when the IDS is found to be incomplete or fails to perform as specified. In the 
event that it becomes necessary to suspend, terminate or reschedule the test, all of the NAVFAC 
and NAVFAC Engineers fees and expenses related to the test shall be deducted from the Contractor's 
retainage. In the event it becomes necessary to suspend, terminate or reschedule the test, the 
Contractor shall work diligently to complete and/or repair all outstanding items as required 
by the Contract Documents. The Contractor shall supply the<BRK/>
NAVFAC and NAVFAC Engineer with a detailed punch list completion schedule outlining task-by-task 
completion dates and a tentative date for a subsequent retest. During the final acceptance test, 
no adjustments, repairs or modifications to the system shall be conducted without the permission 
of the NAVFAC Engineer and NAVFAC.</ITM></SPT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.3   ADJUSTMENT/ALIGNMENT/SYNCHRONIZATION/CLEANING</TTL><BRK/>
<BRK/>
<TXT>Subsequent to installation, clean each system component of dust, dirt, grease, or oil incurred during installation 
or accrued subsequent to installation from other project activities.  Prepare for system activation by following 
manufacturer's recommended procedures for adjustment, alignment, or synchronization.  Prepare each component 
in accordance with appropriate provisions of the component's installation, operations, and maintenance manuals.</TXT></SPT><BRK/>
<BRK/>
<SPT><TTL>3.4   FIELD APPIED PAINTING</TTL><BRK/>
<BRK/>
<TXT>Paint electrical equipment as required to match finish of adjacent surfaces or to meet the indicated or specified 
safety criteria.  Painting shall be as specified in Section <SRF>09 90 00</SRF> PAINTS AND COATINGS</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5   NAMEPLATE MOUNTING</TTL><BRK/>
<BRK/>
<TXT>Provide number, location, and letter designation of nameplates as indicated.  Fasten nameplates to the device 
with a minimum of two sheet-metal screws or two rivets.</TXT><BRK/>
<BRK/></SPT>
</PRT>    <END/><BRK/></SEC>