<SCN>SECTION 33 71 02.00 20</SCN><BRK/>
<BRK/>
<STL>UNDERGROUND ELECTRICAL DISTRIBUTION</STL><BRK/>
<DTE>08/08</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>underground electrical 
work</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification does not cover all possible methods or requirements 
for providing underground facilities.  To do so would be to produce an involved, 
confusing document.  This guide specification presents the usual methods and 
the most used alternatives.  Different materials and methods, properly specified, 
indicated, and economically used will be acceptable when approved by cognizant 
authority.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<BRK/>
<NTE><PGE/><AST/><BRK/>
<NPR>Note:  This section use the following manhole / handhole sketches and details 
found at: <URL HREF="http://www.wbdg.org/ccb/NAVGRAPH/graphtoc.pdf">http://www.wbdg.org/ccb/NAVGRAPH/graphtoc.pdf.</URL></NPR><BRK/>
<BRK/>
<TBL><HL4><HL1>LIST OF SKETCHES </HL1></HL4><BRK/>
<BRK/>
  Sketches are available in metric (SI) and U.S. Customary (IP) system <BRK/>
  dimensions.  Sketch titles and style numbers are unchanged for both <BRK/>
  types.<BRK/>
<BRK/>
  The metric values indicated are a conversion of the IP system <BRK/>
  dimensions.<BRK/>
<BRK/>
  Do not include list of sketches, or sketches themselves, in project <BRK/>
  specifications.  Use manhole / handhole sketches as details on drawings <BRK/>
  whenever possible.  If special features are required for a project, do<BRK/>
  not modify sketches, but indicate these changes on notes below the <BRK/>
  sketch.  The "UG" style numbers and dates should remain on the drawing<BRK/>
  details.<BRK/>
<BRK/>
<THD>         <HL1>SKETCH NUMBER</HL1>                        <HL1>TITLE</HL1><BRK/>
<BRK/></THD>
           UG - 1           Standard Electrical Manhole (Nontraffic), <BRK/>
                             Types 1 and 2<BRK/>
<BRK/>
           UG - 2           Standard Electrical Manhole (Traffic), <BRK/>
                             Types 3 and 4<BRK/>
<BRK/>
           UG - 3           Standard Electrical Manhole (Airfield), <BRK/>
                             Types 5 and 6<BRK/>
<BRK/>
           UG - 4           Standard Electrical Handhole (Nontraffic), <BRK/>
                             Types 1 and 2<BRK/>
<BRK/>
           UG - 5           Standard Electrical Handhole <BRK/>
                             (Traffic/Airfield), Types 3 and 4<BRK/>
<BRK/>
           UG - 6           Standard Electrical Handhole (Nontraffic), <BRK/>
                             (Composite/Fiberglass) <BRK/>
                             Types 5, 6, 7, 8 and 9<BRK/>
<BRK/>
           UG - 7           Details (Pulling-In Irons, Cable Rack, and <BRK/>
                              Duct Entrance)</TBL><BRK/>
<BRK/>
<NPR>NOTE: TO DOWNLOAD UFGS GRAPHICS<BRK/>
<BRK/>
Go to <URL HREF="http://www.wbdg.org/ccb/NAVGRAPH/graphtoc.pdf">http://www.wbdg.org/ccb/NAVGRAPH/graphtoc.pdf</URL>.</NPR><BRK/>
<BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following information shall be shown on the project drawings:</NPR><BRK/>
<BRK/>
<NPR>1.  Where specification identifies type, size, color, finish, or other definitive 
information to be "as indicated," the engineer shall include the information 
on the drawings.</NPR><BRK/>
<BRK/>
<NPR>2.  Location of ducts, and cables.</NPR><BRK/>
<BRK/>
<NPR>3.  Types of wire and cable; number and sizes of conductors.</NPR><BRK/>
<BRK/>
<NPR>4.  Special conditions.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Issue (date) of references included in project specifications need not 
be more current than provided by the latest guide specification.  Use of SpecsIntact 
automated reference checking is recommended for projects based on older guide 
specifications.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ACI INTERNATIONAL (ACI)</ORG><BRK/><BRK/><RID>ACI 318M</RID><RTL>(2008) Metric Building Code Requirements for Structural Concrete and Commentary</RTL><BRK/><BRK/><RID>ACI SP-66</RID><RTL>(2004) ACI Detailing Manual</RTL><BRK/><BRK/></REF><REF><ORG>AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS (AASHTO)</ORG><BRK/><BRK/><RID>AASHTO HB-17</RID><RTL>(2002; Errata 2003; Errata 2005) Standard Specifications for Highway Bridges</RTL><BRK/><BRK/><RID>AASHTO M 198</RID><RTL>(2008) Standard Specification for Joints for Concrete Pipe, Manholes and Precast Box Sections Using Preformed Flexible Joint Sealants</RTL><BRK/><BRK/></REF><REF><ORG>AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)</ORG><BRK/><BRK/><RID>ANSI C135.30</RID><RTL>(1988) Zinc-Coated Ferrous Ground Rods for Overhead or Underground Line Construction</RTL><BRK/><BRK/></REF><REF><ORG>AMERICAN WELDING SOCIETY (AWS)</ORG><BRK/><BRK/><RID>AWS D1.1/D1.1M</RID><RTL>(2008) Structural Welding Code - Steel</RTL><BRK/><BRK/></REF><REF><ORG>ASSOCIATION OF EDISON ILLUMINATING COMPANIES (AEIC)</ORG><BRK/><BRK/><RID>AEIC CS8</RID><RTL>(2000) Extruded Dielectric Shielded Power Cables Rated 5 Through 46 kV</RTL><BRK/><BRK/></REF><REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 48/A 48M</RID><RTL>(2003; R 2008) Standard Specification for Gray Iron Castings</RTL><BRK/><BRK/><RID>ASTM B 1</RID><RTL>(2001; R 2007) Standard Specification for Hard-Drawn Copper Wire</RTL><BRK/><BRK/><RID>ASTM B 231/B 231M</RID><RTL>(2004) Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors</RTL><BRK/><BRK/><RID>ASTM B 3</RID><RTL>(2001; R 2007) Standard Specification for Soft or Annealed Copper Wire</RTL><BRK/><BRK/><RID>ASTM B 400</RID><RTL>(2008) Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductor</RTL><BRK/><BRK/><RID>ASTM B 496</RID><RTL>(2004) Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors</RTL><BRK/><BRK/><RID>ASTM B 609/B 609M</RID><RTL>(1999; R 2004) Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical purposes</RTL><BRK/><BRK/><RID>ASTM B 8</RID><RTL>(2004) Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft</RTL><BRK/><BRK/><RID>ASTM B 800</RID><RTL>(2005) Standard Specification for 8000 Series Aluminum Alloy Wire for Electrical Purposes-Annealed and Intermediate Tempers</RTL><BRK/><BRK/><RID>ASTM B 801</RID><RTL>(2007) Standard Specification for Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation</RTL><BRK/><BRK/><RID>ASTM C 139</RID><RTL>(2005) Standard Specification for Concrete Masonry Units for Construction of Catch Basins and Manholes</RTL><BRK/><BRK/><RID>ASTM C 309</RID><RTL>(2007) Standard Specification for Liquid Membrane-Forming Compounds for Curing Concrete</RTL><BRK/><BRK/><RID>ASTM C 32</RID><RTL>(2005) Standard Specification for Sewer and Manhole Brick (Made from Clay or Shale)</RTL><BRK/><BRK/><RID>ASTM C 478</RID><RTL>(2008) Standard Specification for Precast Reinforced Concrete Manhole Sections</RTL><BRK/><BRK/><RID>ASTM C 478M</RID><RTL>(2008e1) Standard Specification for Precast Reinforced Concrete Manhole Sections (Metric)</RTL><BRK/><BRK/><RID>ASTM C 857</RID><RTL>(2007) Standard Practice for Minimum Structural Design Loading for Underground Precast Concrete Utility Structures</RTL><BRK/><BRK/><RID>ASTM F 512</RID><RTL>(2006) Smooth-Wall Poly (Vinyl Chloride) (PVC) Conduit and Fittings for Underground Installation</RTL><BRK/><BRK/></REF><REF><ORG>INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)</ORG><BRK/><BRK/><RID>IEEE C2</RID><RTL>(2007; Errata 2007; INT 2008) National Electrical Safety Code</RTL><BRK/><BRK/><RID>IEEE C37.20.3</RID><RTL>(2001; R 2006) Metal-Enclosed Interrupter Switchgear</RTL><BRK/><BRK/><RID>IEEE Std 100</RID><RTL>(2000) The Authoritative Dictionary of IEEE Standards Terms</RTL><BRK/><BRK/><RID>IEEE Std 386</RID><RTL>(2006) Standard for Separable Insulated Connector Systems for Power Distribution Systems Above 600V</RTL><BRK/><BRK/><RID>IEEE Std 400.2</RID><RTL>(2004) Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF)</RTL><BRK/><BRK/><RID>IEEE Std 404</RID><RTL>(2006) Extruded and Laminated Dielectric  Shielded Cable Joints Rated 2500 V Through 500 000 V</RTL><BRK/><BRK/><RID>IEEE Std 48</RID><RTL>(1996; R 2003) Test Procedures and Requirements for Alternating-Current Cable Terminations 2.5 kV through 765 kV</RTL><BRK/><BRK/><RID>IEEE Std 81</RID><RTL>(1983) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System (Part 1)Normal Measurements</RTL><BRK/><BRK/></REF><REF><ORG>INSULATED CABLE ENGINEERS ASSOCIATION (ICEA)</ORG><BRK/><BRK/><RID>ICEA S-94-649</RID><RTL>(2004) Standard for Concentric Neutral Cable Rated 5 Through 46 KV</RTL><BRK/><BRK/></REF><REF><ORG>INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)</ORG><BRK/><BRK/><RID>NETA ATS</RID><RTL>(2003) Acceptance Testing Specifications</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)</ORG><BRK/><BRK/><RID>NEMA C119.1</RID><RTL>(2006) Sealed Insulated Underground Connector Systems Rated 600 Volts</RTL><BRK/><BRK/><RID>NEMA RN 1</RID><RTL>(2005) Standard for Polyvinyl Chloride (PVC) Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit</RTL><BRK/><BRK/><RID>NEMA TC 2</RID><RTL>(2003) Standard for Electrical Polyvinyl Chloride (PVC) Tubing and Conduit</RTL><BRK/><BRK/><RID>NEMA TC 3</RID><RTL>(2004) Standard for Polyvinyl Chloride PVC Fittings for Use With Rigid PVC Conduit and Tubing</RTL><BRK/><BRK/><RID>NEMA TC 6 &amp; 8</RID><RTL>(2003) Standard for Polyvinyl Chloride PVC Plastic Utilities Duct for Underground Installations</RTL><BRK/><BRK/><RID>NEMA TC 7</RID><RTL>(2005) Standard for Smooth-Wall Coilable Polyethylene Electrical Plastic Duct</RTL><BRK/><BRK/><RID>NEMA TC 9</RID><RTL>(2004) Standard for Fittings for Polyvinyl Chloride (PVC) Plastic Utilities Duct for Underground Installation</RTL><BRK/><BRK/><RID>NEMA WC 70</RID><RTL>(1999; Errata 2001) Standard for Non-Shielded Power Cable 2000 V or Less for the Distribution of Electrical Energy</RTL><BRK/><BRK/><RID>NEMA WC 71</RID><RTL>(1999) Standard for Nonshielded Cables Rated 2001-5000 Volts for use in the Distribution of Electric Energy</RTL><BRK/><BRK/><RID>NEMA WC 74</RID><RTL>(2006) Standard for 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/></REF><REF><ORG>TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)</ORG><BRK/><BRK/><RID>TIA-758-A</RID><RTL>(2004) Customer-Owned Outside Plant Telecommunications Cabling Standard</RTL><BRK/><BRK/></REF><REF><ORG>U.S. DEPARTMENT OF AGRICULTURE (USDA)</ORG><BRK/><BRK/><RID>RUS Bull 1751F-644</RID><RTL>(2002) Underground Plant Construction</RTL><BRK/><BRK/></REF><REF><ORG>U.S. GENERAL SERVICES ADMINISTRATION (GSA)</ORG><BRK/><BRK/><RID>CID A-A-60005</RID><RTL>(Basic; Notice 1) Frames, Covers, Gratings, Steps, Sump And Catch Basin, Manhole</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 1072</RID><RTL>(2006; Rev thru Sep 2007) Medium-Voltage Power Cables</RTL><BRK/><BRK/><RID>UL 1242</RID><RTL>(2006; Rev thru Jul 2007) Standard for Electrical Intermediate Metal Conduit -- Steel</RTL><BRK/><BRK/><RID>UL 1684</RID><RTL>(2000; Rev thru Aug 2004) Reinforced Thermosetting Resin Conduit (RTRC) and Fittings</RTL><BRK/><BRK/><RID>UL 44</RID><RTL>(2005; Rev thru Nov 2005) Thermoset-Insulated Wires and Cables</RTL><BRK/><BRK/><RID>UL 467</RID><RTL>(2007) Standard for Grounding and Bonding Equipment</RTL><BRK/><BRK/><RID>UL 486A-486B</RID><RTL>(2003; Rev thru Aug 2006) Standard for Wire Connectors</RTL><BRK/><BRK/><RID>UL 510</RID><RTL>(2005; Rev thru Aug 2005) Polyvinyl Chloride, Polyethylene, and Rubber Insulating Tape</RTL><BRK/><BRK/><RID>UL 514A</RID><RTL>(2004; Rev thru Aug 2007) Standard for Metallic Outlet Boxes</RTL><BRK/><BRK/><RID>UL 514B</RID><RTL>(2004; Rev thru Aug 2007) Standard for Conduit, Tubing and Cable Fittings</RTL><BRK/><BRK/><RID>UL 6</RID><RTL>(2007) Standard for Electrical Rigid Metal Conduit-Steel</RTL><BRK/><BRK/><RID>UL 651</RID><RTL>(2005; Rev thru May 2007) Standard for Schedule 40 and 80 Rigid PVC Conduit and Fittings</RTL><BRK/><BRK/><RID>UL 651A</RID><RTL>(2000; Rev thru Sep 2007) Type EB and A Rigid PVC Conduit and HDPE Conduit</RTL><BRK/><BRK/><RID>UL 83</RID><RTL>(20086) Standard for Thermoplastic-Insulated Wires and Cables</RTL><BRK/><BRK/><RID>UL 854</RID><RTL>(2004; Rev thru Oct 2007) Service-Entrance Cables</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   DEFINITIONS</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a. Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, 
and on the drawings, shall be as defined in <RID>IEEE Std 100</RID>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  In the text of this section, the words conduit and duct are used interchangeably and have 
the same meaning.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  In the text of this section, "medium voltage cable splices," and "medium voltage cable joints" 
are used interchangeably and have the same meaning.</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For Navy projects, areas subject to aircraft loading are generally defined 
as follows:<BRK/>
<BRK/>
1.  For fixed wing aircraft facilities:<BRK/>
    a)  On or within <ENG>200 feet</ENG> <MET>61 m</MET> of runway<BRK/>
        sideline<BRK/>
    b)  On or within <ENG>50 feet</ENG> <MET>15 m</MET> of taxiway or<BRK/>
        apron sideline<BRK/>
    c)  Within Type 1 clear zone area as defined by<BRK/>
        NAVFAC Publication P-971 "Airfield &amp;<BRK/>
        Heliport Planning &amp; Design" dated March<BRK/>
        1998.<BRK/>
<BRK/>
2.  For rotary wing aircraft facilities:<BRK/>
    a)  On landing surfaces, primary surfaces, or<BRK/>
        within areas defined as "paved and unpaved<BRK/>
        shoulders" in NAVFAC Publication P-971<BRK/>
        "Airfield &amp; Heliport Planning &amp; Design" <BRK/>
        dated March 1998.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">[d.  Underground structures subject to aircraft loading are indicated on the drawings.]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Submittals must be limited to those necessary for adequate quality control.  
The importance of an item in the project should be one of the primary factors 
in determining if a submittal for the item should be required.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy projects.<BRK/>
<BRK/>
Submittal items not designated with a "G" are considered as being for information 
only for Army projects and for Contractor Quality Control approval for Navy 
projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are <TAI OPT="AIR FORCE,NAVY">[for Contractor Quality Control approval.]</TAI><TAI OPT="ARMY">[for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.] </TAI> The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Precast underground structures</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Submittals are required for each kind, voltage, or type used on the project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM><SUB>Medium voltage cable</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Medium voltage cable joints</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Medium voltage cable terminations</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Live end caps</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Precast concrete structures</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Sealing Material</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Pulling-In Irons</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Manhole frames and covers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Handhole frames and covers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Frames and Covers for Airfield Facilities</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Ductile Iron Frames and Covers for Airfield Facilities</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]]</ITM><BRK/>
<BRK/>
<ITM><SUB>Composite/fiberglass handholes</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Cable supports</SUB> (racks, arms and insulators)[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<TAI OPT="AIR FORCE,ARMY"><NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For Navy projects, do not use protective device coordination studies.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM>[<SUB>Protective Devices and Coordination</SUB> Study[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]]</ITM><BRK/>
<BRK/>
<ITM>[The study shall be submitted with protective device equipment submittals.  No time extension 
or similar contract modifications will be granted for work arising out of the requirements for 
this study.  Approval of protective devices proposed shall be based on recommendations of this 
study.  The Government shall not be held responsible for any changes to equipment, device ratings, 
settings, or additional labor for installation of equipment or devices ordered and/or procured 
prior to approval of the study.]</ITM><BRK/></TAI>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Arc-proofing test</SUB> for cable fireproofing materials[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Medium voltage cable qualification and production tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Field Acceptance Checks and Tests</SUB>; <SUB>G</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Arc-proofing test</SUB> for cable fireproofing tape[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use Cable Installation only when pulling cable between manholes; do not 
use for pulling from pole riser to manhole only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM><SUB>Cable Installation Plan and Procedure</SUB></ITM><BRK/>
<BRK/>
<ITM>  [Six] [_____] copies of the information described below in<MET> 215.9 by 279.4 mm (8-1/2 by 11 
inch)</MET><ENG> 8-1/2 by 11 inch</ENG> binders having a minimum of three rings from which material may readily 
be removed and replaced, including a separate section for each cable pull.  Sections shall be 
separated by heavy plastic dividers with tabs, with all data sheets signed and dated by the 
person supervising the pull.</ITM><BRK/>
<BRK/>
<ITM>  a.  Site layout drawing with cable pulls numerically identified.</ITM><BRK/>
<BRK/>
<ITM>  b.  A list of  equipment used, with calibration certifications. The manufacturer  and quantity 
of lubricant used on pull.</ITM><BRK/>
<BRK/>
<ITM>  c.  The cable manufacturer and type of cable.</ITM><BRK/>
<BRK/>
<ITM>  d.  The dates of cable pulls, time of day, and ambient temperature.</ITM><BRK/>
<BRK/>
<ITM>  e.  The length of cable pull and calculated cable pulling tensions.</ITM><BRK/>
<BRK/>
<ITM>  f.  The actual cable pulling tensions encountered during pull.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Cable splicer/terminator</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Cable Installer Qualifications</SUB></ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.4.1   <SUB>Precast Underground Structures</SUB></TTL><BRK/>
<BRK/>
<TXT>Submittal required for each type used.  Provide calculations and drawings for precast manholes and handholes 
bearing the seal of a registered professional engineer including:</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Material description (i.e., f'c and Fy)</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Manufacturer's printed assembly and installation instructions</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Design calculations</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">d.  Reinforcing shop drawingsin accordance with <RID>ACI SP-66</RID></LST><BRK/>
<BRK/>
<LST INDENT="-0.33">e.  Plans and elevations showing opening and pulling-in iron locations and details</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.2   Certificate of Competency for <SUB>Cable Splicer/Terminator</SUB></TTL><BRK/>
<BRK/>
<TXT>Certification of the qualification of the cable splicer/terminator shall be submitted, for approval, 30 days 
before splices or terminations are to be made in medium voltage (5 kV to 35 kV) cables.  The certification shall 
include the training, and experience of the individual on the specific type and classification of cable to be 
provided under this contract.  The certification shall indicate that the individual has had three or more years 
recent experience splicing and terminating medium voltage cables.  The certification shall also list a minimum 
of three splices/terminations that have been in operation for more than one year.  In addition, the individual 
may be required to perform a dummy or practice splice/termination in the presence of the Contracting Officer, 
before being approved as a qualified cable splicer.  If that additional requirement is imposed, the Contractor 
shall provide short sections of the approved types of cables along with the approved type of splice/termination 
kit, and detailed manufacturer's instructions for the cable to be spliced.  The Contracting Officer reserves 
the right to require additional proof of competency or to reject the individual and call for certification of 
an alternate cable splicer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.3   <SUB>Cable Installer Qualifications</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide at least one onsite person in a supervisory position with a documentable level of competency and experience 
to supervise all cable pulling operations.  Provide a resume showing the cable installers' experience in the 
last three years, including a list of references complete with points of contact, addresses and telephone numbers.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.4   Regulatory Requirements</TTL><BRK/>
<BRK/>
<TXT>In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the 
word, "shall" had been substituted for "should" wherever it appears.  Interpret references in these publications 
to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer.  Equipment, 
materials, installation, and workmanship shall be in accordance with the mandatory and advisory provisions of <RID>
NFPA 70</RID> unless more stringent requirements are specified or indicated.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.5   Standard Products</TTL><BRK/>
<BRK/>
<TXT>Provide materials and equipment that are products of manufacturers regularly engaged in the production of such 
products which are of equal material, design and workmanship.  Products shall have been in satisfactory commercial 
or industrial use for 2 years prior to bid opening.  The 2-year period shall include applications of equipment 
and materials under similar circumstances and of similar size.  The product shall have been on sale on the commercial 
market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.  Where two or 
more items of the same class of equipment are required, these items shall be products of a single manufacturer; 
however, the component parts of the item need not be the products of the same manufacturer unless stated in this 
section.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.4.5.1   Alternative Qualifications</TTL><BRK/>
<BRK/>
<TXT>Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory 
field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is 
furnished.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.5.2   Material and Equipment Manufacturing Date</TTL><BRK/>
<BRK/>
<TXT>Products manufactured more than 3 years prior to date of delivery to site shall not be used, unless specified 
otherwise.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT></PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   CONDUIT, DUCTS, AND FITTINGS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1.1   Rigid Metal Conduit</TTL><BRK/>
<BRK/>
<TXT><RID>UL 6</RID>.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.1.1   Rigid Metallic Conduit, PVC Coated</TTL><BRK/>
<BRK/>
<TXT><RID>NEMA RN 1</RID>, Type A40, except that hardness shall be nominal 85 Shore A durometer, dielectric strength shall be 
minimum<MET> 15.75 kV per mm</MET><ENG> 400 volts per mil</ENG> at 60 Hz, and tensile strength shall be minimum<MET> 25 MPa</MET><ENG> 3500 psi</ENG>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.1.2   Intermediate Metal Conduit</TTL><BRK/>
<BRK/>
<TXT><RID>UL 1242</RID>.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.2.1   Intermediate Metal Conduit, PVC Coated</TTL><BRK/>
<BRK/>
<TXT><RID>NEMA RN 1</RID>, Type A40, except that hardness shall be nominal 85 Shore A durometer, dielectric strength shall be 
minimum<MET> 15.75 kV per mm</MET><ENG> 400 volts per mil</ENG> at 60 Hz, and tensile strength shall be minimum<MET> 25 MPa</MET><ENG> 3500 psi</ENG>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.1.3   Plastic Conduit for Direct Burial</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: Specify EPC-40-PVC or EPC-80-PVC for direct-burial and riser applications.  
Choose UL 651 where conduit is required to be in compliance with NFPA 70 and 
for most applications.  Choose NEMA TC 2 when conduit size is greater than 6 
inches.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[<RID>UL 651</RID>,[Schedule 40] [or] [Schedule 80][as indicated]][<RID>NEMA TC 2</RID>, [EPC-40-PVC] [or] [EPC-80-PVC][as indicated]].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.4   Plastic Duct for Concrete Encasement</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify EPC-40-PVC or EPC-80-PVC for transition to riser applications.      <BRK/>
<BRK/>
EPC-20 and EPC-35 both perform the same functions of providing a form for the 
concrete.  Only EPC-20 is UL listed.  Choose EB-35 where breakage during handling 
is a concern.  Choose EPC-40-PVC where required for design loads or for activity 
requirements. </NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NEMA TC 6 &amp; 8</RID> and <RID>ASTM F 512</RID>, [<RID>UL 651A</RID> Type EPC-20-PVC] [Type EPC-35-PVC] [ UL 651, EPC-40-PVC] [or] [as 
indicated].</TXT><BRK/>
<BRK/></SPT>
<TAI OPT="AIR FORCE,ARMY"><SPT>[<TTL>2.1.5   Bituminized Fiber Duct</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: Do not use for Navy projects.<BRK/>
<BRK/>
For Army and Air Force projects, bituminized fiber duct should be specified 
only for connection to existing bituminized fiber duct systems.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>UL 1684</RID> for [Type I (Thinwall)][Type II (Thickwall)].</TXT><BRK/>
<BRK/>
]</SPT></TAI><SPT><TTL>2.1.6   Innerduct</TTL><BRK/>
<BRK/>
<TXT>Provide corrugated [or solid wall] polyethylene (PE) or PVC innerducts with pullwire.  Size as indicated.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.7   Conduit Sealing Compound</TTL><BRK/>
<BRK/>
<TXT>Compounds for sealing ducts and conduit shall have a putty-like consistency workable with the hands at temperatures 
as low as<MET> 2 degrees C (35 degrees F),</MET><ENG> 35 degrees F,</ENG> shall neither slump at a temperature of<MET> 150 degrees C (300 
degrees F),</MET><ENG> 300 degrees F,</ENG> nor harden materially when exposed to the air.  Compounds shall adhere to clean surfaces 
of fiber or plastic ducts; metallic conduits or conduit coatings; concrete, masonry, or lead; any cable sheaths, 
jackets, covers, or insulation materials; and the common metals.  Compounds shall form a seal without dissolving, 
noticeably changing characteristics, or removing any of the ingredients.  Compounds shall have no injurious effect 
upon the hands of workmen or upon materials.  Inflatable bladders may be used as an option.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.8   Fittings</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1.8.1   Metal Fittings</TTL><BRK/>
<BRK/>
<TXT><RID>UL 514B</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.8.2   PVC Conduit Fittings</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Choose UL listed fittings for most applications and where conduit is 
required to comply with NFPA 70.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[<RID>UL 514B</RID>, <RID>UL 651</RID>][<RID>NEMA TC 3</RID>].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.8.3   PVC Duct Fittings</TTL><BRK/>
<BRK/>
<TXT><RID>NEMA TC 9</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.1.8.4   Outlet Boxes for Steel Conduit</TTL><BRK/>
<BRK/>
<TXT>Outlet boxes for use with rigid or flexible steel conduit shall be cast-metal cadmium or zinc-coated if of ferrous 
metal with gasketed closures and shall conform to <RID>UL 514A</RID>.</TXT><BRK/>
<BRK/>
]</SPT></SPT></SPT><SPT><TTL>2.2   LOW VOLTAGE INSULATED CONDUCTORS AND CABLES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  In most cases NFPA 70 requires listed conductors and cable.  Choose bracketed 
item for NEMA WC 70 only when compliance with NFPA 70 is not required. </NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Insulated conductors shall be rated 600 volts and conform to the requirements of <RID>NFPA 70</RID>, including listing requirements[, 
or in accordance with <RID>NEMA WC 70</RID>].  Wires and cables manufactured more than [24] [12] months prior to date of 
delivery to the site shall not be accepted.  Service entrance conductors shall conform to <RID>UL 854</RID>, type USE.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.1   Conductor Types</TTL><BRK/>
<BRK/>
<TXT>Cable and duct sizes indicated are for copper conductors and THHN/THWN unless otherwise noted. [Conductors No.  
10 AWG and smaller shall be solid copper.  Conductors No. 8 AWG and larger shall be stranded copper.]  [All conductors 
shall be copper.]  [Conductors No. 6 AWG and smaller shall be copper.  Conductors No. 4 AWG and larger shall 
be either copper or aluminum, at the Contractor's option.[  As an exception, do not substitute aluminum for copper 
if the equivalent aluminum conductor size would exceed 500 kcmil.]][  Should the Contractor choose to use aluminum 
for conductors No. 4 AWG and larger, the Contractor shall be responsible for:  Increasing the conductor size 
to have the same ampacity as the copper size indicated; increasing the conduit and pull box sizes to accommodate 
the larger size aluminum conductors in accordance with <RID>NFPA 70</RID>; ensuring that the pulling tension rating of the 
aluminum conductor is sufficient; relocating equipment, modifying equipment terminations, resizing equipment, 
and resolving to the satisfaction of the Contracting Officer problems that are direct results of the use of aluminum 
conductors in lieu of copper.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.2   Conductor Material</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For project applications which require a different insulation than those 
listed below, reference a Government or industry standard that the cable or 
conductor must meet.  For projects which require multiple types of insulations, 
indicate the type for each cable on the project drawings.  Refer to UFC 3-550-1 
for further guidance.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Unless specified or indicated otherwise or required by <RID>NFPA 70</RID>, wires in conduit, other than service entrance, 
shall be 600-volt,[  Type THWN/THHN conforming to <RID>UL 83</RID>][ or][ Type[ XHHW][ or][ RHW] conforming to <RID>UL 44</RID>].  
Copper conductors shall be annealed copper complying with <RID>ASTM B 3</RID> and <RID>ASTM B 8</RID>.  Aluminum conductors shall be 
Type AA-8000 aluminum conductors complying with <RID>ASTM B 800</RID> and <RID>ASTM B 801</RID>, and shall be of an aluminum alloy 
listed or labeled by UL as "component aluminum-wire stock (conductor material).  Type EC/1350 is not acceptable.  
Intermixing of copper and aluminum conductors is not permitted.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.2.3   Jackets </TTL><BRK/>
<BRK/>
<TXT>Multiconductor cables shall have an overall PVC outer jacket.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.2.4   Direct Buried</TTL><BRK/>
<BRK/>
<TXT>Single-conductor [and multi-conductor ]cables shall be of a type identified for direct burial.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.5   In Duct</TTL><BRK/>
<TAI OPT="AIR FORCE,ARMY"><NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For Army and Air Force projects only, coilable plastic duct may be used 
as an alternative to direct burial where extra physical protection is required.</NPR><BRK/>
<AST/><BRK/></NTE>
</TAI><BRK/>
<TXT>Cables shall be single-conductor cable.<TAI OPT="AIR FORCE,ARMY">[  Cables in factory-installed, coilable-plastic-duct assemblies shall 
conform to <RID>NEMA TC 7</RID>.]</TAI></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.6   Cable Marking</TTL><BRK/>
<BRK/>
<TXT>Insulated conductors shall have the date of manufacture and other identification imprinted on the outer surface 
of each cable at regular intervals throughout the cable length. <BRK/>
<BRK/>
Each cable shall be identified by means of a fiber, laminated plastic, or non-ferrous metal tags, or approved 
equal, in each manhole, handhole, junction box, and each terminal.  Each tag shall contain the following information; 
cable type, conductor size, circuit number, circuit voltage, cable destination and phase identification.<BRK/>
<BRK/>
Conductors shall be color coded.  Conductor identification shall be provided within each enclosure where a tap, 
splice, or termination is made.  Conductor identification shall be by color-coded insulated conductors, plastic-coated 
self-sticking printed markers, colored nylon cable ties and plates, heat shrink type sleeves,or colored electrical 
tape. Control circuit terminations shall be properly identified. Color shall be green for grounding conductors 
and white for neutrals; except where neutrals of more than one system are installed in same raceway or box, other 
neutrals shall be white with a different colored (not green) stripe for each.  Color of ungrounded conductors 
in different voltage systems shall be as follows</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  208/120 volt, three-phase</ITM><BRK/>
<BRK/>
<ITM>(1)  Phase A - black</ITM><BRK/>
<BRK/>
<ITM>(2)  Phase B - red</ITM><BRK/>
<BRK/>
<ITM>(3)  Phase C - blue</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  480/277 volt, three-phase</ITM><BRK/>
<BRK/>
<ITM>(1)  Phase A - brown</ITM><BRK/>
<BRK/>
<ITM>(2)  Phase B - orange</ITM><BRK/>
<BRK/>
<ITM>(3)  Phase C - yellow</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  120/240 volt, single phase:  Black and red</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[d.  On three-phase, four-wire delta system, high leg shall be orange, as required by <RID>NFPA 70</RID>
.]</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.3   LOW VOLTAGE WIRE CONNECTORS AND TERMINALS</TTL><BRK/>
<BRK/>
<TXT>Shall provide a uniform compression over the entire conductor contact surface.  Use solderless terminal lugs 
on stranded conductors.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  For use with copper conductors:  <RID>UL 486A-486B</RID>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  For use with aluminum conductors:  <RID>UL 486A-486B</RID>.  For connecting aluminum to copper, connectors 
shall be the circumferentially compressed, metallurgically bonded type.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4   LOW VOLTAGE SPLICES</TTL><BRK/>
<BRK/>
<TXT>Provide splices in conductors with a compression connector on the conductor and by insulating and waterproofing 
using one of the following methods which are suitable for continuous submersion in water and comply <RID>NEMA C119.1</RID>
.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.4.1   Heat Shrinkable Splice</TTL><BRK/>
<BRK/>
<TXT>Provide heat shrinkable splice insulation by means of a thermoplastic adhesive sealant material which shall be 
applied in accordance with the manufacturer's written instructions.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.2   Cold Shrink Rubber Splice</TTL><BRK/>
<BRK/>
<TXT>Provide a cold-shrink rubber splice which consists of EPDM rubber tube which has been factory stretched onto 
a spiraled core which is removed during splice installation.  The installation shall not require heat or flame, 
or any additional materials such as covering or adhesive.  It shall be designed for use with inline compression 
type connectors, or indoor, outdoor, direct-burial or submerged locations.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.5   <SUB>MEDIUM VOLTAGE CABLE</SUB></TTL><BRK/>
<BRK/>
<TXT>Cable (conductor) sizes are designated by American Wire Gauge (AWG) and Thousand Circular Mils (Kcmil).  Conductor 
and conduit sizes indicated are for copper conductors unless otherwise noted.  Insulated conductors shall have 
the date of manufacture and other identification imprinted on the outer surface of each cable at regular intervals 
throughout cable length.  Wires and cables manufactured more than [24][12] months prior to date of delivery to 
the site shall not be accepted.  Provide single conductor type cables unless otherwise indicated.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.5.1   Cable Configuration</TTL><BRK/>
<TAI OPT="NAVY"><NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For Navy projects, use type MV only and delete requirements for concentric 
neutrals throughout.</NPR><BRK/>
<AST/><BRK/></NTE>
</TAI><TAI OPT="AIR FORCE,ARMY"><NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For Army and Air Force projects:<BRK/>
<BRK/>
The two most commonly produced/specified medium voltage cables are Type MV (as 
described in UL 1072) and underground distribution ("UD/URD"), commonly used 
by electrical utilities.  Type MV is a type designation recognized by NFPA 70 
because it is UL listed.  "UD/URD" is not a recognized type designation because 
it is utilized primarily by electrical utilities, who are not governed by NFPA 
70 and for whom a UL listed cable adds unnecessary expense.  Both type MV and 
"UD/URD" can be specified for use in duct or direct buried.  In addition to 
the standard MV-90, NFPA 70 also lists an MV-105 temperature rating.  However, 
MV-105 is not available from all manufacturers.  Provide MV-105, only if needed. <BRK/>
<BRK/>
Use either Type MV or "UD/URD" in ducts, keeping in mind that the concentric 
neutral affects bending radius and pulling tensions, therefore limiting the 
maximum pull and distance between manholes.  Use "UD" for direct buried applications.   <BRK/>
<BRK/>
Choose 133 percent insulation level on 5 kV, 15 kV and 25 kV rated cables.</NPR><BRK/>
<AST/><BRK/></NTE>
</TAI><BRK/>
<TXT>Provide [Type MV cable, conforming to <RID>NEMA WC 74</RID> and <RID>UL 1072</RID>] <TAI OPT="AIR FORCE,ARMY">[concentric neutral underground distribution cable 
conforming to <RID>ICEA S-94-649</RID>] [metallic armored cables, consisting of three-conductor, multi-conductor cables, 
with insulation and shielding, as specified, using [a galvanized steel] [an aluminum] interlocked tape armor 
and thermoplastic jacket]</TAI>.  Provide cables manufactured for use in [duct] [or] [direct burial] applications [as 
indicated]. Cable shall be rated [5 kV] [15 kV] [25 kV] [28 kV] [35 kV] [as indicated] with [100][133] percent 
insulation level.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.2   Conductor Material</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  A concentric compressed conductor has a diameter that is 3 percent less 
than a regular concentric conductor.  A compact conductor has a diameter that 
is 10 percent less than a regular concentric conductor.  Edit to specify compact 
conductors where necessary to limit duct fill (i.e. where new conductors are 
installed in existing ducts).</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide concentric-lay-stranded, Class B [compact round] conductors.  Provide [soft drawn copper cables complying 
with <RID>ASTM B 3</RID> and <RID>ASTM B 8</RID> for regular concentric and compressed stranding or <RID>ASTM B 496</RID> for compact stranding] 
[aluminum alloy 1350 cables, 3/4 hard minimum complying with <RID>ASTM B 609/B 609M</RID> and <RID>ASTM B 231/B 231M</RID> for regular 
concentric and compressed stranding or <RID>ASTM B 400</RID> for compacted stranding].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.3   Insulation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For projects which require multiple types of insulations, or special 
types of cables, such as submarine cable, indicate the type for each cable on 
the project drawings.  Choose XLP or tree retardant XLP for "UD or URD" cable 
and either XLP or EPR for Type MV cable.<BRK/>
  <BRK/>
Choose AEIC CS8, except for concentric neutral cable only, choose ICEA S-94-649.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide [ethylene-propylene-rubber (EPR) insulation conforming to the requirements of <RID>NEMA WC 71</RID> and [<RID>AEIC CS8</RID>
][<RID>ICEA S-94-649</RID>]] [tree-retardant cross-linked thermosetting polyethylene (XLP) insulation conforming to the 
requirements of <RID>NEMA WC 74</RID> and [<RID>AEIC CS8</RID>][<RID>ICEA S-94-649</RID>]].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.4   Shielding</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Choose tape shielding unless wire shielding is allowed or required by 
the Activity.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Cables rated for 2 kV and above shall have a semiconducting conductor shield, a semiconducting insulation shield, 
and an overall copper [tape] [or] [wire] shield for each phase.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.5   Neutrals</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use first bracketed sentence for type MV cable and second bracketed sentence 
for type UD/URD cable.  <BRK/>
<BRK/>
In second bracketed sentence, select full ampacity concentric neutral for single-phase 
applications and one-third ampacity for three-phase applications.<BRK/>
<BRK/>
Include the last bracketed sentence where high impedance grounded neutral systems 
are employed.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Neutral conductors of shall be [copper] [aluminum], employing the same insulation and jacket materials as phase 
conductors, except that a 600-volt insulation rating is acceptable.] <TAI OPT="AIR FORCE,ARMY">[Concentric neutrals conductors shall be 
copper, having a combined ampacity [equal to] [1/3 of] the phase conductor ampacity rating.  ]</TAI>[For high impedance 
grounded neutral systems, the neutral conductors from the neutral point of the transformer or generator to the 
connection point at the impedance shall utilize [copper] [aluminum] conductors, employing the same insulation 
level and construction as the phase conductors.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.6   Jackets</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Polyethylene (LLDPE) is exceptional for direct burial and in duct applications 
where there is significant amounts of water.  PVC is acceptable for duct applications.  
There are many other types of jacket materials available (neoprene, hypalon, 
thermoplastic CPE) for special environments involving exposure to sunlight, 
petroleum products, and corrosive chemicals.  Consult local cable representatives 
to specify the appropriate jacket for the application. <BRK/>
<BRK/>
Choose the last bracketed sentence when PVC is specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Cables shall be provided with a [LLDPE][PVC][_____] jacket.  Direct buried cables shall be rated for direct burial. <TAI OPT="AIR FORCE,ARMY">
 Provide type UD cables with an overall jacket.</TAI>[  Provide PVC jackets with a separator that prevents contact 
when underlying semiconducting insulating shield.]</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.6   <SUB>MEDIUM VOLTAGE CABLE TERMINATIONS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specification sections for equipment, such as pad-mounted transformers, 
SF-6 switches, and unit substations, contain paragraphs for terminations, and 
have not been updated to coordinate with this specification section.  When this 
paragraph is used only for that equipment, specify terminations either in that 
section or in this section, and delete paragraph from the other section.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Indoor terminator/outdoor terminations shall be provided with skirts. 
By including skirts for "indoor" and "within equipment" locations, tracking 
resistance is significantly improved. Provision of skirts for indoor terminations 
automatically makes them IEEE Std 48 Class 1.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>IEEE Std 48</RID> Class 1; of the molded elastomer, prestretched elastomer, or heat-shrinkable elastomer.  Acceptable 
elastomers are track-resistant silicone rubber or track-resistant ethylene propylene compounds, such as ethylene 
propylene rubber or ethylene propylene diene monomer.  Separable insulated connectors may be used for apparatus 
terminations, when such apparatus is provided with suitable bushings. Terminations, where required, shall be 
provided with mounting brackets suitable for the intended installation and with grounding provisions for the 
cable shielding, metallic sheath, or armor.  Terminations shall be provided in a kit, including: skirts, stress 
control terminator, ground clamp, connectors, lugs, and complete instructions for assembly and installation.  
Terminations shall be the product of one manufacturer, suitable for the type, diameter, insulation class and 
level, and materials of the cable terminated.  Do not use separate parts of copper or copper alloy in contact 
with aluminum alloy parts in the construction or installation of the terminator.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.6.1   Cold-Shrink Type</TTL><BRK/>
<BRK/>
<TXT>Terminator shall be a one-piece design, utilizing the manufacturer's latest technology, where high-dielectric 
constant (capacitive) stress control is integrated within a skirted insulator made of silicone rubber.  Termination 
shall not require heat or flame for installation.  Termination kit shall contain all necessary materials (except 
for the lugs).  Termination shall be designed for installation in low or highly contaminated indoor and outdoor 
locations and shall resist ultraviolet rays and oxidative decomposition.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6.2   Heat Shrinkable Type</TTL><BRK/>
<BRK/>
<TXT>Terminator shall consist of a uniform cross section heat shrinkable polymeric construction stress relief tubing 
and environmentally sealed outer covering that is nontracking, resists heavy atmospheric contaminants, ultra 
violet rays and oxidative decomposition.  Provide heat shrinkable sheds or skirts of the same material.  Termination 
shall be designed for installation in low or highly contaminated indoor or outdoor locations.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6.3   Separable Insulated Connector Type</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate the connector ratings required with the equipment specification 
for transformers and switches.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>IEEE Std 386</RID>.  Provide connector with steel reinforced hook-stick eye, grounding eye, test point, and arc-quenching 
contact material.  Provide connectors of the loadbreak or deadbreak type as indicated, of suitable construction 
for the application and the type of cable connected, and that include cable shield adaptors.  Provide external 
clamping points and test points.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">[a.  200 Ampere loadbreak connector ratings:  Voltage:  [15 kV, 95 kV BIL][25 kV, 125 kV BIL][35 
kV, 150 kV BIL].  Short time rating:  10,000 rms symmetrical amperes.]</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: For Navy projects, provide 200 ampere bushing interface on all 600 ampere 
connectors.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">[b.  600 Ampere deadbreak connector ratings:  Voltage:  [15 kV, 95 kV BIL][25 kV, 125 kV BIL][35 
kV, 150 kV BIL].  Short time rating:  25,000 rms symmetrical amperes.[  Connectors shall have 
200 ampere bushing interface[ for surge arresters][ as indicated].]]</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: Include the following paragraph only when the activity requires additional 
grounding elbows and feed-thru inserts.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">[c.  Provide[ [one][____] set[s] of three grounding elbows][ and][ [one][____] set[s] of three 
feed-thru inserts].  [Grounding elbows][ and ][feed-thru inserts] shall be delivered to the 
Contracting Officer.]</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.7   <SUB>MEDIUM VOLTAGE CABLE JOINTS</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide joints (splices) in accordance with <RID>IEEE Std 404</RID> suitable for the rated voltage, insulation level, insulation 
type, and construction of the cable.  Joints shall be certified by the manufacturer for waterproof, submersible 
applications.  Upon request, supply manufacturer's design qualification test report in accordance with <RID>IEEE Std 404</RID>
.  Connectors for joint shall be tin-plated electrolytic copper, having ends tapered and having center stops 
to equalize cable insertion.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.7.1   Heat-Shrinkable Joint</TTL><BRK/>
<BRK/>
<TXT>Consists of a uniform cross-section heat-shrinkable polymeric construction with a linear stress relief system, 
a high dielectric strength insulating material, and an integrally bonded outer conductor layer for shielding.  
Replace original cable jacket with a heavy-wall heat-shrinkable sleeve with hot-melt adhesive coating.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2   Cold-Shrink Rubber-Type Joint</TTL><BRK/>
<BRK/>
<TXT>Joint shall be of a cold shrink design that does not require any heat source for its installation.  Splice insulation 
and jacket shall be of a one-piece factory formed cold shrink sleeve made of black EPDM rubber.  Splice shall 
be packaged three splices per kit, including complete installation instructions.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.8   TELECOMMUNICATIONS CABLING</TTL><BRK/>
<BRK/>
<TXT>Provide telecommunications cabling in accordance with Section <SRF>33 82 00</SRF> TELECOMMUNICATIONS OUTSIDE PLANT (OSP).</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.9   <SUB>LIVE END CAPS</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide live end caps using a "kit" including a heat-shrinkable tube and a high dielectric strength, polymeric 
plug overlapping the conductor.  End cap shall conform to applicable portions of <RID>IEEE Std 48</RID>.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.10   TAPE</TTL><BRK/>
<BRK/>
<SPT><TTL>2.10.1   Insulating Tape</TTL><BRK/>
<BRK/>
<TXT><RID>UL 510</RID>, plastic insulating tape, capable of performing in a continuous temperature environment of 80 degrees 
C.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.10.2   Buried Warning and Identification Tape</TTL><BRK/>
<BRK/>
<TXT>Provide detectable tape in accordance with Section [<SRF>31 23 00.00 20</SRF> EXCAVATION AND FILL][<SRF>31 00 00</SRF> EARTHWORK]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.10.3   Fireproofing Tape</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide the following paragraph where medium voltage cable (2200 volts 
or greater) is installed in manholes, handholes and vaults.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide tape composed of a flexible conformable unsupported intumescent elastomer.  Tape shall be not less than<MET>
 0.762 mm</MET><ENG> .030 inch</ENG> thick, noncorrosive to cable sheath, self-extinguishing, noncombustible, and shall not deteriorate 
when subjected to oil, water, gases, salt water, sewage, and fungus.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.11   PULL ROPE</TTL><BRK/>
<BRK/>
<TXT>Shall be plastic or flat pull line (bull line) having a minimum tensile strength of<MET> 890 N</MET><ENG> 200 pounds</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12   GROUNDING AND BONDING</TTL><BRK/>
<BRK/>
<SPT><TTL>2.12.1   Driven Ground Rods</TTL><BRK/>
<BRK/>
<TXT>Provide [copper-clad steel ground rods conforming to <RID>UL 467</RID>] [zinc-coated steel ground rods conforming to <RID>ANSI C135.30</RID>
] [solid stainless steel ground rods] not less than [<MET> 19 mm (3/4 inch)</MET><ENG> 3/4 inch</ENG>] in diameter by [<MET>3.1 m (10 feet)</MET><ENG>
 10 feet</ENG>] in length.  Sectional type rods may be used for rods 20 feet or longer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12.2   Grounding Conductors</TTL><BRK/>
<BRK/>
<TXT>Stranded-bare copper conductors shall conform to <RID>ASTM B 8</RID>, Class B, soft-drawn unless otherwise indicated.  Solid-bare 
copper conductors shall conform to <RID>ASTM B 1</RID> for sizes No. 8 and smaller.  Insulated conductors shall be of the 
same material as phase conductors and green color-coded, except that conductors shall be rated no more than 600 
volts.  Aluminum is not acceptable.  </TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.13   CAST-IN-PLACE CONCRETE</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use the first bracketed paragraph when project includes a concrete section 
in Division 3; otherwise, the second bracketed paragraph may be used.  Coordinate 
requirements with Section 03 30 00, CAST-IN-PLACE CONCRETE for Navy projects 
and with 03 31 00.00 10 CAST-IN-PLACE STRUCTURALCONCRETE for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide concrete in accordance with Section [<SRF>03 30 00</SRF> CAST-IN-PLACE CONCRETE] [<SRF>03 31 00.00 10</SRF> CAST-IN-PLACE STRUCTURAL 
CONCRETE].  In addition, provide concrete for encasement of underground ducts with<MET> 20 MPa</MET><ENG> 3000 psi</ENG> minimum 28-day 
compressive strength.  Concrete associated with electrical work for other than encasement of underground ducts 
shall be<MET> 30 MPa</MET><ENG> 4000 psi</ENG> minimum 28-day compressive strength unless specified otherwise.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14   UNDERGROUND STRUCTURES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit this paragraph to comply with project requirements concerning the 
type of structure or duct, strength of concrete, concrete mix, metal accessories, 
and excavating and grading. Indicate special reinforcing where required, particularly 
with duct banks of non-rectangular cross-section.  Contact local telephone company, 
where applicable, concerning the size of all signal manholes and the number 
and type of signal duct required.  Determine availability since aircraft or 
H20 highway loadings may not be available in precast.<BRK/>
<BRK/>
For Navy projects only, see standard sketches UG-1 through UG-7, covering manholes 
and handholes located at the Whole Building Design Guide, NAVFAC Specification 
Graphics: http://www.wbdg.org/ccb/NAVGRAPH/UFGS%20and%20NAVFAC%20Graphics%20TOC.pdf.  
Include the required sketches on the project drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide precast concrete underground structures or standard type cast-in-place manhole types as indicated, conforming 
to <RID>ASTM C 857</RID> and <MET><RID>ASTM C 478M</RID></MET> <ENG><RID>ASTM C 478</RID></ENG>.  Top, walls, and bottom shall consist of reinforced concrete.  Walls 
and bottom shall be of monolithic concrete construction.  Locate duct entrances and windows near the corners 
of structures to facilitate cable racking.  Covers shall fit the frames without undue play.  Form steel and iron 
to shape and size with sharp lines and angles.  Castings shall be free from warp and blow holes that may impair 
strength or appearance.  Exposed metal shall have a smooth finish and sharp lines and arises.  Provide necessary 
lugs, rabbets, and brackets.  Set pulling-in irons and other built-in items in place before depositing concrete.  
Install a pulling-in iron in the wall opposite each duct line entrance.  Cable racks, including rack arms and 
insulators, shall be adequate to accommodate the cable.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.14.1   Cast-In-Place Concrete Structures</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit bracketed items at designer's discretion and as required where aircraft 
loading is in project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Concrete shall conform to Section [<SRF>03 30 00</SRF> CAST-IN-PLACE CONCRETE] [<SRF>03 31 00.00 10</SRF> CAST-IN-PLACE STRUCTURAL 
CONCRETE].  [Construct walls on a footing of cast-in-place concrete except that precast concrete base sections 
may be used for precast concrete manhole risers].  [Concrete block shall conform to <RID>ASTM C 139</RID> and Section 
<SRF>04 20 00</SRF>,  MASONRY.]  [Concrete block is not allowed in areas subject to aircraft loading.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.2   Precast Concrete Structures, Risers and Tops</TTL><BRK/>
<BRK/>
<TXT>In lieu of cast-in-place, Contractors, at their option, may provide precast concrete underground structures subject 
to the requirements specified below.  Precast units shall be the product of a manufacturer regularly engaged 
in the manufacture of precast concrete products, including precast manholes.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.14.2.1   General</TTL><BRK/>
<BRK/>
<TXT><SUB>Precast concrete structures</SUB> shall have the same accessories and facilities as required for cast-in-place structures.  
Likewise, precast structures shall have plan area and clear heights not less than those of cast-in-place structures.  
Concrete materials and methods of construction shall be the same as for cast-in-place concrete construction, 
as modified herein.  Slope in floor may be omitted provided precast sections are poured in reinforced steel forms.  
Concrete for precast work shall have a 28-day compressive strength of not less than<MET> 30 MPa</MET><ENG> 4000 psi</ENG>.  Structures 
may be precast to the design and details indicated for cast-in-place construction, precast monolithically and 
placed as a unit, or structures may be assembled sections, designed and produced by the manufacturer in accordance 
with the requirements specified.  Structures shall be identified with the manufacturer's name embedded in or 
otherwise permanently attached to an interior wall face.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.2.2   Design for Precast Structures</TTL><BRK/>
<BRK/>
<TXT><RID>ACI 318M</RID>.  In the absence of detailed on-site soil information, design for the following soil parameters/site 
conditions:</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Angle of Internal Friction (phi) =<MET> 0.523 rad</MET><ENG> 30 degrees</ENG></LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Unit Weight of Soil (Dry) = <MET> 1760 kg/m<SPS>3</SPS></MET><ENG> 110 pcf</ENG>, (Saturated)<BRK/>
=<MET> 2080 kg/m<SPS>3</SPS></MET><ENG> 130 pcf</ENG></LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Coefficient of Lateral Earth Pressure (Ka) = 0.33</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">d.  Ground Water Level = <MET> 915 mm</MET><ENG> 3 feet</ENG> below ground elevation</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify H20 highway loading for most locations.  Revise as required if 
loading in excess of H20 highway loading is required.<BRK/>
<BRK/>
Indicate structures subject to aircraft loading on the drawings.  Also show 
structure design requirements on the drawings.  Decks and covers subject to 
aircraft loadings shall be designed for loadings per FAA AC-150/5320-6 except 
as follows:<BRK/>
<BRK/>
a.  Covers shall be designed for <ENG>100,000 lb</ENG><MET>45 000 kg</MET> wheel loads with <ENG>250 psi</ENG><MET>
1.72 MPa</MET> tire pressure.<BRK/>
<BRK/>
b.  For spans of less than <ENG>2 feet</ENG><MET>0.6 m</MET> in the least direction, a uniform live 
load of <ENG>325 psi</ENG><MET>2.24 Mpa</MET> shall be used.<BRK/>
<BRK/>
c.  For spans of <ENG>2 feet</ENG><MET>0.6 m</MET> or greater in the least direction, the design shall 
be based on the number of wheels which will fit the span. Wheel loads of <ENG>75,000 
pounds</ENG><MET>34,000 kg</MET> each shall be used.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">e.  Vertical design loads shall include full dead, superimposed dead, and live loads including a 30 percent 
magnification factor for impact.  Live loads shall consider all types and magnitudes of vehicular (automotive, 
industrial, or aircraft) traffic to be encountered.  The minimum design vertical load shall be for H20 
highway loading per <RID>AASHTO HB-17</RID>.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">f.  Horizontal design loads shall include full geostatic and hydrostatic pressures for the soil parameters, 
water table, and depth of installation to be encountered.  Also, horizontal loads imposed by adjacent 
structure foundations, and horizontal load components of vertical design loads, including impact, shall 
be considered, along with a pulling-in iron design load of<MET> 26,700 N</MET><ENG> 6000 pounds</ENG>.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">g.  Each structural component shall be designed for the load combination and positioning resulting in 
the maximum shear and moment for that particular component.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">h.  Design shall also consider the live loads induced in the handling, installation, and backfilling 
of the manholes.  Provide lifting devices to ensure structural integrity during handling and installation.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.2.3   Construction</TTL><BRK/>
<BRK/>
<TXT>Structure top, bottom, and wall shall be of a uniform thickness of not less than<MET> 150 mm</MET><ENG> 6 inches</ENG>.  Thin-walled 
knock-out panels for designed or future duct bank entrances shall not be permitted.  Quantity, size, and location 
of duct bank entrance windows shall be as directed, and cast completely open by the precaster.  Size of windows 
shall exceed the nominal duct bank envelope dimensions by at least<MET> 305 mm</MET><ENG> 12 inches</ENG> vertically and horizontally 
to preclude in-field window modifications made necessary by duct bank misalignment.  However, the sides of precast 
windows shall be a minimum of<MET> 150 mm</MET><ENG> 6 inches</ENG> from the inside surface of adjacent walls, floors, or ceilings.  
Form the perimeter of precast window openings to have a keyed or inward flared surface to provide a positive 
interlock with the mating duct bank envelope.  Provide welded wire fabric reinforcing through window openings 
for in-field cutting and flaring into duct bank envelopes.  Provide additional reinforcing steel comprised of 
at least two No. 4 bars around window openings.  Provide drain sumps a minimum of<MET> 305 mm</MET><ENG> 12 inches</ENG> in diameter 
and<MET> 100 mm</MET><ENG> 4 inches</ENG> deep for precast structures.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.2.4   Joints</TTL><BRK/>
<BRK/>
<TXT>Provide tongue-and-groove joints on mating edges of precast components.  Shiplap joints are not allowed.  Design 
joints to firmly interlock adjoining components and to provide waterproof junctions and adequate shear transfer.  
Seal joints watertight using preformed plastic strip conforming to <RID>AASHTO M 198</RID>, Type B.  Install <SUB>sealing material</SUB>
 in strict accordance with the sealant manufacturer's printed instructions.  Provide waterproofing at conduit/duct 
entrances into structures, and where access frame meets the top slab, provide continuous grout seal.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.14.3   <SUB>Manhole Frames and Covers</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide cast iron frames and covers for manholes conforming to <RID>CID A-A-60005</RID>.  Cast the words "ELECTRIC" or "TELECOMMUNICATIONS" 
in the top face of power and telecommunications manhole covers, respectively.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.4   <SUB>Handhole Frames and Covers</SUB></TTL><BRK/>
<BRK/>
<TXT>Frames and covers of steel shall be welded by qualified welders in accordance with standard commercial practice.  
Steel covers shall be rolled-steel floor plate having an approved antislip surface.  Hinges shall be of [stainless 
steel with bronze hinge pin] [wrought steel],<MET> 125 by 125 mm</MET><ENG> 5 by 5 inches</ENG> by approximately<MET> 4.75 mm</MET><ENG> 3/16 inch</ENG> 
thick, without screw holes, and shall be for full surface application by fillet welding.  Hinges shall have nonremovable 
pins and five knuckles.  The surfaces of plates under hinges shall be true after the removal of raised antislip 
surface, by grinding or other approved method.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.14.5   <SUB>Frames and Covers for Airfield Facilities</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use this paragraph for structures subject to aircraft loading.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Fabricate frames and covers for airfield use of standard commercial grade steel welded by qualified welders in 
accordance with <RID>AWS D1.1/D1.1M</RID>.  Covers shall be of rolled steel floor plate having an approved anti-slip surface.  
Steel frames and covers shall be hot dipped galvanized after fabrication.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.14.6   <SUB>Ductile Iron Frames and Covers for Airfield Facilities</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  As an option, the designer may also allow the use of this paragraph for 
structures subject to aircraft loading.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>At the contractor's option, ductile iron covers and frames designed for a minimum proof load of <ENG>100,000 pounds</ENG>
 <MET>45,000 kg</MET>, may be provided in lieu of the steel frames and covers indicated.  Covers shall be of the same material 
as the frames (i.e. ductile iron frame with ductile iron cover, galvanized steel frame with galvanized steel 
cover).  Proof loading shall be performed in accordance with <RID>CID A-A-60005</RID> and <RID>ASTM A 48/A 48M</RID>.  Proof loads 
shall be physically stamped into the cover.  Provide the Contracting Officer copies of previous proof load test 
results performed on the same frames and covers as proposed for this contract.  The top of the structure shall 
be modified to accept the ductile iron structure in lieu of the steel structure indicated.  The finished structure 
shall be level and non-rocking, with the top flush with the surrounding pavement.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.14.7   Brick for Manhole Collar</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Do not use brick for manholes in Iceland.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Brick shall be sewer and manhole brick conforming to <RID>ASTM C 32</RID>, Grade MS.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.8   <SUB>Composite/Fiberglass Handholes</SUB> and Covers</TTL><BRK/>
<BRK/>
<TXT>Provide handholes and covers of polymer concrete, reinforced with heavy weave fiberglass.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.15   <SUB>CABLE SUPPORTS</SUB> (RACKS, ARMS, AND INSULATORS)</TTL><BRK/>
<BRK/>
<TXT>The metal portion of racks and arms shall be zinc-coated after fabrication.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.15.1   Cable Racks</TTL><BRK/>
<BRK/>
<TXT>The wall bracket shall be<MET> 100 mm</MET><ENG> 4 inches</ENG> by approximately<MET> 38 mm by 4.76 mm</MET><ENG> 1-1/2 inch by 3/16 inch</ENG> channel steel,<MET>
 1220 mm</MET><ENG> 48 inches</ENG> long (minimum) in manholes.  Slots for mounting cable rack arms shall be spaced at<MET> 200 mm</MET><ENG> 
8 inch</ENG> intervals.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.2   Rack Arms</TTL><BRK/>
<BRK/>
<TXT>Cable rack arms shall be steel or malleable iron or glass reinforced nylon and shall be of the removable type.  
Rack arm length shall be a minimum of<MET> 200 mm</MET><ENG> 8 inches</ENG> and a maximum of<MET> 305 mm</MET><ENG> 12 inches</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.3   Insulators</TTL><BRK/>
<BRK/>
<TXT>Insulators for metal rack arms shall be dry-process glazed porcelain.  Insulators are not required for nylon 
arms.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.16   CABLE TAGS IN MANHOLES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: Verify cable labeling requirements with the local Activity.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide tags for each power cable located in manholes.  The tags shall be polyethylene.  Do not provide handwritten 
letters.  The first position on the power cable tag shall denote the voltage.  The second through sixth positions 
on the tag shall identify the circuit.  The next to last position shall denote the phase of the circuit and shall 
include the Greek "phi" symbol.  The last position shall denote the cable size.  As an example, a tag could have 
the following designation:  "11.5 NAS 1-8(Phase A)500," denoting that the tagged cable is on the 11.5kV system 
circuit number NAS 1-8, underground, Phase A, sized at 500 kcmil.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.16.1   Polyethylene Cable Tags</TTL><BRK/>
<BRK/>
<TXT>Provide tags of polyethylene that have an average tensile strength of<MET> 22.4 MPa (3250 pounds per square inch)</MET><ENG> 
3250 pounds per square inch</ENG>; and that are<MET> two millimeter (0.08 inch)</MET><ENG> 0.08 inch</ENG> thick (minimum), non-corrosive 
non-conductive; resistive to acids, alkalis, organic solvents, and salt water; and distortion resistant to<MET> 77 
degrees C</MET><ENG> 170 degrees F</ENG>.  Provide<MET> 1.3 mm (0.05 inch)</MET><ENG> 0.05 inch</ENG> (minimum) thick black polyethylene tag holder.  
Provide a one-piece nylon, self-locking tie at each end of the cable tag.  Ties shall have a minimum loop tensile 
strength of<MET> 778.75 N (175 pounds)</MET><ENG> 175 pounds</ENG>.  The cable tags shall have black block letters, numbers, and symbols<MET>
 25 mm (one inch)</MET><ENG> one inch</ENG> high on a yellow background.  Letters, numbers, and symbols shall not fall off or 
change positions regardless of the cable tags' orientation.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.17   CABLE TERMINATING CABINETS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Cable terminating cabinets may be used for above ground applications 
only.  They may be utilized in place of manholes for cable splicing where the 
local water table does not allow for manhole drainage, or in limited applications 
where it is desirable to provide a dead-break circuit sectionalizing point for 
circuit isolation.  Loadbreak connectors are not available for applications 
above 200 A.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Cable terminating cabinets shall be hook-stick operable, deadfront construction conforming to the requirements 
of <RID>IEEE C37.20.3</RID>, Category A.  Cabinets shall be provided with [with 200 A. loadbreak junctions and elbow-type 
separable loadbreak connectors, cable parking stands, and grounding lugs] [with 600 A. dead-break junctions and 
elbow-type separable dead-break connectors, cable parking stands, and grounding lugs].  Provide cable terminating 
equipment in conformance with <RID>IEEE Std 386</RID>.</TXT><BRK/>
<BRK/>
<TBL>Ratings at 60 Hz shall be:<BRK/>
<BRK/>
Nominal voltage (kV)...........................................[_____]<BRK/>
<BRK/>
Rated maximum voltage (kV).....................................[[15][25][35]]<BRK/>
<BRK/>
Rated continuous current (A)...................................[[200][600]]<BRK/>
<BRK/>
Three-second short-time current-carrying capacity (kA).........[_____]<BRK/>
<BRK/>
BIL (kV).......................................................[_____]</TBL><BRK/>
<BRK/></SPT>
<TAI OPT="AIR FORCE,ARMY"><SPT><TTL>2.18   <SUB>PROTECTIVE DEVICES AND COORDINATION</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/>                                                                                                                                                                     <BRK/>
<NPR>NOTE:  Do not use on Navy Projects.<BRK/>
<BRK/>
The designer is responsible for  specifying the requirement for fuses, circuit 
breakers, protective relays, or other protective devices associated with the 
project and depicting them on the drawings.  The protective devices should be 
selected and specified to protect electrical power system conductors or equipment 
against sustained overloads, in-rush conditions, electrical faults, or other 
abnormal power system or equipment operating conditions, in accordance with 
IEEE Std 242, and IEEE Std 141. The designer shall either utilize UFGS 26 28 
01.00 10 or incorporate protective device requirements in this specification.</NPR><BRK/>
<BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide protective devices and coordination as specified in Section <SRF>26 28 01.00 10</SRF></TXT><BRK/>
<BRK/></SPT>
</TAI><SPT><TTL>2.19   SOURCE QUALITY CONTROL</TTL><BRK/>
<BRK/>
<SPT><TTL>2.19.1   <SUB>Arc-Proofing Test</SUB> for Cable Fireproofing Tape</TTL><BRK/>
<BRK/>
<TXT><TST>Manufacturer shall test one sample assembly consisting of a straight lead tube<MET> 305 mm</MET><ENG> 12 inches</ENG> long with a<MET> 65.5 
mm</MET><ENG> 2 1/2 inch</ENG> outside diameter, and a<MET> 3.175-mm</MET><ENG> 1/8 inch</ENG> thick wall, and covered with one-half lap layer of arc 
and fireproofing material per manufacturer's instructions.</TST>  The arc and fireproofing tape shall withstand extreme 
temperature of a high-current fault arc 13,000 degrees K for 70 cycles as determined by using an argon directed 
plasma jet capable of constantly producing and maintaining an arc temperature of 13,000 degrees K.  Temperature 
(13,000 degrees K) of the ignited arc between the cathode and anode shall be obtained from a dc power source 
of 305 (plus or minus 5) amperes and 20 (plus or minus 1) volts.  The arc shall be directed toward the sample 
assembly accurately positioned 5 (plus or minus 1) millimeters downstream in the plasma from the anode orifice 
by fixed flow rate of argon gas (0.18 g per second).  Each sample assembly shall be tested at three unrelated 
points.  Start time for tests shall be taken from recorded peak current when the specimen is exposed to the full 
test temperature.  Surface heat on the specimen prior to that time shall be minimal.  The end point is established 
when the plasma or conductive arc penetrates the protective tape and strikes the lead tube.  Submittals for arc-proofing 
tape shall indicate that the test has been performed and passed by the manufacturer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.19.2   <SUB>Medium Voltage Cable Qualification and Production Tests</SUB></TTL><BRK/>
<BRK/>
<TXT>Results of <RID>AEIC CS8</RID> qualification and production tests as applicable for each type of medium voltage cable.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   INSTALLATION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Soil treatment for termite control shall conform to Section 31 31 16, 
SOIL TREATMENT FOR SUBTERRANEAN TERMITE CONTROL, except that application to 
direct burial cable installation shall be as specified.  In lieu of soil poisoning, 
cable in direct-buried EPC-40-PVC conduit can be a more economical and practical 
way of protecting cable from termites.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  CALPUC publication applies only to State of California Public Utilities 
Commission CALPUC G.O.128, "Construction of Underground Electric Supply and 
Communication System" for underground electrical work.  For other states, delete 
this publication and insert other publications which govern underground electrical 
work for that state.  Revise reference paragraph to include deletion or addition 
of state publication.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Install equipment and devices in accordance with the manufacturer's published instructions and with the requirements 
and recommendations of <RID>NFPA 70</RID> and <RID>IEEE C2</RID> [and CALPUC G.O.128] as applicable.  In addition to these requirements, 
install telecommunications in accordance with <RID>TIA-758-A</RID> and <RID>RUS Bull 1751F-644</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   CABLE INSPECTION</TTL><BRK/>
<BRK/>
<TXT>Prior to installation, each cable reel shall be inspected for correct storage positions, signs of physical damage, 
and broken end seals.  If end seal is broken, moisture shall be removed from cable prior to installation in accordance 
with the cable manufacturer's recommendations.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3   <SUB>CABLE INSTALLATION PLAN AND PROCEDURE</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use this paragraph when pulling cable between manholes.  Do not use this 
paragraph when only installing between poles and manholes  <BRK/>
<BRK/>
Choose checklist for small electrical distribution jobs, and calculations for 
large jobs.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The Contractor shall obtain from the manufacturer an installation manual or set of instructions which addresses 
such aspects as cable construction, insulation type, cable diameter, bending radius, cable temperature limits 
for installation, lubricants, coefficient of friction, conduit cleaning, storage procedures, moisture seals, 
testing for and purging moisture, maximum allowable pulling tension, and maximum allowable sidewall bearing pressure.  
The Contractor shall then [prepare a checklist of significant requirements] [perform pulling calculations and 
prepare a pulling plan] which shall be submitted along with the manufacturers instructions in accordance with 
SUBMITTALS. Cable shall be installed strictly in accordance with the cable manufacturer's recommendations and 
the approved installation plan.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">[Calculations and pulling plan shall include:</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Site layout drawing with cable pulls identified in numeric order of expected pulling sequence 
and direction of cable pull.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  List of cable installation equipment.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Lubricant manufacturer's application instructions.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Procedure for resealing cable ends to prevent moisture from entering cable.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Cable pulling tension calculations of all cable pulls.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Cable percentage conduit fill.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Cable sidewall bearing pressure.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  Cable minimum bend radius and minimum diameter of pulling wheels used.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">i.  Cable jam ratio.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">j.  Maximum allowable pulling tension on each different type and size of conductor.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">k.  Maximum allowable pulling tension on pulling device.</ITM><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.4   UNDERGROUND FEEDERS SUPPLYING BUILDINGS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For Navy only, choose PVC.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Terminate underground feeders supplying building at a point<MET> 1525 mm</MET><ENG> 5 feet</ENG> outside the building and projections 
thereof, except that conductors shall be continuous to the terminating point indicated.  Coordinate connections 
of the feeders to the service entrance equipment with Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM.  Conduit 
shall be [PVC, Type EPC-40][IMC][RGS] from the supply equipment to a point<MET> 1525 mm</MET><ENG> 5 feet</ENG> outside the building 
and projections thereof.  Protect ends of underground conduit with plastic plugs until connections are made.</TXT><BRK/>
<BRK/>
<TXT>[Encase the underground portion of the conduit in a concrete envelope and bury as specified for underground duct 
with concrete encasement.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5   UNDERGROUND STRUCTURE CONSTRUCTION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit this paragraph to comply with project requirements concerning the 
type of structure, strength of concrete, concrete mix, metal accessories, and 
excavating and grading.  Indicate special reinforcing where required.  Contact 
local telephone company, where applicable, concerning the size of all signal 
manholes and the number and type of signal duct required.  Determine availability 
since H20 or aircraft loadings may not be available in precast.</NPR><BRK/>
<BRK/>
<NPR>For Navy projects, see standard sketches UG-1 through UG-7 covering manholes 
and handholes.  Include the required sketches on the project drawings. </NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide standard type cast-in-place construction as specified herein and as indicated, or precast construction 
as specified herein.  Horizontal concrete surfaces of floors shall have a smooth trowel finish.  Cure concrete 
by applying two coats of white pigmented membrane forming-curing compound in strict accordance with the manufacturer's 
printed instructions, except that precast concrete may be steam cured.  Curing compound shall conform to <RID>ASTM C 309</RID>
.  Locate duct entrances and windows in the center of end walls (shorter) and near the corners of sidewalls (longer) 
to facilitate cable racking and splicing.  Covers for underground structures shall fit the frames without undue 
play.  Steel and iron shall be formed to shape and size with sharp lines and angles.  Castings shall be free 
from warp and blow holes that may impair strength or appearance.  Exposed metal shall have a smooth finish and 
sharp lines and arises.  Provide necessary lugs, rabbets, and brackets.  Set pulling-in irons and other built-in 
items in place before depositing concrete.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.5.1   Cast-In-Place Concrete Structures</TTL><BRK/>
<BRK/>
<TXT>[Construct walls on a footing of cast-in-place concrete except that precast concrete base sections may be used 
for precast concrete manhole risers.][Provide concrete block conforming to <RID>ASTM C 139</RID> and Section <SRF>04 20 00</SRF> MASONRY][Concrete 
block is not allowed in areas subject to aircraft loading.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.2   Precast Concrete Construction</TTL><BRK/>
<BRK/>
<TXT>Set commercial precast structures on<MET> 150 mm</MET><ENG> 6 inches</ENG> of level, 90 percent compacted granular fill,<MET> 19 mm to 25 
mm</MET><ENG> 3/4 inch to 1 inch</ENG> size, extending<MET> 305 mm</MET><ENG> 12 inches</ENG> beyond the structure on each side.  Compact granular fill 
by a minimum of four passes with a plate type vibrator.  Installation shall additionally conform to the manufacturer's 
instructions.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.3   <SUB>Pulling-In Irons</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide steel bars bent as indicated, and cast in the walls and floors.  Alternatively, pipe sleeves may be precast 
into the walls and floors where required to accept U-bolts or other types of pulling-in devices possessing the 
strengths and clearances stated herein.  The final installation of pulling-in devices shall be made permanent.  
Cover and seal exterior projections of thru-wall type pulling-in devices with an appropriate protective coating.  
In the floor the irons shall be a minimum of<MET> 150 mm</MET><ENG> 6 inches</ENG> from the edge of the sump, and in the walls the 
irons shall be located within<MET> 150 mm</MET><ENG> 6 inches</ENG> of the projected center of the duct bank pattern or precast window 
in the opposite wall.  However, the pulling-in iron shall not be located within<MET> 150 mm</MET><ENG> 6 inches</ENG> of an adjacent 
interior surface, or duct or precast window located within the same wall as the iron.  If a pulling-in iron cannot 
be located directly opposite the corresponding duct bank or precast window due to this clearance limitation, 
locate the iron directly above or below the projected center of the duct bank pattern or precast window the minimum 
distance required to preserve the<MET> 150 mm</MET><ENG> 6 inch</ENG> clearance previously stated.  In the case of directly opposing 
precast windows, pulling-in irons consisting of a<MET> 915 mm</MET><ENG> 3 foot</ENG> length of No. 5 reinforcing bar, formed into 
a hairpin, may be cast-in-place within the precast windows simultaneously with the end of the corresponding duct 
bank envelope.  Irons installed in this manner shall be positioned directly in line with, or when not possible, 
directly above or below the projected center of the duct bank pattern entering the opposite wall, while maintaining 
a minimum clear distance of<MET> 75 mm</MET><ENG> 3 inches</ENG> from any edge of the cast-in-place duct bank envelope or any individual 
duct.  Pulling-in irons shall have a clear projection into the structure of approximately<MET> 100 mm</MET><ENG> 4 inches</ENG> and 
shall be designed to withstand a minimum pulling-in load of<MET> 26,700 N</MET><ENG> 6000 pounds</ENG>.  Irons shall be hot-dipped 
galvanized after fabrication.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.4   Cable Racks, Arms and Insulators</TTL><BRK/>
<BRK/>
<TXT>Cable racks, arms and insulators shall be sufficient to accommodate the cables.  Racks in power manholes shall 
be spaced not more than<MET> 915 mm</MET><ENG> 3 feet</ENG> apart, and each manhole wall shall be provided with a minimum of two racks.  
Racks in signal manholes shall be spaced not more than<MET> 420 mm</MET><ENG> 16 1/2 inches</ENG> apart with the end rack being no 
further than<MET> 305 mm</MET><ENG> 12 inches</ENG> from the adjacent wall.  Methods of anchoring cable racks shall be as follows:</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Provide a<MET> 15 mm diameter by 125 mm</MET><ENG> 5/8 inch diameter by 5 inch</ENG> long anchor bolt with<MET> 75 mm</MET><ENG> 3 inch</ENG>
 foot cast in structure wall with<MET> 50 mm</MET><ENG> 2 inch</ENG> protrusion of threaded portion of bolt into structure.  
Provide<MET> 15 mm</MET><ENG> 5/8 inch</ENG> steel square head nut on each anchor bolt.  Coat threads of anchor bolts with 
suitable coating immediately prior to installing nuts.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Provide concrete channel insert with a minimum load rating of<MET> 1192 kg per meter</MET><ENG> 800 pounds per foot</ENG>
.  Insert channel shall be steel of the same length as "vertical rack channel;" channel insert shall 
be cast flush in structure wall.  Provide<MET> 15 mm</MET><ENG> 5/8 inch</ENG> steel nuts in channel insert to receive<MET> 15 mm 
diameter by 75 mm</MET><ENG> 5/8 inch diameter by 3 inch</ENG> long steel, square head anchor bolts.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Provide concrete "spot insert" at each anchor bolt location, cast flush in structure wall.  Each 
insert shall have minimum<MET> 365 kg</MET><ENG> 800 pound</ENG> load rating.  Provide<MET> 15 mm diameter by 75 mm</MET><ENG> 5/8 inch diameter 
by 3 inch</ENG> long steel, square head anchor bolt at each anchor point.  Coat threads of anchor bolts with 
suitable coating immediately prior to installing bolts.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.5   Field Painting</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit to match products contained in Part 2.  Choose cast-iron for most 
applications.  Ductile iron or steel may be required for areas subject to heavy 
loading such as airfields or industrial areas.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Cast-iron frames and covers not buried in concrete or masonry shall be cleaned of mortar, rust, grease, dirt 
and other deleterious materials, and given a coat of bituminous paint.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.6   DIRECT BURIAL CABLE SYSTEM</TTL><BRK/>
<BRK/>
<TXT>Cables shall be buried directly in the earth below the frostline [as indicated][to the requirements of NFPA 70 
and IEEE C2, whichever is more stringent].</TXT><BRK/>
<BRK/>
<SPT><TTL>3.6.1   Trenching</TTL><BRK/>
<BRK/>
<TXT>Trenches for direct-burial cables shall be excavated to depths required to provide the minimum necessary cable 
cover. When rock is encountered, remove to a depth of at least<MET> 75 mm</MET><ENG> 3 inches</ENG> below the cable and fill the space 
with sand or clean earth free from particles larger than<MET> 6 mm</MET><ENG> 1/4 inch.</ENG>  Bottoms of trenches shall be smooth 
and free of stones and sharp objects.  Where materials in bottoms of trenches are other than sand, a 75 mm 3 
inch layer of sand shall be laid first and compacted to approximate densities of surrounding firm soil.   Trenches 
shall be not less than<MET> [150] [200] mm</MET><ENG> [6] [8] inches</ENG> wide, and shall be in straight lines between cable markers.  
[Cable plows shall not be used.]  Bends in trenches shall have a radius [of not less than<MET> 915 mm</MET><ENG> 36 inches][consistent 
with the cable manufacturer's published minimum cable bending radius for the cable installed]</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6.2   Cable Installation. </TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where soil is known to be rocky, provide selected backfill for cable 
protection.  Specify bend radius in accordance with NFPA 70.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Cables shall be unreeled along the sides of or in trenches and carefully placed on sand or earth bottoms.  Pulling 
cables into direct-burial trenches from a fixed reel position will not be permitted, except as required to pull 
cables through conduits under paving or railroad tracks.</TXT>   <BRK/>
<BRK/>
<TXT>Where two or more cables are laid parallel in the same trench, space cables laterally at not less than<MET> 75 mm</MET><ENG> 
3 inches</ENG> apart, except that communication cable shall be separated from power cable by a minimum distance of<MET> 
305 mm</MET><ENG> 12 inches</ENG>.</TXT><BRK/>
<BRK/>
<TXT>Where direct-burial cables cross under roads or other paving exceeding<MET> 1.5 m</MET><ENG>5 feet</ENG> in width, such cables shall 
be installed in [concrete-encased] ducts.  Where direct-burial cables cross under railroad tracks, such cables 
shall be installed in [reinforced concrete-encased ducts] [ducts installed through rigid galvanized steel sleeves].  
Ducts shall extend at least<MET> 300 mm</MET><ENG> 1 foot</ENG> beyond each edge of any paving and at least<MET> 1.5 m</MET><ENG> 5 feet</ENG> beyond each 
side of any railroad tracks.  Cables may be pulled into duct from a fixed reel where suitable rollers are provided 
in the trench.  Where direct burial cable transitions to duct-enclosed cable, direct-burial cables shall be centered 
in duct entrances, and a waterproof nonhardening mastic compound shall be used to facilitate such centering.  
If paving or railroad tracks are in place where cables are to be installed, coated rigid steel conduits driven 
under the paving or railroad tracks may be used in lieu of concrete-encased ducts.  Damage to conduit coatings 
shall be prevented by providing ferrous pipe jackets or by predrilling.  Where cuts are made in any paving, the 
paving and subbase shall be restored to their original condition. Where cable is placed in duct(e.g. under paved 
areas, roads, or railroads), slope ducts to drain.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6.3   Splicing</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Direct earth burial cables generally require direct burial splices. Observe 
marker slab requirements previously covered in this specification. Direct burial 
splices are allowable for NAVFAC projects only, do not specify for Army and 
Air Force Projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide cables in one piece without splices between connections except where the distance exceeds the lengths 
in which cables are manufactured. [Where splices are required, provide splices designed and rated for direct 
burial.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6.4   Bends</TTL><BRK/>
<BRK/>
<TXT>Bends in cables shall have an inner radius not less than those specified in <RID>NFPA 70</RID> for the type of cable, or 
manufacturer's recommendation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6.5   Horizontal Slack</TTL><BRK/>
<BRK/>
<TXT>Leave approximately<MET> 915 mm</MET><ENG> 3 feet</ENG> of horizontal slack in the ground on each end of cable runs, on each side of 
connection boxes, and at points where connections are brought above ground.  Where cable is brought above ground, 
leave additional slack to make necessary connections.  [Enclose splices in lead-sheathed or armored cables in 
split-type cast-iron splice boxes; after completion of the connection, fill with insulating filler compound and 
tightly clamp the box.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6.6   Identification Slabs [Markers]</TTL><BRK/>
<BRK/>
<TXT>Provide a slab at each change of direction of cable, over the ends of ducts or conduits which are installed under 
paved areas and roadways[, and over each splice].  Identification slabs shall be of concrete, approximately<MET> 500 
mm square by 150 mm</MET><ENG> 20 inches square by 6 inches</ENG> thick and shall be set flat in the ground so that top surface 
projects not less than<MET> 20 mm</MET><ENG> 3/4 inch</ENG>, nor more than<MET> 30 mm</MET><ENG> 1 1/4 inches</ENG>above ground.  Concrete shall have a compressive 
strength of not less than<MET> 20 MPa</MET><ENG> 3000 psi</ENG> and have a smooth troweled finish on exposed surface. Inscribe an identifying 
legend such as "electric cable," "telephone cable," "splice," or other applicable designation on the top surface 
of the slab before concrete hardens.  Inscribe circuit identification symbols on slabs as indicated.  Letters 
or figures shall be approximately<MET> 50 mm</MET><ENG> 2 inches</ENG> high and grooves shall be approximately<MET> 6 mm</MET><ENG> 1/4 inch</ENG> in width 
and depth.  Install slabs so that the side nearest the inscription on top shall include an arrow indicating the 
side nearest the cable. Provide color, type and depth of warning tape asspecified in Section [<SRF>31 23 00.00 20</SRF> 
EXCAVATION AND FILL][<SRF>31 00 00</SRF> EARTHWORK].</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.7   UNDERGROUND CONDUIT AND DUCT SYSTEMS</TTL><BRK/>
<BRK/>
<SPT><TTL>3.7.1   Requirements</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify cover requirements in accordance with NFPA 70 and IEEE C2.  Indicate 
direct buried conduit and concrete encased conduit on drawings.  Ensure that 
duct is specified to be installed below the frost line depth.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Depths to top of the conduit shall be in accordance with NFPA 70. Run conduit in straight lines except where 
a change of direction is necessary. Numbers and sizes of ducts shall be as indicated.  Ducts shall have a continuous 
slope downward toward underground structures and away from buildings, laid with a minimum slope of<MET> 100 mm per 
30 m.</MET><ENG> [3][4] inches per 100 feet.</ENG>  Depending on the contour of the finished grade, the high-point may be at a 
terminal, a manhole, a handhole, or between manholes or handholes.  Short-radius manufactured 90-degree duct 
bends may be used only for pole or equipment risers, unless specifically indicated as acceptable.  The minimum 
manufactured bend radius shall be<MET> 450 mm (18 inches)</MET><ENG> 18 inches</ENG> for ducts of less than<MET> 80 mm (3 inch)</MET><ENG> 3 inch</ENG> diameter, 
and<MET> 900 mm (36 inches)</MET><ENG> 36 inches</ENG> for ducts<MET> 80 mm (3 inches)</MET><ENG> 3 inches</ENG> or greater in diameter.  Otherwise, long 
sweep bends having a minimum radius of<MET> 7.6 m</MET><ENG> 25 feet</ENG> shall be used for a change of direction of more than 5 degrees, 
either horizontally or vertically.  Both curved and straight sections may be used to form long sweep bends, but 
the maximum curve used shall be 30 degrees and manufactured bends shall be used.  Ducts shall be provided with 
end bells whenever duct lines terminate in structures.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.2   Treatment</TTL><BRK/>
<BRK/>
<TXT>Ducts shall be kept clean of concrete, dirt, or foreign substances during construction.  Field cuts requiring 
tapers shall be made with proper tools and match factory tapers.  A coupling recommended by the duct manufacturer 
shall be used whenever an existing duct is connected to a duct of different material or shape.  Ducts shall be 
stored to avoid warping and deterioration with ends sufficiently plugged to prevent entry of any water or solid 
substances.  Ducts shall be thoroughly cleaned before being laid.  Plastic ducts shall be stored on a flat surface 
and protected from the direct rays of the sun.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.3   Conduit Cleaning</TTL><BRK/>
<BRK/>
<TXT>As each conduit run is completed, for conduit sizes<MET> 75 mm</MET><ENG> 3 inches</ENG> and larger, draw a flexible testing mandrel 
approximately<MET> 305 mm</MET><ENG> 12 inches</ENG> long with a diameter less than the inside diameter of the conduit through the 
conduit.  After which, draw a stiff bristle brush through until conduit is clear of particles of earth, sand 
and gravel; then immediately install conduit plugs.  For conduit sizes less than<MET> 75 mm</MET><ENG> 3 inches</ENG>, draw a stiff 
bristle brush through until conduit is clear of particles of earth, sand and gravel; then immediately install 
conduit plugs. </TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.4   Jacking and Drilling Under Roads and Structures</TTL><BRK/>
<BRK/>
<TXT>Conduits to be installed under existing paved areas which are not to be disturbed, and under roads and railroad 
tracks, shall be zinc-coated, rigid steel, jacked into place.Where ducts are jacked under existing pavement, 
rigid steel conduit will be installed because of its strength.  To protect the corrosion-resistant conduit coating, 
predrilling or installing conduit inside a larger iron pipe sleeve (jack-and-sleeve) is required.  For crossings 
of existing railroads and airfield pavements greater than<MET> 15 m</MET><ENG> 50 feet</ENG> in length, the predrilling method or the 
jack-and-sleeve method will be used.  Separators or spacing blocks shall be made of steel, concrete, plastic, 
or a combination of these materials placed not farther apart than<MET> 1.2 m</MET><ENG> 4 feet</ENG> on centers.  [Hydraulic jet method 
shall not be used.]</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.7.5   Galvanized Conduit Concrete Penetrations</TTL><BRK/>
<BRK/>
<TXT>Galvanized conduits which penetrate concrete (slabs, pavement, and walls) in wet locations shall be PVC coated 
and shall extend from at least<MET> 50 mm</MET><ENG> 2 inches</ENG> within the concrete to the first coupling or fitting outside the 
concrete (minimum of<MET> 150 mm</MET><ENG> 6 inches</ENG> from penetration).]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.6   Multiple Conduits</TTL><BRK/>
<BRK/>
<TXT>Separate multiple conduits by a minimum distance of<MET> 65 mm</MET><ENG> 2 1/2 inches</ENG>, except that light and power conduits 
shall be separated from control, signal, and telephone conduits by a minimum distance of<MET> [75][300] mm</MET><ENG> [3][12] 
inches</ENG>.  Stagger the joints of the conduits by rows (horizontally) and layers (vertically) to strengthen the 
conduit assembly.  Provide plastic duct spacers that interlock vertically and horizontally.  Spacer assembly 
shall consist of base spacers, intermediate spacers, ties, and locking device on top to provide a completely 
enclosed and locked-in conduit assembly.  Install spacers per manufacturer's instructions, but provide a minimum 
of two spacer assemblies per<MET> 3050 mm</MET><ENG> 10 feet</ENG> of conduit assembly.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.7   Conduit Plugs and Pull Rope</TTL><BRK/>
<BRK/>
<TXT>New conduit indicated as being unused or empty shall be provided with plugs on each end.  Plugs shall contain 
a weephole or screen to allow water drainage.  Provide a plastic pull rope having<MET> 915 mm</MET><ENG> 3 feet</ENG> of slack at each 
end of unused or empty conduits.</TXT></SPT><BRK/>
<BRK/>
<SPT><TTL>3.7.8   Conduit and Duct Without Concrete Encasement</TTL><BRK/>
<BRK/>
<TXT>Provide not less than<MET> 75 mm</MET><ENG> 3 inches</ENG> clearance from the conduit to each side of the trench.  Grade bottom of 
trench smooth; where rock, soft spots, or sharp-edged materials are encountered, excavate the bottom for an additional<MET>
 75 mm</MET><ENG> 3 inches</ENG>, fill and tamp level with original bottom with sand or earth free from particles, that would 
be retained on a<MET> 6.25 mm</MET><ENG> 1/4 inch</ENG> sieve. The first<MET> 150 mm</MET><ENG> 6 inch</ENG> layer of backfill cover shall be sand compacted 
as previously specified.  The rest of the excavation shall be backfilled and compacted in<MET> 75 to 150 mm</MET><ENG>3 to 6 
inch</ENG> layers. Provide color, type and depth of warning tape as specified in Section [<SRF>31 23 00.00 20</SRF> EXCAVATION 
AND FILL][<SRF>31 00 00</SRF> EARTHWORK].</TXT><BRK/>
<BRK/>
<SPT><TTL>3.7.8.1   Encasement Under Roads and Structures</TTL><BRK/>
<BRK/>
<TXT>Under roads, paved areas, and railroad tracks, install conduits in concrete encasement of rectangular cross-section 
providing a minimum of<MET> 75 mm</MET><ENG> 3 inch</ENG> concrete cover around ducts.  Concrete encasement shall extend at least<MET> 1525 
mm</MET><ENG> 5 feet</ENG> beyond the edges of paved areas and roads, and<MET> 3660 mm</MET><ENG> 12 feet</ENG> beyond the rails on each side of railroad 
tracks.</TXT> <BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.7.9   Duct Encased in Concrete</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit this paragraph to comply with project requirements concerning type 
of structure or duct, strength of concrete, concrete mix, metal accessories, 
and excavating and grading. Indicate special reinforcing where required, particularly 
with duct banks of non-rectangular cross-section.  Separation of ducts from 
each other (65 mm (2 1/2 inches) may be specified in accordance with calculations 
from NFPA 70.  Separation can be reduced for telecommunication ducts since heat 
gain is not a factor.<BRK/>
<BRK/>
Medium voltage cables and campus distribution cables of telecommunications backbone 
distribution system shall be in duct encased in concrete, unless otherwise required 
by local Activity.  Contact local telephone company, where applicable, concerning 
size of signal manholes and number and type of signal duct required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Construct underground duct lines of individual conduits encased in concrete.  Do not mix different kinds of conduit 
in any one duct bank.    Concrete encasement surrounding the bank shall be rectangular in cross-section and shall 
provide at least<MET> 75 mm</MET><ENG> 3 inches</ENG> of concrete cover for ducts.  Separate conduits by a minimum concrete thickness 
of<MET>  65 mm</MET><ENG> 2 1/2 inches</ENG>, except separate light and power conduits from control, signal, and telecommunications 
conduits by a minimum concrete thickness of<MET> 75 mm</MET><ENG> 3 inches</ENG>.   Before pouring concrete, anchor duct bank assemblies 
to prevent the assemblies from floating during concrete pouring.  Anchoring shall be done by driving reinforcing 
rods adjacent to  duct spacer assemblies and attaching the rods to the spacer assembly.  [Provide color, type 
and depth of warning tape as specified in Section [<SRF>31 00 00</SRF> EARTHWORK][31 23 00.00 20 EXCAVATION AND BACKFILL.]]</TXT><BRK/>
<BRK/>
<SPT><TTL>3.7.9.1   Connections to Manholes</TTL><BRK/>
<BRK/>
<TXT>Duct bank envelopes connecting to underground structures shall be flared to have enlarged cross-section at the 
manhole entrance to provide additional shear strength.  Dimensions of the flared cross-section shall be larger 
than the corresponding manhole opening dimensions by no less than<MET> 300 mm</MET><ENG> 12 inches</ENG> in each direction.  Perimeter 
of the duct bank opening in the underground structure shall be flared toward the inside or keyed to provide a 
positive interlock between the duct bank and the wall of the structure.  Use vibrators when this portion of the 
encasement is poured to assure a seal between the envelope and the wall of the structure.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.9.2   Connections to Existing Underground Structures</TTL><BRK/>
<BRK/>
<TXT>For duct bank connections to existing structures, break the structure wall out to the dimensions required and 
preserve steel in the structure wall. Cut steel and [extend into] [bend out to tie into the reinforcing of] the 
duct bank envelope.  Chip the perimeter surface of the duct bank opening to form a key or flared surface, providing 
a positive connection with the duct bank envelope.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.9.3   Connections to Existing Concrete Pads</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Choose second bracketed option where existing concrete is reinforced. </NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>For duct bank connections to concrete pads, break an opening in the pad out to the dimensions required and preserve 
steel in pad.  Cut the steel and [extend into] [bend out to tie into the reinforcing of] the duct bank envelope.  
Chip out the opening in the pad to form a key for the duct bank envelope.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.9.4   Connections to Existing Ducts</TTL><BRK/>
<BRK/>
<TXT>Where connections to existing duct banks are indicated, excavate the banks to the maximum depth necessary.  Cut 
off the banks and remove loose concrete from the conduits before new concrete-encased ducts are installed.  Provide 
a reinforced concrete collar, poured monolithically with the new duct bank, to take the shear at the joint of 
the duct banks.  [Remove existing cables which constitute interference with the work.]  [Abandon in place those 
no longer used ducts and cables which do not interfere with the work.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.9.5   Partially Completed Duct Banks</TTL><BRK/>
<BRK/>
<TXT>During construction wherever a construction joint is necessary in a duct bank, prevent debris such as mud, and, 
and dirt from entering ducts by providing suitable conduit plugs.  Fit concrete envelope of a partially completed 
duct bank with reinforcing steel extending a minimum of<MET> 610 mm</MET><ENG> 2 feet</ENG> back into the envelope and a minimum of<MET>
 610 mm</MET><ENG> 2 feet</ENG> beyond the end of the envelope.  Provide one No. 4 bar in each corner, <MET> 75 mm</MET><ENG> 3 inches</ENG> from the 
edge of the envelope.  Secure corner bars with two No. 3 ties, spaced approximately<MET> 305 mm</MET><ENG> one foot</ENG>apart.  Restrain 
reinforcing assembly from moving during concrete pouring.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.7.9.6   Removal of Ducts</TTL><BRK/>
<BRK/>
<TXT>Where duct lines are removed from existing underground structures, close the openings to waterproof the structure.  
Chip out the wall opening to provide a key for the new section of wall.</TXT><BRK/>
<BRK/>
]</SPT></SPT></SPT><SPT><TTL>3.8   CABLE PULLING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For Navy projects, choose bracketed item for tape shielding and coordinate 
with Part 2 PRODUCTS.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><TST>[Test existing duct lines with a mandrel and thoroughly swab out to remove foreign material before pulling cables.</TST>
  ]Pull cables down grade with the feed-in point at the manhole or buildings of the highest elevation.  Use flexible 
cable feeds to convey cables through manhole opening and into duct runs.  Do not exceed the specified cable bending 
radii when installing cable under any conditions, including turnups into switches, transformers, switchgear, 
switchboards, and other enclosures.  Cable with [tape] [or] [wire] shield shall have a bending radius not less 
than 12 times the overall diameter of the completed cable.  If basket-grip type cable-pulling devices are used 
to pull cable in place, cut off the section of cable under the grip before splicing and terminating.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.8.1   Cable Lubricants</TTL><BRK/>
<BRK/>
<TXT>Use lubricants that are specifically recommended by the cable manufacturer for assisting in pulling jacketed 
cables.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.9   CABLES IN UNDERGROUND STRUCTURES</TTL><BRK/>
<BRK/>
<TXT>Do not install cables utilizing the shortest path between penetrations, but route along those walls providing 
the longest route and the maximum spare cable lengths. Form cables to closely parallel walls, not to interfere 
with duct entrances, and support on brackets and cable insulators.  Support cable splices in underground structures 
by racks on each side of the splice.  Locate splices to prevent cyclic bending in the spliced sheath.  Install 
cables at middle and bottom of cable racks, leaving top space open for future cables, except as otherwise indicated 
for existing installations.  Provide one spare three-insulator rack arm for each cable rack in each underground 
structure.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.9.1   Cable Tag Installation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  On contracts where existing cables are recircuited special attention 
should be given to changing existing cable identification tags in each manhole 
to reflect new circuit numbers.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Install cable tags in each manhole as specified, including each splice.  Tag wire and cable provided by this 
contract. Install cable tags over the fireproofing, if any, and locate the tags so that they are clearly visible 
without disturbing any cabling or wiring in the manholes.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.10   CONDUCTORS INSTALLED IN PARALLEL</TTL><BRK/>
<BRK/>
<TXT>Conductors shall be grouped such that each conduit of a parallel run contains 1 Phase A conductor, 1 Phase B 
conductor, 1 Phase C conductor, and 1 neutral conductor.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.11   LOW VOLTAGE CABLE SPLICING AND TERMINATING</TTL><BRK/>
<BRK/>
<TXT> Make terminations and splices with materials and methods as indicated or specified herein and as designated 
by the written instructions of the manufacturer.  Do not allow the cables to be moved until after the splicing 
material has completely set.  [Make splices in underground distribution systems only in accessible locations 
such as manholes,handholes, or aboveground termination cabinets.]</TXT><BRK/>
<BRK/>
<SPT>[<TTL>3.11.1   Terminating Aluminum Conductors</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Use particular care in making up joints and terminations.  Remove surface oxides by cleaning 
with a wire brush or emery cloth.  Apply joint compound to conductors, and use UL-listed solid 
aluminum connectors for connecting aluminum conductors.  When connecting aluminum to copper 
conductors, use connectors specifically designed for this purpose.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Terminate aluminum conductors to copper bus either by:  (1) in line splicing a copper pigtail 
to the aluminum conductor (copper pigtail shall have a ampacity at least that of the aluminum 
conductor); or (2) using a circumferential compression type, aluminum bodied terminal lug UL 
listed for AL/CU and steel Belleville spring washers, flat washers, bolts, and nuts.  Belleville 
spring washers shall be cadmium-plated hardened steel.  Install the Belleville spring washers 
with the crown up toward the nut or bolt head, with the concave side of the Belleville bearing 
on a heavy-duty, wide series flat washer of larger diameter than the Belleville.  Tighten nuts 
sufficient to flatten Belleville and leave in that position. Lubricate hardware with joint compound 
prior to making connection.  Wire brush and apply joint compound to conductor prior to inserting 
in lug.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Terminate aluminum conductors to aluminum bus by using all-aluminum nuts, bolts, washers, 
and lugs.  Wire brush and apply inhibiting compound to conductor prior to inserting in lug.  
Lubricate hardware with joint compound prior to making connection; if bus contact surface is 
unplated, scratch-brush and coat with joint compound (without grit).</ITM><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.12   MEDIUM VOLTAGE CABLE TERMINATIONS</TTL><BRK/>
<BRK/>
<TXT>Make terminations in accordance with the written instruction of the  termination kit manufacturer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.13   MEDIUM VOLTAGE CABLE JOINTS</TTL><BRK/>
<BRK/>
<TXT>Provide power cable joints (splices) suitable for continuous immersion in water.  Make joints only in accessible 
locations in manholes or handholes by using materials and methods in accordance with the written instructions 
of the joint kit manufacturer.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.13.1   Joints in Shielded Cables</TTL><BRK/>
<BRK/>
<TXT>Cover the joined area with metallic tape, or material like the original cable shield and connect it to the cable 
shield on each side of the splice.  Provide a bare copper ground connection brought out in a watertight manner 
and grounded to the manhole grounding loop as part of the splice installation.  Ground conductors, connections, 
and rods shall be as specified elsewhere in this section.  Wire shall be trained to the sides of the enclosure 
to prevent interference with the working area.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.14   CABLE END CAPS</TTL><BRK/>
<BRK/>
<TXT>Cable ends shall be sealed at all times with coated heat shrinkable end caps.  Cables ends shall be sealed when 
the cable is delivered to the job site, while the cable is stored and during installation of the cable.  The 
caps shall remain in place until the cable is spliced or terminated.  Sealing compounds and tape are not acceptable 
substitutes for heat shrinkable end caps.  Cable which is not sealed in the specified manner at all times will 
be rejected.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.15   LIVE END CAPS</TTL><BRK/>
<BRK/>
<TXT>Provide live end caps for single conductor medium voltage cables where indicated.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.16   FIREPROOFING OF CABLES IN UNDERGROUND STRUCTURES</TTL><BRK/>
<BRK/>
<TXT>Fireproof (arc proof) wire and cables which will carry current at 2200 volts or more in underground structures.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.16.1   Fireproofing Tape</TTL><BRK/>
<BRK/>
<TXT>Tightly wrap strips of fireproofing tape around each cable spirally in half-lapped wrapping.  Install tape in 
accordance with manufacturer's instructions.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.16.2   Tape-Wrap</TTL><BRK/>
<BRK/>
<TXT>Tape-wrap  metallic-sheathed or metallic armored cables without a nonmetallic protective covering over the sheath 
or armor prior to application of fireproofing.  Wrap shall be in the form of two tightly applied half-lapped 
layers of a pressure-sensitive<MET> 0.254 mm</MET><ENG> 10 mil</ENG> thick plastic tape, and shall extend not less than<MET> 25 mm</MET><ENG> one inch</ENG>
 into the duct.  Even out irregularities of the cable, such as at splices, with insulation putty before applying 
tape.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.17   GROUNDING SYSTEMS</TTL><BRK/>
<BRK/>
<TXT>Provide grounding system as indicated, in accordance with <RID>NFPA 70</RID> and <RID>IEEE C2</RID>, and as specified herein.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Determine the grounding requirements for each project.  Show all necessary 
ground rods and ground girdles on the drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Noncurrent-carrying metallic parts associated with electrical equipment shall have a maximum resistance to solid 
earth ground not exceeding the following values:</TXT><BRK/>
<BRK/>
<BRK/>
<ITM>Pad-mounted transformers without<BRK/>
protective fences                                        5 ohms</ITM><BRK/>
<BRK/>
<ITM>Ground in manholes                                       5 ohms</ITM><BRK/>
<BRK/>
<ITM>Grounding other metal enclosures of<BRK/>
primary voltage electrical and<BRK/>
electrically-operated equipment                          5 ohms</ITM><BRK/>
<BRK/>
<SPT><TTL>3.17.1   Grounding Electrodes</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: Investigate the soil resistivity during the preliminary design phase to 
determine the design required to ensure that the grounding values are obtained.  
For areas where the water table is low and/or the soil resistivity is high (such 
as volcanic soils, sand, or rock), delete the additional electrode provisions 
and provide a design to meet the site requirements.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide cone pointed driven ground rods driven full depth plus<MET> [150 mm</MET><ENG> 6 inches</ENG>][<MET> 300 mm</MET><ENG> 12 inches]</ENG>, installed 
to provide an earth ground of the appropriate value for the particular equipment being grounded.<BRK/>
If the specified ground resistance is not met, an additional ground rod shall be provided in accordance with 
the requirements of NFPA 70 (placed not less than 6 feet from the first rod).  Should the resultant (combined) 
resistance exceed the specified resistance, measured not less than 48 hours after rainfall, the Contracting Officer 
shall be notified immediately.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.17.2   Grounding Connections</TTL><BRK/>
<BRK/>
<TXT>Make grounding connections which are buried or otherwise normally inaccessible, by exothermic weld or compression 
connector.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Make exothermic welds strictly in accordance with the weld manufacturer's written recommendations.  
Welds which are "puffed up" or which show convex surfaces indicating improper cleaning are not 
acceptable.  Mechanical connectors are not required at exothermic welds.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Make compression connections using a hydraulic compression tool to provide the correct circumferential 
pressure.  Tools and dies shall be as recommended by the manufacturer.  An embossing die code 
or other standard method shall provide visible indication that a connector has been adequately 
compressed on the ground wire.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>3.17.3   Grounding Conductors</TTL><BRK/>
<BRK/>
<TXT>Provide bare grounding conductors, except where installed in conduit with associated phase conductors.  Ground 
cable sheaths, cable shields, conduit, and equipment with No. 6 AWG. Ground other noncurrent-carrying metal parts 
and equipment frames of metal-enclosed equipment.  Ground metallic frames and covers of handholes and pull boxes 
with a braided, copper ground strap with equivalent ampacity of No. 6 AWG.  [Provide direct connections to the 
grounding conductor with 600 v insulated, full-size conductor for each grounded neutral of each feeder circuit, 
which is spliced within the manhole.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.17.4   Ground Cable Crossing Expansion Joints</TTL><BRK/>
<BRK/>
<TXT>Protect ground cables crossing expansion joints or similar separations in structures and pavements by use of 
approved devices or methods of installation which provide the necessary slack in the cable across the joint to 
permit movement.  Use stranded or other approved flexible copper cable across such separations.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.17.5   Manhole Grounding</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use bracketed sentence when 4-wire circuit including grounded neutral 
is provided.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Loop a 4/0 AWG grounding conductor around the interior perimeter, approximately <MET>305 mm</MET> <ENG>12 inches</ENG> above finished 
floor.  Secure the conductor to the manhole walls at intervals not exceeding <MET>914 mm</MET> <ENG>36 inches</ENG>.  Connect the conductor 
to the manhole grounding electrode with 4/0 AWG conductor.  Connect all incoming 4/0 grounding conductors to 
the ground loop adjacent to the point of entry into the manhole.  Bond the ground loop to all cable shields, 
metal cable racks, and other metal equipment with a minimum 6 AWG conductor.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.17.6   Fence Grounding</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use this paragraph only when fence is required to be grounded in accordance 
with IEEE C2, NFPA 70, or other requirements.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Fences shall be grounded as indicated.]  [Fences shall be grounded with a ground rod at each fixed gate post 
and at each corner post.]  Drive ground rods until the top is<MET> 305 mm</MET><ENG> 12 inches</ENG> below grade.  Attach a No. 4 AWG 
copper conductor, by exothermic weld to the ground rods and extend underground to the immediate vicinity of fence 
post.  Lace the conductor vertically into<MET> 305 mm</MET><ENG> 12 inches</ENG> of fence mesh and fasten by two approved bronze compression 
fittings, one to bond wire to post and the other to bond wire to fence.  Each gate section shall be bonded to 
its gatepost by a<MET> 3 by 25 mm</MET><ENG> 1/8 by one inch</ENG> flexible braided copper strap and ground post clamps.  Clamps shall 
be of the anti-electrolysis type.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.18   EXCAVATING, BACKFILLING, AND COMPACTING</TTL><BRK/>
<BRK/>
<TXT>Provide in accordance with <RID>NFPA 70</RID> and Section [<SRF>31 23 00.00 20</SRF> EXCAVATION AND FILL][<SRF>31 00 00</SRF> EARTHWORK].</TXT><BRK/>
<BRK/>
<SPT><TTL>3.18.1   Reconditioning of Surfaces</TTL><BRK/>
<BRK/>
<SPT><TTL>3.18.1.1   Unpaved Surfaces</TTL><BRK/>
<BRK/>
<TXT>Restore to their original elevation and condition unpaved surfaces disturbed during installation of duct [or 
direct burial cable].  Preserve sod and topsoil removed during excavation and reinstall after backfilling is 
completed.  Replace sod that is damaged by sod of quality equal to that removed.  When the surface is disturbed 
in a newly seeded area, re-seed the restored surface with the same quantity and formula of seed as that used 
in the original seeding, and provide topsoiling, fertilizing, liming, seeding, sodding, sprigging, or mulching.  
[Provide work in accordance with Section <SRF>32 92 19</SRF> TURF and Section <SRF>32 93 00</SRF> EXTERIOR PLANTS.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.18.1.2   Paving Repairs</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where paving repairs are a very minor part of project, the first bracketed 
paragraph may be used; otherwise, use the second bracketed paragraph and include 
other sections as needed (also include necessary cutting and patching details 
on the drawings.)</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Insert appropriate Section number and title in the blank below.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Where trenches, pits, or other excavations are made in existing roadways and other areas of pavement where surface 
treatment of any kind exists [, restore such surface treatment or pavement the same thickness and in the same 
kind as previously existed, except as otherwise specified, and to match and tie into the adjacent and surrounding 
existing surfaces.]  [Make repairs as specified in Section [<SRF>32 13 13.06</SRF> PORTLAND CEMENT CONCRETE PAVEMENT FOR 
ROADS AND SITE FACILITIES] [_____].]</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>3.19   CAST-IN-PLACE CONCRETE</TTL><BRK/>
<BRK/>
<TXT>Provide concrete in accordance with Section .[<SRF>03 30 00</SRF> CAST-IN-PLACE CONCRETE] [<SRF>03 31 00.00 10</SRF> CAST-IN-PLACE 
STRUCTURAL CONCRETE for Army projects] </TXT><BRK/>
<BRK/>
<SPT><TTL>3.19.1   Concrete Slabs for Equipment</TTL><BRK/>
<BRK/>
<TXT>Unless otherwise indicated, the slab shall be at least<MET> 200 mm</MET><ENG> 8 inches</ENG> thick, reinforced with a<MET> 152 mm x 152 
mm - MW19 by MW19 (6 by 6 - W2.9 by W2.9)</MET><ENG> 6 by 6 - W2.9 by W2.9</ENG> mesh, placed uniformly<MET> 100 mm</MET><ENG> 4 inches</ENG> from the 
top of the slab.  Slab shall be placed on a<MET> 150 mm</MET><ENG> 6 inch</ENG> thick, well-compacted gravel base.  Top of concrete 
slab shall be approximately<MET> 100 mm</MET><ENG> 4 inches</ENG> above finished grade with gradual slope for drainage.  Edges above 
grade shall have<MET> 15 mm</MET><ENG> 1/2 inch</ENG> chamfer.  Slab shall be of adequate size to project at least<MET> 200 mm</MET><ENG> 8 inches</ENG> 
beyond the equipment.</TXT><BRK/>
<BRK/>
<TXT>Stub up conduits, with bushings,<MET> 50 mm</MET><ENG> 2 inches</ENG> into cable wells in the concrete pad.  Coordinate dimensions 
of cable wells with transformer cable training areas.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.19.2   Sealing</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Require sealing of holes (windows) in the concrete pad if rodent intrusion 
is a problem.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>When the installation is complete, the Contractor shall seal all conduit and other entries into the equipment 
enclosure with an approved sealing compound.  Seals shall be of sufficient strength and durability to protect 
all energized live parts of the equipment from rodents, insects, or other foreign matter.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.20   FIELD QUALITY CONTROL</TTL><BRK/>
<BRK/>
<SPT><TTL>3.20.1   Performance of <SUB>Field Acceptance Checks and Tests</SUB></TTL><BRK/>
<BRK/>
<TXT>Perform in accordance with the manufacturer's recommendations, and include the following visual and mechanical 
inspections and electrical tests, performed in accordance with <RID>NETA ATS</RID>.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.20.1.1   Medium Voltage Cables</TTL><BRK/>
<BRK/>
<TXT>Perform tests after installation of cable, splices, and terminators and before terminating to equipment or splicing 
to existing circuits.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Visual and Mechanical Inspection</ITM><BRK/>
<BRK/>
<ITM>(1)  Inspect exposed cable sections for physical damage.</ITM><BRK/>
<BRK/>
<ITM>(2)  Verify that cable is supplied and connected in accordance with contract plans and specifications.</ITM><BRK/>
<BRK/>
<ITM>(3)  Inspect for proper shield grounding, cable support, and cable termination.</ITM><BRK/>
<BRK/>
<ITM>(4)  Verify that cable bends are not less than ICEA or manufacturer's minimum allowable bending 
radius.</ITM><BRK/>
<BRK/>
<ITM>(5)  Inspect for proper fireproofing.</ITM><BRK/>
<BRK/>
<ITM>(6)  Visually inspect jacket and insulation condition.</ITM><BRK/>
<BRK/>
<ITM>(7)  Inspect for proper phase identification and arrangement.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Electrical Tests</ITM><BRK/>
<BRK/>
<ITM>(1)  Perform a shield continuity test on each power cable by ohmmeter method.  Record ohmic 
value, resistance values in excess of 10 ohms per 1000 feet of cable must be investigated and 
justified.</ITM><BRK/>
<BRK/>
<ITM>(2) Perform acceptance test on new cables before the new cables are connected to existing cables 
and placed into service, including terminations and joints. Perform maintenance test on complete 
cable system after the new cables are connected to existing cables and placed into service, 
including existing cable, terminations, and joints. Tests shall be very low frequency (VLF) 
alternating voltage withstand tests in accordance with <RID>IEEE Std 400.2</RID>. VLF test frequency shall 
be 0.05 Hz minimum for a duration of 60 minutes using a sinusoidal waveform. Test voltages shall 
be as follows:<BRK/>
<BRK/>
CABLE RATING AC TEST VOLTAGE for ACCEPTANCE TESTING <BRK/>
5 kV          10kV rms(peak) <BRK/>
8 kV          13kV rms(peak) <BRK/>
15 kV          20kV rms(peak) <BRK/>
25 kV          31kV rms(peak) <BRK/>
35 kV          44kV rms(peak) <BRK/>
<BRK/>
CABLE RATING AC TEST VOLTAGE for MAINTENANCE TESTING <BRK/>
5 kV          7kV rms(peak) <BRK/>
8 kV          10kV rms(peak) <BRK/>
15 kV          16kV rms(peak) <BRK/>
25 kV          23kV rms(peak) <BRK/>
35 kV          33kV rms(peak) </ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>3.20.1.2   Grounding System</TTL><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Visual and mechanical inspection</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">Inspect ground system for compliance with contract plans and specifications</ITM><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Electrical tests</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">Perform ground-impedance measurements utilizing the fall-of-potential method in accordance with <RID>
IEEE Std 81</RID>.  <TST>On systems consisting of interconnected ground rods, perform tests after interconnections 
are complete.  On systems consisting of a single ground rod perform tests before any wire is 
connected.</TST>  Take measurements in normally dry weather, not less than 48 hours after rainfall.  
Use a portable megohmmeter tester in accordance with manufacturer's instructions to test each 
ground or group of grounds.  The instrument shall be equipped with a meter reading directly 
in ohms or fractions thereof to indicate the ground value of the ground rod or grounding systems 
under test.</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.20.2   Follow-Up Verification</TTL><BRK/>
<BRK/>
<TXT><TST>Upon completion of acceptance checks and tests, the Contractor shall show by demonstration in service that circuits 
and devices are in good operating condition and properly performing the intended function.</TST>  As an exception to 
requirements stated elsewhere in the contract, the Contracting Officer shall be given 5 working days advance 
notice of the dates and times of checking and testing.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><BRK/>