<SCN>SECTION 05 40 00</SCN><BRK/>
<BRK/>
<STL>COLD-FORMED METAL FRAMING</STL><BRK/>
<DTE>04/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>framing components 
and erection of load-bearing light gage steel</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following information shall be shown on the project drawings:</NPR><BRK/>
<BRK/>
<NPR>1.  The extent and location of all framing indicating gage, size, section modulus, 
and other structural properties required.</NPR><BRK/>
<BRK/>
<NPR>2.  Connections and other installation details.</NPR><BRK/>
<BRK/>
<NPR>3.  Indicate concentrated loads, e.g., pipe supports, that may overstress a 
flange or connection.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>AMERICAN IRON AND STEEL INSTITUTE (AISI)</ORG><BRK/><BRK/><RID>AISI SG02-1</RID><RTL>(2001) North American Specification for the Design of Cold-Formed Steel Structural Members</RTL><BRK/><BRK/><RID>AISI SG03-3</RID><RTL>(2002) Cold-Formed Steel Design Manual Set</RTL><BRK/><BRK/></REF><REF><ORG>AMERICAN WELDING SOCIETY (AWS)</ORG><BRK/><BRK/><RID>AWS D1.3/D1.3M</RID><RTL>(2008; Errata 2008) Structural Welding Code - Sheet Steel</RTL><BRK/><BRK/></REF><REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 1008/A 1008M</RID><RTL>(2008a) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardened</RTL><BRK/><BRK/><RID>ASTM A 1011/A 1011M</RID><RTL>(2008) Standard Specification for Steel, Sheet, and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability</RTL><BRK/><BRK/><RID>ASTM A 123/A 123M</RID><RTL>(2008) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products</RTL><BRK/><BRK/><RID>ASTM A 153/A 153M</RID><RTL>(2005) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware</RTL><BRK/><BRK/><RID>ASTM A 370</RID><RTL>(2008b) Standard Test Methods and Definitions for Mechanical Testing of Steel Products</RTL><BRK/><BRK/><RID>ASTM A 653/A 653M</RID><RTL>(2008) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process</RTL><BRK/><BRK/><RID>ASTM B 633</RID><RTL>(2007) Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel</RTL><BRK/><BRK/><RID>ASTM C 955</RID><RTL>(2008a) Load-Bearing (Transverse and Axial) Steel Studs, Runners (Tracks), and Bracing or Bridging for Screw Application of Gypsum Panel Products and Metal Plaster Bases</RTL><BRK/><BRK/><RID>ASTM E 329</RID><RTL>(2008) Standard Specification for Agencies Engaged in the Testing and/or Inspection of Materials Used in Construction</RTL><BRK/><BRK/></REF><REF><ORG>SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)</ORG><BRK/><BRK/><RID>SAE J78</RID><RTL>(1998) Steel Self Drilling Tapping Screws</RTL><BRK/><BRK/></REF><REF><ORG>THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)</ORG><BRK/><BRK/><RID>SSPC Paint 25</RID><RTL>(1997; E 2004) Paint Specification No. 25Zinc Oxide, Alkyd, Linseed Oil Primer for Use Over Hand Cleaned Steel Type I and Type II</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Framing Components</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  a.  Cross sections, plans, and/or elevations showing component types and locations for each 
framing application; including shop coatings and material thicknesses for each framing component.</ITM><BRK/>
<BRK/>
<ITM>  b.  Connection details showing fastener type, quantity, location, and other information to 
assure proper installation.</ITM><BRK/>
<BRK/>
<ITM>  c.  Drawings depicting panel configuration, dimensions, components, locations, and construction 
sequence if the Contractor elects to install prefabricated/prefinished frames.</ITM><BRK/>
<BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM>Steel <SUB>studs,joists</SUB>, tracks, bracing, bridging and accessories</ITM><BRK/>
<BRK/>
[<LST><SUB>SD-05 Design Data</SUB></LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Require calculations for items considered critical by the designer.  
Delete paragraph if calculations are not necessary.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM><SUB>Metal framing calculations</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Load-bearing cold-formed metal framing</SUB></ITM><BRK/>
<BRK/>
<ITM>  Mill certificates or test reports from independent testing agency, qualified in accordance 
with <RID>ASTM E 329</RID>, showing that the steel sheet used in the manufacture of each cold-formed component 
complies with the minimum yield strengths and uncoated steel thickness specified.  Test reports 
shall be based on the results of three coupon tests in accordance with <RID>ASTM A 370</RID>.</ITM><BRK/>
<BRK/>
<ITM><SUB>Welds</SUB></ITM><BRK/>
<BRK/>
<ITM>  Certified copies of welder qualifications test records showing qualification in accordance 
with <RID>AWS D1.3/D1.3M</RID>.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   DELIVERY, STORAGE, AND HANDLING</TTL><BRK/>
<BRK/>
<TXT>Deliver materials to job site and store in adequately ventilated, dry locations.  Storage area shall permit easy 
access for inspection and handling.  If necessary to store materials outside, stack off the ground, support on 
a level platform, and protect from the weather as approved.  Handle materials to prevent damage.  Finish of the 
framing members shall be maintained at all times, using an approved high zinc dust content, galvanizing repair 
paint whenever necessary to prevent the formation of rust.  Replace damaged items with new, as directed by the 
Contracting Officer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   <SUB>LOAD-BEARING COLD-FORMED METAL FRAMING</SUB></TTL><BRK/>
<BRK/>
<TXT>Include [top and bottom tracks,] bracing, fastenings, and other accessories necessary for complete installation.  
Framing members shall have the structural properties indicated.  Where physical structural properties are not 
indicated, they shall be as necessary to withstand all imposed loads. Design framing in accordance with <RID>AISI SG03-3</RID>
.  [Non-load-bearing metal framing, furring, and ceiling suspension systems are specified in Section 
<SRF>09 22 00</SRF> SUPPORTS FOR PLASTER AND GYPSUM BOARD.]  [Metal suspension systems for acoustical ceilings are specified 
in Section <SRF>09 51 00</SRF> ACOUSTICAL CEILINGS.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5   MAXIMUM DEFLECTION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Modify to suit project requirements.  Use maximum deflection of L/360 
unless special considerations require modification.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">a.  Exterior Studs:</ITM><BRK/>
<TBL><THD><BRK/>
               <HL1>Deflection Criteria</HL1>                <HL1>Exterior Finish</HL1><BRK/></THD>
<BRK/>
               L/240 or L/360                Synthetic Plaster, Metal Panels<BRK/>
               L/360                         Cement Plaster, Wood Veneer<BRK/>
               L/600                         Brick Veneer, Stone Panels<BRK/>
<BRK/>
  Wall deflections shall be computed on the basis that studs withstand all lateral forces independent of any composite 
action from sheathing materials.  Studs abutting windows or louvers shall also be designed not to exceed<MET> 6 mm</MET><ENG> 1/4 
inch</ENG> maximum deflection.<BRK/></TBL>
<BRK/>
<ITM INDENT="-0.33">b.  Floor Joists:</ITM><BRK/>
<BRK/>
<ITM>L/360 - Live load only</ITM><BRK/>
<ITM>L/240 - Total load</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Roof Rafters:</ITM><BRK/>
<BRK/>
<ITM>L/240 - Live load only</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.6.1   Drawing Requirements</TTL><BRK/>
<BRK/>
<TXT>Submit <SUB>framing components</SUB> to show sizes, thicknesses, layout, material designations, methods of installation, 
and accessories.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>1.6.2   Design Data Required</TTL><BRK/>
<BRK/>
<TXT>Submit <SUB>metal framing calculations</SUB> to verify sizes, gages, and spacing of members and connections.  Show methods 
and practices used in installation.</TXT><BRK/>
<BRK/>
]</SPT></SPT></PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   STEEL <SUB>STUDS, JOISTS</SUB>, TRACKS, BRACING, BRIDGING AND ACCESSORIES</TTL><BRK/>
<BRK/>
<TXT>Framing components shall comply with <RID>ASTM C 955</RID> and the following.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  It is assumed that members will be protected from the weather.  If members 
will be exposed or subject to moisture directly, by water infiltration, or via 
vapor transmission and condensation or indirectly in a corrosive atmosphere, 
delete carbon steels (painted) and specify coating Class<MET> Z275</MET><ENG> G90</ENG> for such members.  
Specify G40 for brick ties and screw fasteners. See special option below for 
deflection limit on exterior wall brick construction.  Grades specified are 
normally used for this type of framing.  See manufacturer's current literature 
for other grades and section properties available.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.1.1   Studs and Joists of<MET> 1.5 mm</MET><ENG> 16 Gage (0.0598 Inch)</ENG> and Heavier</TTL><BRK/>
<BRK/>
<TXT>Galvanized steel, <RID>ASTM A 653/A 653M</RID>, SS Grade 50,<MET> [Z180] [Z275]</MET><ENG> [G60] [G90]</ENG> [; or carbon steel, <RID>ASTM A 1011/A 1011M</RID>
, Grade 50, painted].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   Studs and Joists of<MET> 1.2 mm</MET><ENG> 18 Gage (0.0478 Inch)</ENG> and Lighter</TTL><BRK/>
<BRK/>
<TXT>Studs and Joists of<MET> 1.2 mm</MET><ENG> 18 Gage (0.0478 Inch)</ENG> and Lighter, Track, and Accessories (All Gages):  Galvanized 
steel, <RID>ASTM A 653/A 653M</RID>, SS,<MET> Grade 345 230 MPa</MET><ENG> Grade 50 33,000 psi</ENG><MET> Z180</MET><ENG> G60</ENG>[; or carbon steel, <RID>ASTM A 1008/A 1008M</RID>
, Grade C, painted].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.3   Sizes, Gages, Section Modulus, and Other Structural Properties</TTL><BRK/>
<BRK/>
<TXT>Size and gage as indicated.  Steel stud deflection shall be limited to L/600 for exterior wall brick veneer construction.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2   MARKINGS</TTL><BRK/>
<BRK/>
<TXT>Studs and track shall have product markings stamped on the web of the section.  The markings shall be repeated 
throughout the length of the member at a maximum spacing of <MET>1200 mm</MET> <ENG>4 feet</ENG> on center and shall be legible and 
easily read.  The product marking shall include the following:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.   An ICBO number.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Manufacturer's identification.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Minimum delivered uncoated steel thickness.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Protective coating designator.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Minimum yield strength.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3   CONNECTIONS</TTL><BRK/>
<BRK/>
<TXT>Screws for steel-to-steel connections shall be self-drilling tapping in compliance with <RID>SAE J78</RID> of the type, 
size, and location as shown on the drawings.  Electroplated screws shall have a Type II coating in accordance 
with <RID>ASTM B 633</RID>.  Screws, bolts, and anchors shall be hot-dipped galvanized in accordance with <RID>ASTM A 123/A 123M</RID>
 or <RID>ASTM A 153/A 153M</RID> as appropriate.  Screws bolts, and anchors shall  be hot dipped galvanized in accordance 
with <RID>ASTM A 123/A 123M</RID> or <RID>ASTM A 153/A 153M</RID> as appropriate.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.4   PAINT</TTL><BRK/>
<BRK/>
<TXT>Ungalvanized steel, if used, shall be thoroughly cleaned, phosphate treated, and coated with corrosion-inhibiting 
primer, <RID>SSPC Paint 25</RID>.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.5   PLASTIC GROMMETS</TTL><BRK/>
<BRK/>
<TXT>Supply plastic grommets, recommended by stud manufacturer, to protect electrical wires.  Prevent metal to metal 
contact for plumbing pipes.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   FASTENING</TTL><BRK/>
<BRK/>
<TXT>Fasten framing members together by welding or by using self-drilling or self-tapping screws.  Electrodes and 
screw connections shall be as required and indicated in the design calculations.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.1.1   <SUB>Welds</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The welding of cold-formed steel should be performed by qualified workmen.  
The Contractor, Subcontractor, or Fabricator shall provide verification that 
welders are qualified in accordance with AWS D1.3/D1.3M.</NPR><BRK/>
<BRK/>
<NPR>TI 809-07 provides suggested design values for fillet and flare-bevel welds.  
Welding is not recommended on minimum metal thickness of less than 1.09 mm (0.0428 
inch).</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>All welding shall be performed in accordance with <RID>AWS D1.3/D1.3M</RID>, as modified by <RID>AISI SG02-1</RID>.  All welders, welding 
operations, and welding procedures shall be qualified according to <RID>AWS D1.3/D1.3M</RID>.  All welds shall be cleaned 
and coated with rust inhibitive galvanizing paint.  Do not field weld materials lighter than<MET> 1.2 mm</MET><ENG> 18 gage</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.2   Screws</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  TI 809-07 provides suggested capacities of screw connections.  Screws 
will not be used to resist pullout type loadings.</NPR><BRK/>
<BRK/>
<HL4>Minimum Screw Sizes for Steel-to-Steel Connections</HL4><BRK/>
<BRK/>
        Point            Minimum          Total Thickness of Steel<BRK/>
        Size            Screw Size                (mm (in))<BRK/>
<BRK/>
         2                 #8            2.540 mm (0.100 inches max)<BRK/>
         2                 #10           2.794 mm (0.110 inches max)<BRK/>
         2                 #12           3.556 mm (0.140 inches max)<BRK/>
         3                 #8            3.556 mm (0.140 inches max)<BRK/>
         3                 #10           4.445 mm (0.175 inches max)<BRK/>
         3                 #12           5.334 mm (0.210 inches max)<BRK/>
<BRK/>
Total thickness of steel is combined thickness of all connected steel members.<BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Screws shall be [of the] [self-drilling self-tapping]type, size, and location shown on the drawings.  Screw penetration 
through joined materials shall not be less than three exposed threads.  Minimum spacings and edge distances for 
screws shall be as specified in <RID>AISI SG02-1</RID>.  Screws covered by sheathing materials shall have low profile heads.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.3   Anchors</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: TI 809-07 provides suggested capacities of expansion and power type anchors.  
Power driven anchors can be used to attach tracks to structural steel and concrete 
floors and foundations.  Power driven anchors will not be used to anchor shear 
walls.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Anchors shall be of the type, size, and location shown on the drawings.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.2   INSTALLATION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.2.1   Tracks</TTL><BRK/>
<BRK/>
<TXT>Provide accurately aligned runners at top and bottom of partitions.  Anchor tracks as indicated in design calculations.  
Butt weld joints in tracks or splice with stud inserts.  Fasteners shall be at least<MET> 75 mm</MET><ENG> 3 inches</ENG> from the 
edge of concrete slabs.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.2   Studs</TTL><BRK/>
<BRK/>
<TXT>Cut studs square and set with firm bearing against webs of top and bottom tracks.  Position studs vertically 
in tracks and space as indicated in design.  Do not splice studs.  Provide at least two studs at jambs of doors 
and other openings<MET> 600 mm</MET><ENG> 2 feet</ENG> wide or larger.  Provide jack studs over openings, as necessary, to maintain 
indicated stud spacing.  Provide tripled studs at corners, positioned to receive interior and exterior finishes.  
Fasten studs to top and bottom tracks by welding or screwing both flanges to the tracks.  Framed wall openings 
shall include headers and supporting components as shown on the drawings.  Headers shall be installed in all 
openings that are larger than the stud spacing in a wall.  In curtain wall construction, provide for vertical 
movement where studs connect to the structural frame.  Provide horizontal bracing in accordance with the design 
calculations and <RID>AISI SG03-3</RID>, consisting of, as a minimum, runner channel cut to fit between and welded to the 
studs or hot- or cold-rolled steel channels inserted through cutouts in web of each stud and secured to studs 
with welded clip angles. Bracing shall be not less than the following:</TXT><BRK/>
<MET><TBL><THD><BRK/>
           <HL1>LOAD</HL1>                 <HL1>HEIGHT</HL1>              <HL1>BRACING</HL1><BRK/></THD>
<BRK/>
        Wind load only        Up to 3000 mm    One row at mid-height<BRK/>
                              Over 3000 mm     Rows 1500 mm o.c. maximum<BRK/>
<BRK/>
        Axial load            Up to 3000 mm    Two rows at 1/3 points<BRK/>
                              Over 3000 mm     Rows 900 mm o.c. maximum<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
            <HL1>LOAD</HL1>                 <HL1>HEIGHT</HL1>              <HL1>BRACING</HL1><BRK/></THD>
<BRK/>
        Wind load only        Up to 10 feet    One row at mid-height<BRK/>
                              Over 10 feet     Rows 5'-0" o.c. maximum<BRK/>
<BRK/>
        Axial load            Up to 10 feet    Two rows at 1/3 points<BRK/>
                              Over 10 feet     Rows 3'-4" o.c. maximum<BRK/></TBL>
</ENG><BRK/></SPT>
<SPT><TTL>3.2.3   Joists and Trusses</TTL><BRK/>
<BRK/>
<TXT>Locate each joist or truss directly above a stud.  Provide doubled joists under parallel partitions wherever 
partition length exceeds 1/2 of joist span. Joists shall have at least<MET> 60 mm</MET><ENG> 2.50 inches</ENG> of bearing on steel,<MET>
 100 mm</MET><ENG> 4 inches</ENG> on masonry, and shall be reinforced over bearings where required to prevent web crippling.  
Splice joists over bearings only.  Lap and weld splices as indicated.  Provide manufacturer's standard bridging 
which shall not be less than the following:</TXT><BRK/>
<MET><TBL><THD><BRK/>
           <HL1>CLEAR SPAN</HL1>               <HL1>BRIDGING</HL1><BRK/></THD>
<BRK/>
            Up to 4200 mm          One row near center<BRK/>
            4200 mm to 6000 mm     Two rows at 1/3 points<BRK/>
            6000 mm to 7800 mm     Three rows at 1/4 points<BRK/>
            7800 mm to 10600 mm    Four rows at 1/5 points<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
           <HL1>CLEAR SPAN</HL1>               <HL1>BRIDGING</HL1><BRK/></THD>
<BRK/>
            Up to 14 feet          One row near center<BRK/>
            14 to 20 feet          Two rows at 1/3 points<BRK/>
            20 to 26 feet          Three rows at 1/4 points<BRK/>
            26 to 32 feet          Four rows at 1/5 points<BRK/></TBL>
</ENG><BRK/>
<TXT>Temporary bracing shall be provided and remain in place until work is permanently stabilized.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.4   Erection Tolerances</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Framing members which will be covered by finishes such as wallboard, plaster, or ceramic 
tile set in a mortar setting bed, shall be within the following limits:</ITM><BRK/>
<BRK/>
<ITM>(1)  Layout of walls and partitions: <MET> 6 mm</MET><ENG> 1/4 inch</ENG> from intended position;</ITM><BRK/>
<BRK/>
<ITM>(2)  Plates and runners: <MET> 6 mm in 2400 mm</MET><ENG> 1/4 inch in 8 feet</ENG> from a straight line;</ITM><BRK/>
<BRK/>
<ITM>(3)  Studs: <MET> 6 mm in 2400 mm</MET><ENG> 1/4 inch in 8 feet</ENG> out of plumb, not cumulative; and</ITM><BRK/>
<BRK/>
<ITM>(4)  Face of framing members: <MET> 6 mm in 2400 mm</MET><ENG> 1/4 inch in 8 feet</ENG> from a true plane.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Framing members which will be covered by ceramic tile set in dry-set mortar, latex-portland 
cement mortar, or organic adhesive shall be within the following limits:</ITM><BRK/>
<BRK/>
<ITM>(1)  Layout of walls and partitions: <MET> 6 mm</MET><ENG> 1/4 inch</ENG> from intended position;</ITM><BRK/>
<BRK/>
<ITM>(2)  Plates and runners: <MET> 3 mm in 2400 mm</MET><ENG> 1/8 inch in 8 feet</ENG> from a straight line;</ITM><BRK/>
<BRK/>
<ITM>(3)  Studs: <MET> 3 mm in 2400 mm</MET><ENG> 1/8 inch in 8 feet</ENG> out of plumb, not cumulative; and</ITM><BRK/>
<BRK/>
<ITM>(4)  Face of framing members: <MET> 3 mm in 2400 mm</MET><ENG> 1/8 inch in 8 feet</ENG> from a true plane.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.5   Special Inspection and Testing for Seismic-Resisting Systems</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include this paragraph <HL1>only</HL1> when special inspection and testing for seismic-resisting 
systems is required by paragraph 3.2 of FEMA 302, NEHRP RECOMMENDED PROVISIONS 
FOR SEISMIC REGULATIONS FOR NEW BUILDINGS AND OTHER STRUCTURES.</NPR><BRK/>
<BRK/>
<NPR>This paragraph will be applicable to both new buildings designed according to 
TI 809-04, SEISMIC DESIGN FOR BUILDINGS, and to existing building seismic rehabilitation 
designs done according to TI 809-05, SEISMIC EVALUATION AND REHABILITATION FOR 
BUILDINGS.</NPR><BRK/>
<BRK/>
<NPR>The designer must indicate on the drawings all locations and all features for 
which special inspection and testing is required in accordance with Chapter 
3 of FEMA 302.  This includes indicating the locations of all structural components 
and connections requiring inspection.</NPR><BRK/>
<BRK/>
<NPR>Add any additional requirements as necessary.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Special inspections and testing for seismic-resisting systems and components shall be done in accordance with 
Section <SRF>01 45 35</SRF> SPECIAL INSPECTION FOR SEISMIC-RESISTING SYSTEMS.</TXT><BRK/>
<BRK/></SPT>