<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA               UFGS-07 22 00 (November 2008)<BRK/>
                                             -----------------------------<BRK/>
Preparing Activity:  <PRA>NAVFAC</PRA>                  Superseding<BRK/>
                                             UFGS-07 22 00 (January 2007)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 07 22 00</SCN><BRK/>
<BRK/>
<STL>ROOF AND DECK INSULATION</STL><BRK/>
<DTE>11/08</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>insulation materials 
used below built-up roofing and single ply roofing systems</SCP>.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.<BRK/>
<BRK/>
Use of electronic communication is encouraged.<BRK/>
<BRK/>
This guide specification includes tailoring options for NAVY and USACE.  Selection 
or deselection of a tailoring option will include or exclude that option in 
the section, but editing the resulting section to fit the project is still required.<BRK/>
<BRK/>
Brackets are used in the text to indicate designer choices or locations where 
text must be supplied by the designer.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR><HL3>Insulation materials applies to both organic and inorganic materials used for 
thermal protection as part of roofing assemblies or under decks.</HL3></NPR><BRK/>
<BRK/>
<NPR>In new construction, provide at least a<MET> one in 24</MET><ENG> 1/2 inch per foot</ENG> slope in 
the structural deck and use non-tapered insulation.  When it is clearly impracticable 
to provide at least the required slope or when reroofing where there is insufficient 
slope, consider the use of tapered insulation.  Also, use tapered insulation 
for the construction of saddles and crickets to provide slope to drains.</NPR><BRK/>
<BRK/>
<NPR>Insulation for prefabricated metal buildings is not included in this section.  
Insulating sheathing, other materials which are not primarily thermal insulating 
materials, and insulating concrete are also not included.  Such products are 
classified according to their primary use, and should be specified under the 
appropriate sections.  Spray-applied polyurethane foam roof insulation is specified 
in Section 07571, "Foamed Roofing."</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  On the drawings, show:</NPR><BRK/>
<BRK/>
<NPR>1.  Extent and locations of work to be accomplished.</NPR><BRK/>
<BRK/>
<NPR>2.  Dimensions when space limitations or construction features govern thickness 
of insulation materials.</NPR><BRK/>
<BRK/>
<NPR>3.  Details at cants, edge strips, and nailers.</NPR><BRK/>
<BRK/>
<NPR>4.  Location and spacing of wood nailers.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM C 1050</RID><RTL>(1991) Standard Specification for Rigid Cellular Polystyrene-Cellulosic Fiber Composite Roof Insulation</RTL><BRK/><BRK/><RID>ASTM C 1177/C 1177M</RID><RTL>(2008) Standard Specification for Glass Mat Gypsum Substrate for Use as Sheathing</RTL><BRK/><BRK/><RID>ASTM C 1289</RID><RTL>(2008) Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board</RTL><BRK/><BRK/><RID>ASTM C 208</RID><RTL>(2008a) Cellulosic Fiber Insulating Board</RTL><BRK/><BRK/><RID>ASTM C 552</RID><RTL>(2007) Standard Specification for Cellular Glass Thermal Insulation</RTL><BRK/><BRK/><RID>ASTM C 578</RID><RTL>(2008b) Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation</RTL><BRK/><BRK/><RID>ASTM C 726</RID><RTL>(2005e1) Mineral Fiber Roof Insulation Board</RTL><BRK/><BRK/><RID>ASTM C 728</RID><RTL>(2005) Perlite Thermal Insulation Board</RTL><BRK/><BRK/><RID>ASTM D 2178</RID><RTL>(2004) Asphalt Glass Felt Used in Roofing and Waterproofing</RTL><BRK/><BRK/><RID>ASTM D 226</RID><RTL>(2006) Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing</RTL><BRK/><BRK/><RID>ASTM D 312</RID><RTL>(2000; R 2006) Standard Specification for Asphalt Used in Roofing</RTL><BRK/><BRK/><RID>ASTM D 41</RID><RTL>(2005) Asphalt Primer Used in Roofing, Dampproofing, and Waterproofing</RTL><BRK/><BRK/><RID>ASTM D 4586</RID><RTL>(2007) Asphalt Roof Cement, Asbestos-Free</RTL><BRK/><BRK/><RID>ASTM D 4601</RID><RTL>(2004) Asphalt-Coated Glass Fiber Base Sheet Used in Roofing</RTL><BRK/><BRK/><RID>ASTM D 4897</RID><RTL>(2001) Asphalt-Coated Glass-Fiber Venting Base Sheet Used in Roofing</RTL><BRK/><BRK/><RID>ASTM E 84</RID><RTL>(2008a) Standard Test Method for Surface Burning Characteristics of Building Materials</RTL><BRK/><BRK/></REF><REF><ORG>FM GLOBAL (FM)</ORG><BRK/><BRK/><RID>FM 4470</RID><RTL>(1986; R 1992) Class I Roof Covers</RTL><BRK/><BRK/><RID>FM P7825</RID><RTL>(2005) Approval Guide</RTL><BRK/><BRK/><RID>FM P7825c</RID><RTL>(2005) Approval Guide Building Materials</RTL><BRK/><BRK/><RID>FM P9513</RID><RTL>(2002) Specialist Data Book Set for Roofing Contractors; contains 1-22 (2001), 1-28 (2002), 1-29 (2002), 1-28R/1-29R (1998), 1-30 (2000), 1-31 (2000), 1-32 (2000), 1-33 (2000), 1-34 (2001), 1-49 (2000), 1-52 (2000), 1-54 (2001)</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL Bld Mat Dir</RID><RTL>(2008) Building Materials Directory</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify shop drawings for wood nailers when nailers are required for 
securing insulation on roofs sloped<MET> one in 24</MET><ENG> 1/8 inch per foot</ENG> or more.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM>[<SUB>Wood nailers</SUB>]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Tapered roof insulation</SUB> system[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]]</ITM><BRK/>
<BRK/>
<ITM>[Taper cants and crickets]</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include requirement for backnailing felts when backnailing of felts is 
specified for built-up roofing.  Include bracketed second and third sentences 
when tapered insulation is specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM>[Show location and spacing of wood nailers that are required for securing insulation [and for 
backnailing of roofing felts]].  [Show a complete description of the procedures for the installation 
of each phase of the system indicating the type of materials, thicknesses, identity codes, sequence 
of laying insulation, location of ridges and valleys, special methods for cutting and fitting 
of insulation, and special precautions. The drawings shall be based on field measurements.]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>[Fasteners]</SUB> [<SUB>Asphalt</SUB>][; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Insulation</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Insulation may be specified solely for use on steel decks as underlayment 
for roofing when insulation is not required for thermal properties.  FM Approval 
Guide includes requirements for fasteners for 1-60 or 1-90 classifications or 
resistance to wind uplift pressures of<MET> 2.87 or 4.31 kPa</MET><ENG> 60 or 90 psf</ENG>, respectively.  
Refer to MIL-HDBK-1002/2, for wind loads.  Refer to FM Loss Prevention Data 
Sheet 1-7 for wind uplift prevention design.  Specify no less than<MET> 4.31 kPa</MET><ENG> 
90 psf</ENG> for roofs located in coastal areas.  Specify other fastener requirements 
if 1-90 standards are determined to be inadequate.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM>[Include minimum thickness of insulation for steel and concrete decks and fastener pattern for 
insulation on steel decks.]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Flame spread and smoke developed ratings</SUB></ITM><BRK/>
<BRK/>
<ITM>Submit in accordance with <RID>ASTM E 84</RID>.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include these requirements when tapered insulation is to be used.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM>Installer <SUB>qualifications</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-08 Manufacturer's Instructions</SUB></LST><BRK/>
<BRK/>
<ITM>Nails and <SUB>fasteners</SUB></ITM><BRK/>
<BRK/>
<ITM>Roof <SUB>insulation</SUB>, including field of roof and perimeter attachment requirements.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   MANUFACTURER'S CERTIFICATE</TTL><BRK/>
<BRK/>
<TXT>Submit certificate from the insulation manufacturer attesting that the installer has the proper <SUB>qualifications</SUB>
 for installing tapered roof insulation systems.</TXT><BRK/>
<BRK/>
<ITM>Certificate attesting that the expanded perlite or polyisocyanurate insulation contains recovered 
material and showing estimated percent of recovered material.  Certificates of compliance for 
felt materials.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT>[<TTL>1.4.1   Insulation on [Combustible] [Steel] [or] [Concrete] Decks</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include this requirement when insulation is installed over plywood, wood 
planks other than nominal<MET> 50 mm</MET><ENG> 2 inch</ENG> thick, tongue-and-groove type, or steel 
deck.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Roof insulation shall have a flame spread rating not greater than 75 and a smoke developed rating not greater 
than 150, exclusive of covering, when tested in accordance with <RID>ASTM E 84</RID>.  Insulation bearing the UL label and 
listed in the <RID>UL Bld Mat Dir</RID> as meeting the flame spread and smoke developed ratings will be accepted in lieu 
of copies of test reports. Compliance with <SUB>flame spread and smoke developed ratings</SUB> will not be required when 
insulation has been tested as part of a roof construction assembly of the type used for this project and the 
construction is listed as fire-classified in the <RID>UL Bld Mat Dir</RID> or listed as Class I roof deck construction in 
the <RID>FM P7825</RID>.  Insulation tested as part of a roof construction assembly shall bear UL or FM labels attesting 
to the ratings specified herein.]</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>1.4.2   Foam Board on [Combustible] [Steel] Decks</TTL><BRK/>
<BRK/>
<TXT>Separate [polyurethane] [or] [polystyrene] insulation from a [combustible] [steel] deck with a thermal barrier 
of glass mat gypsum roof board or roof insulation in accordance with the requirements of the <RID>UL Bld Mat Dir</RID> or 
the <RID>FM P7825</RID>.]</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.5   DELIVERY, STORAGE, AND HANDLING</TTL><BRK/>
<BRK/>
<SPT><TTL>1.5.1   Delivery</TTL><BRK/>
<BRK/>
<TXT>Deliver materials to site in manufacturer's unopened and undamaged standard commercial containers bearing the 
following legible information:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Name of manufacturer;</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Brand designation;</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Specification number, type, and class, as applicable, where materials are covered by a referenced 
specification; and</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[d.  Asphalt's flashpoint (FP), equiviscous temperature (EVT), and finished blowing temperature 
(FBT).]</ITM><BRK/>
<BRK/>
<TXT>Deliver materials in sufficient quantity to allow continuity of the work.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5.2   Storage and Handling</TTL><BRK/>
<BRK/>
<TXT>Store and handle materials in a manner to protect from damage, exposure to open flame or other ignition sources, 
and from wetting, condensation or moisture absorption.  Store in an enclosed building or trailer that provides 
a dry, adequately ventilated environment.  [Store felt rolls on ends.  For the 24 hours immediately before application 
of felts, store felts in an area maintained at a temperature no lower than<MET> 10 degrees C</MET><ENG> 50 degrees F</ENG> above grade 
and having ventilation around all sides.]  Replace damaged material with new material.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.6   ENVIRONMENTAL CONDITIONS</TTL><BRK/>
<BRK/>
<TXT>Do not install roof insulation during inclement weather or when air temperature is below<MET> 4 degrees C</MET><ENG> 40 degrees 
F</ENG> and interior humidity is 45 percent or greater, or when there is visible ice, frost, or moisture on the roof 
deck.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.7   PROTECTION OF PROPERTY</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where built-up roofing is applied over insulation, delete paragraphs 
entitled "Flame Heated Equipment" through "Drippage of Bitumen" and specify 
requirement enclosed in brackets in paragraph entitled "Protection of Property."  
Insert in blank provided the number and title of section covering roofing where 
protection requirements are specified.  Delete paragraphs entitled "Flame-Heated 
Equipment," "Protective Coverings," "Special Protection," and "Drippage of Bitumen" 
when roofing system or insulation does not require hot asphalt or torches for 
application.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Provide protection as specified in [_____].]</TXT><BRK/>
<BRK/>
<SPT>[<TTL>1.7.1   Flame-Heated Equipment</TTL><BRK/>
<BRK/>
<TXT>Locate and use flame-heated equipment so as not to endanger the structure or other materials on the site or adjacent 
property.  Do not place flame-heated equipment on the roof.  Provide and maintain a fire extinguisher near each 
item of flame-heated equipment.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>1.7.2   Protective Coverings</TTL><BRK/>
<BRK/>
<TXT>Install protective coverings at paving and building walls adjacent to hoist and kettles prior to starting the 
work.  Lap protective coverings at least<MET> 150 mm</MET><ENG> 6 inches</ENG>, secure them against wind, and vent them to prevent 
collection of moisture on the covered surfaces.  Keep protective coverings in place for the duration of the work 
with asphalt products.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>1.7.3   Special Protection</TTL><BRK/>
<BRK/>
<TXT>Provide special protection approved by the insulation manufacturer, or avoid heavy traffic on completed work 
when ambient temperature is above<MET> 27 degrees C</MET><ENG> 80 degrees F</ENG>.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>1.7.4   Drippage of Bitumen</TTL><BRK/>
<BRK/>
<TXT>Seal joints in and at edges of deck as necessary to prevent drippage of asphalt into building or down exterior 
walls.</TXT><BRK/>
<BRK/>
]</SPT></SPT></PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   <SUB>INSULATION</SUB></TTL><BRK/>
<BRK/>
<SPT><TTL>2.1.1   Insulation Types</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify all types of insulation listed as Contractor options, except 
where method of construction and/or special requirements prohibit use.  Thermal 
barrier of glass mat gypsum roof board or suitable roof insulation board must 
be installed directly on roof deck when polystyrene board will be applied over 
decks constructed of materials other than poured-gypsum; poured-concrete; nominal<MET>
 50 mm</MET><ENG> 2 inch</ENG> thick, tongue-and-groove wood plank or precast roof deck panels; 
or planks approved by FM as noncombustible roof deck construction.  <BRK/>
<BRK/>
For SOUTHNAVFACENGCOM projects, do not specify mineral fiber, glass fiber or 
cellular glass boards.</NPR><BRK/>
<BRK/>
<NPR>Roof insulation should be specified by thermal resistance (R value) necessary 
to obtain required overall thermal transmittance (U value) needed to satisfy 
design criteria for particular type of facility.  Thickness of insulation will 
vary with type of material furnished to provide specified R value.  When thickness 
of insulating material is governed by space limitations or construction features, 
R value and corresponding thickness should be coordinated with space available.  
Provide insulation of sufficient thickness to ensure that temperature of vapor 
retarder surface, when used, will be above dewpoint.  R value for insulation 
should never be less than R value used in design of heating and/or air conditioning 
systems.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: Roof construction, air-to-air, may include finish ceilings, provided that 
ceilings extend over the entire same roof area; and space above the ceiling 
is not vented to the exterior and is not used as a plenum.  Generally, roof 
insulation over mechanical rooms need not be increased in thickness when the 
mechanical room has no ceiling and the rest of the building has a ceiling.<BRK/>
<BRK/>
Designer will determine the required R-value and show the R-value at the appropriate 
detail on the drawings.  The required R-value will never be less than that used 
in the Energy Budget Analysis.  The R-value of impermeable faced iso-foams and 
permeable faced polyisocyanurate components will be calculated using the aged 
R-value of 1.0 square meter K/W ("R" value 5.56) per 25 mm (inch) of thickness; 
k = 0.31 W/m.k (k = 0.18).<BRK/>
<BRK/>
The R-value of impermeable faced (ex. aluminum foil) polyisocyanurate components 
will be calculated using the aged R-value of 1.27 square meter k/w ("R" value 
7.2) per 25 mm (1 inch) of thickness; k = 0.24 W/m.k (k = 0.14).<BRK/>
<BRK/>
Delete foil-faced board when roofing is single-ply and fully adhered.  Delete 
polystyrene and polystyrene composite when insulation will be applied with hot asphalt.<BRK/>
<BRK/>
The recovered materials content levels specified below are based on the weight 
(not the volume) of the materials in the insulating core, excluding skins or facings.<BRK/>
<BRK/>
Insulation shall be a standard product of the manufacturer and shall be factory 
marked with the manufacturer's name or trade mark, the material specification 
number, the R-value at 24 degrees C, 75 degrees F, and the thickness.  Minimum 
thickness shall be as recommended by the manufacturer.  Boards shall be marked 
individually.  The thermal resistance of insulation shall be not less than the 
R-value shown on the drawings.  The insulation manufacturing process shall not 
include chlorofluoro carbons (CFC) in conformance with Section 01670 RECYCLED/RECOVERED 
MATERIALS.  Insulation shall be one, or a combination of the following materials: </NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Roof insulation shall be one or an assembly of a maximum of three of the following materials and compatible with 
attachment methods for the specified insulation and roof membrane:</TXT><BRK/>
<BRK/>
<BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: Detailed information concerning EPA requirements on recycled/recovered 
materials is available at the following URL's:  http://www.epa.gov/cpg/products/ 
and then click on the appropriate item from the list (building.htm for building 
insulation, for example).<BRK/>
http://www.epa.gov/cpg/products.htm (similar results).<BRK/>
http://www.gov/cpg/pdf/back.pdf which opens up EPA530-R-98-003 (dated July, 
1998, titled BACKGROUND DOCUMENT FOR PROPOSED CPG III AND DRAFT RMAN III).<BRK/>
<BRK/>
Using data from listed locations, fill in blank space (below and in subsequent 
paragraphs) for required percentage of recycled or recovered material.  This 
is in accordance with the requirements of 40 CFR 247 and Section 01670 which 
should be included in all projects. </NPR><BRK/>
<AST/><BRK/></NTE>
<ITM INDENT="-0.33">a.  Expanded Perlite Board:  <RID>ASTM C 728</RID>.  Minimum<MET> 19 mm</MET><ENG> 3/4 inch</ENG> thick when both top and bottom 
surfaces will be in contact with asphalt.</ITM><NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete foil-faced board when fully adhered, cold-applied single ply roofing 
is specified.</NPR><BRK/>
<BRK/>
<NPR>Blistering of roofing membranes has occurred over some polyurethane and composite 
(polyurethane) board insulation, possibly due to either release of gases from 
polyurethane, moisture entrapped in facing or plying felt, differential movement 
between roofing membrane and polyurethane resulting from thermal stresses on 
the materials, or inadequate brooming and mopping. When hot-applied built-up, 
modified bitumen sheet, or PIB sheet roofing is installed over insulation, it 
is recommended that thin layer of mineral fiber, wood fiberboard,  expanded 
perlite board insulation, or glass mat gypsum roof board be placed over top 
surface of polyurethane board, embedded in solid asphalt mopping with joints 
of mineral fiber, wood fiberboard, or perlite board, or glass mat gypsum roof 
board staggered in both directions with respect to polyurethane board below. 
The same precautionary procedure should be followed when polyisocyanurate foam 
boards are specified even though there may not be documentation of similar problems 
with these types.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">b.  Polyisocyanurate Board:  <RID>ASTM C 1289</RID> [Type I -- foil faced both sides] [or] [Type II, fibrous 
felt or glass mat membrane both sides], except minimum compressive strength shall be<MET> 140 kPa</MET><ENG>
 20 pounds per square inch (psi)</ENG>.</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete polystyrene composite board when insulation will be applied with 
hot asphalt.</NPR><BRK/>
<AST/></NTE><BRK/>
<ITM INDENT="-0.33">c.  Composite Boards:  <RID>ASTM C 1289</RID>, [Type III, perlite insulation board faced one side, fibrous 
felt or glass fiber mat membrane on other side.] [Type V, oriented strand board or waferboard 
on one side and fibrous felt or glass fiber mat membrane or aluminum foil on the other.]; <RID>ASTM C 1289</RID>
 (Polyisocyanurate-perlite) [; or <RID>ASTM C 1050</RID> (Polystyrene-wood fiberboard), Type III, Grade 
1, Class A].</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Cellular Glass Boards:  <RID>ASTM C 552</RID>, Type IV.</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete non-composite polystyrene board when insulation will be applied 
with hot asphalt or used under hot asphalt-applied roofing.  This type of insulation 
is sensitive to hot asphalt, various solvents, and certain single ply roofing 
membranes.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Expanded or extruded polystyrene insulation board is flexible enough 
for use on arched roofs.  For this application, each layer must be thin enough 
to permit the required bending and each layer must be mechanically fastened.  
Check individual manufacturer requirement prior to application.</NPR><BRK/>
<AST/></NTE><BRK/>
<BRK/>
<ITM INDENT="-0.33">[e.  Polystyrene Board:  Shall be in accordance with <RID>ASTM C 578</RID>, Type II, IV, or X.]</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: Specify high density type wood fiberboard where the board is used as an 
overlayment and fully-adhered single-ply roofing is specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: Grade 1 insulating board is primarily for use under built-up roof systems.  
Grade 2 board is primarily for use under single-ply roof systems. </NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<BRK/>
<BRK/>
<ITM INDENT="-0.33">[f.  Wood Fiberboard:  <RID>ASTM C 208</RID>[, high density], except 4 by 4 feet maximum board size.</ITM><BRK/>
<BRK/>
<TXT><RID>ASTM C 208</RID> Type II, Grade 1 or 2, roof insulating board, treated with sizing, wax or bituminous impregnation.  
Bituminous impregnation shall be limited to 4 percent by weight when used over steel decks.  Maximum board size: 
4 feet by 4 feet.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   Mineral-Fiber Insulation Board</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM C 726</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.3   Recovered Materials</TTL><BRK/>
<BRK/>
<TXT>Provide thermal insulation materials containing recycled materials to the extent practical.  The required minimum 
recycled material content for the listed materials are:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">Perlite Composition Board:      23  percent postconsumer paper</ITM><BRK/>
<ITM INDENT="-0.33">Polyisocyanurate/polyurethane:   9  percent recovered material</ITM><BRK/>
<ITM INDENT="-0.33">Phenolic Rigid Foam:             5  percent recovered material</ITM><BRK/>
<ITM INDENT="-0.33">Wood Fiberboard                [  ] percent recovered material</ITM><BRK/>
<BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Whenever possible, provide insulation which has a minimum of 4 percent 
post consumer waste or 20 percent recycled material by weight of installed products 
as defined by (NIBS) September 1999.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/></SPT>
<SPT><TTL>2.1.4   Insulation Thickness</TTL><BRK/>
<BRK/>
<TXT>As necessary to provide a thermal resistance (R value) of [_____] or more [for average thickness of tapered system].  
Thickness shall be based on the "R" value for aged insulation.  [Insulation over steel decks shall satisfy both 
specified R value and minimum thickness for width of rib opening recommended in insulation manufacturer's published 
literature].</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.1.5   <SUB>Tapered Roof Insulation</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where tapered roof insulation is used on a substrate sloped<MET> one in 48</MET><ENG>
 1/4 inch per foot</ENG> and greater, insulation having a slope of<MET> one in 48</MET><ENG> 1/4 inch 
per foot</ENG> may be specified.  Otherwise, specify tapered insulation having a slope 
of<MET> one in 24</MET><ENG> 1/2 inch per foot</ENG>.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>One layer of the tapered roof insulation assembly shall be factory tapered to a slope of not less than<MET> one in 
[24] [48]</MET><ENG> [1/4] [1/2] inch per foot</ENG>.  Provide starter and filler blocks as required to provide the total thickness 
of insulation necessary to meet the specified slope and thermal conductance. Mitered joints shall be factory 
fabricated and shall consist of two diagonally cut boards or one board shaped to provide the required slopes. 
Identify each piece of tapered insulation board by color or other identity coding system, allowing the identification 
of different sizes of tapered insulation board required to complete the roof insulation system.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.6   Cants and Tapered Edge Strips</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: Generally cant strips are not required for single ply roofing systems.  
However, if cant strips are necessary, coordinate the location of cant strips 
with mechanical drawings to ensure that no projections, such as vent pipes and 
braces, will be constructed through cant strips or within<MET> 250 mm</MET><ENG> 10 inches</ENG> from 
cant strips.  Specify wood cants, edge strips, and pressure preservative treatment 
in Section 06 10 00.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide preformed cants and tapered edge strips of the same material as the roof insulation; or, when roof insulation 
material is unavailable, provide pressure-preservative treated wood, wood fiberboard, or rigid perlite board 
cants and edge strips as recommended by the roofing manufacturer, unless otherwise indicated.  Face of cant strips 
shall have incline of 45 degrees and vertical height of<MET> 100 mm</MET><ENG> 4 inches</ENG>.  Taper edge strips at a rate of<MET> 85 to 
125 mm per meter</MET><ENG> one to 1 1/2 inch per foot</ENG> down to approximately<MET> 3 mm</MET><ENG> 1/8 inch</ENG> thick.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT>[<TTL>2.2   PROTECTION BOARD</TTL><BRK/>
<BRK/>
<TXT>For use as a thermal barrier (underlayment), fire barrier (overlayment), or protection board for hot-mopped, 
torched-down, or adhesively-applied roofing membrane over roof insulation. </TXT><BRK/>
<BRK/>
]<SPT>[<TTL>2.2.1   Glass Mat Gypsum Roof Board</TTL><BRK/>
<BRK/>
<NTE><AST/><BRK/>
<NPR>NOTE:  Specify glass mat gypsum roof board as a contractor's option to wood 
fiberboard, expanded perlite, or other suitable material, when an underlayment 
or overlayment is required for the roof insulation board.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>ASTM C 1177/C 1177M</RID>, 0 Flame Spread and 0 Smoke Developed when tested in accordance with <RID>ASTM E 84</RID>, <MET>3450 kPa </MET><ENG>
500 psi</ENG>, Class A, non-combustible, <MET>[6][13][16] mm </MET><ENG>[1/4][1/2][5/8] inch</ENG> thick, <MET>1220 by 2440 mm </MET><ENG>4 by 8 feet</ENG> board 
size.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT>[<TTL>2.3   BITUMENS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where insulation is installed under roofing that does not require hot 
asphalt and vapor retarder is not required, delete asphalt, asphalt roof cement, 
asphalt-saturated felt, asphalt-coated glass felt, and asphalt primers.  Always 
mechanically secure first layer of insulation to steel decks.  For installation 
over steel and other decks not requiring vapor retarders or where asphalt is 
not used in installing insulation, specify only mechanical fastening of insulation.  
Coordinate requirements of this section with section specifying the roofing.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT>[<TTL>2.3.1   Asphalt Primer</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM D 41</RID>.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.3.2   Asphalt</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM D 312</RID>, Type III or IV.  Asphalt flash point, finished blowing temperature, and equiviscous temperature (EVT) 
for mop and for mechanical spreader application shall be indicated on bills of lading or on individual containers.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.3.3   <SUB>Asphalt</SUB> Roof Cement</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM D 4586</RID>, Type I for horizontal surfaces and for surfaces sloped from 0 to 3 inches per foot, Type II for 
vertical and surfaces sloped more than 3 inches per foot.</TXT><BRK/>
<BRK/>
]</SPT>]</SPT><SPT>[<TTL>2.4   SHEATHING PAPER FOR WOOD DECKS</TTL><BRK/>
<BRK/>
<TXT>Rosin-sized building paper or unsaturated felt weighing not less than<MET> 2.5 kilograms per 10 square meters</MET><ENG> 5 pounds 
per 100 square feet</ENG>.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.5   MOISTURE CONTROL</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: Vapor retarder should be specified only where:</NPR><BRK/>
<BRK/>
<NPR>1.  Outside, average January temperature is below<MET> 4 degrees C</MET><ENG> 40 degrees F</ENG>, 
and expected winter interior relative humidity is 45 percent or greater;</NPR><BRK/>
<BRK/>
<NPR>2.  Roofing system will be subject to continuing excessively high interior humidity; 
and</NPR><BRK/>
<BRK/>
<NPR>3.  Results of detailed analysis indicate potential roofing problem resulting 
from water-vapor infiltration.</NPR><BRK/>
<BRK/>
<NPR>Delete contractor's option for single-layer vapor retarder for roofs over areas 
having excessively high interior humidity such as swimming pools and laundries.  
Generally, vapor retarder should be in direct contact with deck.  However, compute 
dewpoint temperature and location and locate vapor retarder below dewpoint location.  
Avoid use of vapor retarder over steel decks unless vapor retarder is determined 
to be absolutely necessary.  Do not specify wood fiberboard or any type of insulation 
that is highly sensitive to moisture for layer directly on steel deck.  Specify 
installation of insulation over vapor retarder using hot asphalt to avoid puncturing 
vapor retarder.  Combination of two or more layers of insulation should be of 
such thickness that dewpoint temperature will occur above vapor retarder located 
directly over first layer of insulation.  Topside venting should always be provided 
by insulation vents and perimeter edge vents when vapor retarder is used.  Specify 
venting requirements in roofing membrane specification section.</NPR><BRK/>
<BRK/>
<NPR>Unless otherwise directed, do not specify vapor retarder for projects in the 
SOUTHNAVFACENGCOM area.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT>[<TTL>2.5.1   Vapor Retarder]</TTL><BRK/>
<BRK/>
<SPT>[<TTL>2.5.1.1   Asphalt-Saturated Felt Base Sheet for Single Layer Application</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM D 4601</RID>, weighing not less than<MET> 17.5 kilograms per 10 square meters</MET><ENG> 35 pounds per 100 square feet</ENG>.]</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.5.1.2   Asphalt-Coated Glass Felt</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM D 2178</RID>, Type [IV] [VI].</TXT>]<BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>2.5.2   Ventilating Felt for [Poured] [Precast] Concrete Decks</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify ventilating felt for new and existing concrete decks suspected 
of having retained moisture to aid in dissipation of any moisture retained in 
concrete.  This felt shall not be considered to be a vapor retarder.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>ASTM D 4897</RID>, Type II, non-perforated, with spot mopping holes where specified.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.3   Organic Roofing</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM D 226</RID>, Type I.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.6   <SUB>FASTENERS</SUB></TTL><BRK/>
<BRK/>
<TXT>Flush-driven through flat round or hexagonal steel or plastic plates. Steel plates shall be zinc-coated, flat 
round not less than<MET> 35 mm</MET><ENG> 1 3/8 inch</ENG> diameter or hexagonal not less than<MET> 0.4 mm</MET><ENG> 28 gage</ENG>.  Plastic plates shall 
be high-density, molded thermoplastic with smooth top surface, reinforcing ribs and not less than<MET> 75 mm</MET><ENG> 3 inches</ENG>
 in diameter.  Fastener head shall recess fully into the plastic plate after it is driven.  Plates shall be formed 
to prevent dishing.  Do not use bell-or cup-shaped plates. Fasteners shall conform to insulation manufacturer's 
recommendations except that holding power, when driven, shall be not less than [<MET>178 N </MET><ENG>40 pounds</ENG>] [<MET>534 N </MET><ENG>120 pounds</ENG>
] each in steel deck.  Fasteners for steel or concrete decks shall conform to <RID>FM P7825c</RID> for Class I roof deck 
construction, and shall be spaced to withstand an uplift pressure of <MET>[2.87] [4.3] [_____] kPa </MET><ENG>[60] [90] [_____] 
pounds per square foot</ENG>.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.6.1   Roofing Nails for Wood Decks</TTL><BRK/>
<BRK/>
<TXT>Barbed<MET> 3 mm</MET><ENG> 11 gage</ENG>, zinc-coated nails with<MET> 11 to 16 mm</MET><ENG> 7/16 to 5/8 inch</ENG> diameter heads or annular ring shank, 
square head, one-piece composite nails.  Nails shall be long enough to penetrate wood deck at least<MET> 16 mm</MET><ENG> 5/8 
inch</ENG> but shall not protrude through underside of decking.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6.2   Fasteners for Plywood Decks</TTL><BRK/>
<BRK/>
<TXT>Annular ring shank, square head, one-piece composite nails long enough to penetrate into plywood decks approximately<MET>
 13 mm</MET><ENG> 1/2 inch</ENG> but not protrude through underside of decking.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6.3   Fasteners for Steel Decks</TTL><BRK/>
<BRK/>
<TXT>Approved hardened penetrating fasteners or screws conforming to <RID>FM 4470</RID> and listed in <RID>FM P7825c</RID> for Class I roof 
deck construction.  Quantity and placement to withstand a minimum uplift pressure of<MET> [2.87] [4.31] [_____] kPa</MET><ENG>
 [60] [90] [_____] psf</ENG> conforming to <RID>FM P7825</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6.4   Fasteners for Poured Concrete Decks</TTL><BRK/>
<BRK/>
<TXT>Approved hardened fasteners or screws to penetrate deck at least<MET> 25 mm</MET><ENG> one inch</ENG> but not more than<MET> 38 mm</MET><ENG> 1 1/2 
inches</ENG>, conforming to <RID>FM 4470</RID>, and listed in <RID>FM P7825</RID> for Class I roof deck construction.  Quantity and placement 
to withstand an uplift pressure of<MET> [2.87] [4.31] [_____] kPa</MET><ENG> [60] [90] [_____] psf</ENG> conforming to <RID>FM P7825</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.7   <SUB>WOOD NAILERS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When roof slope exceeds<MET> one in 24</MET><ENG> 1/2 inch per foot</ENG>, insulating materials 
beneath built-up roofing should be both mopped and held in place by treated 
wood nailers.  Non-nailable decks should be provided with surface-applied nailing 
strips of same thickness as insulation.  See built-up bituminous roofing specifications 
for requirements on nailing of roofing felts.  For all insulated roof decks, 
treated wood nailers should be applied at eave edgings and sides of roofs and 
around curbs and elsewhere as necessary to provide nailing for gravel stops 
and flashings.  Refer to FM Loss Prevention Data Sheet 1-49 for method of attachment 
of nailers. A water-borne preservative treatment should be specified in Section 
06 10 00 for wood which will be in contact with bituminous materials.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Pressure-preservative-treated as specified in Section <SRF>06 10 00</SRF> ROUGH CARPENTRY.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   EXAMINATION AND PREPARATION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1.1   Surface Inspection</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Unless otherwise directed, do not refer to vapor retarders for projects 
in the SOUTHNAVFACENGCOM area.  Vapor retarder may be specified for heated buildings 
where the average January temperature is below 5 degrees C (40 degrees F) and 
the expected interior winter humidity exceeds 45 percent.  Vapor retarder will 
be specified for heated buildings where a high humidity condition is expected, 
such as indoor swimming pool or laundry.<BRK/>
<BRK/>
Where a vapor retarder is to be installed, the designer will make sure that 
the computations show that the dew point is on the cold side of the vapor retarder.  
Computations should use recognized methods in agreement with ASHRAE Handbook, 
Fundamentals.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Surfaces shall be clean, smooth, and dry.  [Surfaces receiving vapor retarder shall be free of projections which 
might puncture the vapor retarder.]  Check roof deck surfaces, including surfaces sloped to roof drains and outlets, 
for defects before starting work.  </TXT><BRK/>
<BRK/>
<TST><TXT>The [Contractor shall] [Contracting Officer will] inspect and approve the surfaces immediately before starting 
installation.  Prior to installing [vapor retarder] [ventilating felt] [insulation], perform the following:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">[a.  Examine wood decks to ascertain that deck boards have been properly nailed and that exposed 
nail heads have been set.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Examine steel decks to ensure that panels are properly secured to structural members and 
to each other and that surfaces of top flanges are flat or slightly convex.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[c.  Examine precast concrete decks to ensure that joints between precast units are properly 
grouted and leveled to provide suitable surfaces for installation of [ventilating felt] [vapor 
retarder] [and] insulation.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[d.  In the presence of the Contracting Officer perform the following surface-dryness test on 
concrete substrates:</ITM><BRK/>
<BRK/>
<ITM>(1)  Foaming:  When poured on the deck, one pint of asphalt when heated in the range of<MET> 176 
to 204 degrees C</MET><ENG> 350 to 400 degrees F</ENG>, shall not foam upon contact.</ITM><BRK/>
<BRK/>
<ITM>(2)  Strippability:  After asphalt used in the foaming test application has cooled to ambient 
temperatures, test coating for adherence. Should a portion of the sample be readily stripped 
clean from surface, do not consider surface to be dry and do not start application.  Should 
rain occur during application, stop work and do not resume until surface has been tested by 
method above and found dry.]</ITM></TST><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.2   Surface Preparation</TTL><BRK/>
<BRK/>
<TXT>Correct defects and inaccuracies in roof deck surface to eliminate poor drainage and hollow or low spots and 
perform the following:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Install wood nailers the same thickness as insulation at eaves, edges, curbs, walls, and 
roof openings for securing cant strips, gravel stops, [gutters,] and flashing flanges.  [On 
decks with slopes of<MET> one in 12</MET><ENG> one inch per foot</ENG> or more, install wood nailers perpendicular 
to slope for securing insulation [and for backnailing of roofing felts].  Space nailers in accordance 
with approved shop drawings.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Fill or cover cracks or knot holes larger than<MET> 13 mm</MET><ENG> 1/2 inch</ENG> in diameter in wood decks 
as necessary to form an unyielding surface.]</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include the following requirements when a vapor retarder is required 
over wood deck or when insulation is applied directly to the wood deck with 
hot asphalt.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">[c.  Cover wood decks with a layer of rosin-sized building paper or unsaturated felt.  Lap sides 
and ends not less than<MET> 75 mm</MET><ENG> 3 inches</ENG>.  Nail sufficiently to prevent tearing or buckling during 
installation.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[d.  Cover steel decks with a layer of insulation board of sufficient thickness to span the 
width of a deck rib opening, and conforming to fire safety requirements.  Secure with piercing 
or self-drilling, self-tapping fasteners of quantity and placement conforming to <RID>FM P7825</RID>.  
Insulation joints parallel to ribs of deck shall occur on solid bearing surfaces only, not over 
open ribs.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[e.  Solidly apply asphalt primer to [poured] [precast] concrete decks at the rate of<MET> 4 liters 
per 10 square meters</MET><ENG> one gallon per 100 square feet</ENG> of roof surface [, stopping approximately<MET>
 100 mm</MET><ENG> 4 inches</ENG> from joints between the precast concrete units].  Allow primer to dry thoroughly.  
[Place felt strips,<MET> 100 mm</MET><ENG> 4 inches</ENG> or more in width, over joints,<MET> 50 mm</MET><ENG> 2 inches</ENG> on each side, 
between precast concrete units in a heavy coating of cold-applied asphalt roof cement.]]</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.2   INSTALLATION OF VAPOR RETARDER</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Unless directed otherwise, do not specify a vapor retarder for projects 
in the SOUTHNAVFACENGCOM area.<BRK/>
<BRK/>
Vapor retarder may be specified for heated buildings where the average January 
temperature is below 5 degrees C (40 degrees F) and the expected interior winter 
humidity exceeds 45 percent.  Vapor retarder will be specified for heated buildings 
where a high humidity condition is expected, such as indoor swimming pool or laundry.<BRK/>
<BRK/>
Where a vapor retarder is to be installed, the designer will make sure that 
the computations show that the dew point is on the cold side of the vapor retarder.  
Computations should use recognized methods in agreement with ASHRAE Handbook, 
Fundamentals.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Install vapor retarder in direct contact with [roof deck surface] [ventilating felt] [insulation].  Vapor retarder 
shall consist of [either] two plies of No. 15 asphalt-saturated felt, two plies of asphalt-coated glass felt 
[, or one layer of asphalt-saturated felt base sheet].  Lay vapor retarder at right angles to direction of slope.  
Install first ply of felt [or base sheet] as specified herein for the specific deck.  Apply second ply of 2-ply 
vapor retarder system using asphalt at rate of<MET> 10 to 18 kgs per 10 square meters</MET><ENG> 20 to 35 lbs per 100 square 
feet</ENG>, applied within plus or minus <MET> 15 degrees C</MET><ENG>25 degrees F</ENG> of EVT.  Do not heat asphalt above asphalt's FBT 
or<MET> 275 degrees C</MET><ENG> 525 degrees F</ENG>, whichever is less.  Use thermometers to check temperatures during heating and 
application. Side and end laps shall be completely sealed.  Asphalt shall be visible beyond all edges of each 
ply as it is being installed.  Plies shall be laid free of wrinkles, buckles, creases or fishmouths.  Workers 
shall not walk on mopped surfaces when the asphalt is sticky.  Press out air bubbles to obtain complete adhesion 
between surfaces.  At walls, eaves and rakes, and other vertical surfaces, the vapor retarder organic felts shall 
be extended <MET>225 mm, </MET><ENG>9 inches, </ENG>or separate organic felt plies shall be extended <MET>225 mm, </MET><ENG>9 inches, </ENG>with not less 
than <MET>225 mm </MET><ENG>9 inches</ENG> on the substrate, and the extended portion turned back and mopped in over the top of the 
insulation.  At roof penetrations other than walls, eaves and rakes, and vertical surfaces, the vapor retarder 
or separate plies shall be extended <MET>225 mm </MET><ENG>9 inches</ENG> to form a lap which shall later be folded back over the edge 
of the insulation.  Asphalt roof cement shall be used under the vapor retarder for at least <MET>225 mm </MET><ENG>9 inches</ENG> from 
walls, eaves, rakes and other penetrations.</TXT><BRK/>
<BRK/>
<SPT>[<TTL>3.2.1   Vapor Retarder on Poured Concrete Decks</TTL><BRK/>
<BRK/>
<TXT>Solidly mop primed substrate with asphalt at rate of<MET> 10 to 18 kgs per 10 square meters</MET><ENG> 20 to 35 lbs per 100 square 
feet</ENG> before installing vapor retarder.  Lay first ply of 2 ply system with each sheet lapping<MET> 480 mm</MET><ENG> 19 inches</ENG>
 over the preceding sheet.  Lap ends not less than<MET> 100 mm</MET><ENG> 4 inches</ENG>.  Stagger laps a minimum of<MET> 300 mm</MET><ENG> 12 inches</ENG>
.  [For a vapor retarder consisting of one layer of asphalt base sheet, provide side and end laps not less than<MET>
 100 mm</MET><ENG> 4 inches</ENG>.  Stagger laps a minimum of <MET>300 mm</MET> <ENG>12 inches</ENG>.  Cement base sheets together with a solid mopping 
of asphalt.]</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.2.2   Vapor Retarder on Precast Concrete Decks</TTL><BRK/>
<BRK/>
<TXT>Solidly mop primed substrate with asphalt at rate of<MET> 10 to 18 kgs per square meters</MET><ENG> 20 to 35 lbs per 100 square 
feet</ENG> before installing vapor retarder.  Lay first ply of 2 ply system with each sheet lapping<MET> 480 mm</MET><ENG> 19 inches</ENG>
 over preceding sheet.  Lap ends not less than<MET> 100 mm</MET><ENG> 4 inches</ENG>.  Stagger laps a minimum of<MET> 300 mm</MET><ENG> 12 inches</ENG>.  
[For vapor retarder consisting of one layer of asphalt base sheet, provide side and end laps not less than<MET> 100 
mm</MET><ENG> 4 inches</ENG> and stagger laps a minimum of<MET> 300 mm</MET><ENG> 12 inches</ENG>.  Cement base sheets together with a solid mopping 
of asphalt.]</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.2.3   Vapor Retarder on Wood Decks</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  A vapor retarder should be specified only where:</NPR><BRK/>
<BRK/>
<NPR>1.  The outside, average January temperature is below<MET> 4 degrees C</MET><ENG> 40 degrees 
F</ENG>, and the expected winter interior relative humidity is 45 percent or greater;</NPR><BRK/>
<BRK/>
<NPR>2.  The roofing system will be subject to continuing excessively high interior 
humidity; and</NPR><BRK/>
<BRK/>
<NPR>3.  The results of a detailed analysis indicate a potential roofing problem 
resulting from water-vapor infiltration.</NPR><BRK/>
<BRK/>
<NPR>Delete contractor's option for a single-layer vapor retarder for roofs over 
areas having excessively high interior humidity such as swimming pools and laundries.  
Generally, the vapor retarder should be in direct contact with deck.  However, 
compute dewpoint temperature and location and locate vapor retarder below dewpoint 
location.  Avoid use of vapor retarder over steel decks unless vapor retarder 
is determined to be absolutely necessary.  Do not specify wood fiberboard or 
any other type of insulation sensitive to moisture for the layer directly on 
steel deck.  Glass mat gypsum roof board is not sensitive to moisture and may 
be used in such situations.  Specify installation of insulation over vapor retarder 
using hot asphalt to avoid puncturing the vapor retarder.  The combination of 
two or more layers of insulation shall be of such thickness that the dewpoint 
temperature will occur above vapor retarder located directly over first layer 
of insulation.  Topside venting should always be provided by insulation vents 
and perimeter edge vents when a vapor retarder is used.  Specify venting requirements 
in roofing membrane specification section.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Lay first ply of 2 ply system dry with each sheet lapping<MET> 50 mm</MET><ENG> 2 inches</ENG> over the preceding sheet.  Lap ends 
not less than<MET> 100 mm</MET><ENG> 4 inches</ENG>.  Stagger laps a minimum of<MET> 300 mm</MET><ENG> 12 inches</ENG>.  Nail felt at<MET> 150 mm</MET><ENG> 6 inch</ENG> intervals 
along side laps and install two rows of nails approximately<MET> 275 mm</MET><ENG> 11 inches</ENG> apart down longitudinal center of 
each sheet, with nails staggered at<MET> 450 mm</MET><ENG> 18 inches</ENG> O.C.  [For vapor retarder consisting of one layer of asphalt 
base sheet, lap each sheet<MET> 100 mm</MET><ENG> 4 inches</ENG> over the preceding sheet.  Provide end laps not less than<MET> 100 mm</MET><ENG> 4 
inches</ENG> and stagger laps a minimum of<MET> 300 mm</MET><ENG> 12 inches</ENG>.]  Cement side and end laps together with solid mopping 
of asphalt or heavy coat of asphalt roof cement.  Nail side laps at<MET> 150 mm</MET><ENG> 6 inch</ENG> intervals.  Apply asphalt mopping 
at rate of<MET> 10 to 18 kgs per 10 square meters</MET><ENG> 20 to 35 lbs per 100 square feet</ENG>.  Install two rows of nails approximately<MET>
 275 mm</MET><ENG> 11 inches</ENG> apart down longitudinal center of each sheet, with nails staggered at<MET> 450 mm</MET><ENG> 18 inches</ENG> O.C.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.2.4   Vapor Retarder on Steel Decks</TTL><BRK/>
<BRK/>
<TXT>Solidly mop the mechanically secured insulation surface with asphalt before installing vapor retarder.  For a 
2 ply vapor retarder, install each sheet lapping<MET> 480 mm</MET><ENG> 19 inches</ENG> over the preceding sheet.  Lap ends not less 
than<MET> 100 mm</MET><ENG> 4 inches</ENG>.  Stagger the laps a minimum of<MET> 300 mm</MET><ENG> 12 inches</ENG>.  Cement felts together with solid mopping 
of asphalt.  Apply asphalt moppings at rate of<MET> 10 to 18 kgs per 10 square meters</MET><ENG> 20 to 35 lbs per 100 square 
feet</ENG>.  [For a vapor retarder consisting of one layer of asphalt base sheet, lap each sheet<MET> 100 mm</MET><ENG> 4 inches</ENG>over 
preceding sheet.  Lap ends not less than <MET>100 mm</MET><ENG> 4 inches</ENG>, and stagger laps a minimum of<MET> 300 mm</MET><ENG> 12 inches</ENG>.  Cement 
base sheets together with solid mopping of asphalt.]</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.2.5   Over Gypsum Insulating Concrete or Lightweight Insulating Concrete</TTL><BRK/>
<BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: Some types of light weight insulating concrete may require bottom side 
deck venting; edit this paragraph accordingly if bottom side-venting is used. </NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>One ply of venting inorganic base sheet shall be laid, without mopping, at right angle to the slope with <MET>100 
mm </MET><ENG>4 inch</ENG> side laps and <MET>150 mm </MET><ENG>6 inch</ENG> end laps.  Laps shall be bonded with hot asphalt.  End laps shall be staggered.  
Base sheet shall be [nailed <MET>220 mm </MET><ENG>9 inches</ENG> on centers at side laps and in 2 rows <MET>270 mm </MET><ENG>11 inches</ENG> apart down 
the center of the sheet with nails <MET>450 mm </MET><ENG>18 inches</ENG> on centers and staggered] [attached to the concrete as determined 
by uplift requirements].  The 2-ply vapor retarder shall then be applied over the base sheet as specified above.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.6   Over Concrete Decks and First Layer of Insulation on Steel Decks</TTL><BRK/>
<BRK/>
<TXT>The 2-ply vapor retarder shall be applied as specified above except that venting inorganic base sheet shall be 
deleted.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.7   Over Structural Concrete on Non-Venting Support</TTL><BRK/>
<BRK/>
<TXT>One ply of venting inorganic base sheet with mopping holes shall be laid dry at right angle to the slope with <MET>
100 mm </MET><ENG>4 inch</ENG> side laps and <MET>150 mm </MET><ENG>6 inch</ENG> end laps.  The vapor retarder shall then be applied as specified.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>3.3   INSTALLATION OF VENTILATING FELT</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: Specify ventilating felt for new and existing concrete decks suspected 
of having retained moisture to aid in dissipation of any moisture retained in 
concrete.  This felt shall not be considered to be a vapor retarder.</NPR><BRK/>
<BRK/>
<NPR>Include bracketed phrase only when insulation is to be applied with hot asphalt.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Apply ventilating felt in accordance with manufacturer's printed instructions[, spot-mopped with asphalt to concrete 
deck].  Extend over roof cants, up vertical surfaces and terminate under cap flashing; at roof edges terminate 
under outside edge of perimeter edge nailers or under gravel stop fascia.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.4   INSULATION INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Apply insulation in two layers with staggered joints when total required thickness of insulation exceeds<MET> 13 mm</MET><ENG>
 1/2 inch</ENG>.  Lay insulation so that continuous longitudinal joints are perpendicular to direction of [felts for 
the built-up] roofing, as specified in Section [_____, "_____"], and end joints of each course are staggered 
with those of adjoining courses.  When using multiple layers of insulation, joints of each succeeding layer shall 
be parallel and offset in both directions with respect to layer below.  Keep insulation<MET> 13 mm</MET><ENG> 1/2 inch</ENG> clear 
of vertical surfaces penetrating and projecting from roof surface.</TXT><BRK/>
<BRK/>
<SPT>[<TTL>3.4.1   Installation Using Asphalt</TTL><BRK/>
<BRK/>
<TXT>Firmly embed each layer in solid asphalt mopping; mop only sufficient area to provide complete embedment of one 
board at a time.  Provide<MET> 10 to 18 kgs</MET><ENG> 20 to 35 lbs</ENG> of asphalt per<MET> 10 square meters</MET><ENG> 100 square feet</ENG> of roof deck 
for each layer of insulation.  Apply asphalt when temperature is within plus or minus<MET> 15 degrees C</MET><ENG> 25 degrees 
F</ENG> of EVT.  Do not heat asphalt above asphalt's FBT or<MET> 275 degrees C</MET><ENG> 525 degrees F</ENG>, whichever is less, for longer 
than 4 consecutive hours.  Use thermometers to check temperatures during heating and application.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.4.2   Installation Using Asphalt on Steel Decks</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete these requirements and include paragraph entitled "Installation 
Using Asphalt" when a vapor retarder is required over steel decks.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Secure first layer of insulation [and thermal barrier] to deck with piercing or self-drilling, self-tapping fasteners.  
Engage fasteners by driving them through insulation into top flange of steel deck.  Use driving method prescribed 
by fastener manufacturer.  Insulation joints parallel to ribs of deck shall occur on solid bearing surfaces only, 
not over open ribs.  Secure succeeding layers with solid asphalt moppings.  Where insulation is applied over 
steel deck, long edge joints shall continuously bear on surfaces of the steel deck.  Insulation which can be 
readily lifted after installation is not considered to be adequately secured.  Insulation shall be applied so 
that all roof insulation applied each day is waterproofed the same day.  Phased construction will not be permitted.  
Application of impermeable faced insulation shall be performed without damage to the facing.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.4.3   Installation Using Only Mechanical Fasteners</TTL><BRK/>
<BRK/>
<TXT>Secure total thickness of insulation with penetrating type fasteners.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.4.4   Special Precautions for Installation of Foam Insulation</TTL><BRK/>
<BRK/>
<SPT><TTL>3.4.4.1   Polyisocyanurate Insulation</TTL><BRK/>
<BRK/>
<TXT>Where polyisocyanurate foam board insulation is provided, install<MET> 13 mm</MET><ENG> 1/2 inch</ENG> thick wood fiberboard, glass 
mat gypsum roof board, or<MET> 19 mm</MET><ENG> 3/4 inch</ENG> thick expanded perlite board insulation over top surface of foam board 
insulation.  Stagger joints of insulation with respect to foam board insulation below.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.4.4.2   Polystyrene Insulation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include these requirements when polystyrene insulation is used under 
fully-adhered EPDM, CPE, PIB, or PVC roofing.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">a.  Over top surface of non-composite polystyrene board, install<MET> 13 mm</MET><ENG> 1/2 inch</ENG> thick high density 
wood fiberboard,<MET> 19 mm</MET><ENG> 3/4 inch</ENG> thick expanded perlite board, glass mat gypsum roof board, or 
other overlayment approved by roofing sheet manufacturer.  Tightly butt and stagger joints of 
field applied overlayment board at least<MET> 150 mm</MET><ENG> 6 inches</ENG> with respect to the polystyrene board 
below.  Apply<MET> 150 mm</MET><ENG> 6 inch</ENG> wide glass fiber roofing tape centered over joints and edges of 
overlayment board.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Where composite boards consisting of polystyrene insulation are provided, apply<MET> 150 mm</MET><ENG> 6 
inch</ENG> wide glass-fiber roofing tape centered over joints and edges of composite board.  Apply 
joint strips as recommended by roofing sheet manufacturer.</ITM><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.4.5   Cant Strips</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Generally cant strips are not required for single ply roofing systems.  
However, if cant strips are necessary, coordinate location with mechanical drawings 
to ensure that no projections, such as vent pipes and braces, will be constructed 
through or within<MET> 250 mm</MET><ENG> 10 inches</ENG> of cant strips.  Specify wood cants, edge 
strips, and pressure preservative treatment in Section 06 10 00.  Delete reference 
to asphalt application unless asphalt is used in applying the insulation.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Where indicated, provide cant strips at intersections of roof with walls, parapets, and curbs extending above 
roof.  Wood cant strips shall bear on and be anchored to wood blocking.  Fit cant strips flush against vertical 
surfaces.  Where possible, nail cant strips to adjoining surfaces.  Where cant strips are installed against non-nailable 
materials, install in [heavy mopping of asphalt or set in a heavy coating of asphalt roof cement] [an approved 
adhesive].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4.6   Tapered Edge Strips</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete reference to asphalt application unless asphalt is used in installing 
the insulation.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Where indicated, provide edge strips in the right angle formed by junction of roof and wood nailing strips that 
extend above level of roof.  Install edge strips flush against vertical surfaces of wood nailing strips.  Where 
possible, nail edge strips to adjoining surfaces.  Where installed against non-nailable materials, install in 
[heavy mopping of asphalt or set in heavy coating of asphalt roof cement] [an approved adhesive].</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.5   PROTECTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.5.1   Protection of Applied Insulation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Insert appropriate Section number and title in the blank below using 
format per UFC 1-300-02.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Completely cover each day's installation of insulation with the finished roofing specified in [_____] on same 
day.  Do not permit phased construction.    Protect open spaces between insulation and parapets or other walls 
and spaces at curbs, scuttles, and expansion joints, until permanent roofing and flashing are applied.  Do not 
permit storing, walking, wheeling, or trucking directly on insulation or on roofed surfaces.  Provide smooth, 
clean board or plank walkways, runways, and platforms near supports, as necessary, to distribute weight to conform 
to [indicated live load limits of roof construction] [a [_____]<MET> kg/sq. m</MET><ENG> psf</ENG> live load limit].  Exposed edges 
of the insulation shall be protected by cutoffs at the end of each work day or whenever precipitation is imminent.  
Cutoffs shall be 2 layers of bituminous-saturated felt set in plastic bituminous cement [or single ply] [or EPDM 
membrane] set in roof cement.  Fill all profile voids in cut-offs to prevent entrapping of moisture into the 
area below the membrane.  Cutoffs shall be removed when work is resumed.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.2   Damaged Work and Materials</TTL><BRK/>
<BRK/>
<TXT>Restore work and materials that become damaged during construction to original condition or replace with new 
materials.</TXT><BRK/></SPT>
<BRK/></SPT>
<SPT><TTL>3.6   INSPECTION</TTL><BRK/>
<BRK/>
<NTE><AST/><BRK/>
<NPR>NOTE: When justified by the amount or criticality of the insulation and roofing 
involved, and when requirements for a roof insulation technician are not established 
for the Contractor Quality Control organization, the following requirement will 
be added at the end of this paragraph:  "A roof insulation technician, responsible 
directly to the Contractor and experienced in the installation of roof insulation 
and related work, shall perform the inspection functions and be on the site 
whenever roof insulation operations are in progress." </NPR><BRK/>
<AST/><BRK/></NTE>
<TXT>The Contractor shall establish and maintain an inspection procedure to assure compliance of the installed roof 
insulation with the contract requirements.  Any work found not to be in compliance with the contract shall be 
promptly removed and replaced or corrected in an approved manner.  Quality control shall include, but not be 
limited to, the following:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Observation of environmental conditions; number and skill level of insulation workers; start 
and end time of work.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Verification of certification, listing or label compliance with <RID>FM P9513</RID>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Verification of proper storage and handling of insulation and vapor retarder materials before, 
during, and after installation.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Inspection of vapor retarder application, including edge envelopes and mechanical fastening.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.   Inspection of mechanical fasteners; type, number, length, and spacing.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Coordination with other materials, cants, sleepers, and nailing strips.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Inspection of insulation joint orientation and laps between layers, joint width and bearing 
of edges of insulation on deck.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.   Installation of cutoffs and proper joining of work on subsequent days.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">i.  Continuation of complete roofing system installation to cover insulation installed same 
day.</ITM><BRK/>
<BRK/></SPT>
</PRT>    <END/><BRK/></SEC>