<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA      UFGS-44 44 46 (April 2006)<BRK/>
                                    ------------------------------<BRK/>
Preparing Activity:  <PRA>NAVFAC</PRA>         Replacing without change<BRK/>
                                    UFGS-11706 (August 2004)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 44 44 46</SCN><BRK/>
<BRK/>
<STL>HYDROTHERAPY EQUIPMENT</STL><BRK/>
<DTE>04/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>prefabricated hydrotherapy 
equipment and required accessories</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 167</RID><RTL>(1999; R 2004) Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip</RTL><BRK/><BRK/><RID>ASTM B 221</RID><RTL>(2008) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes</RTL><BRK/><BRK/><RID>ASTM B 221M</RID><RTL>(2007) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric)</RTL><BRK/><BRK/><RID>ASTM E 162</RID><RTL>(2008a) Surface Flammability of Materials Using a Radiant Heat Energy Source</RTL><BRK/><BRK/><RID>ASTM E 84</RID><RTL>(2008a) Standard Test Method for Surface Burning Characteristics of Building Materials</RTL><BRK/><BRK/></REF><REF><ORG>INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS (IAPMO)</ORG><BRK/><BRK/><RID>IAPMO Z124.1.2</RID><RTL>(2005) Plastic Bathtub and Shower Units</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/><RID>NFPA 99</RID><RTL>(2005; Errata 2005) Health Care Facilities</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 544</RID><RTL>(1998; Rev thru Jul 1999) Medical and Dental Equipment</RTL><BRK/><BRK/><RID>UL 723</RID><RTL>(2008) Standard for Test for Surface Burning Characteristics of Building Materials</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   RELATED REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Conform to Sections <SRF>11 70 00</SRF> GENERAL REQUIREMENTS FOR MEDICAL AND DENTAL EQUIPMENT; <SRF>23 03 00.00 20</SRF> BASIC MECHANICAL 
MATERIALS AND METHODS; <SRF>22 00 00</SRF> PLUMBING SYSTEMS; <SRF>22 60 70</SRF> GAS AND VACUUM SYSTEMS FOR HEALTHCARE FACILITIES; 
<SRF>26 00 00.00 20</SRF> BASIC ELECTRICAL MATERIALS AND METHODS; and <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete any items that are not used; add any additional items requiring 
shop drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM><SUB>Bath, Whirlpool, Arm Treatment</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Bath, Whirlpool, Leg Treatment</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Bath, Hydrotreatment</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Bath, Hydrotherapy, Burn Treat</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Bath, Hydrotherapy Treatment</SUB>, Sitting[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Bath, Whirlpool, Arm Treatment</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Bath, Whirlpool, Leg Treatment</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Bath, Hydrotreatment</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Bath, Hydrotherapy Burn Treat</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Bath, Hydrotherapy Treatment</SUB>, Sitting[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Valve</SUB>, Thermostic Mixing[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   MATERIALS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1.1   Stainless Steel</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM A 167</RID>, Class 301, 302, or 304.  Satin finish for exposed surfaces and No. 4 finish for interior surfaces.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   Aluminum Alloy</TTL><BRK/>
<BRK/>
<TXT><MET><RID>ASTM B 221M</RID></MET><ENG><RID>ASTM B 221</RID></ENG> equivalent in ultimate tensile, yield, and shear strengths to Alloy 6063-T5 or 6063-T6, 
as applicable.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2   COMPONENTS</TTL><BRK/>
<BRK/>
<TXT>Provide:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Tank construction, stainless steel</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Tank fittings</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Dial thermometer</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Thermostatic water-mixing valve</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Electric turbine ejector and aerator</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Screening or similar protective devices</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Turbine-ejector elevator</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3   ITEMS</TTL><BRK/>
<BRK/>
<TTL>2.3.1   <SUB>Bath, Whirlpool, Arm Treatment</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide stainless steel pedestal mounted hydrotherapy unit suitable for arm treatment.  Include:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Treatment tank:  Welded construction, approximately<MET> 900 mm</MET><ENG> 36 inches</ENG> high,<MET> 375 mm</MET><ENG> 15 inches</ENG>
 wide, and<MET> 710 mm</MET><ENG> 28 inches</ENG> long with a depth of<MET> 450 mm</MET><ENG> 18 inches</ENG>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Drain system: <MET> 50 mm</MET><ENG> 2 inch</ENG>, handle-operated with<MET> 50 mm</MET><ENG> 2 inch</ENG> overflow for positive water 
overflow and water surface scum clearance.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Electric turbine ejector and aerator with motor and turbine ejector raising and lowering 
device.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Dial thermometer: <MET> 85 mm</MET><ENG> 3 1/2 inches</ENG> in diameter, tank mounted.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Chromium-plated water inlet assembly for connection to thermostatic valve, complete with 
vacuum breaker, volume control valve, piping, and fittings.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Thermostatic valve (<MET>38 lpm</MET><ENG>10 gpm</ENG>) designed for wall mounting.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Armrest:  One each, fabricated of stainless steel, for supporting arm inside tank during 
treatment.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  Electrical characteristics:  110-volt, 60 Hz.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">i.  Electrical convenience outlets:  Duplex-type, grounded, 3-wire, 20A, 110-volt, 60 Hz, two 
each, tank-mounted by manufacturer.</ITM><BRK/>
<BRK/>
<TTL>2.3.2   <SUB>Bath, Whirlpool, Leg Treatment</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide stainless steel floor mounted unit approximately <MET> 1500 mm</MET><ENG> 60 inches</ENG> long,<MET> 600 mm</MET><ENG> 24 inches</ENG> wide, and<MET> 
450 mm</MET><ENG> 18 inches</ENG> (long and low), tank complete with<MET> 245 watt</MET><ENG> 1/3 hp</ENG>, high-speed motor, 3,450 rpm, 110 vac, 60 
Hz.  Thermostatic mixing valve.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.3.1   <SUB>Bath, Hydrotreatment</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate hoist assembly requirements with structural conditions and 
building service on the drawings.  Unit requires an exposed steel I-beam located 
above tank.  Cord reel is designed for use with hoist to keep power cable reeled 
up and out of way.  Indicate location on drawings.  It should be positioned 
midpoint in travel of hoist. Verify that drawings include necessary power to 
reel.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Stainless steel tank,<MET> 1.8 mm thick</MET><ENG> 14 gage</ENG>, seamlessly welded; two electric turbine ejectors; two ejector carriages; 
two turbine ejector elevators; a<MET> 85 mm</MET><ENG> 3 1/2 inch</ENG> dial thermometer for tank; tank fittings, headrest; body hammock; 
body plinth; steel base supported by chromium-plated legs to include thermostatic water mixing valve assembly; 
hoist and trolley; water stretcher with two canvas crossbars and suspensions; and two canvas body slings.  Overall 
dimensions approximately<MET> 2700 mm</MET><ENG> 8 feet 10 inches</ENG> long,<MET> 1980 mm</MET><ENG> 6 feet 6 inches</ENG>wide,<MET> 865 mm</MET><ENG> 34 inches</ENG> high.  
Inside measurement of tank approximately<MET> 2185 mm</MET><ENG> 7 feet 2 inches</ENG> long,<MET> 1800 mm</MET><ENG> 6 feet</ENG>wide at head end,<MET> 1345 mm</MET><ENG>
 4 feet 5 inches</ENG> wide at foot end, and middle inset<MET> 875 mm</MET><ENG> 35 inches</ENG> wide,<MET> 550 mm</MET><ENG> 22 inches</ENG> deep, including related 
accessories.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.2   <SUB>Bath, Hydrotherapy Burn Treat</SUB></TTL><BRK/>
<BRK/>
<TXT>Rectangular treatment bath with water hydraulic lift cylinder and armlift for patient transfer.  Control panel 
with separate thermostat mixers for filling and shower.  Disinfection unit with flowmeter for variable concentration 
of disinfection.  Flexible connection hoses with shutoff valve for incoming hot water (hw) and cold water (cw).  
Bath is with a hydrotherapy unit.  Pump capacity is<MET> 190 lpm</MET><ENG> 50 gpm</ENG>.  Outside dimensions are approximately<MET> 3025 
mm</MET><ENG> 9 feet 11 inches</ENG> long,<MET> 1000 mm</MET><ENG> 3 feet 4 inches</ENG> wide, and<MET> 350 mm</MET><ENG> 14 inches</ENG> deep inside tub.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.3   <SUB>Bath, Hydrotherapy Treatment</SUB>, Sitting</TTL><BRK/>
<BRK/>
<TXT><RID>IAPMO Z124.1.2</RID>, <RID>ASTM E 84</RID>, <RID>ASTM E 162</RID> and <RID>UL 723</RID>.  Gel-coated fiberglass.  Tank shall have seat and footrest 
for sitting body treatment. Electric turbine ejector and aerator with motor.  Includes dial thermometer for tank 
and built-in thermostatic mixing valve.  Tank dimensions approximately<MET> 875 mm</MET><ENG> 35 inches</ENG> high by<MET> 1420 mm</MET><ENG> 56 inches</ENG>
 long,<MET> 750 mm</MET><ENG> 30 inches</ENG> deep at the footrest, and<MET> 600 mm</MET><ENG> 24 inches</ENG> deep at the seat.  Electrical characteristics:  
110-volt, 60 Hz, single phase.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.4   <SUB>Valve</SUB>, Thermostatic Mixing</TTL><BRK/>
<BRK/>
<TXT>Assembly with washout hose for use with portable whirlpool equipment.  Thermostatic valve to maintain temperature 
between<MET> 21 and 43 degrees C</MET><ENG> 70 and 110 degrees F</ENG> with a flow rate of<MET> 38 liters</MET><ENG> 10 gallons</ENG> per minute.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   WORKMANSHIP</TTL><BRK/>
<BRK/>
<TXT>Comply with <RID>UL 544</RID>.  Surfaces to be welded are to be free from gease, oil, dirt or other foreign materials.  
Grind exposed welds smooth to blend with adjacent surfaces.  Welds to be continuous, sound, unbroken, clean, 
and free from pitting, splatter and discoloration.<BRK/>
<BRK/>
Exposed corners and edges to be rounded to eliminae sharp edges.  All exposed surfaces, including inside of tank, 
to be free from pit-marks, weld seams, and scale.  Finish to be No. 4 commercial, uniform and free of course 
grind marks or scratched areas.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Install items at locations indicated.  Conform to Section <SRF>11 70 00</SRF> GENERAL REQUIREMENTS FOR MEDICAL AND DENTAL 
EQUIPMENT, <RID>NFPA 70</RID> and <RID>NFPA 99</RID>.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.2.1   Inspection</TTL><BRK/>
<BRK/>
<TXT>Examine each item for visual defects and conformance to specifications.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.2   Test</TTL><BRK/>
<BRK/>
<TXT>Test each item to ensure that <TST>equipment is operational</TST> and conforms to specification requirements.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT>    <END/><BRK/></SEC>