<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA            UFGS-42 22 13 (August 2008)<BRK/>
                                          --------------------------------<BRK/>
Preparing Activity:  <PRA>NASA</PRA>                 Superseding<BRK/>
                                          UFGS-42 22 13.00 40 (April 2008)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 42 22 13</SCN><BRK/>
<BRK/>
<STL>CENTRIFUGAL PROCESS CHILLERS AND COOLERS</STL><BRK/>
<DTE>08/08</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This specification covers the requirements for <SCP>packaged self-contained 
hermetic compressor units</SCP>.  Rewrite if unit is not self-contained per definition.</NPR><BRK/>
<BRK/>
<NPR>Drawings or schedule shall include capacity, capacity conditions, pressure drops, 
control diagrams, and refrigerant used.</NPR><BRK/>
<BRK/>
<NPR>Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.</NPR><BRK/>
<BRK/>
<NPR>Remove information and requirements not required in respective project, whether 
or not brackets are present.</NPR><BRK/>
<BRK/>
<NPR>Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.</NPR><BRK/>
<BRK/>
<NPR>Submit recommended changes to a UFGS as a <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request (CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification.  The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
<BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
<BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>AIR-CONDITIONING, HEATING AND REFRIGERATION INSTITUTE (AHRI)</ORG><BRK/><BRK/><RID>AHRI 480</RID><RTL>(2007) Standard for Refrigerant-Cooled Liquid Coolers, Remote Type</RTL><BRK/><BRK/><RID>AHRI 520</RID><RTL>(2004) Performance Rating of Positive Displacement Condensing Units</RTL><BRK/><BRK/><RID>AHRI 550/590</RID><RTL>(2003) Standard for Water-Chilling Packages Using the Vapor Compression Cycle</RTL><BRK/><BRK/></REF><REF><ORG>AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING ENGINEERS (ASHRAE)</ORG><BRK/><BRK/><RID>ASHRAE EQUIP SI HDBK</RID><RTL>(2004) Handbook, HVAC Systems and Equipment (SI Edition)</RTL><BRK/><BRK/></REF><REF><ORG>ASME INTERNATIONAL (ASME)</ORG><BRK/><BRK/><RID>ASME BPVC SEC VIII D1</RID><RTL>(2007; Addenda 2008) Boiler and Pressure Vessel Code; Section VIII, Pressure Vessels Division 1 - Basic Coverage</RTL><BRK/><BRK/></REF><REF><ORG>INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO)</ORG><BRK/><BRK/><RID>ISO 1940-1</RID><RTL>(2003; Corrigendum 2005) Mechanical Vibration - Balance Quality Requirements for Rotors in a Constant (Rigid) State - Part 1:  Specification and Verification of Balance Tolerance - International Restrictions</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)</ORG><BRK/><BRK/><RID>NEMA 250</RID><RTL>(2003) Enclosures for Electrical Equipment (1000 Volts Maximum)</RTL><BRK/><BRK/><RID>NEMA MG 1</RID><RTL>(2007; Errata 2008) Standard for Motors and Generators</RTL><BRK/><BRK/></REF><REF><ORG>U.S. DEPARTMENT OF ENERGY (DOE)</ORG><BRK/><BRK/><RID>DOE CE-2</RID><RTL>(2000) How to Buy an Energy-Efficient Water-Cooled Electric Chiller</RTL><BRK/><BRK/><RID>DOE CE-6</RID><RTL>(2000) How to Buy an Energy-Efficient Air-Cooled Electric Chiller</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review Submittal Description (SD) definitions in Section <SRF>01 33 00</SRF> SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Keep submittals to the minimum required for adequate quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  Submit the following 
in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-01 Preconstruction Submittals</SUB></LST><BRK/>
<BRK/>
<ITM>Submit <SUB>Material, Equipment, and Fixture Lists</SUB> for centrifugal chiller systems in accordance 
with paragraph entitled, "General Requirements," of this section.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM>Submit connection diagrams indicating the relations and connections of the following items.  
Drawings shall indicate the physical layout of all controls, and internal tubing and wiring 
details.</ITM><BRK/>
<BRK/>
<ITM><SUB>Centrifugal Water Chiller</SUB></ITM><BRK/>
<ITM><SUB>Compressor</SUB></ITM><BRK/>
<ITM><SUB>Condenser</SUB></ITM><BRK/>
<ITM><SUB>Cooler</SUB></ITM><BRK/>
<ITM><SUB>Purge System</SUB></ITM><BRK/>
<ITM><SUB>Motors</SUB></ITM><BRK/>
<ITM><SUB>Control and Control Panels</SUB></ITM><BRK/>
<BRK/>
<ITM>Submit <SUB>Control Diagrams</SUB> for centrifugal chiller units in accordance with paragraph entitled, 
"General Requirements," of this section.</ITM><BRK/>
<BRK/>
<ITM>Submit installation drawings for centrifugal chiller systems in accordance with the paragraph 
entitled, "Installation," of this section.  Drawings shall indicate overall physical features, 
dimensions, ratings, service requirements, and equipment weights.</ITM><BRK/>
<BRK/>
<ITM>Submit <SUB>Record Drawings</SUB> for centrifugal chiller units in accordance with paragraph entitled, 
"General Requirements," of this section.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM>Submit <SUB>Equipment Foundation Data</SUB> for the following items in accordance with paragraph entitled, 
"General Requirements," of this section.</ITM><BRK/>
<BRK/>
<ITM><SUB>Centrifugal Water Chiller</SUB></ITM><BRK/>
<ITM><SUB>Compressor</SUB></ITM><BRK/>
<ITM><SUB>Condenser</SUB></ITM><BRK/>
<ITM><SUB>Cooler</SUB></ITM><BRK/>
<ITM><SUB>Purge System</SUB></ITM><BRK/>
<ITM><SUB>Motors</SUB></ITM><BRK/>
<BRK/>
<ITM>Submit <SUB>Equipment and Performance Data</SUB> for centrifugal water chillers in accordance with paragraph 
entitled, "General Requirements," of this section.</ITM><BRK/>
<BRK/>
<ITM>Submit manufacturer's catalog data for the following items:</ITM><BRK/>
<BRK/>
<ITM><SUB>Centrifugal Water Chiller</SUB></ITM><BRK/>
<ITM><SUB>Compressor</SUB></ITM><BRK/>
<ITM><SUB>Condenser</SUB></ITM><BRK/>
<ITM><SUB>Cooler</SUB></ITM><BRK/>
<ITM><SUB>Purge System</SUB></ITM><BRK/>
<ITM><SUB>Motors</SUB></ITM><BRK/>
<ITM><SUB>Control and Control Panels</SUB></ITM><BRK/>
<ITM><SUB>Insulation</SUB></ITM><BRK/>
<ITM><SUB>Vibration Isolation</SUB></ITM><BRK/>
<ITM><SUB>Special Tools</SUB></ITM><BRK/>
<ITM><SUB>Spare Parts</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-04 Samples</SUB></LST><BRK/>
<BRK/>
<ITM>Submit <SUB>Manufacturer's Standard Color Chart</SUB> in accordance with paragraph entitled, "General Requirements," 
of this section.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-05 Design Data</SUB></LST><BRK/>
<BRK/>
<ITM>Submit <SUB>Design Analysis and Calculations</SUB> in accordance with paragraph entitled, "General Requirements," 
of this section.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM>Submit <SUB>Test Reports</SUB> for chiller units indicating the results of performance tests performed 
in accordance with the paragraph entitled, "Field Testing," of this section.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM>Submit <SUB>Listing of Product Installation</SUB> for centrifugal chiller units in accordance with paragraph 
entitled, "Installation," of this section.</ITM><BRK/>
<BRK/>
<ITM>Submit certificates for following items showing conformance with the referenced standards contained 
in this section.</ITM><BRK/>
<BRK/>
<ITM><SUB>Centrifugal Water Chiller</SUB></ITM><BRK/>
<ITM><SUB>Compressor</SUB></ITM><BRK/>
<ITM><SUB>Condenser</SUB></ITM><BRK/>
<ITM><SUB>Cooler</SUB></ITM><BRK/>
<ITM><SUB>Purge System</SUB></ITM><BRK/>
<ITM><SUB>Motors</SUB></ITM><BRK/>
<ITM><SUB>Control and Control Panels</SUB></ITM><BRK/>
<ITM><SUB>Insulation</SUB></ITM><BRK/>
<ITM><SUB>Vibration Isolation</SUB></ITM><BRK/>
<ITM><SUB>Special Tools</SUB></ITM><BRK/>
<ITM><SUB>Spare Parts</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM>Submit <SUB>Operation and Maintenance Manuals</SUB> in accordance with paragraph entitled, "Manufacturer's 
Representative," of this section.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   GENERAL REQUIREMENTS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If Section <SRF>23 00 00</SRF> AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST 
SYSTEMS is not included in the project specification, applicable requirements 
therefrom should be inserted and the following paragraph deleted.  If Section 
<SRF>23 05 48</SRF> VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT is not 
included in the project specification, applicable requirements therefrom should 
be inserted and the second paragraph deleted.  If Section <SRF>26 60 13.00 40</SRF> LOW-VOLTAGE 
MOTORS is not included in the project specification, applicable requirements 
therefrom should be inserted and the third paragraph deleted.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Section <SRF>23 00 00</SRF> AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS applies to work specified in this 
section.]</TXT><BRK/>
<BRK/>
<TXT>[Section <SRF>23 05 48</SRF> VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT applies to work specified in this 
section.]</TXT><BRK/>
<BRK/>
<TXT>[Section <SRF>26 60 13.00 40</SRF> LOW-VOLTAGE MOTORS applies to this section.]</TXT><BRK/>
<BRK/>
<TXT>Submit <SUB>Control Diagrams</SUB> for centrifugal chiller units showing the physical and functional relationship of equipment.  
Electrical diagrams shall show the size, type, and capacity of the system.</TXT><BRK/>
<BRK/>
<TXT>Submit <SUB>Record Drawings</SUB> for centrifugal chiller units providing current factual information including deviations 
from, and amendments to, the drawings and concealed and visible changes in the work.</TXT><BRK/>
<BRK/>
<TXT>Submit <SUB>Material, Equipment, and Fixture Lists</SUB> for centrifugal chiller systems including manufacturer's style 
or catalog numbers, specification and drawing reference numbers, warranty information, and fabrication site information.</TXT><BRK/>
<BRK/>
<TXT>Submit <SUB>Equipment and Performance Data</SUB> for centrifugal water chillers indicating the guaranteed maximum brake 
power at 75-, 50-, 25-, and 10- percent points of full compressor capacity at design condenser water temperature.  
Develop this information from data specified herein.</TXT><BRK/>
<BRK/>
<TXT>Submit <SUB>Equipment Foundation Data</SUB> including equipment weight and operating loads, location and projection of anchor 
bolts, and horizontal and vertical clearances for installation, operation, and maintenance.  Data shall also 
include dimensions of foundations and relative elevations, and installation requirements such as noise abatement, 
vibration isolation, and utility services.</TXT><BRK/>
<BRK/>
<TXT><SUB>Manufacturer's Standard Color Chart</SUB> shall indicate the manufacturer's standard color selections and finishes 
for chiller units.</TXT><BRK/>
<BRK/>
<TXT>Submit <SUB>Design Analysis and Calculations</SUB> for centrifugal chillers indicating the manufacturer's recommended power 
ratings, rotational speeds, and piston speeds.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Pump and Motor balance shall conform to ISO 1940-1 - (1986) Balance Quality 
Requirements of Rigid Rotors - Determination of Permissible Residual Unbalance 
unless otherwise noted.  Motor vibration levels shall conform to NEMA Specification 
MG-1, Motors and Generators, Part 7 unless otherwise noted.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  All rotating machinery shall be capable of having shaft alignment and 
machine balance following installation.  This requirement shall include "skid-mounted" 
and "self-contained" units.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Balance is the process of improving the mass distribution of the pump 
components in order to minimize damaging centrifugal forces. No component can 
be perfectly balanced.  There will always be some remaining unbalance.  The 
minimum recommended balance grade is ISO grade 2.5. Select an ISO grade or insert 
a standard.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.1   <SUB>CENTRIFUGAL WATER-CHILLER</SUB> PACKAGE</TTL><BRK/>
<BRK/>
<TXT>Ensure centrifugal water-chiller assembly is packaged and self-contained, and includes compressor-condenser, 
cooler (refrigerant evaporator) accessories, control panel, and intercomponent piping and wiring ready for field-terminal 
connections.</TXT><BRK/>
<BRK/>
<TXT>Unit and <SUB>spare parts</SUB> shall conform to the applicable requirements of <RID>AHRI 550/590</RID>, <RID>AHRI 480</RID>, and specified requirements.  
Energy efficiency ratings shall meet or exceed the full-load efficiency and the integrated part-load value (IPLV) 
efficiency ratings as described in <RID>AHRI 550/590</RID> and the recommended levels specified in <RID>DOE CE-2</RID> and <RID>DOE CE-6</RID>
.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2   <SUB>COMPRESSOR</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  At higher than 3,600 rpm speeds, reevaluate 0.025 millimeter vibration 
limit.  Do not use compressor that will operate at 20,000 or higher rpm.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Compressor shall be [single] [multistage], [direct] [gear-driven] centrifugal type, with hermetically sealed, 
compressor-motor assembly. Motor windings shall be [refrigerant] [water-cooled].  Rotor assembly shall be statically 
and dynamically balanced to <RID>ISO 1940-1</RID> -1986, [G6.3] [G2.5] [G1.0] [_____].  Shaft main bearings shall be replaceable 
sleeve-insert type.</TXT><BRK/>
<BRK/>
<TXT>Lubrication system shall be of the forced-feed type with oil sump, hermetically sealed motor-driven positive 
displacement pump, oil filter, and strainer.  Oil temperature shall be thermostatically controlled.  Provide 
a mechanically operated oil supply to the bearings during spin down in event of power interruption.  A differential 
oil-pressure cutout shall be interlocked with starting equipment and shall allow the compressor to operate only 
when the required oil pressure is available at the bearings.</TXT><BRK/>
<BRK/>
<TXT>Provide compressor with temperature-actuated capacity reduction and of the multiple radial blade or butterfly-damper 
type Variable Frequency Drive (VFD) compressor motor control to provide automatic capacity regulation from 100 
percent to 10 percent of capacity.  Provide automatic hot-gas bypass if required to maintain stable operation.  
Control system shall include automatic stopping, when load falls below 10 percent capacity point, and automatic 
unloaded restarting on load demand.  Capacity modulation shall be controlled by the temperature of the water 
leaving the cooler.  Unit controller shall be able to maintain leaving-water temperature at plus or minus<MET> 0.25 
degrees C</MET><ENG> 0.5 degree F</ENG> of the set point.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3   <SUB>CONDENSER</SUB></TTL><BRK/>
<BRK/>
<TXT>Condenser shall be of the shell-and-tube cleanable-type construction. Condenser shall comply with<MET> <RID>ASHRAE EQUIP SI HDBK</RID>
, Chapter 13, and</MET> <RID>ASME BPVC SEC VIII D1</RID>regarding quality of materials used, methods of construction, design of 
components, and testing of materials, assemblies, connections, and appurtenances.  Minimum water-side working 
pressure shall be<MET> 1050 kilopascal</MET><ENG>150 psig</ENG>, and minimum refrigerant-side working pressure shall be saturation 
pressure of refrigerant used at<MET> 29 degrees C</MET><ENG> 85 degrees F</ENG>.  Spaces not subject to ASME code due to size or other 
limitations shall be pneumatically tested at 1-1/2 times working pressure or<MET> 310 kilopascal</MET><ENG> 45 psig</ENG>, whichever 
is greater.</TXT><BRK/>
<BRK/>
<TXT>Tubes shall be seamless copper tubing with integral fins and individually removable from either end of shell.  
Tubes shall be rolled or brazed into tube sheet.  Provide intermediate tube supports so that distance between 
supports does not exceed approximately<MET> 900 millimeter</MET><ENG> 3 feet</ENG>.  Supports shall be fitted to the tubes in a manner 
that will preclude corrosion, vibration, and abrasion.</TXT><BRK/>
<BRK/>
<TXT>Fit and arrange water boxes or removable elbows to permit cleaning of tubes without disturbing piping beyond 
elbows.  Elbows shall be flanged- or grooved-coupling type.  End bells shall be hinged-mounted.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  R-12 is designated as a restricted material.  Use available substitutes 
as apply to specifier's application.  CFC's shall be phased out.  No new designs 
using CFC's allowed.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Design the unit to permit pump-down and isolation of the entire refrigerant charge within 80 percent of available 
condenser volume.  If the unit condenser does not have sufficient pump-down capacity, provide a separate pump-out 
tank.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Many present-day nonchromate water treatment chemicals degrade at temperatures 
as low as<ENG> 100 to 135 degrees F</ENG><MET> 38 to 57 degrees C</MET> and tend to severely foul 
heat-transfer surfaces.  The difference between a fouling factor of 0.0005 and 
0.001 could approximate 7 percent of machine capacity.  Cost of unit with 0.001 
fouling factor will be higher and may be restrictive.<BRK/>
<BRK/>
Limiting water velocity to<MET> 2 meter per second</MET><ENG> 7 feet per second (fps)</ENG> could 
force selection of next larger size machine.<BRK/>
<BRK/>
Tube protectors are usually required at velocities in excess of<MET> 2 meter per 
second</MET><ENG> 7 fps</ENG>.<BRK/>
<BRK/>
Select one of the following two paragraphs. Normally, select the first paragraph.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Base the condenser performance on a maximum water velocity of<MET> 3 meter per second</MET><ENG> 10 feet per second (fps)</ENG> and 
a fouling factor of 0.001.  Design and construction provisions shall preclude tube failure due to erosion.</TXT><BRK/>
<BRK/>
<TXT>Base the condenser performance on a maximum water velocity of<MET> 2 meter per second</MET><ENG> 7 fps</ENG> and a fouling factor of 
0.001.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4   <SUB>COOLER</SUB> (REFRIGERANT EVAPORATOR)</TTL><BRK/>
<BRK/>
<TXT>Cooler shall conform to the requirements specified herein in paragraph entitled, "Condenser," and the following:</TXT><BRK/>
<BRK/>
<TXT>Base the cooler capacity on refrigerant suction temperature in excess of<MET> 0 degrees C</MET><ENG> 32 degrees F</ENG> and a fouling 
factor of 0.0005.</TXT><BRK/>
<BRK/>
<TXT>Provide a frangible safety relief device.  Device to be piped to building exterior.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5   <SUB>PURGE SYSTEM</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  R-11 and R-113 are restricted materials.  Purge system applies only to 
existing units and modifications.  An available substitute should be found and 
incorporated immediately.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>When HCFC-123 refrigerant is used, provide and connect a high efficiency purge system to the main refrigeration 
system.  When in operation, the purge system shall function to automatically remove air, water vapor, and noncondensable 
gases from the refrigeration system and to condense, separate, and return to the system any refrigerant present 
therein.  Purge system shall be manually or automatically started and stopped and shall be assembled as a compact 
unit.  Purge system shall be complete with operating and safety devices and with an oil separator if recommended 
by the manufacturer.  When a positive-pressure refrigerant is used by the manufacturer in the basic liquid chiller 
unit, a purge system will not be required.  Units shall purge no more than<MET> 0.045 kg</MET><ENG> 0.1 pounds</ENG> of non-condensable.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6   <SUB>CONTROL AND CONTROL PANELS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the following paragraph only after checking control panel sizes 
and numbers to be sure they can be unit mounted.  Some or all starters may be 
mounted in motor control center and unit will not be totally self-contained.<BRK/>
<BRK/>
Coordinate with Section <SRF>23 09 33.00 40</SRF> ELECTRIC AND ELECTRONIC CONTROL SYSTEM 
FOR HVAC and electrical requirements.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide water-chilling unit with one or more control panels containing safety and operating devices and intercomponent 
piping and wiring for field terminal connection and fully automatic operation.</TXT><BRK/>
<BRK/>
<TXT>Coordinate the controls with automatic temperature controls systems and electrical work specified and indicated.  
Control panel shall contain control equipment specified, and control equipment normally furnished and recommended 
by the manufacturer for optimum operation of the system. Control panel items shall be permanently identified, 
including at least the following:</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following are manufacturer's standard items.  If the last two listed 
items, motor controllers and NEMA 1 enclosures, are specified elsewhere, delete 
from this paragraph.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST>Refrigerant suction and discharge pressure gages<BRK/>
<BRK/>
Oil-pressure gages<BRK/>
<BRK/>
Purge-drum pressure gage<BRK/>
<BRK/>
Refrigerant low-temperature or low-pressure cutout<BRK/>
<BRK/>
Refrigerant high-pressure cutout<BRK/>
<BRK/>
Time delay relays<BRK/>
<BRK/>
Motor high-temperature cutout<BRK/>
<BRK/>
Lubricating-oil high-temperature cutout if required by equipment<BRK/>
<BRK/>
Oil differential-pressure interlock<BRK/>
<BRK/>
Interlock relays and reset button<BRK/>
<BRK/>
Manual/automatic selector switches and controls for purge pumps<BRK/>
<BRK/>
Pilot lights indicating position of safety controls<BRK/>
<BRK/>
System start/stop provisions with condition-indicating lights<BRK/>
<BRK/>
Load-limiting device to operate capacity-control mechanism<BRK/>
<BRK/>
Cooler refrigerant thermometer with well<BRK/>
<BRK/>
Main circuit protective and interruptive device<BRK/>
<BRK/>
Transformers for any other source-voltage requirements<BRK/>
<BRK/>
Terminals for field-installed equipment<BRK/>
<BRK/>
Motor controllers<BRK/>
<BRK/>
<RID>NEMA 250</RID>, Type 1 enclosures</LST><BRK/>
<BRK/>
<TXT>Provide the following items as part of the installation:</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate with drawings.  Select, delete, or supplement.  These are 
normally field-installed by the Contractor.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST>Audible-alarm bell,<MET> 100 millimeter</MET><ENG> 4-inch</ENG> diameter<BRK/>
<BRK/>
Chilled-water and condenser supply-and-return thermometers with wells<BRK/>
<BRK/>
Indicating-type chilled-water thermostat with well<BRK/>
<BRK/>
Chilled-water low-temperature cutout</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7   <SUB>MOTORS</SUB></TTL><BRK/>
<BRK/>
<TXT>Hermetically sealed motors shall conform to <RID>NEMA MG 1</RID> <RID>AHRI 520</RID> and to requirements for motors as specified herein.</TXT><BRK/>
<BRK/>
<TXT>Bearings shall be [oil-lubricated, replaceable-sleeve, insertable type] [permanently lubricated, rolling element 
type].</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Normally delete the following paragraph. Review.  Limit percent of full-load 
amperes at which motor controller overload will trip (105 percent, trane), gas 
pressure differential, pumps, sprays, unit capacity, or other.  Coordinate with 
motor controller specification and drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Motor shall have two manually resettable thermal-overload protective devices located within windings.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate the following with the following motor controller specification 
and drawings.  Rewrite as necessary to suit designed size and type equipment.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>If water-chilled unit or any component could be damaged by reverse motor operation, and when proposed water-chiller 
unit contains a mechanically driven lubricating-oil pump, the manufacturer's responsibility shall include:</TXT><BRK/>
<BRK/>
<LST>Providing reverse-phase rotation protection, if motor controllers are provided as part of package.</LST><BRK/>
<BRK/>
<LST>Indicating in shop drawings that reverse-phase rotation protection is necessary if motor controllers 
are in a motor-control center not provided by the manufacturer.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.8   <SUB>INSULATION</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the following paragraphs only when specified equipment is to be 
provided with factory insulation.  Normally provide for field insulation of 
cooler headers.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Cooler shell and suction piping between evaporator and first stage of each compressor unit shall be insulated 
and vapor-sealed.  Insulate the water boxes to provide for ease of access to heads for inspection and repair. 
Where motors are the gas-cooled type, provide insulation and vapor seal on the cold-gas inlet connection to the 
motor.</TXT><BRK/>
<BRK/>
<TXT>Vapor-seal material shall be manufacturer's standard color elastomeric unicellular foam of<MET> 25 millimeter</MET><ENG> 1 inch</ENG>
 minimum thickness to preclude condensation of ambient moisture on any surface under site-operating conditions.  
If unicellular material is black or is otherwise coated, only use polyvinylchloride lacquer for coating.  Remove 
and replace any coating that cracks when unicellular material is compressed with specified coating at no additional 
expense to the Government.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9   <SUB>VIBRATION ISOLATION</SUB></TTL><BRK/>
<BRK/>
<TXT>Vibration isolation provisions shall conform to requirements specified in Section <SRF>23 05 48</SRF> VIBRATION AND SEISMIC 
CONTROLS FOR HVAC PIPING AND EQUIPMENT.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.10   <SUB>SPECIAL TOOLS</SUB></TTL><BRK/>
<BRK/>
<TXT>One complete set of special tools, as recommended by the manufacturer, shall be provided for field maintenance 
of the system.  Tools shall be contained in a locked toolbox.  Provide two keys to the Contracting Officer.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Install equipment as specified, and in accordance with manufacturer's recommendations.</TXT><BRK/>
<BRK/>
<TXT>Submit <SUB>Listing of Product Installation</SUB> for centrifugal chiller units showing at least 5 installed units, similar 
to those proposed for use, that have been in successful service for a minimum period of 5 years.  List shall 
include purchaser, address of installation, service organization, and date of installation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   MANUFACTURER'S REPRESENTATIVE</TTL><BRK/>
<BRK/>
<TXT>Services of a competent factory-trained representative shall be provided to supervise the assembly, charging, 
testing, and startup of equipment; in addition, Government personnel shall receive 8 hours of instructions in 
proper operation and maintenance procedures.  A factory performance test will be conducted on every chiller in 
accordance with <RID>AHRI 550/590</RID>.  Test will be witnessed by Government and Contractor.</TXT><BRK/>
<BRK/>
<TXT>Contractor shall submit [6] [_____] copies of the <SUB>Operation and Maintenance Manuals</SUB> 30 calendar days prior to 
testing the centrifugal chiller system.  Update and resubmit data for final approval no later than 30 calendar 
days prior to contract completion.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3   REFRIGERANT AND OIL CHARGE</TTL><BRK/>
<BRK/>
<TXT>Completely charge unit(s) with refrigerant and oil before operation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4   ALIGNMENT</TTL><BRK/>
<BRK/>
<TXT>Before attempting alignment, the contractor will demonstrate that the pump does not have any load/force imposed 
by the piping system.  Minimum alignment values (below) are for pump and driver at normal running temperatures.  
Ensure values are compensated for thermal growth.  Ensure limited movement of the pump or driver (commonly known 
as bolt-bound) is corrected to ensure alignment capability.  Hold down bolts shall not be undercut in order to 
perform adjustment.</TXT><BRK/>
<BRK/>
<TXT>Shims shall be commercially die-cut, without seams  or folds, and be made of corrosion resistant stainless steel. 
Use no more than four shims at any single point.</TXT><BRK/>
<BRK/>
<TXT>Units with drive motor over [7.5][10][15][20][25] hp shall have alignment jack bolts installed.</TXT><BRK/>
<BRK/>
<TXT>Pump and driver may have an intermediate shaft, spacer, or spool piece (sometimes called a jackshaft) Based on 
the motor nominal operating speed, the Pump and driver shall be aligned to the following minimum specifications:</TXT><BRK/>
<BRK/>
<TBL><THD>      Speed(RPM)   Close-Coupled   Close-Coupled   Spool Piece Angle<BRK/>
                   Offset (mils)   Angle(mils/in.) (mils/in. @ coupling pt.)<BRK/>
<BRK/></THD>
        600            6.0             2.0                 3.0<BRK/>
        900            5.0             1.5                 2.0<BRK/>
        1200           4.0             1.0                 1.5<BRK/>
        1800           3.0             0.5                 1.0<BRK/>
        3600           1.5             0.4                 0.5<BRK/>
        7200           1.0             0.3                 0.4<BRK/></TBL>
<BRK/>
<TXT>Perform pump alignment under the direction of the manufacturer's representative.</TXT><BRK/>
<BRK/>
<TXT>Provide final alignment settings as part of the final test data.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5   FIELD TESTING</TTL><BRK/>
<BRK/>
<TXT>Prior to final acceptance, vibration analysis shall verify pump and motor conformance to specifications.  Vibration 
levels shall not be more than .075 in/sec at 1 times run speed and at pump frequency, and .04 in/sec at other 
multiples of run speed.</TXT><BRK/>
<BRK/>
<TXT>Contractor shall use an Fast Fourier Transformer (FFT) analyzer to measure vibration levels.  It shall have the 
following characteristics: A dynamic range greater than 70 dB; a minimum of 400 line resolution; a frequency 
response range of 5 Hz-10 KHz(300-600000 cpm); the capacity to perform ensemble averaging, the capability to 
use a Hanning window; auto-ranging frequency amplitude; a minimum amplitude accuracy over the selected frequency 
range of plus or minus 20 percent or plus or minus 1.5 dB.  An accelerometer, either stud-mounted or mounted 
using a rare earth, low mass magnet and sound disk(or finished surface) shall be used with the FFT analyzer to 
collect data.  The mass of the accelerometer and its mounting shall have minimal influence on the frequency response 
of the system over the selected measurement range.</TXT><BRK/>
<BRK/>
<TXT>Upon completion of the installation, and within 60 calendar days after the date of initial operation, <TST>performance 
tests shall be conducted in the presence of the Contracting Officer</TST>.  Conduct these tests until the performance 
of the system is proven, with 8 hours of successful operation as a minimum period.  Any equipment defects or 
performance deficiencies shall be corrected, and the tests repeated until performance is fully satisfactory.  
Determine the water flows from pressure-drop across chiller and condenser, and from pump curves.  Provide calibrated 
test instruments.  Government will provide load.</TXT><BRK/>
<BRK/>
<TXT><TST>Ensure each unit is tested for leaks under pressure and evacuated and dehydrated to<MET> 2 degrees C</MET><ENG> 35 degrees F</ENG> 
wet bulb, or an absolute pressure of not over<MET> 813 pascal</MET><ENG> 0.24 inch of mercury</ENG></TST></TXT><BRK/>
<BRK/>
<TXT>Provide final <SUB>test reports</SUB> to the Contracting Officer.  Reports shall have a cover letter/sheet clearly marked 
with the System name, Date, and the words "Final Test Reports - Forward to the Systems <NED/>Engineer/Condition Monitoring 
Office/Predictive Testing Group for inclusion in the Maintenance Database."</TXT><BRK/>
<BRK/></SPT>
</PRT>    <END/><BRK/></SEC>