<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA   UFGS-28 31 63.00 20 (October 2007)<BRK/>
                                 ------------------------------<BRK/>
Preparing Activity:  <PRA>NAVFAC</PRA>      Superseding<BRK/>
                                 UFGS-28 31 63.00 20 (April 2006)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 28 31 63.00 20</SCN><BRK/>
<BRK/>
<STL>ANALOG/ADDRESSABLE INTERIOR FIRE ALARM SYSTEM</STL><BRK/>
<DTE>10/07</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>analog/ addressable 
interior fire alarm systems in single or multiple buildings</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ASME INTERNATIONAL (ASME)</ORG><BRK/><BRK/><RID>ASME A17.1</RID><RTL>(2007) Safety Code for Elevators and Escalators</RTL><BRK/><BRK/></REF><REF><ORG>FM GLOBAL (FM)</ORG><BRK/><BRK/><RID>FM P7825</RID><RTL>(2005) Approval Guide</RTL><BRK/><BRK/></REF><REF><ORG>INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)</ORG><BRK/><BRK/><RID>IEEE C62.41.1</RID><RTL>(2002) IEEE Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power Circuits</RTL><BRK/><BRK/><RID>IEEE C62.41.2</RID><RTL>(2002) IEEE Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 101</RID><RTL>(2008) Life Safety Code, 2006 Edition</RTL><BRK/><BRK/><RID>NFPA 241</RID><RTL>(2004) Safeguarding Construction,Alteration, and Demolition Operations</RTL><BRK/><BRK/><RID>NFPA 72</RID><RTL>(2006) National Fire Alarm Code</RTL><BRK/><BRK/><RID>NFPA 90A</RID><RTL>(2008) Standard for the Installation of Air Conditioning and Ventilating Systems</RTL><BRK/><BRK/></REF><REF><ORG>U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)</ORG><BRK/><BRK/><RID>47 CFR 90</RID><RTL>Private Land Mobile Radio Services</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 1971</RID><RTL>(2002; Rev thru Oct 2008) Signaling Devices for the Hearing Impaired</RTL><BRK/><BRK/><RID>UL 228</RID><RTL>(2006; Rev thru Nov 2008) Door Closers-Holders, With or Without Integral Smoke Detectors</RTL><BRK/><BRK/><RID>UL 268</RID><RTL>(2006) Standard for Smoke Detectors for Fire Alarm Signaling Systems</RTL><BRK/><BRK/><RID>UL 464</RID><RTL>(2003; Rev thru Feb 2008) Standard for Audible Signal Appliances</RTL><BRK/><BRK/><RID>UL 864</RID><RTL>(2003; Rev thru May 2007) Control Units and Accessories for Fire Alarm Systems</RTL><BRK/><BRK/><RID>UL Electrical Constructn</RID><RTL>(2008) Electrical Construction Equipment Directory</RTL><BRK/><BRK/><RID>UL Fire Prot Dir</RID><RTL>(2008) Fire Protection Equipment Directory</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   RELATED REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Section <SRF>26 00 00.00 20</SRF> BASIC ELECTRICAL MATERIALS AND METHODS, applies to this section, with the additions and 
modifications specified herein.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   DESCRIPTION OF WORK</TTL><BRK/>
<BRK/>
<SPT><TTL>1.3.1   Scope</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Indicate the location of fire alarm system devices and riser locations 
on floor plans. Provide a fire alarm system riser diagram indicating circuits 
and risers.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>This work includes designing and providing [a new, complete,] [and] [modifying the existing] analog/addressable 
fire alarm system as described herein and on the contract drawings for the [Building name].  The system shall 
include wiring, raceways, pull boxes, terminal cabinets, outlet and mounting boxes, control equipment, alarm, 
and supervisory signal initiating devices, alarm notification appliances, supervising station fire alarm system 
transmitter, and other accessories and miscellaneous items required for a complete operating system even though 
each item is not specifically mentioned or described.  Provide system[s] complete and ready for operation. Equipment, 
materials, installation, workmanship, inspection, and testing shall be in strict accordance with the required 
and advisory provisions of <RID>NFPA 72</RID> [and] [_____] except as modified herein.  [The system layout on the drawings 
show the intent of coverage and are shown in suggested locations. Final quantity, layout, and coordination is 
the responsibility of the Contractor.]  [A single fire alarm control panel is indicated with terminal cabinets 
at each floor at each riser location.  Where remote fire alarm control units are needed, they shall be provided 
at a terminal cabinet location.]  Each remote fire alarm control unit shall be powered from a wiring riser specifically 
for that use or from a local emergency power panel located on the same floor as the remote fire alarm control 
unit.  Where remote fire control units are provided, equipment for notification appliances may be located in 
the remote fire alarm control units.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.4   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<TXT>Provide six complete sets of submittals.  Partial submittals will not be acceptable and will be returned without 
review.  [The [_____] Division] [Engineering Field Activity (EFA) [_____]], Naval Facilities Engineering Command, 
Fire Protection Engineer, will review and approve submittals.</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide 25 percent spare capacity where buildings are presently sprinkler 
protected throughout or where such protection is being provided under this design.  
Where automatic sprinkler protection will be provided later, use 50 percent 
spare capacity.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM>  Provide point-to-point wiring diagrams showing the points of connection and terminals used 
for electrical field connections in the system, including interconnections between the equipment 
or systems which are supervised or controlled by the system.  Diagrams shall show connections 
from field devices to the FACP and remote fire alarm control units, initiating circuits, switches, 
relays and terminals.</ITM><BRK/>
<BRK/>
<ITM>  Provide plan view drawing showing device locations, terminal cabinet locations, junction boxes, 
other related equipment, conduit routing, wire counts, circuit identification in each conduit, 
and circuit layouts for all floors.</ITM><BRK/>
<BRK/>
<ITM>  Provide a complete description of the system operation [in matrix format] on the drawings.</ITM><BRK/>
<BRK/>
<ITM>  Provide a complete list of device addresses and corresponding messages.</ITM><BRK/>
<BRK/>
<ITM>  Provide detailed drawings of the graphic annunciator.</ITM><BRK/>
<BRK/>
<ITM>  Include annotated catalog data, in table format on the drawings, showing manufacturer's name, 
model, voltage, and catalog numbers for equipment and components.</ITM><BRK/>
<BRK/>
<ITM>  Provide complete riser diagrams indicating the wiring sequence of devices and their connections 
to the control equipment.  Include a color code schedule for the wiring.  Include floor plans 
showing the locations of devices and equipment.</ITM><BRK/>
<BRK/>
<ITM><SUB>Battery power calculations</SUB></ITM><BRK/>
<BRK/>
<ITM>  Submit shop drawings not smaller than <MET>600 by 900 mm</MET> <ENG>24 by 36 inches</ENG>.  As a minimum, the shop 
drawing submittal shall include the items listed above.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Fire alarm control panel (FACP)</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Printers</SUB>, covers, console rack, <SUB>video display unit (VDU)</SUB>, etc.[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Terminal cabinets</SUB>/assemblies[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Manual stations</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Transmitters</SUB> (including housing)[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Batteries</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Battery chargers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Smoke sensors</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Thermal sensors</SUB>; <SUB>G</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Wiring</SUB> and cable[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Notification appliances</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Addressable interface devices</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
[<ITM><SUB>Graphic annunciator</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
[<ITM><SUB>Amplifiers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
[<ITM><SUB>Tone generators</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
[<ITM><SUB>Digitalized voice generators</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
[<ITM><SUB>Firefighter telephone</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
<ITM><SUB>Waterflow detectors</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Tamper switches</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
[<ITM><SUB>Electromagnetic door holders</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
[<ITM><SUB>Remote fire alarm control units</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
<ITM><SUB>Smoke sensor testing procedures</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
[<ITM><SUB>Radio transmitter and interface panels</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
[<ITM><SUB>Digital alarm communicator transmitter (DACT)</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
[<ITM><SUB>Telegraphic transmitter</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
<ITM>  Submit data on proposed equipment, including, but not limited to the items listed above.  
Include UL or FM listing cards for equipment provided.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM>  Furnish preliminary test results to the Contracting Officer. Include the control panel and 
initiating and indicating devices, a unique identifier for each device with an indication of 
test results, and signature of the factory-trained technician of the control panel manufacturer 
and equipment installer.  With reports on preliminary tests, include printer information.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Qualifications of installer</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>INTERIOR FIRE ALARM SYSTEM</SUB>, Data Package [5] [_____][; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE DATA.</ITM><BRK/>
<BRK/>
<ITM><SUB>Record drawing software</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-11 Closeout Submittals</SUB></LST><BRK/>
<BRK/>
<ITM>  Prepare and submit to the Contracting Officer six sets of detailed as-built drawings.  The 
drawings shall include complete wiring diagrams showing connections between devices and equipment, 
both factory and field wired. Include a riser diagram and drawings showing the as-built location 
of devices and equipment.  The drawings shall show the system as installed, including deviations 
from both the project drawings and the approved shop drawings.  The drawings shall be prepared 
on uniform sized mylar sheets not less than<MET> 760 by 1065 mm with 200 by 100 mm</MET><ENG> 30 by 42 inches 
with 8 by 4 inch</ENG> title block similar to contract drawings.  These drawings shall be submitted 
within 2 weeks after the final acceptance test of the system.  At least one set of as-built 
(marked-up) drawings shall be provided at the time of, or prior to the final acceptance test.</ITM><BRK/>
<BRK/>
<ITM>  Submit the installer’s training history for the employees involved with this contract.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5   ADDITIONAL SUBMITTAL REQUIREMENTS</TTL><BRK/>
<BRK/>
<SPT><TTL>1.5.1   <SUB>Battery Power Calculations</SUB></TTL><BRK/>
<BRK/>
<TXT>Verify that battery capacity exceeds supervisory and alarm power requirements.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Provide complete battery calculations for both the alarm and supervisory power requirements.  
Ampere hour requirements for each system component shall be submitted with the calculations.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Provide data on each circuit to indicate that there is at least 25 percent spare capacity 
for notification appliances, [25] [50] percent spare capacity for initiating devices.  Annotate 
data for each circuit on the drawings.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[c.  Provide data to indicate that the amplifiers have sufficient capacity to simultaneously 
drive fire alarm speakers at their 1/2 watt tap plus 50 percent spare capacity.  Annotate data 
for each circuit on the drawings.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[d.  Provide a detailed description of the final acceptance testing procedures (including equipment 
nencessary for testing smoke detectors using real smoke).]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5.2   <SUB>Qualifications of Installer</SUB></TTL><BRK/>
<BRK/>
<TXT>[Design shall be by a National Institute for Certification in Engineering Technologies (NICET) Level III or Level 
IV Technician.]  Installer shall have an office, which has been in existence for at least 3 years[, within a 
[_____] mile radius of the job site].  Installation shall be accomplished by an electrical contractor with a 
minimum of 5 years' experience in the installation of fire alarm systems.  The Contracting Officer may reject 
any proposed installer who cannot show evidence of such qualifications.  The services of a technician provided 
by the control equipment manufacturer shall be provided to supervise installation, adjustments, and tests of 
the system.  The Contractor shall furnish evidence that the fire alarm equipment supplier has an experienced 
and effective service organization which carries a stock of repair parts for the system to be furnished.  The 
Contractor shall guarantee labor, materials, and equipment provided under this contract against defects for a 
period of one year after the date of final acceptance of this work by the Contracting Officer and the receipt 
of as-built drawings and schematics of all equipment.  Prior to installation, submit data for approval by the 
[[_____] Division] [EFA [_____]], Naval Facilities Engineering Command, Fire Protection Engineer, showing that 
the Contractor has successfully installed addressable, analog intelligent interior fire alarm systems of the 
same type as specified herein, or that the Contractor has a firm contractual agreement with a subcontractor having 
such required experience.  Include the names and locations of at least three installations where the Contractor, 
or the subcontractor referred to above, has installed such systems.  Indicate the type and design of each system 
and certify that each system has performed satisfactorily in the manner intended for a period of not less than 
18 months.  Submit names and phone numbers of points of contact at each site.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5.3   <SUB>Record Drawing Software</SUB></TTL><BRK/>
<BRK/>
<TXT>Furnish one set of floppy diskettes containing CAD based drawings in DXF format of as-built drawings and schematics.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.6   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<TXT>Equipment and devices shall be compatible and operable with existing station fire alarm system and shall not 
impair reliability or operational functions of existing supervising station fire alarm system.  [Existing supervising 
station fire alarm system is [_____].]</TXT><BRK/>
<BRK/>
<SPT><TTL>1.6.1   Regulatory Requirements</TTL><BRK/>
<BRK/>
<TXT>Devices and equipment for fire alarm service shall be listed by <RID>UL Fire Prot Dir</RID> or approved by <RID>FM P7825</RID>.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.6.1.1   Requirements for Fire Protection Service</TTL><BRK/>
<BRK/>
<TXT>Equipment and material shall have been tested by UL and listed in <RID>UL Fire Prot Dir</RID> or approved by FM and listed 
in <RID>FM P7825</RID>.  Where the terms "listed" or "approved" appear in this specification, they shall mean listed in <RID>
UL Fire Prot Dir</RID> or <RID>FM P7825</RID>.  The omission of these terms under the description of any item of equipment described 
shall not be construed as waiving this requirement.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6.1.2   Testing Services or Laboratories</TTL><BRK/>
<BRK/>
<TXT> Fire alarm and fire detection equipment shall be constructed in accordance with <RID>UL Fire Prot Dir</RID>, <RID>UL Electrical Constructn</RID>
, or <RID>FM P7825</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.6.2   Standard Products</TTL><BRK/>
<BRK/>
<TXT>Provide materials, equipment, and devices that have been tested by a nationally recognized testing laboratory, 
such as UL or FM, and listed or approved for fire protection service when so required by <RID>NFPA 72</RID> or this specification.  
Select material from one manufacturer, where possible, and not a combination of manufacturers, for any particular 
classification of materials.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6.3   Modification of References</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  In NFPA publications referred to herein, consider advisory provisions to be mandatory, as 
though the word "shall" had been substituted for "should" wherever it appears; interpret reference 
to "authority having jurisdiction" to mean the [[_____] Division] [EFA [_____]], Naval Facilities 
Engineering Command, Fire Protection Engineer.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b. The recommended practices stated in the manufacturer's literature or documentation shall 
be considered as mandatory requirements.]</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.7   DELIVERY, STORAGE, AND HANDLING</TTL><BRK/>
<BRK/>
<TXT>Protect equipment delivered and placed in storage from the weather, humidity, and temperature variation, dirt 
and dust, and other contaminants.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.8   SPARE PARTS AND TOOLS</TTL><BRK/>
<BRK/>
<SPT><TTL>1.8.1   Interchangeable Parts</TTL><BRK/>
<BRK/>
<TXT>Spare parts furnished shall be directly interchangeable with the corresponding components of the installed system.  
Spare parts shall be suitably packaged and identified by nameplate, tagging, or stamping.  Spare parts shall 
be delivered to the Contracting Officer at the time of the final acceptance testing.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.8.2   Spare Parts</TTL><BRK/>
<BRK/>
<TXT>Furnish the following spare parts and accessories:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  [4][_____]audiovisual devices of each type installed</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  [4] [_____] fuses for each fused circuit</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  [1] [_____] electromagnetic door holders</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  [1] [_____] manual stations</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  [9] [_____] spare reams of paper for the system printer, plus sufficient paper for fire 
alarm acceptance tests</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  [2] [_____] smoke sensors and base of each type installed</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  [2] [_____] heat sensors and base of each type installed</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  [3] [_____] spare printer ribbons</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">i.  [3] [_____] test magnets/devices for each type of sensors installed</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">j.  [3] [_____] break rods for manual stations</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.8.3   Parts List</TTL><BRK/>
<BRK/>
<TXT>Furnish a list, in duplicate, of all other parts and accessories which the manufacturer of the system recommends 
to be stocked for maintenance.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.9   KEYS</TTL><BRK/>
<BRK/>
<TXT>Keys and locks for equipment shall be identical.  Provide not less than six keys of each type required.  Keys 
shall be CAT [60] [_____].</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT>[<TTL>2.1   EXISTING FIRE ALARM EQUIPMENT</TTL><BRK/>
<BRK/>
<TXT>Existing fire alarm equipment shall be maintained fully operational until the new equipment has been tested and 
accepted by the Contracting Officer.  As new equipment is installed, it shall be labeled "NOT IN SERVICE" until 
the new equipment is accepted.  Once the new system is completed, tested, and accepted by the Government, it 
shall be placed in service and connected to the station fire alarm system.  New equipment shall have tags removed 
and the existing equipment shall be tagged "NOT IN SERVICE" until removed from the building.</TXT><BRK/>
<BRK/>
<SPT>[<TTL>2.1.1   Equipment Removal</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Contact the Contracting Officer, Base Fire Prevention Office, and/or 
Base Maintenance Personnel to determine what action is appropriate for the salvaging 
of existing fire alarm equipment.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>After acceptance of the new system by the Contracting Officer, existing equipment not connected to the new system 
shall be removed, unused exposed conduit shall be removed, and damaged surfaces shall be restored.  The material 
shall be removed from the site and disposed of by the Contractor.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.2   Repair Service/Replacement Parts</TTL><BRK/>
<BRK/>
<TXT>Repair services and replacement parts for the system furnished under this contract shall be be available for 
a period of 10 years after the date of final acceptance of this work by the Contracting Officer.  On-site service 
during the guarantee period shall be provided within 24 hours after notification.  All repairs shall be completed 
within 48 hours after notification.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.1.3   Other Divisions To Be Coordinated With</TTL><BRK/>
<BRK/>
<TXT>Refer to the following sections for related work and coordination:<BRK/>
<BRK/>
[Section <SRF>21 13 13.00 20</SRF> WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION] [Section <SRF>21 30 00</SRF> FIRE PUMPS] [Section 
<SRF>21 23 00.00 20</SRF> WET DRY CHEMICAL FIRE EXTINGUISHING SYSTEMS] [Section <SRF>21 13 16.00 20</SRF> DRY PIPE FIRE SUPPRESSION 
SPRINKLERS] [Section <SRF>21 13 19.00 20</SRF> DELUGE PREACTION FIRE SUPPRESSION SPRINKLERS] [Section <SRF>23 00 00</SRF> AIR SUPPLY, 
DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS].<BRK/>
<BRK/>
[Section <SRF>08 71 00</SRF> DOOR HARDWARE for [door release] [door unlocking] and additional work related to finish hardware.]<BRK/>
<BRK/>
[Section[s] [<SRF>14 21 00.00 20</SRF> ELECTRIC TRACTION ELEVATORS][<SRF>14 21 13</SRF> ELECTRIC TRACTION FREIGHT ELEVATORS][
<SRF>14 21 23</SRF> ELECTRIC TRACTION PASSENGER ELEVATORS] [<SRF>14 24 00</SRF> HYDRAULIC ELEVATORS] for additional work related to elevators.]<BRK/>
<BRK/>
[Section <SRF>07 84 00</SRF> FIRESTOPPING for additional work related to firestopping.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.4   Manufacturer Qualifications</TTL><BRK/>
<BRK/>
<TXT>Components shall be of current design and shall be in regular and recurrent production at the time of installation.  
Provide design, materials, and devices for a protected premises fire alarm system, complete, conforming to <RID>NFPA 72</RID>
, except as otherwise or additionally specified herein.</TXT><BRK/>
<BRK/></SPT>
]</SPT><SPT><TTL>2.2   <SUB>INTERIOR FIRE ALARM SYSTEM</SUB> DESIGN</TTL><BRK/>
<BRK/>
<SPT><TTL>2.2.1   Definitions</TTL><BRK/>
<BRK/>
<TXT>Wherever mentioned in this specification or on the drawings, the equipment, devices, and functions shall be defined 
as follows:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Analog/Addressable System:  A system in which multiple signals are transmitted via the same 
conduction path to a remote fire alarm control unit and fire alarm control panel, decoded and 
separated so that each signal will initiate the specified response.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Hard Wired System:  A system in which alarm and supervisory initiating devices are directly 
connected, through individual dedicated conductors, to a central control panel without the use 
of analog/addressable circuits or devices.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Interface Device:  An addressable device which interconnects hard wired systems or devices 
to an analog/addressable system.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Fire Alarm Control Unit:  A control panel, remote from the fire alarm control panel, that 
receives inputs from automatic and manual fire alarm devices; may supply power to detection 
devices and interface devices; may provide transfer of power to the notification appliances; 
may provide transfer of condition to relays or devices connected to the control unit; and reports 
to and receives signals from the fire alarm control panel.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Fire Alarm Control Panel (FACP):  A master control panel having the features of a fire alarm 
control unit and to which fire alarm control units are interconnected.  The panel has central 
processing, memory, input and output terminals, [video display units (VDUs),] [and] [printers].</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Terminal Cabinet:  A steel cabinet with locking, hinge-mounted door in which terminal strips 
are securely mounted.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.2   System Operation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The supply and return portions of the Style 6 loop shall not be located 
in the same room or shaft to ensure system reliability.  They shall be separated 
by a sufficient distance so that a single fire will not involve both the supply 
and return portions of the loop.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The system shall be a complete, supervised, noncoded, analog/addressable fire alarm system conforming to <RID>NFPA 72</RID>
.  The system shall have an interconnected riser loop or network having Style [6] [_____] supervision that shall 
not be located in the same room or shaft.  The return portion of the loop shall be remote from the supply portion 
of the loop.  [Where the building has two stairs for egress from floors above grade, a single impairment cannot 
adversely affect more than one floor.  Where three or more stairs are provided for egress from floors above grade, 
a single impairment cannot adversely affect more than 1/2 of any floor.]  [Any single impairment of the system 
shall not affect the system on more than [one] [one-half] of any floor.]  The system shall operate in the alarm 
mode upon actuation of any alarm initiating device.  The system shall remain in the alarm mode until initiating 
device(s) are reset and the fire alarm control panel is manually reset and restored to normal.  The system shall 
provide the following functions and operating features:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  The FACP and fire alarm control units, if used, shall provide power, annunciation, supervision, 
and control for the system.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Provide Style [B] [_____] initiating device circuits [for conductor lengths of<MET>3050 mm</MET><ENG> 10 
feet</ENG> or less].</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Provide Style [4] [_____] signaling line circuits for each floor.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Provide Style [6] [_____] signaling line circuits for the network.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.   Provide Style [Z] [_____] notification appliance circuits.  The visual alarm notification 
appliances shall have the flash rates synchronized.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Provide electrical supervision of the primary power (AC) supply, presence of the battery, 
battery voltage, and placement of system modules within the control panel.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Provide an audible and visual trouble signal to activate upon a single break or open condition, 
or ground fault.  The trouble signal shall also operate upon loss of primary power (AC) supply, 
absence of a battery supply, low battery voltage, or removal of alarm or supervisory panel modules.  
Provide a trouble alarm silence feature which shall silence the audible trouble signal, without 
affecting the visual indicator.  After the system returns to normal operating conditions, the 
trouble signal shall again sound until the trouble is acknowledged.  A smoke sensor in the process 
of being verified for the actual presence of smoke shall not initiate a trouble condition.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  Provide a notification appliance silencing switch which, when activated, will silence the 
audible signal appliance, but will not affect the visual alarm indicator, the liquid crystal 
display, or the automatic notification of the [fire department] [central station service].  
This switch shall be overridden upon activation of a subsequent alarm.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">i.  Provide alarm verification capability for smoke sensors.  Alarm verification shall initially 
be set for [30] [_____] seconds.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">j.  Provide program capability via switches in a locked portion of the FACP to bypass the automatic 
notification appliance circuits, [fire reporting system] [air handler shutdown] [smoke control 
operation] [elevator recall] [door release] [door unlocking] features.  Operation of this programming 
shall indicate this action on the FACP display and printer output.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">k.  Alarm, supervisory, and/or trouble signals shall be automatically transmitted to the [fire 
department] [a UL listed central station].</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">l.  Alarm functions shall override trouble or supervisory functions.  Supervisory functions 
shall override trouble functions.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">m.  The system shall be capable of being programmed from the panel’s keyboard.  Programmed information 
shall be stored in non-volatile memory.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">n.  The system shall be capable of operating, supervising, and/or monitoring both addressable 
and non-addressable alarm and supervisory devices.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">o.  There shall be no limit, other than maximum system capacity, as to the number of addressable 
devices which may be in alarm simultaneously.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">p.  Where the fire alarm system is responsible for initiating an action in another emergency 
control device or system, such as [an HVAC system] [an atrium exhaust system] [a smoke control 
system] [an elevator system], the addressable fire alarm relay shall be within<MET>915 mm</MET><ENG> 3 feet</ENG> 
of the emergency control device.</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following shall be shown in matrix format either in this specification 
or on the drawings.  If a matrix is provided, omit subparagraphs q, r, and s.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">q.  An alarm signal shall automatically initiate the following functions:</ITM><BRK/>
<BRK/>
<ITM>(1)  Transmission of an alarm signal to [the fire department] [a UL listed central station].</ITM><BRK/>
<BRK/>
<ITM>(2)  Visual indication of the device operated on the fire alarm control panel (FACP), [video 
display unit (VDU),] [and on the graphic annunciator].  [Indication on the graphic annunciator 
shall be by floor, zone or circuit, and type of device.]</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where a high-rise building in which the fire alarm system is being provided 
is fully sprinkler protected, the fire alarm notification appliances should 
operate only on the fire floor, (one/two) floor(s) above, and floor below.  
Where the building has some fire protection or life safety concerns or the building 
can be evacuated quickly, the fire alarm system should operate all notification 
appliances in the building upon a fire alarm.  In those buildings designed for 
total evacuation due to fire protection or life safety concerns, design the 
system so that it can easily be modified when the fire protection or life safety 
improvements have been made to the building.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM>(3)  [Continuous actuation of all alarm notification appliances, except those in stairs or in 
elevator cabs.]  [Continuous actuation of alarm notification appliances on the floor of fire 
alarm origin, the floor above the floor of fire alarm origin, and the floor below the floor 
of fire alarm origin, except those in stairs or in elevator cabs.]</ITM><BRK/>
<BRK/>
<ITM>[(4)  Recording of the event via the system printer.]</ITM><BRK/>
<BRK/>
<ITM>[(5)  Release of doors held open by electromagnetic devices.]</ITM><BRK/>
<BRK/>
<ITM>[(6)  Operation of the [smoke control system] [atrium exhaust system].]</ITM><BRK/>
<BRK/>
<ITM>[(7)  Release of power to electric locks on doors which are part of the means of egress.]</ITM><BRK/>
<BRK/>
<ITM>[(8)  Operation of a smoke sensor in an elevator lobby or other location associated with the 
automatic recall of elevators, shall recall the elevators in addition to other requirements 
of this paragraph.]</ITM><BRK/>
<BRK/>
<ITM>[(9)  Operation of a duct smoke sensor shall shut down the appropriate air handler in accordance 
with <RID>NFPA 90A</RID> in addition to other requirements of this paragraph.]</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use this paragraph only where a sensor or detection system is to release 
a special fire extinguishing system.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM>[(10)  Operation of [_____] shall release the [_____] fire extinguishing system after a [_____] 
second time delay.]</ITM><BRK/>
<BRK/>
<ITM>[(11)  Operation of a sprinkler waterflow switch serving an elevator machinery room shall operate 
shunt trip circuit breaker(s) to shut down power to the elevators in accordance with <RID>ASME A17.1</RID>
.]</ITM><BRK/>
<BRK/>
<ITM>[(12)  Operation of an interface, which operates vibrating pagers worn by hearing-impaired occupants.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">r.  A supervisory signal shall automatically initiate the following functions:</ITM><BRK/>
<BRK/>
<ITM>(1)  Visual indication of the device operated on the FACP, [VDU,] and on the graphic annunciator, 
and sound the audible alarm at the respective panel.</ITM><BRK/>
<BRK/>
<ITM>(2)  Transmission of a supervisory signal to [the fire department] [a UL listed central station].</ITM><BRK/>
<BRK/>
<ITM>[(3)  Recording of the event via the system printer.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">s.  A trouble condition shall automatically initiate the following functions:</ITM><BRK/>
<BRK/>
<ITM>(1)  Visual indication of the system trouble on the FACP, [VDU,] and on the graphic annunciator, 
and sound the audible alarm at the respective panel.</ITM><BRK/>
<BRK/>
<ITM>(2)  Transmission of a trouble signal to [the fire department] [a UL listed central station].</ITM><BRK/>
<BRK/>
<ITM>[(3)  Recording of the event via the system printer.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">t.  The maximum permissible elapsed time between the actuation of an initiating device and its 
indication at the FACP shall be 15 seconds.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">u.  The maximum elapsed time between the occurrence of the trouble condition and its indication 
at the FACP shall not exceed 200 seconds.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.3   System Monitoring</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Valves:  Each valve affecting the proper operation of a fire protection system, including 
automatic sprinkler control valves, standpipe control valves, sprinkler service entrance valve, 
valves at fire pumps, and valves at backflow preventers, whether supplied under this contract 
or existing, shall be electrically monitored to ensure its proper position.  Each tamper switch 
shall be provided with a separate address[, unless they are within the same room, then a maximum 
of [5] [_____] can use the same address].</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Independent Fire Detection System:  Each existing independent smoke detection subsystem, 
and kitchen fire extinguishing system shall be monitored both for the presence of an alarm condition 
and for a trouble condition.  Each monitored condition shall be provided with a separate address.]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.4   Overvoltage and Surge Protection</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Signaling Line Circuit Surge Protection:  For systems having circuits located outdoors, 
communications equipment shall be protected against surges induced on any signaling line circuit 
and shall comply with the applicable requirements of <RID>IEEE C62.41.1</RID> and <RID>IEEE C62.41.2</RID>.  Cables 
and conductors, which serve as communications links, shall have surge protection circuits installed 
at each end that meet the following waveform[s]:</ITM><BRK/>
<BRK/>
<ITM>(1)  A 10 microsecond by 1000 microsecond waveform with a peak voltage of 1500 volts and a peak 
current of 60 amperes.</ITM><BRK/>
<BRK/>
<ITM>[(2)  An 8 microsecond by 20 microsecond waveform with a peak voltage of 1000 volts and a peak 
current of 500 amperes. Protection shall be provided at the equipment.  Additional triple electrode 
gas surge protectors, rated for the application, shall be installed on each wireline circuit 
within<MET> 915 mm</MET><ENG> 3 feet</ENG> of the building cable entrance.  Fuses shall not be used for surge protection.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Sensor Wiring Surge Protection:  Digital and analog inputs and outputs shall be protected 
against surges induced by sensor wiring installed outdoors and as shown.  The inputs and outputs 
shall be tested with the following waveform[s]:</ITM><BRK/>
<BRK/>
<ITM>(1)  A 10 by 1000 microsecond waveform with a peak voltage of 1500 volts and a peak current 
of 60 amperes.</ITM><BRK/>
<BRK/>
<ITM>[(2)  An 8 by 20 microsecond waveform with a peak voltage of 1000 volts and a peak current of 
500 amperes.  Fuses shall not be used for surge protection.]]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.5   <SUB>Addressable Interface Devices</SUB></TTL><BRK/>
<BRK/>
<TXT>The addressable interface (AI) device shall provide an addressable input interface to the FACP for monitoring 
normally open or normally closed contact devices such as waterflow switches, valve supervisory switches, fire 
pump monitoring, independent smoke detection systems, relays for output function actuation, etc.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.2.6   <SUB>Smoke Sensors</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide smoke sensors only in spaces where they are specifically required 
by MIL-HDBK-1008.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.2.6.1   Photoelectric Smoke Sensors</TTL><BRK/>
<BRK/>
<TXT>Provide addressable photoelectric smoke sensors as follows:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Provide analog/addressable photoelectric smoke sensors utilizing the photoelectric light 
scattering principle for operation in accordance with <RID>UL 268</RID>.  Smoke sensors shall be listed 
for use with the fire alarm control panel.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Provide self-restoring type sensors which do not require any readjustment after actuation 
at the FACP to restore them to normal operation.  Sensors shall be UL listed as smoke-automatic 
fire sensors.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Components shall be rust and corrosion resistant.  Vibration shall have no effect on the 
sensor's operation.  Protect the detection chamber with a fine mesh metallic screen which prevents 
the entrance of insects or airborne materials.  The screen shall not inhibit the movement of 
smoke particles into the chamber.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Provide twist lock bases for the sensors.  The sensors shall maintain contact with their 
bases without the use of springs.  Provide companion mounting base with screw terminals for 
each conductor.  Terminate field wiring on the screw terminals.  The sensor shall have a visual 
indicator to show actuation.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  The sensor address shall identify the particular unit, its location within the system, and 
its sensitivity setting.  Sensors shall be of the low voltage type rated for use on a 24 VDC 
system.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  An operator at the control panel, having a proper access level, shall have the capability 
to manually access the following information for each initiating device.</ITM><BRK/>
<BRK/>
<ITM>(1)  Primary status</ITM><BRK/>
<ITM>(2)  Device type</ITM><BRK/>
<ITM>(3)  Present average value</ITM><BRK/>
<ITM>(4)  Present sensitivity selected</ITM><BRK/>
<ITM>(5)  Sensor range (normal, dirty, etc.)</ITM><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.2.6.2   Ionization Type Smoke Sensors</TTL><BRK/>
<BRK/>
<TXT>Provide addressable ionization type smoke sensors as follows:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Provide analog smoke sensors which operate on the ionization principle and are actuated 
by the presence of visible or invisible products of combustion.  Smoke sensors shall be listed 
for use with the fire alarm control panel.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Provide self-restoring type sensors which do not require any readjustment after actuation 
at the FACP to restore them to normal operation.  Sensors shall be UL listed as smoke-automatic 
fire sensors.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Components shall be rust and corrosion resistant.  Vibration shall have no effect on the 
sensor's operation.  Protect the detection chamber with a fine mesh metallic screen which prevents 
the entrance of insects or airborne materials.  The screen shall not inhibit the movement of 
smoke particles into the chamber.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Provide twist lock bases for the sensors.  The sensors shall maintain contact with their 
bases without the use of springs.  Provide companion mounting base with screw terminals for 
each conductor.  Terminate field wiring on the screw terminals.  The sensor shall have a visual 
indicator to show actuation.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[e.  The sensor address shall identify the particular unit, its location within the system, 
and its sensitivity setting.  Sensors shall be of the low voltage type rated for use on a 24 
VDC system.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  An operator at the control panel, having a proper access level, shall have the capability 
to manually access the following information for each initiating device.</ITM><BRK/>
<BRK/>
<ITM>(1)  Primary status</ITM><BRK/>
<ITM>(2)  Device type</ITM><BRK/>
<ITM>(3)  Present average value</ITM><BRK/>
<ITM>(4)  Present sensitivity selected</ITM><BRK/>
<ITM>(5)  Sensor range (normal, dirty, etc.)</ITM><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.2.6.3   Duct Smoke Sensors</TTL><BRK/>
<BRK/>
<TXT>Duct smoke sensors shall be analog/addressable photoelectric type as described in paragraph entitled "Photoelectric 
Smoke Sensors," and shall be provided in ductwork in accordance with <RID>NFPA 90A</RID> and in accordance with manufacturer’s 
recommendations.</TXT><BRK/>
<BRK/></SPT>
]<SPT><TTL>2.2.6.4   Smoke Sensor Testing</TTL><BRK/>
<BRK/>
<TXT>Smoke sensors shall be tested in accordance with manufacturer's recommended calibrated test method.  Submit <SUB>smoke 
sensor testing procedures</SUB> for approval.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2.7   <SUB>Thermal Sensors</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Heat detectors provided in elevator machinery rooms are strictly for 
the warning sign in the elevator cab and shall not be connected to the FACP.  
Coordinate with Section 14 20 00 and/or Section 14 24 00.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">a.  Thermal sensors shall be combination rate-of-rise/fixed temperature sensing.  The alarm 
condition shall be determined by comparing sensor valve with the stored values.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  A moving average of the sensor’s heat sensing value to automatically compensate for conditions 
that could affect detection operations.  System shall automatically maintain a constant heat 
sensing sensitivity from each sensor by compensating for environmental factors.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Automatic self-test routines shall be performed on each sensor which will functionally check 
sensor sensitivity electronics and ensure the accuracy of the value being transmitted.  Any 
sensor that fails this test shall indicate a trouble condition with the sensor location at the 
control panel.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  An operator at the control panel, having the proper access level, shall have the capability 
to manually access the following information for each heat sensor:</ITM><BRK/>
<BRK/>
<ITM>(1)  Primary status</ITM><BRK/>
<BRK/>
<ITM>(2)  Device type</ITM><BRK/>
<BRK/>
<ITM>(3)  Present average value</ITM><BRK/>
<BRK/>
<ITM>(4)  Sensor range ([_____])</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  An operator at the control panel, having the proper access level, shall have the capability 
to manually control the following information for each heat sensor:</ITM><BRK/>
<BRK/>
<ITM>(1)  Alarm detection sensitivity values</ITM><BRK/>
<BRK/>
<ITM>(2)  Enable or disable the point/device</ITM><BRK/>
<BRK/>
<ITM>(3)  Control sensor’s relay driver output</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.8   Electric Power</TTL><BRK/>
<BRK/>
<SPT><TTL>2.2.8.1   Primary Power</TTL><BRK/>
<BRK/>
<TXT>Provide primary power for the FACP from the normal AC service to the building [where shown on the drawings] [or] 
[_____].  Power shall be 120 VAC service, transformed through a two-winding, isolation type transformer and rectified 
to low voltage DC for operation of circuits and devices.  Make the service connection for the FACP at the [main 
service switchgear] [emergency distribution panel where shown] [a main distribution panel where shown].  Provide 
appropriate equipment to protect against power surges.  Provide a separate NEMA 1 "general purpose enclosure" 
for the circuit breaker.  The circuit breaker enclosure shall be painted red, marked "FIRE ALARM SYSTEM," provided 
with a red and white engraved plastic sign permanently affixed to the face of the switch, and provided with a 
lockable handle or cover.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.2.8.2   Generator</TTL><BRK/>
<BRK/>
<TXT>Where any emergency generator provides a standby power supply for life safety system circuits, provide a connection 
from one of the circuits for the fire alarm system.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>2.2.9   Emergency Power Supply</TTL><BRK/>
<BRK/>
<TXT>Provide for system operation in the event of primary power source failure.  Transfer from normal to auxiliary 
(secondary) power or restoration from auxiliary to normal power shall be automatic and shall not cause transmission 
of a false alarm.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.9.1   <SUB>Batteries</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide sealed, maintenance-free, [lead-calcium] [sealed lead acid] [gel cell] [nickel-cadmium] [lithium] batteries 
as the source for emergency power to the FACP.  Batteries shall contain suspended electrolyte.  The battery system 
shall be maintained in a fully charged condition by means of a solid state battery charger.  Provide an automatic 
transfer switch to transfer the load to the batteries in the event of the failure of primary power.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.9.2   Capacity</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use 48 hours if the building has no generator providing standby power 
to the fire alarm system.  If such a generator exists, use 4 hours.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide the batteries with sufficient capacity to operate the system under supervisory and trouble conditions, 
including audible trouble signal devices for [48] [_____] hours and audible and visual signal devices under alarm 
conditions for an additional [10] [_____] minutes.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.9.3   <SUB>Battery Chargers</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide a solid state, fully automatic, variable charging rate battery charger.  The charger shall be capable 
of providing 150 percent of the connected system load and shall maintain the batteries at full charge.  In the 
event the batteries are fully discharged, the charger shall recharge the batteries back to 95 percent of full 
charge within 48 hours.  Provide pilot light to indicate when batteries are manually placed on a high rate of 
charge as part of the unit assembly if a high rate switch is provided.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2.10   System Field Wiring</TTL><BRK/>
<BRK/>
<SPT><TTL>2.2.10.1   Wiring Within Cabinets, Enclosures, Boxes, Junction Boxes, and Fittings</TTL><BRK/>
<BRK/>
<TXT>Provide wiring installed in a neat and workmanlike manner and installed parallel with or at right angles to the 
sides and back of any box, enclosure, or cabinet.  Conductors which are terminated, spliced, or otherwise interrupted 
in any enclosure, cabinet, mounting, or junction box shall be connected to terminal blocks.  Mark each terminal 
in accordance with the wiring diagrams of the system.  Make connections with approved pressure type terminal 
blocks, which are securely mounted.  The use of wire nuts or similar devices shall be prohibited.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.10.2   <SUB>Terminal Cabinets</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide terminal cabinets on each floor where the fire alarm system supply 
riser is located and where the fire alarm return riser is located.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide a terminal cabinet at the base of any circuit riser, on each floor at each riser, and where indicated 
on the drawings.  Terminal size shall be appropriate for the size of the wiring to be connected.  Conductor terminations 
shall be labeled and a drawing containing conductors, their labels, their circuits, and their interconnection 
shall be permanently mounted in the terminal cabinet.  Minimum size is <MET>200 mm by 200 mm</MET> <ENG>8 inches high by 8 inches</ENG>
.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.10.3   Alarm <SUB>Wiring</SUB></TTL><BRK/>
<BRK/>
<TXT>Signaling line circuits and initiating device circuit field wiring shall be copper, No. [16] [18] [_____] AWG 
size conductors at a minimum.  Notification appliance circuit conductors, that contain audible alarm devices, 
[other than speakers,] shall be solid copper No. 14 AWG size conductors at a minimum.  [Speaker circuits shall 
be copper No. [16] [_____] AWG size conductors at a minimum.]  [Firefighter telephone circuits shall be No. [16] 
[18] [_____] AWG size conductors as a minimum.]  Wire size shall be sufficient to prevent voltage drop problems.  
Circuits operating at 24 VDC shall not operate at less than 21.6 volts.  Circuits operating at any other voltage 
shall not have a voltage drop exceeding 10 percent of nominal voltage.  Power wiring, operating at 120 VAC minimum, 
shall be No. 12 AWG solid copper having similar insulation.  Provide all wiring in rigid metal conduit or intermediate 
metal conduit.  Electrical metallic tubing conduit is acceptable in dry locations not enclosed in concrete or 
where not subject to mechanical damage.  Conceal conduit in finished areas of new construction and wherever practicable 
in existing construction.  The use of flexible conduit not exceeding a <MET>1830 mm</MET><ENG> [6] [_____] foot</ENG> length shall 
be permitted in initiating device circuits.  Run conduit or tubing concealed unless specifically shown otherwise 
on the drawings.  Shielded wiring shall be utilized where recommended by the manufacturer.  For shielded wiring, 
the shield shall be grounded at only one point, which shall be in or adjacent to the FACP.  T-taps are permitted 
in Style 4 circuits with interconnections occurring on terminal strips.  Color coding is required for circuits 
and shall be maintained throughout the circuit.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.10.4   Conductor Terminations</TTL><BRK/>
<BRK/>
<TXT>Labeling of conductors at terminal blocks in terminal cabinets, FACP, and remote fire alarm control units shall 
be provided at each conductor connection.  Each conductor or cable shall have a shrink-wrap label to provide 
a unique and specific designation.  Each terminal cabinet, FACP, and fire alarm control unit shall contain a 
laminated drawing which indicates each conductor, its label, circuit, and terminal.  The laminated drawing shall 
be neat, using 12 point lettering minimum size, and mounted within each cabinet, panel, or unit so that it does 
not interfere with the wiring or terminals.  Maintain existing color code scheme where connecting to existing 
equipment.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.10.5   Wiring to Station Telegraphic Fire Alarm Circuit</TTL><BRK/>
<BRK/>
<TXT>Wiring from the master fire alarm box to the station telegraphic fire alarm circuit shall be a two-conductor 
No. [12] [10] [_____] AWG type UF cable [in conduit].</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2.11   <SUB>Fire Alarm Control Panel (FACP)</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For high-rise buildings, locate the FACP in an emergency control center 
having one door opening to the outside.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide a complete control panel fully enclosed in a lockable steel enclosure as specified herein.  Operations 
required for testing or for normal care and maintenance of the systems shall be performed from the front of the 
enclosure.  If more than a single unit is required at a location to form a complete control panel, the unit enclosures 
shall match exactly.  [If more than a single unit is required, and is located in the lobby/entrance, notify the 
[_____ Division] [EFA _____] Fire Protection Engineer, via the Contracting Officer, prior to installing the equipment.]  
Each control unit shall provide power, supervision, control, and logic for the entire system, utilizing solid 
state, modular components, internally mounted and arranged for easy access.  Each control unit shall be suitable 
for operation on a 120 volt, 60 hertz, normal building power supply.  Provide each panel with supervisory functions 
for power failure, internal component placement, and operation.  Visual indication of alarm, supervisory, or 
trouble initiation on the fire alarm control panel shall be by liquid crystal display or similar means with a 
minimum of 80 characters of which at least 32 are field changeable.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.11.1   Cabinet</TTL><BRK/>
<BRK/>
<TXT>Install control panel components in cabinets large enough to accommodate all components and also to allow ample 
gutter space for interconnection of panels as well as field wiring.  The enclosure shall be identified by an 
engraved laminated phenolic resin nameplate.  Lettering on the nameplate shall say "Fire Alarm Control Panel" 
and shall not be less than one inch high.  Provide prominent rigid plastic or metal identification plates for 
lamps, circuits, meters, fuses, and switches.  The cabinet shall be provided in a sturdy steel housing, complete 
with back box, hinged steel door with cylinder lock, and surface mounting provisions.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.11.2   Control Modules</TTL><BRK/>
<BRK/>
<TXT>Provide power and control modules to perform all functions of the FACP.  Provide audible signals to indicate 
any alarm, supervisory, or trouble condition.  The alarm signals shall be different from the trouble signal.  
Connect circuit conductors entering or leaving the panel to screw-type terminals with each terminal marked for 
identification.  Locate diodes and relays, if any, on screw terminals in the FACP.  Circuits operating at 24 
VDC shall not operate at less than 21.6 volts.  Circuits operating at any other voltage shall not have a voltage 
drop exceeding 10 percent of nominal voltage.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.11.3   Silencing Switches</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Alarm Silencing Switch:  Provide an alarm silencing switch at the FACP which shall silence 
the audible signal but not affect the visual alarm indicator.  This switch shall be overridden 
upon activation of a subsequent alarm.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Supervisory/Trouble Silencing Switch:  Provide supervisory and trouble silencing switch 
which shall silence the audible trouble and supervisory signal, but not extinguish the visual 
indicator.  This switch shall be overridden upon activation of a subsequent alarm, supervision, 
or trouble condition.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.11.4   Non-Interfering</TTL><BRK/>
<BRK/>
<TXT>Power and supervise each circuit such that a signal from one device does not prevent the receipt of signals from 
any other device.  Circuits shall be manually resettable by switch from the FACP after the initiating device 
or devices have been restored to normal.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.2.11.5   Fire Alarm Voice Message</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use the proper bracketed item depending upon whether the fire alarm system 
is to cause total evacuation upon an alarm.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>A fire alarm shall activate notification appliance circuits.  Textual audible appliances shall produce a slow 
whoop tone for three cycles followed by a voice message which is repeated until the control panel is reset or 
silenced.  Automatic messages shall be broadcast through speakers on appropriate floors, but not in stairs or 
elevator cabs.  The visual strobes and audible message shall automatically be broadcast on the floor of fire 
alarm origin, [the floor] [two floors] immediately above the floor of fire alarm origin, and the floor immediately 
below the floor of fire alarm origin.  A live voice message shall override the automatic audible output through 
use of a microphone input at the control panel.  When using the microphone, live messages shall be broadcast 
through speakers in stairs, in elevator cabs, and throughout a selected floor or floors.  The system shall be 
capable of operating all speakers at the same time.  The digitalized voice message shall consist of a non-volatile 
(EPROM) microprocessor based input to the amplifiers.  The microprocessor shall actively interrogate circuitry, 
field wiring, and digital coding necessary for the immediate and accurate rebroadcasting of the stored voice 
data into the appropriate amplifier input.  Loss of operating power, supervisory power, or any other malfunction 
which could render the digitalized voice module inoperative shall automatically cause the slow whoop tone to 
take over all functions assigned to the failed unit.  Messages shall utilize a [male] [female] voice and shall 
be as follows:</TXT><BRK/>
<BRK/>
<TXT>["May I have your attention, please.  May I have your attention, please.  A fire has been reported which may 
affect your floor.  Please walk to the nearest exit and evacuate the building." (Provide a [2] [_____] second 
pause.)  "May I have your attention, please...(repeat the message)."]</TXT><BRK/>
<BRK/>
<TXT>["May I have your attention please.  May I have your attention please.  A fire emergency has been reported in 
the building. Please leave the building by the nearest exit or exit stairway.  Do not use the elevators."  (Provide 
a [2] [_____] second pause.)  "May I have your attention please..(repeat the message)."]</TXT><BRK/>
<BRK/>
<TXT>[_____]</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.11.6   Fire Alarm Signal</TTL><BRK/>
<BRK/>
<TXT>A fire alarm shall activate notification appliances throughout the building.  Audible devices shall be fire alarm 
horns which produce a [three-pulse temporal pattern] [continuous slow whoop tone] [_____].  Visual devices shall 
be strobes operating in accordance with <RID>NFPA 72</RID>.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.2.11.7   Memory</TTL><BRK/>
<BRK/>
<TXT>Provide each control unit with non-volatile memory and logic for all functions.  The use of long life batteries, 
capacitors, or other age-dependent devices shall not be considered as equal to non-volatile processors, PROMS, 
or EPROMS.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.11.8   Field Programmability</TTL><BRK/>
<BRK/>
<TXT>Provide control units and control panels that are fully field programmable for control, initiation, notification, 
supervisory, and trouble functions of both input and output.  The system program configuration shall be menu 
driven.  System changes shall be password protected and shall be accomplished using personal computer based equipment.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.11.9   Input/Output Modifications</TTL><BRK/>
<BRK/>
<TXT>The FACP shall contain features which allow the bypassing of input devices from the system or the modification 
of system outputs.  These control features shall consist of a panel mounted keypad [and a keyboard].  Any bypass 
or modification to the system shall indicate a trouble condition on the FACP[, VDU] [and a printed output of 
the trouble condition].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.11.10   Resetting</TTL><BRK/>
<BRK/>
<TXT>Provide the necessary controls to prevent the resetting of any alarm, supervisory, or trouble signal while the 
alarm, supervisory or trouble condition on the system still exists.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.11.11   Instructions</TTL><BRK/>
<BRK/>
<TXT>Provide a typeset printed or typewritten instruction card mounted behind a Lexan plastic or glass cover in a 
stainless steel or aluminum frame.  [Install the instructions on the interior of the FACP.]  [Install the frame 
in a conspicuous location observable from the FACP.]  The card shall show those steps to be taken by an operator 
when a signal is received as well as the functional operation of the system under all conditions, normal, alarm, 
supervisory, and trouble.  The instructions shall be approved by the Contracting Officer before being posted.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.11.12   Walk Test</TTL><BRK/>
<BRK/>
<TXT>The FACP shall have a walk test feature.  When using this feature, operation of initiating devices shall result 
in limited system outputs, so that the notification appliances operate for only a few seconds and the event is 
indicated on the system printer, but no other outputs occur.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.11.13   History Logging</TTL><BRK/>
<BRK/>
<TXT>In addition to the required printer output, the control panel shall have the ability to store a minimum of 400 
events in a log.  These events shall be stored in a battery-protected memory and shall remain in the memory until 
the memory is downloaded or cleared manually.  Resetting of the control panel shall not clear the memory.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.11.14   RS-232-C Output</TTL><BRK/>
<BRK/>
<TXT>Each local control panel shall be capable of operating remote service type cathode ray tubes (CRTs), printers, 
and/or modems.  The output shall be paralleled ASCII from an EIA RS-232-C connection with a baud rate of 1200 
or 2400 to allow use of any commonly available CRT, printer, or modem.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2.12   <SUB>Remote Fire Alarm Control Units</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide complete remote control units fully enclosed in a lockable steel enclosure as specified herein.  Operations 
required for testing or for normal care and maintenance of the control units shall be performed from the front 
of the enclosure.  If more than a single unit is required at a location to form a complete control panel, the 
unit enclosures shall match exactly.  Each control unit shall provide power, supervision, control, and logic 
for its portion of the entire system, utilizing solid state, modular components, internally mounted and arranged 
for easy access.  Each control unit shall be suitable for operation on a 120 volt, 60 hertz, normal building 
power supply.  Provide each unit with supervisory functions for power failure, internal component placement, 
and operation.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.12.1   Cabinet</TTL><BRK/>
<BRK/>
<TXT>Install remote control unit components in cabinets large enough to accommodate components and also to allow ample 
gutter space for interconnection of units as well as field wiring.  The enclosure shall be identified by an engraved 
laminated phenolic resin nameplate.  Lettering on the nameplate shall be labeled "Remote Fire Alarm Control Unit" 
and shall not be less than one inch high.  Provide prominent rigid plastic or metal identification plates for 
lamps, circuits, meters, fuses, and switches.  The cabinet shall be provided in a sturdy steel housing, complete 
with back box, hinged steel door with cylinder lock, and surface mounting provisions.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.12.2   Control Modules</TTL><BRK/>
<BRK/>
<TXT>Provide power and control modules to perform all functions of the remote control unit.  Provide audible signals 
to indicate any alarm or trouble condition.  The alarm signals shall be different from the trouble signal.  Connect 
circuit conductors entering or leaving the panel to screw-type terminals with each terminal marked for identification.  
Locate diodes and relays, if any, on screw terminals in the remote control unit.  Circuits operating at 24 VDC 
shall not operate at less than 21.6 volts.  Circuits operating at any other voltage shall not have a voltage 
drop exceeding 10 percent of nominal voltage.  Circuits shall be arranged so that there is 25 percent spare capacity 
for any circuit.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.12.3   Silencing Switches</TTL><BRK/>
<BRK/>
<TXT>Provide an alarm silencing switch at the remote control unit which will silence the audible signal but not affect 
the visual alarm indicator.  This switch shall be overridden upon activation of a subsequent alarm.  Provide 
trouble and supervisory silencing switch which will silence the audible trouble and supervisory signal, but not 
extinguish the visual indicator.  This switch shall be overridden upon activation of a subsequent trouble or 
supervisory signal.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.12.4   Non-Interfering</TTL><BRK/>
<BRK/>
<TXT>Power and supervise each circuit such that a signal from one device does not prevent the receipt of signals from 
any other device.  Circuits shall be manually resettable by switch from the remote control unit after the initiating 
device or devices have been restored to normal.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.12.5   Memory</TTL><BRK/>
<BRK/>
<TXT>Provide each control unit with non-volatile memory and logic for all functions.  The use of long life batteries, 
capacitors, or other age-dependent devices shall not be considered as equal to non-volatile processors, PROMS, 
or EPROMS.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.12.6   Field Programmability</TTL><BRK/>
<BRK/>
<TXT>Provide control units that are fully field programmable for control, initiating, supervisory, and trouble functions 
of both input and output.  The system program configuration shall be menu driven.  System changes shall be password 
protected and shall be accomplished using personal computer based equipment.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.12.7   Input/Output Modifications</TTL><BRK/>
<BRK/>
<TXT>Each remote control unit shall contain features which allow the elimination of input devices from the system 
or the modification of system outputs.  Any such modifications shall indicate a trouble condition on the remote 
control unit, the FACP, and a printed output of the trouble condition.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.12.8   Resetting</TTL><BRK/>
<BRK/>
<TXT>Provide the necessary controls to prevent the resetting of any alarm, supervisory, or trouble signal while the 
alarm, supervisory, or trouble condition on the system still exists.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.12.9   Instructions</TTL><BRK/>
<BRK/>
<TXT>Provide a typeset printed or typewritten instruction card mounted behind a Lexan plastic or glass cover in a 
stainless steel or aluminum frame.  Install the frame in a conspicuous location observable from the remote fire 
alarm control unit.  [Install the frame in a conspicuous location observable from the remote fire alarm control 
unit.]  The card shall show those steps to be taken by an operator when a signal is received as well as the functional 
operation of the system under all conditions, normal, alarm, supervisory, and trouble.  The instructions shall 
be approved by the Contracting Officer before being posted.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.12.10   Walk Test</TTL><BRK/>
<BRK/>
<TXT>Each remote control unit shall have a walk test feature.  When using this feature, operation of initiating devices 
shall result in limited system outputs, so that the notification appliances operate for only a few seconds and 
the event is indicated on the system printer, but no other outputs occur.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.12.11   History Logging</TTL><BRK/>
<BRK/>
<TXT>In addition to the required printer output, the control panel shall have the ability to store a minimum of 400 
events in a log.  These events shall be stored in a battery-protected memory and shall remain in the memory until 
the memory is downloaded or cleared manually.  Resetting of the control panel shall not clear the memory.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>2.2.13   <SUB>Amplifiers</SUB>, Preamplifiers, <SUB>Tone Generators</SUB></TTL><BRK/>
<BRK/>
<TXT>Any amplifiers, preamplifiers, tone generators, <SUB>digitalized voice generators</SUB>, and other hardware necessary for 
a complete, operational, textual audible circuit conforming to <RID>NFPA 72</RID> shall be housed in a fire alarm control 
unit, terminal cabinet, or in the fire alarm control panel.  The system shall automatically operate and control 
all building fire alarm speakers except those installed in the stairs and within elevator cabs.  The speakers 
in the stairs and elevator cabs shall operate only when the microphone is used to deliver live messages.  Each 
amplifier shall have two channels; one to broadcast a message and the other for paging.</TXT><BRK/>
<BRK/>
<SPT>[<TTL>2.2.13.1   Construction</TTL><BRK/>
<BRK/>
<TXT>Amplifiers shall utilize computer grade solid state components and shall be provided with output protection devices 
sufficient to protect the amplifier against any transient up to 10 times the highest rated voltage in the system.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.13.2   Inputs</TTL><BRK/>
<BRK/>
<TXT>Each system shall be equipped with separate inputs from the tone generator, digitalized voice driver and panel 
mounted microphone.  Microphone inputs shall be of the low impedance, balanced line type.  Both microphone and 
tone generator input shall be operational on any amplifier.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.13.3   Tone Generator</TTL><BRK/>
<BRK/>
<TXT>The tone generator shall be of the modular, plug-in type with securely attached labels to identify the component 
as a tone generator and to identify the specific tone it produces.  The tone generator shall produce a slow whoop 
tone, which shall slowly ascend from low (500 hertz) to high (1200 hertz), and shall be constantly repeated until 
interrupted by either the digitalized voice message, the microphone input, or the alarm silence mode as specified.  
Each slow whoop cycle shall last approximately 4 seconds.  The tone generator shall be single channel with an 
automatic backup generator per channel such that failure of the primary tone generator causes the backup generator 
to automatically take over the functions of the failed unit and also causes transfer of the common trouble relay.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.13.4   Protection Circuits</TTL><BRK/>
<BRK/>
<TXT>Each amplifier shall be constantly supervised for any condition which could render the amplifier inoperable at 
its maximum output.  Failure of any component shall cause automatic transfer to a designated backup amplifier, 
illumination of a visual "amplifier trouble" indicator on the control panel, appropriate logging of the condition 
on the system printer, and other actions for trouble conditions as specified.</TXT><BRK/>
<BRK/>
]</SPT>]</SPT><SPT>[<TTL>2.2.14   <SUB>Video Display Unit (VDU)</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Contact the EFD or Engineering Field Activity (EFA) Fire Protection Engineer 
to determine if a VDU is to be provided.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">a.  The VDU shall be the secondary operator-to-system interface for data retrieval, alarm annunciation, 
commands,and programming functions.  The desk mounted VDU shall consist of a CRT monitor and 
a keyboard.  The VDU shall have a <MET>[300] [430] [_____] mm</MET><ENG> [12] [17] [_____] inch</ENG> minimum [touch] 
screen, capable of displaying 25 lines of 80 characters each.  Communications with the FACP 
shall be supervised.  Faults shall be recorded on the printer.  Power required shall be 120 
VAC, 60 Hz from the same source as the fire alarm control panel.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  To eliminate confusion during an alarm situation, the screen shall have dedicated areas 
for the following functions:</ITM><BRK/>
<BRK/>
<ITM>(1)  Alarm and returns to normal</ITM><BRK/>
<BRK/>
<ITM>(2)  Commands, reports, and programming </ITM><BRK/>
<BRK/>
<ITM>(3)  Time, day, and date</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Full English language shall be used throughout to describe system activity and instructions.  
Full English language descriptors defining system points shall be 100 percent field programmable 
by factory trained personnel, alterable and user definable to accurately describe building areas.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Alarms and other changes of status shall be displayed in the screen area reserved for this 
information.  The following information shall be provided in English:</ITM><BRK/>
<BRK/>
<ITM>(1)  Condition of device (alarm, trouble, or supervisory).</ITM><BRK/>
<BRK/>
<ITM>(2)  Type of device (manual pull, waterflow, etc.)</ITM><BRK/>
<BRK/>
<ITM>(3)  Location of device plus numerical system address.</ITM><BRK/>
<BRK/>
<ITM>Upon receipt of alarm, an audible alarm shall sound and the condition and point type shall flash 
until acknowledged by the operator.  Returns to normal shall also be annunciated and shall require 
operator acknowledgment.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  The system shall have multiple levels of priority for displaying alarms to conform with <RID>
UL 864</RID>.  Priority levels shall be as follows:</ITM><BRK/>
<BRK/>
<ITM>(1)  Level 1 - Fire Alarms</ITM><BRK/>
<BRK/>
<ITM>(2)  Level 2 - Supervisory Alarms</ITM><BRK/>
<BRK/>
<ITM>(3)  Level 3 - Trouble Signals</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  The system shall be provided with memory so that no alarm shall be lost.  A highlighted 
message shall advise the operator when unacknowledged alarms are in the system.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Multiple levels of access shall be provided for operators and supervisors via user-defined 
passwords.  The following functions shall be provided for each level:</ITM><BRK/>
<BRK/>
<ITM>(1)  Operator level access functions</ITM><BRK/>
<BRK/>
<ITM>(a)  Display system directory, definable by device.</ITM><BRK/>
<BRK/>
<ITM>(b)  Display status of an individual device.</ITM><BRK/>
<BRK/>
<ITM>(c)  Manual command (alarm device with an associated command shall use the same system address 
for both functions).</ITM><BRK/>
<BRK/>
<ITM>(d)  Report generation, definable by device, output on either the VDU or printer, as desired 
by the operator.</ITM><BRK/>
<BRK/>
<ITM>(e)  Activate building notification appliances.</ITM><BRK/>
<BRK/>
<ITM>(2)  Supervisory level access functions</ITM><BRK/>
<BRK/>
<ITM>(a)  Reset time and date.</ITM><BRK/>
<BRK/>
<ITM>(b)  Enable or disable event initiated programs, printouts, and initiators.</ITM><BRK/>
<BRK/>
<ITM>(c)  Enable or disable individual devices and system components.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  The above supervisory level functions shall not require computer programming skills.  Changes 
to system programs shall be recorded on the printer and maintained in the control panel as a 
trouble condition.</ITM><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.15   <SUB>Graphic Annunciator</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide the graphic annunciator at a location convenient for fire department.  
It should be near the door through which they will enter the building as indicated 
in their pre-fire plan.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT>[<TTL>2.2.15.1   Annunciator Panel</TTL><BRK/>
<BRK/>
<TXT>Provide a graphic annunciator which indicates the building floor plan, including the locations of stairs and 
elevators.  Stairs and elevators shall be identified by [letter] [number].  Alarm circuit boundaries shall be 
clearly marked on the floor plan.  Annunciator shall include a north arrow, [location of the fire alarm control 
panel,] and a "you are here" indicator.  The graphic annunciator shall be [a minimum size of <MET>915 by 915 mm</MET><ENG> 3 
by 3 feet</ENG>] [as indicated on the contract drawings].</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.15.2   Indicating Lights</TTL><BRK/>
<BRK/>
<TXT>Provide the graphic annunciator with individual light emitting diode (LED) indicating lights for each type of 
alarm and supervisory device.  Provide an amber LED for indicating a system trouble condition and a separate 
amber LED for indicating a supervisory condition.  Provide a green LED to indicate presence of power and a red 
LED to indicate an alarm condition.  The actuation of any alarm signal shall cause the illumination of a boundary 
LED, a floor LED, and a device LED.  System supervisory or trouble shall cause the illumination of a trouble 
LED.  In addition to all of these LED indicators, provide normal power and emergency power indicating LEDs. Provide 
a push button LED test switch.  The test switch shall not require key operation.  Annunciator LEDs shall only 
be extinguished by operation of the system reset switch on the FACP.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.15.3   Material</TTL><BRK/>
<BRK/>
<TXT>Construct the graphic annunciator face plate of [smoked Plexiglas] [bronze].  The LEDs shall be backlit.  Control 
equipment and wiring shall be housed in a [recessed] [semi-recessed] [surface mounted] back box.  The exposed 
portions of the back box shall be [chrome plated] [bronze plated] with knockouts.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.15.4   Programming</TTL><BRK/>
<BRK/>
<TXT>Where programming for the operation of the proper LEDs is accomplished by a separate software program than the 
software for the FACP, the software program shall not require reprogramming after loss of power. The software 
shall be reprogrammable in the field.</TXT><BRK/>
<BRK/>
]</SPT>]</SPT><SPT>[<TTL>2.2.16   System <SUB>Printers</SUB></TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Provide a system printer to record alarm, supervisory, and trouble conditions without loss 
of any signal or signals.  Printout shall be by circuit, device, and function as provided in 
the FACP.  Printer shall operate on a 120 VAC, 60 Hz power supply.</ITM><BRK/>
<BRK/>
<ITM>(1)  The printer shall have at least 80 characters per line and have a 96 ASCII character set.  
The printer shall have a microprocessor-controlled, bi-directional, logic seeking head capable 
of printing 120 characters per second utilizing a 9 by 7 dot matrix print head.  Printer shall 
not contain internal software which is essential for proper operation.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  When the FACP receives a signal, the alarm, supervisory, and trouble condition shall be 
printed.  The printout shall include the type of signal, the circuit or device reporting, the 
date, and the time of the occurrence.  The printer shall differentiate alarm signals from other 
printed indications.  When the system is reset, this condition shall also be printed including 
the same information concerning device, location, date, and time.  Provide a means to automatically 
print a list of existing alarm, supervisory, and trouble conditions in the system.  If a printer 
is off-line when an alarm is received, the system shall have a buffer to retain the data and 
it shall be printed when the printer is restored to service.  The printer shall have an indicator 
to alert the operator that the paper has run out.</ITM><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.17   <SUB>Firefighter Telephone</SUB> Communication System</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide a master control station at the FACP with remote telephone stations 
in each stair at each floor landing, in each elevator lobby on each floor, and 
in elevator cabs.  In addition, provide them at specific locations containing 
essential fire protection equipment, such as the fire pump room and outside 
the emergency generator room.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">a.  Provide a firefighter telephone system as follows:</ITM><BRK/>
<BRK/>
<ITM>(1)  Provide a firefighter telephone communication system with complete, common talk, closed 
circuits.  The system shall include, but not be limited to, a master control station mounted 
in the fire alarm control panel, a power supply and standby battery system, and remote telephone 
stations.</ITM><BRK/>
<BRK/>
<ITM>(2)  Provide a master control station which shall provide power, supervision, and control for 
wiring, components, and circuits.  The act of lifting any remote telephone hand set from its 
cradle shall cause both a visual and audible signal to annunciate at the master control station.  
Removing the hand set at the master control station and depressing a button at the remote telephone 
hand set shall cause the automatic silencing of the audible signal. Communication between the 
master control station hand set and any/or all remote hand sets shall require the depressing 
of a push-to-talk switch located on any/all remote hand sets.  During the time that the master 
control hand set is removed from its cradle it shall be possible to communicate between five 
remote hand sets and the master control station.  Hand sets shall be able to monitor any conversation 
in progress and join the conversation by pressing the push-to-talk button.  It shall not be 
possible to communicate between two or more remote hand sets with the master control station 
hand set in its cradle.  The master control station hand set shall be red in color and equipped 
with a 5-foot long strain-relieved coiled cord.  Wiring connections shall be made to terminal 
strips.  The master control station shall monitor wire and connections for any opens, shorts, 
or grounds which would render the system inoperable or unintelligible.  The master control station 
shall be equipped with a silencing switch and ring-back feature such that any audible trouble 
signal can be silenced and shall be so indicated by the lighting of an amber LED. Once any trouble 
condition has been corrected, the amber LED shall be extinguished and the silencing switch shall 
sound again until the switch is restored to its original position.  The master control station 
shall be equipped with a separate, LED annunciated switch for each telephone circuit.  In addition, 
LEDs shall provide for the annunciation of operating and supervisory power.  The loss of operating 
or supervisory power shall cause an audible and visual indication at the master control station 
and shall also cause the fire alarm trouble signal to sound on the FACP.  Switches, LEDs, and 
controls shall be fully labeled.</ITM><BRK/>
<BRK/>
<ITM>(3)  Provide [surface] [flush] mounted remote telephone stations.  Each station shall be equipped 
with a hinged door that is magnetically locked.  Each hand set shall be permanently wired in 
place with a coiled cord.  Each hand set shall be red high-impact cycolac and shall be equipped 
with a push-to-talk switch which, when operated, shall signal the master control station and 
a switch-equipped, storage cradle.</ITM><BRK/>
<BRK/>
<ITM>(4)  Provide operating and supervising power from the same supply circuit(s) utilized for the 
fire alarm control panel.</ITM><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.2.18   <SUB>Manual Stations</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide metal or plastic, semi-flush mounted, double action, addressable manual stations, which are not subject 
to operation by jarring or vibration.  Stations shall be equipped with screw terminals for each conductor.  Stations 
which require the replacement of any portion of the device after activation are not permitted.  Stations shall 
be finished in fire-engine red with molded raised lettering operating instructions of contrasting color.  The 
use of a key or wrench shall be required to reset the station.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.19   <SUB>Notification Appliances</SUB></TTL><BRK/>
<BRK/>
<SPT>[<TTL>2.2.19.1   Fire Alarm Speakers</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Locate speakers throughout the building with a maximum spacing of <MET>92.9 
square meters</MET> <ENG>1000 square feet</ENG> per speaker.  Where sound has to pass through 
more than one partition or wall to be heard in a space, provide an additional 
speaker.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">a.  Provide fire alarm speakers conforming to <RID>UL 464</RID> having a minimum of three tap settings 
and separate terminations for each in and out connection.  Tap settings shall include taps of 
1/4, 1/2 and 1 watt.  Speakers shall utilize the 1/2 watt tap in the system.  Speakers shall 
have an output rating of 84 dBA at <MET>3050 mm</MET><ENG> 10 feet</ENG> as determined by the reverberant room test; 
data on peak output as determined in an anechoic chamber is not suitable.  Speakers shall be 
capable of installation on standard <MET>100 mm</MET><ENG> 4 inch</ENG> square electrical boxes.  Where speakers and 
strobes are provided in the same location, they may be combined into a single wall mounted unit.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Provide speaker mounting plates constructed of cold rolled steel having a minimum thickness 
of 16 gage and equipped with mounting holes and other openings as needed for a complete installation.  
Fabrication marks and holes shall be ground and finished to provide a smooth and neat appearance 
for each plate.  Each plate shall be primed and painted.</ITM><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.2.19.2   Visual Alarm Signals</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Locate strobes wall mounted in corridors no more than <MET>4570 mm</MET><ENG> 15 feet</ENG>
 from the end of a corridor with <MET>30.48 m</MET><ENG> 100 feet</ENG> maximum distance between strobes.  
Where there is an obstruction to the viewing path in the corridors, such as 
a cross-corridor door or ceiling elevation change, consider the obstruction 
as defining a new corridor.  Provide wall mounted strobes in rooms accessible 
to the public, such as conference rooms, restrooms, courtrooms, cafeterias, 
and auditoriums in accordance with NFPA 72.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide strobe light visual alarm signals which operate on a supervised 24 volt DC circuit.  The strobe lens 
shall comply with <RID>UL 1971</RID> and conform to the Americans With Disabilities Act.  The light pattern shall be disbursed 
so that it is visible above and below the strobe and from a 90 degree angle on both sides of the strobe.  The 
strobe flash output shall be a minimum of [15] [_____] candela based on the <RID>UL 1971</RID> test.  The strobe shall have 
a xenon flash tube.  Visible appliances may be part of an audio-visual assembly.  [Where more than two appliances 
are located in the same room or corridor, provide synchronized operation.]</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.2.19.3   Fire Alarm Horns</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where horns or bells are used for fire alarm notification, calculate 
the proper locations for these devices as detailed in "Designing Fire Alarm 
Audibility," which is contained in the Society of Fire Protection Engineers 
(SFPE) Handbook of Fire Protection Engineering.  Submit the calculations at 
the 35 percent design review.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide [surface] [semi-flush] mounted electronic multi-tone horns that produce a minimum of four distinct sounds, 
suitable for use in an electrically supervised circuit.  Horns shall have a rating of 90 dBA at <MET>3050 mm</MET><ENG> 10 feet</ENG>
 when tested in accordance with <RID>UL 464</RID> while emitting a slow whoop tone.  Output from the horn shall be [three-pulse 
temporal pattern] [the slow whoop tone] [_____].  Where horns and strobes are provided in the same location, 
they may be combined into a single unit.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.19.4   Fire Alarm Bells</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where horns or bells are used for fire alarm notification, calculate 
the proper locations for these devices as detailed in "Designing Fire Alarm 
Audibility," which is contained in the Society of Fire Protection Engineers 
(SFPE) Handbook of Fire Protection Engineering.  Submit the calculations at 
the 35 percent design review.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide [surface] [flush] mounted bells suitable for use in an electrically supervised circuit.  Bells shall 
be <MET>255 mm</MET><ENG> 10 inch</ENG> vibrating type with a sound output rating of at least 90 dBA at <MET>3050 mm</MET><ENG> 10 feet</ENG> when tested 
in accordance with <RID>UL 464</RID>.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.2.19.5   Connections</TTL><BRK/>
<BRK/>
<TXT>Provide screw terminals for each notification appliance.  Terminals shall be designed to accept the size conductors 
used in this project without modification.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>2.2.20   Valve Monitor Switches (<SUB>Tamper Switches</SUB>)</TTL><BRK/>
<BRK/>
<TXT>Provide a tamper switch for each fire protection system control valve.  Tamper switches shall be UL listed as 
"Extinguishing System Attachment" for the location and type of valve supervised.  The device shall contain double 
pole, double throw contacts.  Operation of the switch shall cause a supervisory signal to be transmitted to the 
FACP upon not more than two complete turns of the valve wheel or a closure of 10 percent, whichever is less.  
Tamper switches shall be equipped with screw terminals for each conductor.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.21   <SUB>Waterflow Detectors</SUB></TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  [Provide vane type waterflow detectors for wet pipe sprinkler systems.  The device shall 
contain double pole, double throw contacts.  Equip the detector with a pneumatic time delay, 
field adjustable from 0 to 90 seconds.  The time delay shall be set initially to [30] [45] [_____] 
seconds.  The device shall be a UL listed extinguishing system attachment rated for the particular 
pressure and location at which it is installed.  Flow switches shall be equipped with screw 
terminals for each conductor.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Provide pressure type waterflow detectors for dry pipe sprinkler systems.  The device shall 
contain double pole, double throw contacts.  The device shall be a UL listed extinguishing system 
attachment rated for the particular pressure and location at which it is installed.  Switch 
shall be equipped with screw terminals for each conductor.</ITM><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.22   <SUB>Electromagnetic Door Holders</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide electromagnetic door holders only for cross-corridor doors and 
for doors likely to be propped open once construction is complete.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Where indicated on the drawings, provide magnetic fire door hold open devices.  The electromagnetic holding devices 
shall be designed to operate on 120 VAC, and require not more than 3 watts of power to develop <MET>172.4 kPa</MET><ENG> 25 psi</ENG>
 of holding force.  The initiation of any fire alarm shall cause the release of the electromagnetic door holding 
device permitting the door to be closed by the door closer.  The device shall be UL listed based on <RID>UL 228</RID> tests.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.2.23   Automatic <SUB>Transmitters</SUB></TTL><BRK/>
<BRK/>
<SPT>[<TTL>2.2.23.1   <SUB>Telegraphic Transmitter</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide transmitter of the electric motor-driven or pre-wound spring mechanism type which shall transmit not 
less than four rounds of code.  When motor-driven transmitters are provided, the motor shall be connected to 
a supervised circuit in a control panel.  Provide metallic or rigid plastic code number plates on the exterior 
face of transmitters.  Transmitters shall be designed to provide the same features as the fire alarm boxes for 
electrically supervised, coded positive noninterfering type and shall have the ability to transmit signals on 
grounded or open circuits.  Activation of box when a single open fault is present on exterior fire alarm circuit 
shall have box to idle for one complete round only, then immediately transmit four complete code rounds via the 
box earth ground connection.  Transmitter shall have a local energy type auxiliary tripping device.  Code wheel 
shall be metallic and box code shall be as directed by the Contracting Officer.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.23.2   <SUB>Radio Transmitter and Interface Panels</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide radio transmitter with antenna that is compatible with the existing supervising station fire alarm system.  
Transmitter shall have a means to transmit alarm, supervisory, and trouble conditions via a single transmitter.  
Provide transmitters in accordance with applicable portions of [<RID>NFPA 72</RID>,] Federal Communications Commission (FCC) <RID>
47 CFR 90</RID>.  Protect the antenna from physical damage.  Transmitter shall have a source of power for operation 
which conforms to <RID>NFPA 72</RID>.  Transmitter shall be capable of initiating a test signal daily at any selected time.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.23.3   <SUB>Digital Alarm Communicator Transmitter (DACT)</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide DACT that is compatible with the existing supervising station fire alarm system.  Transmitter shall have 
a means to transmit alarm, supervisory, and trouble conditions via a single transmitter.  Transmitter shall have 
a source of power for operation which conforms to <RID>NFPA 72</RID>. Transmitter shall be capable of initiating a test 
signal daily at any selected time.  Transmitter shall be arranged to seize telephone circuits in accordance with <RID>
NFPA 72</RID>.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.2.23.4   Signals To Be Transmitted to the Base Receiving Station</TTL><BRK/>
<BRK/>
<TXT>The following signals shall be sent to the base receiving station:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">[a.  Sprinkler water flow]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Manual pull stations]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[c.  Smoke detectors]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[d.  Duct smoke detectors]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[e.  Sleeping room smoke detectors]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[f.  Heat detectors]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[g.  Sprinkler valve supervision]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[h.  Fire pump running]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[i.  Fire pump loss of power/phase reversal]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[j. [_____]]</ITM><BRK/>
<BRK/>
]</SPT></SPT></SPT><SPT><TTL>2.3   NAMEPLATES</TTL><BRK/>
<BRK/>
<TXT>Major components of equipment shall have the manufacturer's name, address, type or style, model or serial number, 
catalog number, date of installation, installing Contractor's name and address, and the contract number provided 
on a new plate permanently affixed to the item or equipment.  Major components include, but are not limited to, 
the following:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  FACPs</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Automatic transmitter</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Printer</ITM><BRK/>
<BRK/>
<TXT>Furnish to obtain approval by the Contracting Officer before installation.  Obtain approval by the Contracting 
Officer for installation locations.  Nameplates shall be etched metal or plastic, permanently attached by screws 
to panels or adjacent walls.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4   <SUB>WIRING</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide wiring materials under this section as specified in Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM with 
the additions and modifications specified herein.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   INSTALLATION OF FIRE ALARM INITIATING AND INDICATING DEVICES</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  FACP:  Locate the FACP [where indicated on the drawings] [_____].  [Recess] [Semi-recess] 
[Surface mount] the enclosure with the top of the cabinet <MET>1830 mm</MET><ENG> 6 feet </ENG> above the finished 
floor or center the cabinet at <MET>[1525] [_____] mm</MET><ENG> [5] [_____] feet</ENG>, whichever is lower.  Conductor 
terminations shall be labeled and a drawing containing conductors, their labels, their circuits, 
and their interconnection shall be permanently mounted in the FACP.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Manual Stations:  Locate manual stations [as required by <RID>NFPA 101</RID> and <RID>NFPA 72</RID>] [where shown 
on the drawings] [_____].  Mount stations so that their operating handles are <MET>1220 mm</MET><ENG> 4 feet</ENG>
 above the finished floor.  Mount stations so they are located no farther than <MET>[1525] [_____] 
mm</MET><ENG> [5] [_____] feet</ENG> from the exit door they serve, measured horizontally.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Notification Appliance Devices:  Locate notification appliance devices [as required by <RID>NFPA 72</RID>
] [where shown on the drawings].  Mount assemblies on walls <MET>2030 mm</MET><ENG> 80 inches</ENG> above the finished 
floor or <MET>150 mm</MET><ENG> 6 inches</ENG> below the ceiling whichever is lower.  [Ceiling mounted speakers shall 
conform to <RID>NFPA 72</RID>].</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[d.  Smoke and Heat Sensors:  Locate sensors [as required by <RID>NFPA 72</RID> and their listings] [as 
shown on the drawings] on a<ENG> 4 inch</ENG> mounting box.  Sensors located on the ceiling shall be installed 
not less than <MET>100 mm</MET><ENG> 4 inches</ENG> from a side wall to the near edge.  Those located on the wall 
shall have the top of the sensor at least <MET>100 mm</MET><ENG> 4 inches</ENG> below the ceiling, but not more than <MET>
300 mm</MET><ENG> 12 inches</ENG> below the ceiling.  In raised floor spaces, the smoke sensors shall be installed 
to protect <MET>20.9 square meters</MET><ENG> 225 square feet</ENG> per sensor.  Install smoke sensors no closer than <MET>
1525 mm</MET><ENG> 5 feet</ENG> from air handling supply outlets.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[e.  Graphic Annunciator:  Locate the graphic annunciator as shown on the drawings.  Surface 
mount the panel, with the top of the panel <MET>1830 mm</MET><ENG> 6 feet</ENG> above the finished floor or center 
the panel at <MET>[1525] [_____] mm</MET><ENG> [5] [_____] feet</ENG>, whichever is lower.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[f.  Water Flow Detectors and Tamper Switches:  Locate water flow detectors and tamper switches 
[where shown on the drawings] [at each supervised] sprinkler valve station.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[g.  Firefighter Telephones:  Locate wall mounted in each stair at each floor landing, in each 
elevator lobby, and in each elevator cab <MET>1220 mm</MET><ENG> 4 feet</ENG> above the finished floor.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[h.  The modification of any fire alarm system and the procedures shall comply with the requirements 
of <RID>NFPA 241</RID>.]</ITM><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.2   DISCONNECTION AND REMOVAL OF EXISTING SYSTEM</TTL><BRK/>
<BRK/>
<TXT>Fire alarm control panels and fire alarm devices disconnected and removed shall be turned over to the Contracting 
Officer.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  The existing fire alarm and smoke detection system shall remain in operation at all times 
during the installation and commissioning of the new system. Once this new system is on-line 
and accepted by the Government, remove the old system.  As new equipment is installed, label 
it "NOT IN SERVICE."  Upon acceptance, remove labels.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Disconnect and remove the existing fire alarm and smoke detection systems where indicated 
and elsewhere in the specification.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Properly dispose of fire alarm outlet and junction boxes, wiring, conduit, supports, and 
other such items.</ITM><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.3   CONNECTION OF NEW SYSTEM</TTL><BRK/>
<BRK/>
<TXT>The following new system connections shall be made during the last phase of construction, at the beginning of 
the preliminary tests.  New system connections shall include:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">[a.  Connection of new control modules to existing magnetically held smoke door (hold-open) 
devices.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Connection of new elevator recall smoke sensors to existing wiring and conduit.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[c.  Connection of new system transmitter to existing base fire reporting system.]</ITM><BRK/>
<BRK/>
<TXT>Once these connections are made, system shall be left energized and new audio/visual devices deactivated.  Report 
immediately to the Contracting Officer, coordination and field problems resulting from the connection of the 
above components.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.4   FIRESTOPPING</TTL><BRK/>
<BRK/>
<TXT>Provide firestopping for holes at conduit penetrations through floor slabs, fire rated walls, partitions with 
fire rated doors, corridor walls, and vertical service shafts in accordance with Section <SRF>07 84 00</SRF> FIRESTOPPING.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5   PAINTING</TTL><BRK/>
<BRK/>
<TXT>Paint exposed electrical, fire alarm conduit, and surface metal raceway to match adjacent finishes in exposed 
areas.  Paint [junction boxes] [conduit] [and] [surface metal raceways] red in unfinished areas.  Painting shall 
comply with Section <SRF>09 90 00</SRF> PAINTS AND COATINGS.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6   FIELD QUALITY CONTROL</TTL><BRK/>
<BRK/>
<SPT><TTL>3.6.1   Tests</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Megger Tests:  After wiring has been installed, and prior to making any connections to panels 
or devices, wiring shall be megger tested for insulation resistance, grounds, and/or shorts.  
Conductors with 300 volt rated insulation shall be tested at a minimum of 250 VDC.  Conductors 
with 600 volt rated insulation shall be tested at a minimum of 500 VDC.  The tests shall be 
witnessed by the Contracting Officer and test results recorded for use at the final acceptance 
test.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Loop Resistance Tests:  Measure and record the resistance of each circuit with each pair 
of conductors in the circuit short-circuited at the farthest point from the circuit origin.  
The tests shall be witnessed by the Contracting Officer and test results recorded for use at 
the final acceptance test.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Preliminary Testing:  Conduct preliminary tests to ensure that devices and circuits are 
functioning properly.  Tests shall meet the requirements of paragraph entitled "Minimum System 
Tests."  After preliminary testing is complete, provide a letter certifying that the installation 
is complete and fully operable.  The letter shall state that each initiating and indicating 
device was tested in place and functioned properly.  The letter shall also state that panel 
functions were tested and operated properly.  The letter shall include the names and titles 
of the witnesses to the preliminary tests.  The Contractor and an authorized representative 
from each supplier of equipment shall be in attendance at the preliminary testing to make necessary 
adjustments.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Request for Formal Inspection and Tests:  When tests have been completed and corrections 
made, submit a signed, dated certificate with a request for formal inspection and tests to the 
Contraction Officer.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Final Testing:  Notify the Contracting Officer in writing when the system is ready for final 
acceptance testing.  Submit request for test at least 15 calendar days prior to the test date.  
A final acceptance test will not be scheduled until the operation and maintenance (O&amp;M) 
manuals are furnished to the Contracting Officer and the following are provided at the job site:</ITM><BRK/>
<BRK/>
<ITM>(1)  The systems manufacturer's technical representative</ITM><BRK/>
<BRK/>
<ITM>(2)  Marked-up red line drawings of the system as actually installed</ITM><BRK/>
<BRK/>
<ITM>(3)  Megger test results</ITM><BRK/>
<BRK/>
<ITM>(4)  Loop resistance test results</ITM><BRK/>
<BRK/>
<ITM>(5)  Complete program printout including input/output addresses</ITM><BRK/>
<BRK/>
<TXT>The final tests shall be witnessed by the [[____] Division] [EFA [____]], Naval Facilities Engineering Command, 
Fire Protection Engineer.  At this time, any and all required tests shall be repeated at their discretion.  Following 
acceptance of the system, as-built drawings and O&amp;M manuals shall be delivered to the Contracting Officer 
for review and acceptance.  In existing buildings, the transfer of devices from the existing system to the new 
system and the permission to begin demolition of the old fire alarm system will not be permitted until the as-built 
drawings and O&amp;M manuals are received.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6.2   Minimum System Tests</TTL><BRK/>
<BRK/>
<TXT>Test the system in accordance with the procedures outlined in <RID>NFPA 72</RID>.  The required tests are as follows:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Verify the absence of unwanted voltages between circuit conductors and ground.  The tests 
shall be accomplished at the preliminary test with results available at the final system test.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Verify that the control unit is in the normal condition as detailed in the manufacturer's 
O&amp;M manual.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Test each initiating and indicating device and circuit for proper operation and response 
at the control unit.  Smoke sensors shall be tested in accordance with manufacturer's recommended 
calibrated test method.  Testing of duct smoke detectors shall comply with the requirements 
of <RID>NFPA 72</RID>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Test the system for specified functions in accordance with the contract drawings and specifications 
and the manufacturer's O&amp;M manual.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Test both primary power and secondary power.  Verify, by test, the secondary power system 
is capable of operating the system for the time period and in the manner specified.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Determine that the system is operable under trouble conditions as specified.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Visually inspect wiring.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  Test the battery charger and batteries.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">i.  Verify that software control and data files have been entered or programmed into the FACP.  
Hard copy records of the software shall be provided to the Contracting Officer.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">j.  Verify that red-line drawings are accurate.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">k.   Measure the current in circuits to ensure there is the calculated spare capacity for the 
circuits.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">l.  Measure voltage readings for circuits to ensure that voltage drop is not excessive.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">m.  Disconnect the verification feature for smoke sensors during tests to minimize the amount 
of smoke needed to activate the sensor.  Testing of smoke sensors shall be conducted using real 
smoke.  The use of canned smoke is prohibited.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">n.  Measure the voltage drop at the most remote appliance on each notification appliance circuit.</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.7   INSTRUCTION OF GOVERNMENT EMPLOYEES</TTL><BRK/>
<BRK/>
<TXT>Equipment manufacturer shall provide 3 days on site [and 5 days of technical training to the Government at the 
manufacturing facility.]  Training shall allow for classroom instruction as well as individual hands on programming, 
troubleshooting and diagnostics exercises.  [Room and board costs shall be included for two Government personnel.]  
[Factory] training shall occur within [6] [12] [_____] months of system acceptance.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.7.1   Instructor</TTL><BRK/>
<BRK/>
<TXT>Include in the project the services of an instructor, who shall have received specific training from the manufacturer 
for the training of other persons regarding the inspection, testing, and maintenance of the system provided.  
The instructor shall train the Government employees designated by the Contracting Officer, in the care, adjustment, 
maintenance, and operation of the fire alarm [and fire detection] system.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.2   Qualifications</TTL><BRK/>
<BRK/>
<TXT>Each instructor shall be thoroughly familiar with all parts of this installation.  The instructor shall be trained 
in operating theory as well as in practical O&amp;M work.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.3   Required Instruction Time</TTL><BRK/>
<BRK/>
<TXT>Provide 16 hours of instruction after final acceptance of the system.  The instruction shall be given during 
regular working hours on such dates and times as are selected by the Contracting Officer.  The instruction may 
be divided into two or more periods at the discretion of the Contracting Officer.  The training shall allow for 
rescheduling for unforeseen maintenance and/or fire department responses.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT>    <END/><BRK/></SEC>