<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA      UFGS-07 21 16 (April 2006)<BRK/>
                                    ------------------------------<BRK/>
Preparing Activity:  <PRA>NAVFAC</PRA>         Replacing without change<BRK/>
                                    UFGS-07212 (August 2004)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<BRK/>
<SCN>SECTION 07 21 16</SCN><BRK/>
<BRK/>
<STL>MINERAL FIBER BLANKET INSULATION</STL><BRK/>
<DTE>04/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>mineral fiber blanket 
thermal insulation in attics, ceilings, walls, and floors</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification is intended for both retrofit of existing buildings 
and new construction.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  On the drawings, show:</NPR><BRK/>
<BRK/>
<NPR>1.  Locations where insulation will be used.</NPR><BRK/>
<BRK/>
<NPR>2.  Thermal resistance value (R-Value) for each location.</NPR><BRK/>
<BRK/>
<NPR>3.  Location of vapor retarder, if required.</NPR><BRK/>
<BRK/>
<NPR>4.  Location and size of attic ventilation openings where required.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Attic Ventilation</NPR><BRK/>
<BRK/>
<NPR>1.  Provide net, unobstructed ventilation areas to attics over insulated ceilings 
as recommended by ASHRAE Handbook of Fundamentals, Chapter 21 and as follows:</NPR><BRK/>
<BRK/>
<NPR>2.  For attics with vapor retarder, provide<MET> 0.1 square meter</MET><ENG> one square foot</ENG>
 of net ventilation area for each<MET> 30 square meters</MET><ENG> 300 square feet</ENG> of attic 
floor area.</NPR><BRK/>
<BRK/>
<NPR>3.  For attics without vapor retarder, provide<MET> 0.1 square meter</MET><ENG>one square foot</ENG>
 of net ventilation area for each<MET> 15 square meters</MET><ENG> 150 square feet</ENG> of attic 
floor area.</NPR><BRK/>
<BRK/>
<NPR>4.  For insulation of cathedral ceilings, provide at least a<MET> 50 mm</MET><ENG> 2 inch</ENG> gap 
between upper face of insulation and underside of roof sheathing.  Provide ventilation 
openings at bottom and top of ventilated cavity; show on drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Develop and specify density, type of material, and thickness of mineral 
fiber blanket insulation used for sound control based on acoustic analysis.  
For reduction of sound transmission through walls, select a blanket thickness<MET>
 13 mm</MET><ENG> 1/2 inch</ENG> greater than the wall cavity.  Edit this specification accordingly.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM C 665</RID><RTL>(2006) Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing</RTL><BRK/><BRK/><RID>ASTM C 930</RID><RTL>(2005) Potential Health and Safety Concerns Associated with Thermal Insulation Materials and Accessories</RTL><BRK/><BRK/><RID>ASTM D 3833/D 3833M</RID><RTL>(1996; R 2006) Water Vapor Transmission of Pressure-Sensitive Tapes</RTL><BRK/><BRK/><RID>ASTM D 4397</RID><RTL>(2008) Standard Specification for Polyethylene Sheeting for Construction, Industrial, and Agricultural Applications</RTL><BRK/><BRK/><RID>ASTM D 828</RID><RTL>(1997; R 2002) Tensile Properties of Paper and Paperboard Using Constant-Rate-of-Elongation Apparatus</RTL><BRK/><BRK/><RID>ASTM E 136</RID><RTL>(2004) Behavior of Materials in a Vertical Tube Furnace at 750 Degrees C</RTL><BRK/><BRK/><RID>ASTM E 84</RID><RTL>(2008a) Standard Test Method for Surface Burning Characteristics of Building Materials</RTL><BRK/><BRK/><RID>ASTM E 96/E 96M</RID><RTL>(2005) Standard Test Methods for Water Vapor Transmission of Materials</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 211</RID><RTL>(2006) Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances</RTL><BRK/><BRK/><RID>NFPA 31</RID><RTL>(2006; Errata 2006; Errata 2007) Installation of Oil Burning Equipment</RTL><BRK/><BRK/><RID>NFPA 54</RID><RTL>(2008) National Fuel Gas Code</RTL><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/></REF><REF><ORG>TECHNICAL ASSOCIATION OF THE PULP AND PAPER INDUSTRY (TAPPI)</ORG><BRK/><BRK/><RID>TAPPI T803 OM</RID><RTL>(2006) Puncture Test of Container Board</RTL><BRK/><BRK/></REF><REF><ORG>U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)</ORG><BRK/><BRK/><RID>29 CFR 1910.134</RID><RTL>Respiratory Protection</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Blanket insulation</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Sill sealer insulation</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Vapor retarder</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Pressure sensitive tape</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Accessories</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-08 Manufacturer's Instructions</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Insulation</SUB></ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   DELIVERY, STORAGE, AND HANDLING</TTL><BRK/>
<BRK/>
<SPT><TTL>1.3.1   Delivery</TTL><BRK/>
<BRK/>
<TXT>Deliver materials to site in original sealed wrapping bearing manufacturer's name and brand designation, specification 
number, type, grade, R-value, and class.  Store and handle to protect from damage.  Do not allow insulation materials 
to become wet, soiled, crushed, or covered with ice or snow.  Comply with manufacturer's recommendations for 
handling, storing, and protecting of materials before and during installation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3.2   Storage</TTL><BRK/>
<BRK/>
<TXT>Inspect materials delivered to the site for damage; unload and store out of weather in manufacturer's original 
packaging.  Store only in dry locations, not subject to open flames or sparks, and easily accessible for inspection 
and handling.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.4   SAFETY PRECAUTIONS</TTL><BRK/>
<BRK/>
<SPT><TTL>1.4.1   Respirators</TTL><BRK/>
<BRK/>
<TXT>Provide installers with dust/mist respirators, training in their use, and protective clothing, all approved by 
National Institute for Occupational Safety and Health (NIOSH)/Mine Safety and Health Administration (MSHA) in 
accordance with <RID>29 CFR 1910.134</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.2   Smoking</TTL><BRK/>
<BRK/>
<TXT>Do not smoke during installation of blanket thermal insulation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.3   Other Safety Concerns</TTL><BRK/>
<BRK/>
<TXT>Consider other safety concerns and measures as outlined in <RID>ASTM C 930</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   <SUB>BLANKET INSULATION</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Fire Safety Requirements</NPR><BRK/>
<BRK/>
<NPR>1.  Most vapor retarder materials and the binder used in some mineral fiber 
insulations are combustible. Do not leave such material exposed to accessible 
spaces, but cover with fire retardant finish.</NPR><BRK/>
<BRK/>
<NPR>2.  See MIL-HDBK-1008, and local building code for fire retardant classifications 
required, flame spread and smoke developed ratings, and other fire protection 
requirements, such as finish materials required in various occupancies.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>ASTM C 665</RID>, Type [I, blankets without membrane coverings] [and] [II, blankets with non-reflecting coverings] 
[and] [III, blankets with reflective coverings]; Class [A, membrane-faced surface with a flame spread of 25 or 
less] [B, membrane-faced surface with a flame propagation resistance; critical radiant flux of<MET> 0.12 W/m2</MET><ENG> 0.11 
Btu/ft2</ENG> or greater], except a flame spread rating of [25] [75] [100] or less [and a smoke developed rating of 
150 or less] when tested in accordance with <RID>ASTM E 84</RID>.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.1   Thermal Resistance Value (R-VALUE)</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select R-Value for Thermal Insulation required to meet the energy target/budget 
as indicated in MIL-HDBK-1190, Facility Planning Design Guide.  Preferably show 
R-Value on drawings.  If R-Values are not shown on drawings, specify here.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>As indicated</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   Recycled Materials</TTL><BRK/>
<BRK/>
<TXT>Provide Thermal Insulation containing recycled materials to the extent practicable, provided the material meets 
all other requirements of this section.  The minimum required recycled materials content by weight are:</TXT><BRK/>
<BRK/>
<TXT>Rock Wool:   75 percent slag</TXT><BRK/>
<TXT>Fiberglass:  20 to 25 percent glass cullet</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.3   Prohibited Materials</TTL><BRK/>
<BRK/>
<TXT>Do not provide asbestos-containing materials.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>2.2   <SUB>SILL SEALER INSULATION</SUB></TTL><BRK/>
<BRK/>
<TXT><RID>ASTM C 665</RID>, Type I.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.3   BLOCKING</TTL><BRK/>
<BRK/>
<TXT>Wood, metal, unfaced mineral fiber blankets in accordance with <RID>ASTM C 665</RID>, Type I, or other approved materials.  
Use only non-combustible materials meeting the requirements of <RID>ASTM E 136</RID> for blocking around chimneys and heat 
producing devices.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.4   <SUB>VAPOR RETARDER</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:</NPR><BRK/>
<BRK/>
<NPR>1.  Determine the need for a water vapor retarder and its required permeance 
value based on a project and climate specific moisture analysis.  For guidance 
see ASHRAE Handbook of Fundamentals, Chapter 20, "Thermal Insulations and Vapor 
Retarders;" ASTM C 755, "Selection of Vapor Retarders for Thermal Insulations;" 
and MIL-HDBK-1011/1, "Tropical Engineering" (for humid climates).  The computer 
Program "MOIST" which is on CCB, is a user friendly tool based on hourly weather 
data that provides information on moisture content of materials and on the duration 
of high moisture content excursions.  Traditionally, vapor retarders were considered 
materials having a permeance of<MET> 5.72 x 10-8 g/Pa.s.m2</MET><ENG> 1 perm (grain/h*ft2*in.Hg)</ENG>
 or less.  However, that value may not be adequate for the particular construction 
or climate and in some instances a much lower value should be specified.</NPR><BRK/>
<BRK/>
<NPR>2.  Vapor retarders, where required, can be provided as membranes or, alternatively, 
vapor retardant finishes labeled by manufacturer as having a water vapor permeance 
of no more than the required value can be used.  Alternate materials include:  
Paints, vinyl wall coverings, or foil-faced gypsum board.  Specify these in 
Sections 09 90 00, PAINTS AND COATINGS, Section 09 72 00, WALLCOVERINGS, or 
Section 09 29 00, GYPSUM BOARD, respectively and delete all paragraphs and references 
relating to vapor retarders from this section.</NPR><BRK/>
<BRK/>
<NPR>3.  A vapor retarder is only effective if it prevents diffusion of water vapor 
as well as the passage of moisture laden air through openings and around material.  
Accordingly, proper installation to assure air tightness by sealing of joints, 
tears, and around utility penetrations is as important as proper selection of 
water vapor retarder materials.</NPR><BRK/>
<BRK/>
<NPR>4.  Vapor retarders not only retard movement of water vapor into building envelope 
cavities, but also retard drying out of moisture that may have infiltrated the 
cavity. Accordingly, use vapor retarders only where their need is indicated 
by the moisture analysis.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">[a.<MET> 0.15 mm</MET><ENG> 6 mil</ENG> thick polyethylene sheeting conforming to <RID>ASTM D 4397</RID> and having a water vapor 
permeance of<MET> 5.72 x 10-8g/Pa.s.m2</MET><ENG> 1 perm</ENG> or less when tested in accordance with <RID>ASTM E 96/E 96M</RID>
.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Membrane with the following properties:</ITM><BRK/>
<BRK/>
<ITM>Water Vapor Permeance:  <RID>ASTM E 96/E 96M</RID>: <MET> [5.72 x 10-8] [_____] g/Pa.s.m2</MET> <ENG>[1] [_____] perm</ENG></ITM><BRK/>
<ITM>[Maximum Flame Spread:  <RID>ASTM E 84</RID>:  [25] [50] [_____]]</ITM><BRK/>
<ITM>[Combustion Characteristics:  Passing <RID>ASTM E 136</RID>]</ITM><BRK/>
<ITM>[Puncture Resistance:  <RID>TAPPI T803 OM</RID>:  [15] [25] [50]]</ITM><BRK/>
<ITM>[Tensile Strength:  <RID>ASTM D 828</RID>:  [15] [20] [35]]]</ITM><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.5   <SUB>PRESSURE SENSITIVE TAPE</SUB></TTL><BRK/>
<BRK/>
<TXT>As recommended by the vapor retarder manufacturer and having a water vapor permeance rating of<MET> 5.72 x 10-8 g/Pa.s.m2</MET><ENG>
 one perm</ENG> or less when tested in accordance with <RID>ASTM D 3833/D 3833M</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6   <SUB>ACCESSORIES</SUB></TTL><BRK/>
<BRK/>
<SPT><TTL>2.6.1   Adhesive</TTL><BRK/>
<BRK/>
<TXT>As recommended by the insulation manufacturer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6.2   Mechanical Fasteners</TTL><BRK/>
<BRK/>
<TXT>Corrosion resistant fasteners as recommended by the insulation manufacturer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6.3   Wire Mesh</TTL><BRK/>
<BRK/>
<TXT>Corrosion resistant and as recommended by the insulation manufacturer.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   EXISTING CONDITIONS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>Note:  For retrofit projects, inspect facility to determine conditions which 
may adversely affect execution of work or create safety hazard.  Identify relevant 
conditions on the drawings and, if required, develop additional specification 
sections for corrective actions.  Conditions that warrant investigation:</NPR><BRK/>
<BRK/>
<NPR>1.  Discolorations or mold growth indicating previous water leaks.</NPR><BRK/>
<BRK/>
<NPR>2.  Heat producing devices, such as recessed lighting fixtures, chimneys, and 
flues.</NPR><BRK/>
<BRK/>
<NPR>3.  Faulty electrical systems:</NPR><BRK/>
<BRK/>
<NPR>(a)  Lights dimming or flickering</NPR><BRK/>
<BRK/>
<NPR>(b)  Fuses blowing</NPR><BRK/>
<BRK/>
<NPR>(c)  Circuit breakers tripping frequently</NPR><BRK/>
<BRK/>
<NPR>(d)  Electrical sparks and "glowing" from receptacles</NPR><BRK/>
<BRK/>
<NPR>(e)  Cover plates on switches and outlets warm to touch.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Before installing insulation, ensure that areas that will be in contact with the insulation are dry and free 
of projections which could cause voids, compressed insulation, or punctured vapor retarders.  If moisture or 
other conditions are found that do not allow the workmanlike installation of the insulation, do not proceed but 
notify Contracting Officer of such conditions.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   PREPARATION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.2.1   Blocking at Attic Vents and Access Doors</TTL><BRK/>
<BRK/>
<TXT>Prior to installation of insulation, install permanent blocking to prevent insulation from slipping over, clogging, 
or restricting air flow through soffit vents at eaves.  [Install permanent blocking around attic trap doors.]  
[Install permanent blocking to maintain accessibility to equipment or controls that require maintenance or adjustment.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.2   Blocking Around Heat Producing Devices</TTL><BRK/>
<BRK/>
<TXT>Install non-combustible blocking around heat producing devices to provide the following clearances:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Recessed lighting fixtures, including wiring compartments, ballasts, and other heat producing 
devices, unless these are certified by the manufacturer for installation surrounded by insulation:<MET>
 75 mm</MET><ENG> 3 inches</ENG> from outside face of fixtures and devices or as required by <RID>NFPA 70</RID> and, if 
insulation is to be placed above fixture or device,<MET> 600 mm</MET><ENG> 24 inches</ENG> above fixture.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Masonry chimneys or masonry enclosing a flue: <MET> 50 mm</MET><ENG> 2 inches</ENG> from outside face of masonry.  
Masonry chimneys for medium and high heat operating appliances: Minimum clearances required 
by <RID>NFPA 211</RID>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Vents and vent connectors used for venting the products of combustion, flues, and chimneys 
other than masonry chimneys: Minimum clearances as required by <RID>NFPA 211</RID>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Gas Fired Appliances:  Clearances as required in <RID>NFPA 54</RID>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Oil Fired Appliances:  Clearances as required in <RID>NFPA 31</RID>.</ITM><BRK/>
<BRK/>
<TXT>Blocking around flues and chimneys is not required when insulation blanket, including any attached vapor retarder, 
passed <RID>ASTM E 136</RID>, in addition to meeting all other requirements stipulated in Part 2.  Blocking is also not 
required if the chimneys are certified by the manufacturer for use in contact with insulating materials.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.3   INSTALLATION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.3.1   <SUB>Insulation</SUB></TTL><BRK/>
<BRK/>
<TXT>Install and handle insulation in accordance with manufacturer's instructions.  Keep material dry and free of 
extraneous materials.  Ensure personal protective clothing and respiratory equipment is used as required.  Observe 
safe work practices.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.3.1.1   Electrical wiring</TTL><BRK/>
<BRK/>
<TXT>Do not install insulation in a manner that would sandwich electrical wiring between two layers of insulation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.1.2   Continuity of Insulation</TTL><BRK/>
<BRK/>
<TXT>Install blanket insulation to butt tightly against adjoining blankets and to studs, rafters, joists, sill plates, 
headers and any obstructions.  [Where insulation required is thicker than depth of joist, provide full width 
blankets to cover across top of joists.]  Provide continuity and integrity of insulation at corners, wall to 
ceiling joints, roof, and floor.  Avoid creating thermal bridges.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.1.3   Installation at Bridging and Cross Bracing</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify only unfaced blankets in installations with bridging and cross 
bracing. If a vapor retarder is required, specify a separate vapor retarder.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Insulate at bridging and cross bracing by splitting blanket vertically at center and packing one half into each 
opening.  Butt insulation at bridging and cross bracing; fill in bridged area with loose or scrap insulation.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.3.1.4   Cold Climate Requirement</TTL><BRK/>
<BRK/>
<TXT>Place insulation to the outside of pipes.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.3.1.5   Insulation Blanket with Affixed Vapor Retarder</TTL><BRK/>
<BRK/>
<TXT>Locate vapor retarder as indicated.  Do not install blankets with affixed vapor retarders unless so specified.  
Unless the insulation manufacturer's instructions specifically recommend not to staple the flanges of the vapor 
retarder facing, staple flanges of vapor retarder at<MET> 150 mm</MET><ENG> 6 inch</ENG> intervals flush with face or set in the side 
of truss, joist, or stud.  Avoid gaps and bulges in insulation and "fishmouth" in vapor retarders.  Overlap both 
flanges when using face method.  Seal joints and edges of vapor retarder with pressure sensitive tape.  Stuff 
pieces of insulation into small cracks between trusses, joists, studs and other framing, such as at attic access 
doors, door and window heads, jambs, and sills, band joists, and headers.  Cover these insulated cracks with 
vapor retarder material and tape all joints with pressure sensitive tape to provide air and vapor tightness.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.3.1.6   Insulation without Affixed Vapor Retarder</TTL><BRK/>
<BRK/>
<TXT>Provide snug friction fit to hold insulation in place.  Stuff pieces of insulation into cracks between trusses, 
joists, studs and other framing, such as at attic access doors, door and window heads, jambs, and sills, band 
joists, and headers.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.3.1.7   Sizing of Blankets</TTL><BRK/>
<BRK/>
<TXT>Provide only full width blankets when insulating between trusses, joists, or studs.  Size width of blankets for 
a snug fit where trusses, joists or studs are irregularly spaced.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.3.1.8   Special Requirements for Ceilings</TTL><BRK/>
<BRK/>
<TXT>Place insulation under electrical wiring occurring across joists.  Pack insulation into narrowly spaced framing.  
Do not block flow of air through soffit vents.  [Attach insulation to attic door by adhesive or staples.]</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.3.1.9   Installation of Sill Sealer</TTL><BRK/>
<BRK/>
<TXT>Size sill sealer insulation and place insulation over top of masonry or concrete perimeter walls or concrete 
perimeter floor slab on grade.  Fasten sill plate over insulation.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.3.1.10   Special Requirements for Floors</TTL><BRK/>
<BRK/>
<TXT>Hold insulation in place with corrosion resistant wire mesh, wire fasteners, or wire lacing.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.3.1.11   Access Panels and Doors</TTL><BRK/>
<BRK/>
<TXT>Affix blanket insulation to access panels greater than one square foot and access doors in insulated floors and 
ceilings.  Use insulation with same R-Value as that for floor or ceiling.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT>[<TTL>3.3.2   Installation of Separate Vapor Retarder</TTL><BRK/>
<BRK/>
<TXT>Apply continuous vapor retarder as indicated.  Overlap joints at least<MET> 150 mm</MET><ENG> 6 inches</ENG> and seal with pressure 
sensitive tape.  Seal at sill, header, windows, doors and utility penetrations.  Repair punctures or tears with 
pressure sensitive tape.</TXT><BRK/>
<BRK/>
]</SPT></SPT></PRT>    <END/><BRK/></SEC>