<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><BRK/>
<MTA NAME="SUBFORMAT" CONTENT="NEW"/><HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA            UFGS-07 53 23 (November 2008)<BRK/>
                                          --------------------------------<BRK/>
Preparing Activity:  <PRA>NAVFAC</PRA>               Superseding<BRK/>
                                          UFGS-07 53 23 (January 2007)<BRK/>
                                          UFGS-07 53 00.00 40 (April 2006)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 07 53 23</SCN><BRK/>
<BRK/>
<STL>ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING</STL><BRK/>
<DTE>11/08</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>ethylene propylene 
diene terpolymer (EPDM) elastomeric sheet roofing, with associated elastomeric 
sheet flashing, for installations with the insulation below the membrane</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Standard application methods include loose-laid ballasted, fully adhered, 
and mechanically fastened systems.  Also included is a special combined fully 
adhered and mechanically fastened system for excessive wind loading conditions.  
This guide specification does not include the structural roof deck, insulation, 
sheet metal fascias, gravel stops, flashings, nor use of elastomeric sheets 
for roofing located adjacent to kitchen or food service exhaust system discharge 
ducts.  Grease and oil attack EPDM.  Exhaust fumes must be directed away from 
the roofing system.<BRK/>
<BRK/>
Coordinate this section with other roof system components specifications such 
as rough carpentry, insulation and sheet metal flashing.  Also coordinate this 
section with the criteria contained in Unified Facilities Criteria (UFC) 3-110-06 
DESIGN: ROOFING as it relates to the specific project and Service Exceptions 
indicated therein.<BRK/>
<BRK/>
Specified membrane attachment must be compatible with the insulation specified.  
Do not adhere membrane directly to polystyrene, perlite or standard wood fiber, 
insulation.  Facer on polyisocyanurate insulations must be compatible with the 
adhesive of a fully adhered membrane application.  Glass mat, moisture resistant 
gypsum roof board can be used as an underlayment over insulation for adhesive 
application of roof membrane with approval of the membrane manufacturer.  Top 
insulation layer under ballasted roofing systems must be wood fiberboard, perlite, 
or glass mat, moisture resistant gypsum roof board.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
<BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
<BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)</ORG><BRK/><BRK/><RID>ANSI/SPRI RD-1</RID><RTL>(2004) Standard for Retrofit Roof Drains</RTL><BRK/><BRK/></REF><REF><ORG>AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)</ORG><BRK/><BRK/><RID>ASCE 7</RID><RTL>(2005; Supp 1) Minimum Design Loads for Buildings and Other Structures</RTL><BRK/><BRK/></REF><REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM D 448</RID><RTL>(2008) Sizes of Aggregate for Road and Bridge Construction</RTL><BRK/><BRK/><RID>ASTM D 4637</RID><RTL>(2008) EPDM Sheet Used in Single-Ply Roof Membrane</RTL><BRK/><BRK/><RID>ASTM D 4811</RID><RTL>(2006) Nonvulcanized (Uncured) Rubber Sheet Used as Roof Flashing</RTL><BRK/><BRK/><RID>ASTM D 6369</RID><RTL>(1999; R 2006) Design of Standard Flashing Details for EPDM Roof Membranes</RTL><BRK/><BRK/><RID>ASTM E 108</RID><RTL>(2007a) Fire Tests of Roof Coverings</RTL><BRK/><BRK/></REF><REF><ORG>FM GLOBAL (FM)</ORG><BRK/><BRK/><RID>FM 4470</RID><RTL>(1986; R 1992) Class I Roof Covers</RTL><BRK/><BRK/><RID>FM P7825</RID><RTL>(2005) Approval Guide</RTL><BRK/><BRK/><RID>FM P7825c</RID><RTL>(2005) Approval Guide Building Materials</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL ROOFING CONTRACTORS ASSOCIATION (NRCA)</ORG><BRK/><BRK/><RID>NRCA 0405</RID><RTL>(2001; R 2003, 5th Ed) Roofing and Waterproofing Manual</RTL><BRK/><BRK/></REF><REF><ORG>SINGLE PLY ROOFING INDUSTRY (SPRI)</ORG><BRK/><BRK/><RID>SPRI RP-4</RID><RTL>(2002) Wind Design Standard for Ballasted Single-Ply Roofing Systems</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 790</RID><RTL>(2004; Rev thru Oct 2008) Test Methods for Fire Tests of Roof Coverings</RTL><BRK/><BRK/><RID>UL RMSD</RID><RTL>(2008) Roofing Materials and Systems Directory</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   DESCRIPTION OF ROOF MEMBRANE SYSTEM[S]</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate with Part 2 materials specification.<BRK/>
<BRK/>
Select the application method required.  Delete other options.<BRK/>
<BRK/>
Where EPDM systems are utilized, fully adhered systems applied over minimum 
two layers of rigid board roof insulation is the preferred norm.<BRK/>
<BRK/>
Do not specify stone ballasted systems along flight lines, in wind zones exceeding 
160 km/h 100 mph, within 8 km 5 miles of coastline, within 457 m 1500 feet of 
open body of water, and on or adjacent to critical facilities such as hospitals.  
Where ballasted systems are required, utilize interlocking pavers designed to 
resist the required wind loads.  Ballasted systems on air permeable decks (e.g., 
metal decks, precast concrete panels or planks) must incorporate an air barrier 
in the assembly.<BRK/>
<BRK/>
Mechanically fastened systems must also incorporate an air barrier in the roof 
assembly.  Use reinforced membrane in wind zones exceeding 160 km/h 100 mph, 
within 8 km 5 miles of coastline or within 457 m 1500 feet of open body of water.<BRK/>
<BRK/>
Specify combination attachment only  for isolated geographic locations that 
experience extreme and extended wind conditions such as portions of Alaska and 
Iceland, or as otherwise required by the Government.<BRK/>
<BRK/>
Where one membrane system is required for all roof areas, use the first paragraph.  
Where different systems are required, use the second paragraph successively 
and replace the open brackets with a description of the substrate(s) or area 
of the building or project where each system is to be applied.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Fully adhered][Mechanically fastened][Ballasted][Combination fully adhered and mechanically fastened] EPDM roof 
membrane system applied over [insulation][recovery board][concrete roof deck] substrate.</TXT><BRK/>
<BRK/>
<TXT>[_______]:  [Fully adhered][Mechanically fastened][Ballasted][Combination fully adhered and mechanically fastened] 
EPDM roof membrane system applied over [insulation][recovery board][concrete roof deck] substrate.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review Submittal Description (SD) definitions in Section <SRF>01 33 00</SRF> SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  Submit the following 
in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Roof Plan Drawing</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Wind Load Calculations</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Boundaries of Enhanced Perimeter</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Corner Attachments of Roof System Components</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Location of Perimeter Half-Sheets</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Spacing of Perimeter, Corner, and Infield Fasteners</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Slopes and Drain Locations</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit the product data submission requirements as necessary for the system 
specified.  Include bracketed requirements as applicable to the system being 
specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM><SUB>Cement</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>EPDM Sheet</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Seam Tape</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Bonding Adhesive</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Lap Splice Adhesive</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Water Cutoff Mastic/Water Block</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Lap Cleaner, Lap Sealant, and Edge Treatment</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Flashings</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Flashing Accessories</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Flashing Tape</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Fasteners and Plates</SUB></ITM><BRK/>
<BRK/>
<ITM>[<SUB>Ballast</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Roof Insulation</SUB></ITM><BRK/>
<BRK/>
<ITM>[<SUB>Protection Mat</SUB>]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Pre-Manufactured Accessories</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Sample <SUB>warranty</SUB> certificate[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Submit all data required together with requirements of this section.  Include a written acceptance 
by the roof membrane manufacturer of the insulation and other products and accessories to be 
provided.  List products in the applicable wind uplift and fire rating classification listings, 
unless approved otherwise by the Contracting Officer.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-05 Design Data</SUB></LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Incorporate this paragraph for ballasted systems and anytime non-FM rated 
systems are permissible.  Coordinate with requirements of "Wind Uplift" paragraph.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM><SUB>Wind Uplift Calculations</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>[Engineering calculations validating the wind resistance of roof system.]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Qualification of Manufacturer</SUB></ITM><BRK/>
<BRK/>
<ITM>Certify that the manufacturer of the roof membrane meets requirements specified under paragraph 
entitled "Qualification of Manufacturer."</ITM><BRK/>
<BRK/>
<ITM><SUB>Qualification of Applicator</SUB></ITM><BRK/>
<BRK/>
<ITM>Certify that the applicator meets requirements specified under paragraph entitled "Qualification 
of Applicator."  </ITM><BRK/>
<BRK/>
<ITM><SUB>Wind Uplift Resistance</SUB> classification, as applicable[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Fire Resistance</SUB> classification[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Submit the roof system assembly [wind uplift and] fire rating classification listings.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-08 Manufacturer's Instructions</SUB></LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit the manufacturers instructions submission requirements as necessary 
for the system specified.  Include bracketed requirements only as applicable 
to the system being specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM><SUB>Application</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Application Method</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>], including pattern and frequency of mechanical attachments 
required in the field of roof, corners, and perimeters to provide for the specified wind resistance</ITM><BRK/>
<BRK/>
<ITM><SUB>Membrane Flashing</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Seam Tape</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Tape Seams / Lap Splices</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Adhesive Seams / Lap Splices</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Perimeter Attachment</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Primer</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Fasteners</SUB></ITM><BRK/>
<BRK/>
<ITM>[<SUB>Pavers</SUB>]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Protection Mat</SUB>]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Pre-Manufactured Accessories</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Cold Weather</SUB> Installation[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Include detailed application instructions and standard manufacturer drawings altered as required 
by these specifications. Explicitly identify in writing, differences between manufacturer's 
printed instructions and the specified requirements.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-11 Closeout Submittals</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Warranty</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Information Card</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Instructions To Government Personnel</SUB></ITM><BRK/>
<BRK/>
<ITM>Include copies of Material Safety Data Sheets for maintenance/repair materials.</ITM><BRK/>
<BRK/>
<SPT><TTL>1.3.1   Shop Drawings</TTL><BRK/>
<BRK/>
<TXT><SUB>Roof plan drawing</SUB> depicting <SUB>wind load calculations</SUB> and <SUB>boundaries of enhanced perimeter</SUB> and <SUB>corner attachments 
of roof system components</SUB>, [<SUB>location of perimeter half-sheets</SUB>][, <SUB>spacing of perimeter, corner, and infield fasteners</SUB>
,] as applicable.  The drawing must reflect the project roof plan of each roof level and conditions indicated.  
Provide all <SUB>slopes and drain locations</SUB>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.4   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.4.1   <SUB>Qualification of Manufacturer</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify 5 years manufacturer experience unless directed otherwise by 
the Government </NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>EPDM sheet roofing membrane manufacturer must have at least [5][_____] years experience in manufacturing EPDM 
roofing products.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.2   <SUB>Qualification of Applicator</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify 3 years as an approved Contractor unless directed otherwise by 
the Government </NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Roofing system applicator must be approved, authorized, or licensed in writing by the roof membrane manufacturer 
and must have a minimum of [three][_____] years experience as an approved, authorized, or licensed applicator 
with that manufacturer and be approved at a level capable of providing the specified warranty.  The applicator 
must supply the names, locations and client contact information of 5 projects of similar size and scope that 
the applicator has constructed using the manufacturer's roofing products submitted for this project within the 
previous three years.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.3   <SUB>Fire Resistance</SUB></TTL><BRK/>
<BRK/>
<TXT>Complete roof covering assembly must:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Be Class A rated in accordance with <RID>ASTM E 108</RID>, <RID>FM 4470</RID>, or <RID>UL 790</RID>; and</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Be listed as part of Fire-Classified roof deck construction in the <RID>UL RMSD</RID> or Class I roof 
deck construction in the <RID>FM P7825</RID>.</ITM><BRK/>
<BRK/>
<TXT>FM or UL approved components of the roof covering assembly must bear the appropriate FM or UL label.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.4   <SUB>Wind Uplift Resistance</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Determine the required wind uplift resistance based on ASCE 7 wind loading 
calculations or applicable building code requirements.<BRK/>
<BRK/>
The specified FM approval rating incorporates a safety factor of 2 over the 
maximum calculated uplift pressure in inch-pound units.  Therefore, a FM approval 
rating of 1-90 correlates to a maximum uplift calculation of 2.2 kPa 45 psf.  
When specifying an FM rated system, ensure the designed roof system is capable 
of providing the specified FM approval rating.  Where non-rated systems may 
be permissible, include the bracketed portion of the second sentence and the 
third sentence.</NPR><BRK/>
<BRK/>
<NPR>Ballast for loose-laid ballasted application should be designed in accordance 
with ANSI/RMA/SPRI RP-4.  Where ballasted systems are specified include the 
bracketed option at the end of the paragraph.</NPR><BRK/>
<BRK/>
<NPR>Higher ratings are available if wind load calculations determine a need.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Complete roof covering assembly, including insulation, must be rated Class 1-[60][90][_____] in accordance with <RID>
FM P7825</RID> capable of withstanding an uplift pressure of<MET> [2.85][3.59][4.31][5.03][5,75][6.46][_____] kPa per square 
meter</MET> <ENG> [60][75][90][105][120][135][_____] psf</ENG>.  Do not install non-rated systems[, except as approved by the 
Contracting Officer].  Provide wind load calculations and submit engineering calculations and substantiating 
data to validate wind resistance of any non-rated roof system.  Apply <SUB>wind uplift calculations</SUB> based on a design 
wind speed of<MET> [_____] km/h</MET> <ENG>[_____] mph</ENG> in accordance with <RID>ASCE 7</RID>[ or applicable building code requirements]. 
[Resistance to wind uplift for loose-laid ballasted application must be in accordance with requirements of <RID>SPRI RP-4</RID>
.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.5   Preroofing Conference</TTL><BRK/>
<BRK/>
<TXT>After approval of submittals and before performing roofing [and insulation] system installation work, hold a 
preroofing conference to review the following:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Drawings, specifications and submittals related to the roof work;</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Roof system components installation;</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Procedure for the roof manufacturer's technical representative's onsite inspection and acceptance 
of the roofing substrate, the name of the manufacturer's technical representatives, the frequency 
of the onsite visits, distribution of copies of the inspection reports from the manufacturer's 
technical representative;</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Contractor's plan for coordination of the work of the various trades involved in providing 
the roofing system and other components secured to the roofing; and</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Quality control plan for the roof system installation;</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Safety requirements.</ITM><BRK/>
<BRK/>
<TXT>Coordinate preroofing conference scheduling with the Contracting Officer.  The conference must be attended by 
the Contractor, the Contracting Officer's designated personnel, personnel directly responsible for the installation 
of roofing[ and insulation], flashing and sheet metal work, [[mechanical] [and] [electrical] work], other trades 
interfacing with the roof work, and representative of the roofing materials manufacturer.  Before beginning roofing 
work, provide a copy of meeting notes and action items to all attending parties.  Note action items requiring 
resolution prior to start of roof work.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.5   DELIVERY, STORAGE, AND HANDLING</TTL><BRK/>
<BRK/>
<SPT><TTL>1.5.1   Delivery</TTL><BRK/>
<BRK/>
<TXT>Deliver materials in their original, unopened containers or wrappings with labels intact and legible.  Where 
materials are covered by a referenced specification number, the labels must bear the specification number, type, 
class, and shelf life expiration date where applicable.  Deliver materials in sufficient quantity to allow continuity 
of work.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5.2   Storage</TTL><BRK/>
<BRK/>
<TXT>Store and protect materials from damage and weather in accordance with manufacturer's printed instructions, except 
as specified otherwise.  Keep materials clean and dry.  Store and maintain adhesives, sealants, primers and other 
liquid materials above<MET> 15 degrees C</MET><ENG> 60 degrees F</ENG>.  Insulated hot boxes or other enclosed warming devices must 
be required in cold weather.  Mark and remove damaged materials from the site.  Use pallets to support and canvas 
tarpaulins to completely cover material materials stored outdoors.  Do not use polyethylene as a covering.  Locate 
materials temporarily stored on the roof in approved areas, and distribute the load to stay within the live load 
limits of the roof construction.  Remove unused materials from the roof at the end of each days work.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5.3   Handling</TTL><BRK/>
<BRK/>
<TXT>Prevent damage to edges and ends of roll materials.  Do not install damaged materials in the work.  Select and 
operate material handling equipment so as not to damage materials or applied roofing.  Do not use materials contaminated 
by exposure or moisture.  Remove contaminated materials from the site.  When hazardous materials are involved, 
adhere to the special precautions of the manufacturer.  Adhesives may contain petroleum distillates and may be 
extremely flammable; prevent personnel from breathing vapors, and do not use near sparks or open flame.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.6   ENVIRONMENTAL REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Do not install EPDM sheet roofing during high winds or inclement weather, or when there is ice, frost, moisture, 
or visible dampness on the substrate surface, or when condensation develops on surfaces during application.  
Unless recommended otherwise by the EPDM sheet manufacturer and approved by the Contracting Officer, do not install 
EPDM sheet when air temperature is below<MET> 4 degrees C</MET><ENG> 40 degrees F</ENG> or within<MET> 3 degrees C</MET><ENG> 5 degrees F</ENG> of the dewpoint.  
Follow manufacturer's printed instructions for installation during <SUB>cold weather</SUB> conditions.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.7   SEQUENCING</TTL><BRK/>
<BRK/>
<TXT>Coordinate the work with other trades to ensure that components which are to be secured to or stripped into the 
roofing system are available and that permanent flashing and counterflashing are installed as the work progresses.  
Ensure temporary protection measures are in place to preclude moisture intrusion or damage to installed materials.  
[Application of roofing must immediately follow application of insulation as a continuous operation.  Coordinate 
roofing operations with insulation work so that all roof insulation applied each day is covered with roof membrane 
installation the same day.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.8   <SUB>WARRANTY</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide roof system material and workmanship warranties meeting specified requirements.  Provide revision or 
amendment to standard membrane manufacturer warranty as required to comply with the specified requirements.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.8.1   Roof Membrane Manufacturer Warranty</TTL> <BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Insulated and routinely occupied facilities or facilities containing 
sensitive equipment or operations require a warranty of not less than 15 years.  
Designer may specify 5 or 10 year manufacturer warranty on facilities of small 
roof area and of minor importance where interiors and contents are not severely 
impacted by potential water intrusion.  Environmentally controlled interiors 
require minimum 10 year warranty regardless of small size.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Furnish the roof membrane manufacturer's [5][10][15][_____] year no dollar limit roof system materials and installation 
workmanship warranty, including flashing, insulation, and accessories necessary for a watertight roof system 
construction.  The warranty must run directly to the Government and commence at time of Government's acceptance 
of the roof work.  The warranty must state that:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  If within the warranty period the roof system, as installed for its intended use in the 
normal climatic and environmental conditions of the facility, becomes non-watertight, shows 
evidence of moisture intrusion within the assembly, splits, tears, cracks, delaminates, separates 
at the seams, shrinks to the point of bridging or tenting membrane at transitions, or shows 
evidence of excessive weathering due to defective materials or installation workmanship, the 
repair or replacement of the defective and damaged materials of the roof system assembly and 
correction of defective workmanship must be the responsibility of the roof membrane manufacturer.  
The roof membrane manufacturer is responsible for all costs associated with the repair or replacement 
work.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  When the manufacturer or his approved applicator fail to perform the repairs within 72 hours 
of notification, emergency temporary repairs performed by others does not void the warranty.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.8.2   Roofing System Installer Warranty</TTL> <BRK/>
<BRK/>
<TXT>Warrant for a period of not less than two years that the roof system, as installed, is free from defects in installation 
workmanship, to include the roof membrane, flashing, insulation, accessories, attachments, and sheet metal installation 
integral to a complete watertight roof system assembly.  The warranty must run directly to the Government.  The 
roof system installer is responsible for correction of defective workmanship and replacement of damaged or affected 
materials.  The installer is responsible for all costs associated with the repair or replacement work.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.8.3   Continuance of Warranty</TTL><BRK/>
<BRK/>
<TXT>Approve repair or replacement work that becomes necessary within the warranty period, as required, and accomplish 
in a manner so as to restore the integrity of the roof system assembly and validity of the roof membrane manufacturer 
warranty for the remainder of the manufacturer warranty period.</TXT><BRK/>
<BRK/></SPT>
 </SPT><SPT><TTL>1.9   CONFORMANCE AND COMPATIBILITY</TTL><BRK/>
<BRK/>
<TXT>The entire roofing and flashing system must be in accordance with specified and indicated requirements, including 
fire and wind resistance requirements.  Work not specifically addressed and any deviation from specified requirements 
must be in general accordance with recommendations of the <RID>NRCA 0405</RID>, membrane manufacturer published recommendations 
and details, <RID>ASTM D 6369</RID>, and compatible with surrounding components and construction.  Submit any deviation 
from specified or indicated requirements to the Contracting Officer for approval prior to installation.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   MATERIALS</TTL><BRK/>
<BRK/>
<TXT>Coordinate with other specification sections related to the roof work.  Furnish a combination of specified materials 
that comprise a roof system acceptable to the roof membrane manufacturer and meeting specified requirements.  
Protect materials provided from defects and make suitable for the service and climatic conditions of the installation.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.1   <SUB>EPDM Sheet</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Refer to Designer Note in PART 1 - DESCRIPTION OF ROOF MEMBRANE SYSTEM 
for guidance regarding membrane attachment method and in editing the membrane 
materials requirements.<BRK/>
<BRK/>
Specify 1.1 mm 0.045 inch Type II reinforced membrane for mechanically fastened 
applications in wind zones exceeding 160 km/h 100 mph, within 8 km 5 miles of 
coastline or within 457 m 1500 feet of open body of water.  <BRK/>
<BRK/>
Typically specify 1.5 mm 0.060 inch Type II non-reinforced membrane for fully 
adhered or ballasted application, except that 1.1 mm 0.045 inch Type III membrane 
with fleece-backing may be used in fully adhered installations.  When Type III 
membrane is required the adhesive is typically a spray applied compound, spray 
foam adhesive, or hot asphalt.  Modify related portions of this specification 
for proper adhesive and application parameters when Type III membrane is specified.<BRK/>
<BRK/>
2.3 mm 0.090 inch membrane is a special material with limited availability.  
Specify 2.3 mm 0.090 inch membrane only for applications that experience regular 
heavy traffic conditions or regular extreme wind conditions.  2.3 mm 0.090 inch 
membrane must only be fully adhered.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Ethylene Propylene Diene Terpolymer (EPDM), <RID>ASTM D 4637</RID>, [Type I, non-reinforced][Type II, scrim or fabric reinforced][Type 
III, fabric or fleece backed],<MET> 1.1 mm</MET><ENG> 0.045 inch</ENG><MET> 1.5 mm</MET><ENG> 0.060 inch</ENG><MET> 2.3 mm</MET><ENG> 0.090 inch</ENG> nominal thickness for [mechanically 
fastened] [fully adhered] [loose-laid ballasted] [combined fully adhered and mechanically fastened] application.  
The minimum thickness must not be less than minus 10 percent of the specified thickness value.  EPDM membrane 
thickness specified is exclusive of backing material on the EPDM membrane.  Principal polymer used in manufacture 
of the membrane sheet must be greater than 95 percent EPDM. Width and length of sheet must be [as recommended 
by the manufacturer.][maximum width attainable as recommended by the manufacturer to minimize field formed seams 
in the field of the roof.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   <SUB>Seam Tape</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Seam tapes have proven most effective in maintaining long term seal of 
field seams of roof membrane.  Seam tapes can be difficult to apply to membrane 
flashing situations.  As such, lap splice adhesive or self-adhering flashing 
membrane are used as alternatives in difficult membrane flashing areas.<BRK/>
<BRK/>
Seam tapes must be minimum 75 mm 3 inch wide.  Some specific situations may 
require wider seam tapes as recommended by the membrane manufacturer.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Double-sided synthetic rubber tape, minimum<MET> 0.76 mm</MET><ENG> 0.03 inch</ENG> thick, minimum<MET>75 mm</MET><ENG> 3 inch</ENG> wide.  The roof membrane 
manufacturer must supply seam tape recommended by the manufacturer's printed data for forming watertight bond 
of EPDM sheet materials to each other for the application specified and conditions encountered.  <MET>150 mm</MET><ENG> 6 inch</ENG>
 wide tape is required for seam seals along lines of mechanical attachment of membrane.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.3   <SUB>Lap Splice Adhesive</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Lap splice adhesive is used for some membrane to membrane bond applications.<BRK/>
<BRK/>
Include bracketed options as applicable.<BRK/>
<BRK/>
Low VOC materials may be required in some geographic locations and on occupied 
buildings to minimize potential irritation to occupants.<BRK/>
<BRK/>
Include second and third brackets options at end of paragraph when lap splice 
adhesive is prohibited for field seams of roof membrane.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Low volatile organic compound (VOC)] synthetic rubber adhesive as supplied by roof membrane manufacturer and 
recommended by the manufacturer's printed data for forming watertight bond of EPDM sheet membrane materials to 
each other [in areas of membrane flashing].  [Do not use splice adhesive to form membrane seams in field of roof 
or at standard base flashing conditions.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.4   <SUB>Bonding Adhesive</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Bonding adhesive is used for adhering EPDM membrane to materials other 
than EPDM.<BRK/>
<BRK/>
Low VOC materials may be required in some geographic locations and on occupied 
buildings to minimize potential irritation to occupants.<BRK/>
<BRK/>
When Type III (fleece-backed) membrane is specified, include the first bracketed 
option as applicable, delete the second bracketed option, and write in a description 
of the adhesive required as the third bracketed option.  When hot asphalt is 
the specified adhesive, in Part 3, include parameters for heating of asphalt 
and application similar to those found in UFGS 07511.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Low volatile organic compound (VOC)] [synthetic rubber][_____] adhesive as supplied by roof membrane manufacturer 
and recommended by the manufacturer's printed data for bonding EPDM membrane materials to insulation, wood, metal, 
concrete or other substrate materials.  Do not use bonding adhesive to bond membrane materials to each other.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.5   <SUB>Lap Cleaner, Lap Sealant, and Edge Treatment</SUB></TTL><BRK/>
<BRK/>
<TXT>As supplied by the roof membrane manufacturer and recommended by the manufacturer's printed data.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.6   <SUB>Water Cutoff Mastic/Water Block</SUB></TTL><BRK/>
<BRK/>
<TXT>As supplied by the roof membrane manufacturer and recommended by the manufacturer's printed data.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.7   Membrane Flashings and <SUB>Flashing Accessories</SUB></TTL><BRK/>
<BRK/>
<TXT>Membrane flashing, including self-adhering membrane flashing, perimeter flashing, flashing around roof penetrations, 
and prefabricated pipe seals, must be minimum<MET> 1.1 mm</MET><ENG> 0.045 inch</ENG> minimum cured EPDM, as recommended by the roof 
membrane manufacturer or minimum<MET> 1.4 mm</MET><ENG> 0.055 inch</ENG> thick uncured EPDM sheet in compliance with <RID>ASTM D 4811</RID>, Type 
I.  Use cured EPDM membrane to the maximum extent recommended by the roof membrane manufacturer.  Limit uncured 
flashing material to reinforcing inside and outside corners and angle changes in plane of membrane, and to flash 
scuppers, pourable sealer pockets, and other formed penetrations or unusually shaped conditions as recommended 
by the roof membrane manufacturer where the use of cured material is impractical.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.7.1   <SUB>Flashing Tape</SUB></TTL><BRK/>
<BRK/>
<TXT>EPDM-backed synthetic rubber tape, minimum<MET> 150 mm</MET><ENG> 6 inch</ENG> wide as supplied by the roof membrane manufacturer and 
recommended by the manufacturer's printed data.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.1.8   Membrane <SUB>Fasteners and Plates</SUB></TTL><BRK/>
<BRK/>
<TXT>Coated, corrosion-resistant fasteners as recommended by the roof membrane manufacturer and meeting the requirements 
of <RID>FM 4470</RID> and <RID>FM P7825c</RID> for Class I roof deck construction and the wind uplift resistance specified.  As supplied 
and warranted for the substrate type(s) by EPDM sheet manufacturer and recommended by EPDM sheet manufacturer's 
printed data.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.8.1   Stress Plates for Fasteners</TTL><BRK/>
<BRK/>
<TXT>Flat corrosion-resistant round stress plates as recommended by the roof membrane manufacturer's printed instructions 
and meeting the requirements of <RID>FM 4470</RID>; not less than<MET> 50 mm</MET><ENG> 2 inch</ENG> in diameter.  Provide pre-formed discs to 
prevent dishing or cupping.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.8.2   Auxiliary Fasteners</TTL><BRK/>
<BRK/>
<TXT>Corrosion resistance screws, nails, or anchors suitable for intended attachment purpose and as recommended by 
the roof membrane manufacturer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.8.3   Powder-Driven Fasteners</TTL><BRK/>
<BRK/>
<TXT>Powder-driven fasteners may be used only when approved in writing.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.8.4   Metal Disks</TTL><BRK/>
<BRK/>
<TXT>Provide flat metal disks of minimum<MET> 25 mm</MET><ENG> 1 inch</ENG> in diameter.  Metal disks must be of nonferrous material compatible 
with the nails or fasteners.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>2.1.9   Ballast</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete these paragraphs unless loose-laid ballasted system is specified.  
Normally specify stone ballast for a ballasted system.  Specify paver ballast 
when:</NPR><BRK/>
<BRK/>
<NPR>a.  There is danger of aggregate being drawn into air intakes of jet aircraft.</NPR><BRK/>
<BRK/>
<NPR>b.  There is danger of wind-blown aggregate jeopardizing property and life safety.<BRK/>
<BRK/>
c.  In wind zones exceeding 160 km/h 100 mph, within 8 km 5 miles of coastline, 
within 457 m 1500 feet of open body of water, and on or adjacent to critical 
facilities such as hospitals.</NPR><BRK/>
<BRK/>
<NPR>d.  Heavy foot traffic over large areas of roof is expected.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT>[<TTL>2.1.9.1   Stone Ballast</TTL><BRK/>
<BRK/>
<TXT>Smooth, rounded, river-washed stone graded in accordance with <RID>ASTM D 448</RID>, sizes 1, 2, 24, 3, and 4, nominal<MET> 19 
mm to 38 mm</MET><ENG> 3/4 inch to 1-1/2</ENG> diameter, except as recommended otherwise by the roof membrane manufacturer and 
approved by the Contracting Officer.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.9.2   Ballast <SUB>Pavers</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify paver weight based on calculated wind load conditions and ANSI/RMA/SPRI RP-4.  <BRK/>
<BRK/>
Lightweight interlocking paver ballast may be used in lieu of heavier weight 
non-interlocking pavers in wind zones in excess of 160 km/h 100 mph, within 
8 km 5 miles of coastline or within 457 m 1500 feet of open body of water.  
Non-interlocking pavers should weight not less than 88 kg per square meter 18 
pounds per square foot.<BRK/>
<BRK/>
Elevated paver systems and pavers intended to support pedestrian traffic, such 
as plaza decks or observation decks, should be minimum 50 mm 2 inch thick, 600 
mm 24 inch square, and minimum 51,700 kPa 7500 psi compressive strength.<BRK/>
<BRK/>
Specify paver pedestrals for pavers without drainage channels.  Specify adjustable 
pedestals for systems required to be elevated to a level plane such as a plaza 
or observation deck.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide weather resistant, precast [interlocking] concrete roof pavers [with drainage channels on the underside], 
and as recommended by the roof membrane manufacturer.  Provide pavers of minimum<MET> 20,680 kPa</MET><ENG> 3000 psi</ENG><MET> 51,700 kPa</MET><ENG>
 7500 psi</ENG> compressive strength, weigh not less than<MET> 58 kg per square meter</MET><ENG> 12 pounds per square foot</ENG><MET> 88 kg per 
square meter</MET><ENG> 18 pounds per square foot</ENG> [_____], not less than<MET> 30 mm</MET><ENG> 1-1/4 inch</ENG><MET> 50 mm</MET><ENG> 2 inch</ENG> thick and nominal<MET>
 600 mm</MET><ENG> 24 inch</ENG> [_____] in length and width and without sharp edges and projections.  [Elevate pavers above the 
roof membrane surface with paver manufacturer's recommended [adjustable] pedestal system [to provide for level 
walking surface] as required by the roof membrane manufacturer.]</TXT><BRK/>
<BRK/>
]</SPT>]</SPT><SPT>[<TTL>2.1.10   <SUB>Protection Mat</SUB> / Slip Sheet</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify protection mat for application between roof membrane and ballast 
when ballasted systems are specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Minimum<MET> 154 gram per square meter</MET><ENG> 4.5 ounce per square yard</ENG><MET> 200 gram per square meter</MET><ENG> 6 ounce per square yard</ENG>
 ultraviolet resistant polypropylene, non-woven, needle punched fabric for use as protection mat under ballast 
system and as recommended by the roof membrane manufacturer.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.11   <SUB>Pre-Manufactured Accessories</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit, delete, and insert accessory materials requirements as required 
for the specific project and components to be installed.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Pre-manufactured accessories must be manufacturer's standard for intended purpose,[ comply with applicable specification 
section,] compatible with the membrane roof system and approved for use by the roof membrane manufacturer.</TXT><BRK/>
<BRK/>
<SPT>[<TTL>2.1.11.1   Pre-fabricated Curbs</TTL><BRK/>
<BRK/>
<TXT>Provide [_____] gauge [G90 galvanized][AZ55 galvalume][_____] curbs with minimum<MET> 100 mm</MET><ENG> 4 inch</ENG> flange for attachment 
to roof nailers.  Provide minimum height of<MET> 250 mm</MET><ENG> 10 inch</ENG> above the finished roof membrane surface.</TXT><BRK/>
<BRK/>
]</SPT>]</SPT><SPT>[<TTL>2.1.12   [Rubber Walkboards] [and] [Precast Concrete Paver Block Walkways]</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use pavers or rubber walkboards as walkways where the roof or areas of 
the roof are intended to bear foot traffic for maintenance or other purposes 
once per month or more frequently.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide [either of] the following:</TXT><BRK/>
<BRK/>
<SPT>[<TTL>2.1.12.1   Rubber Walkboards</TTL><BRK/>
<BRK/>
<TXT>Preformed reprocessed rubber, compatible with the EPDM sheet,<MET> 6 mm</MET><ENG> 1/4 inch</ENG> minimum thickness, and weighing not 
less than<MET> .68 kg per square meter</MET><ENG> 1-1/2 pounds per square foot</ENG>.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.12.2   Precast Concrete Paver Block</TTL><BRK/>
<BRK/>
<TXT>Precast concrete blocks,<MET> 450 mm by 450 mm</MET><ENG> 18 inch by 18 inch</ENG> <MET>600 mm by 600 mm</MET><ENG> 24 inch by 24 inch</ENG>, without sharp 
edges and projections, and weighing no more than<MET> 20 kg</MET><ENG> 45 pounds</ENG><MET> 36 kg</MET><ENG> 80 pounds</ENG> each.</TXT><BRK/>
<BRK/>
]</SPT>]</SPT><SPT><TTL>2.1.13   <SUB>Roof Insulation</SUB> Below EPDM Sheet</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If the roofing system contains insulation, coordinate with the appropriate 
insulation specification section.  The insulation specification should include 
materials and installation up to the substrate on which the roof membrane is applied.<BRK/>
<BRK/>
Do not fully adhere single ply membrane to perlite, polystyrene, or standard 
wood fiber insulation board.  High density wood fiber board is acceptable if 
approved by the roof membrane manufacturer for the wind resistance condition 
specified.</NPR><BRK/>
<BRK/>
<NPR>Coordinate insulation system attachment with the wind resistance requirements.  
In many instances, insulation system must be adhered or mechanically fastened 
to deck in corner and perimeter areas, if not throughout the field of the roof, 
when specifying a ballasted roof system.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Insulation system and facer material must be compatible with membrane application specified and as approved by 
the roof membrane manufacturer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.14   Wood Products</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate with Section <SRF>06 10 00</SRF> ROUGH CARPENTRY.  Some fire retardant 
treatment (FRT) chemicals may affect EPDM materials.  MSDS listing active ingredients 
for the FRT wood must be submitted to EPDM manufacturer prior to applying EPDM 
materials in contact with FRT wood.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Do not allow fire retardant treated materials be in contact with EPDM membrane or EPDM accessory products, unless 
approved by the membrane manufacturer and the Contracting Officer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.15   Membrane Liner</TTL><BRK/>
<BRK/>
<TXT>[Self-adhering ]EPDM membrane liner conforming to <RID>ASTM D 4637</RID>, or other waterproof membrane liner material as 
approved by the roof membrane manufacturer and the Contracting Officer.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2   FLASHING <SUB>CEMENT</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide a self-vulcanizing butyl compound flashing cement for splicing laps and for flashings workable at<MET> minus 
7 degrees C</MET><ENG> 20 degrees F</ENG>.  Obtain a recommendation for such flashing cement from the roofing membrane manufacturer.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   EXAMINATION</TTL><BRK/>
<BRK/>
<TXT>Ensure that the following conditions exist prior to application of the roofing materials:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  [Drains,] [curbs,] [control joints,] [expansion joints,] [perimeter walls,] [roof penetrating 
components,] [and] [equipment supports] are in place.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Surfaces are rigid, clean, dry, smooth, and free from cracks, holes, and sharp changes in 
elevation.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  The plane of the substrate does not vary more than<MET> 6 mm</MET><ENG> 1/4 inch</ENG> within an area<MET> 3 by 3 meters</MET><ENG>
 10 by 10 feet</ENG> when checked with a<MET> 3 meter</MET><ENG> 10 foot</ENG> straight edge placed anywhere on the substrate.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Substrate is sloped to provide positive drainage.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Walls and vertical surfaces are constructed to receive counterflashing, and will permit 
mechanical fastening of the base flashing materials.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.   Treated wood nailers are in place on non-nailable surfaces, to permit nailing of base flashing 
at minimum height of<MET> 200 mm</MET><ENG> 8 inch</ENG> above finished roofing surface.</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate with Section <SRF>06 10 00</SRF> ROUGH CARPENTRY to ensure that preservative 
treatment is specified for wood which will be in contact with roofing components.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">g.  Pressure-preservative treated wood nailers are fastened in place at eaves, gable ends, openings, 
and intersections with vertical surfaces for securing of membrane, edging strips, attachment 
flanges of sheet metal, and roof fixtures.  [Embedded nailers are flush with deck surfaces.]  
[Surface-applied nailers are the same thickness as the roof insulation.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  Avoid contact of EPDM materials with fire retardant treated wood, except as approved by 
the roof membrane manufacturer and Contracting Officer.</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Wood cants should also be used where there are non-wall supported flashings 
at wood blocking forming area dividers and expansion joints, and at wall and 
roof intersections where roof deck is not supported on wall.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">i.  Cants are securely fastened in place in the angles formed by walls and other vertical surfaces.  
The angle of the cant is 45 degrees and the height of the vertical leg is not less than<MET> 89 mm</MET><ENG>
 3-1/2 inch</ENG>.</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include venting provision for wet fill substrate materials like lightweight 
cellular concrete.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
[<ITM INDENT="-0.33">j.  Venting is provided in accordance with the following:</ITM><BRK/>
<BRK/>
<ITM>[(1)  Edge Venting:  Perimeter nailers are kerfed across the width of the nailers to permit 
escape of gaseous pressure at roof edges.]</ITM><BRK/>
<BRK/>
<ITM>[(2)  Underside Venting:  Vent openings are provided in steel form decking for cast-in-place 
concrete substrate.]</ITM><BRK/>
<BRK/>
<ITM>[(3)  Vapor pressure relief vents:  Holes equal to the outside diameter of vents are provided 
through the insulation where vents are required.  Space vents in accordance with membrane manufacturer's 
recommendations.]</ITM><BRK/>
<BRK/>
]<ITM INDENT="-0.33">[k.  Exposed nail heads in wood substrates are properly set.  Warped and split [boards] [sheets] 
have been replaced.  There are no cracks or end joints<MET> 6 mm</MET><ENG> 1/4 inch</ENG> in width or greater.  [Joints 
in plywood substrates are taped or otherwise sealed to prevent air leakage from the underside.]]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[l.  Insulation boards are installed smoothly and evenly, and are not broken, cracked, or curled.  
There are no gaps in insulation board joints exceeding<MET> 6 mm</MET><ENG> 1/4 inch</ENG> in width.  Insulation is 
being roofed over on the same day the insulation is installed.]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   <SUB>APPLICATION</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate application method with paragraphs "Description of Roof Membrane 
System" and appropriate subparagraph under "EPDM Sheet Roofing". </NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Apply entire EPDM sheet utilizing [fully adhered] [loose-laid ballasted] [mechanically fastened] [combined fully 
adhered and mechanically fastened] application method[s].  Apply roofing materials as specified herein unless 
approved otherwise by the Contracting Officer.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.2.1   Special Precautions</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Do not dilute coatings or sealants unless specifically recommended by the materials manufacturer's 
printed application instructions. Do not thin liquid materials with cleaners used for cleaning 
EPDM sheet.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Keep liquids in airtight containers, and keep containers closed except when removing materials.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Use liquid components, including adhesives, within their shelf life period.  Store adhesives 
at<MET> 15 to 27 degrees C</MET><ENG> 60 to 80 degrees F</ENG> prior to use.  Avoid excessive adhesive application 
and adhesive spills, as they can be destructive to some elastomeric sheets and insulations; 
follow adhesive manufacturer's printed application instructions.  Mix and use liquid components 
in accordance with label directions and manufacturer's printed instructions.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Provide clean, dry cloths or pads for applying membrane cleaners and cleaning of membrane </ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Do not use heat guns or open flame to expedite drying of adhesives or primers.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Require workmen and others who walk on the membrane to wear clean, soft-soled shoes to avoid 
damage to roofing materials.</ITM><BRK/>
<BRK/>
 <ITM INDENT="-0.33">g.  Do not use equipment with sharp edges which could puncture the EPDM sheet.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  Shut down air intakes and any related mechanical systems and seal open vents and air intakes 
when applying solvent-based materials in the area of the opening or intake.  Coordinate shutdowns 
with the Contracting Officer.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.2   EPDM Sheet Roofing</TTL><BRK/>
<BRK/>
<TXT>Provide a watertight roof membrane sheet free of contaminants and defects that might affect serviceability.  
Provide a uniform, straight, and flat edge.  Unroll EPDM sheet roofing in position without stretching membrane.  
Inspect for holes.  Remove sections of EPDM sheet roofing that are damaged. Allow sheets to relax minimum 30 
minutes before seaming.  Lap sheets as specified, to shed water, and as recommended by the roof membrane manufacturer's 
published installation instructions for the application required but not less than<MET> 75 mm</MET><ENG> 3 inch</ENG> in any case.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.3   <SUB>Application Method</SUB></TTL><BRK/>
<BRK/>
<SPT>[<TTL>3.2.3.1   Combined Fully Adhered and Mechanically Fastened Application</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete this paragraph unless a combined fully adhered and mechanically 
fastened application is specified.  Where this paragraph is included, include 
and edit the fully adhered and mechanically fastened membrane application paragraphs 
to remove redundancy of requirements.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Install combined fully adhered and mechanically fastened roof membrane system in the manner specified and including 
seaming, perimeter and infield fastening and half sheets.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.2.3.2   Fully Adhered Membrane Application</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete this paragraph unless a fully adhered or combined fully adhered 
and mechanically fastened application is specified.<BRK/>
<BRK/>
Delete the bracketed option in the fourth sentence and delete the fifth sentence 
when non-standard adhesives are specified such as sprayed foam or hot asphalt 
used with fleece-backed membrane.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Layout membrane and side lap adjoining sheets in accordance with membrane manufacturer's printed installation 
instructions.  Allow for sufficient membrane to form proper membrane terminations.  Remove dusting agents and 
dirt from membrane and substrate areas where bonding adhesives are to be applied.  Apply specified adhesive evenly 
and continuously to substrate [and underside of sheets] at rates recommended by the roof membrane manufacturer's 
printed application instructions.  When adhesive is spray applied, roll with a paint roller to ensure proper 
contact and coverage.  Do not apply bonding adhesive to surfaces of membrane in seam or lap areas. Allow adhesive 
to flash off or dry to consistency prescribed by manufacturer before adhering sheets to the substrate.  Roll 
each sheet into adhesive slowly and evenly to avoid wrinkles; broom or roll the membrane to remove air pockets 
and fishmouths and to ensure full, continuous bonding of sheet to substrate.  Form field lap splices or seams 
as specified.  Check all seams and ensure full lap seal.  Apply lap sealant to all adhesive formed seams and 
all cut edges of reinforced membrane materials.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.2.3.3   Mechanically Fastened Membrane Application</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete this paragraph unless a mechanically fastened or combined fully 
adhered and mechanically fastened application is specified.<BRK/>
<BRK/>
Membrane side lap depends on method of mechanical attachment, wind resistance 
testing of the specific system provided, and requirements of the membrane manufacturer.  
Generally, attachments must be positioned such that minimum 75 mm 3 inch seam 
width remains beyond the outer edge of the attachment plate or batten strip.  
Fastener and plate attachment typically requires 175 mm to 200 mm 7 to 8 inch 
membrane overlap.  Batten attachment typically requires 100 mm to 150 mm 4 to 
6 inch membrane overlap.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Layout membrane and lap adjoining sheets in accordance with membrane manufacturer's printed instructions such 
that a minimum<MET> 75 mm</MET><ENG> 3 inch</ENG> [_____] seam width is maintained and seam width is as required by tested assembly 
meeting specified wind resistance requirements.  Account for additional overlap required for placement of fasteners 
and plates or battens beyond the closed seam.  Allow for sufficient membrane to form proper membrane terminations.  
Ensure membrane is free of wrinkles and ridges in the installation.  Mechanically secure the membrane sheet with 
specified fasteners in the lap area.  Space fasteners as required to provide the wind uplift resistance specified 
and in accordance with submitted fastener patterns for the field, corner, and perimeter roof areas.  Set fasteners 
firm to plate or batten.  Form field lap splices or seams as specified.  Check all seams and ensure full lap 
seal.  Apply lap sealant to all adhesive formed seams and all cut edges of reinforced membrane materials.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.2.3.4   Ballasted Membrane Application</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete this paragraph unless a loose-laid ballasted application is specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Layout membrane and side lap adjoining sheets minimum<MET> 100 mm</MET><ENG> 4 inch</ENG> and according to membrane manufacturer's 
printed instructions.  Allow for sufficient membrane to form proper membrane terminations.  Ensure membrane is 
free of wrinkles and ridges in the installation.  Form field lap splices or seams as specified and of width required 
by the membrane manufacturer's installation instructions.  Check seams to ensure continuous seal before proceeding 
with further work.  Apply continuous lap sealant to all adhesive formed seams and all cut edges of reinforced 
membrane materials.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.2.4   <SUB>Tape Seams / Lap Splices</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Seam tape must be the primary seaming, or lap splice, technique.  Adhesive 
seaming in the field of the roof must only be specified with Government approval.  
Adhesive seaming of flashing in limited areas may be required where tapes are 
difficult to apply.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Field form seams, or lap splices, with seam tape in accordance with membrane manufacturer's printed instructions 
and as specified.  Clean and prime mating surfaces in the seam area.  After <SUB>primer</SUB> has dried or set in accordance 
with membrane manufacturer's instructions, apply seam tape to bottom membrane and roll with a<MET> 75 mm to 100 mm</MET><ENG>
 3 inch to 4 inch</ENG> wide smooth silicone or steel hand roller, or other manufacturer approved rolling device, to 
ensure full contact and adhesion of tape to bottom membrane.  Tape end laps must be minimum<MET> 25 mm</MET><ENG> 1 inch</ENG>.  Roll 
top membrane into position to check for proper overlap and alignment.  Remove release paper from top of seam 
tape and form seam splice.  Ensure top membrane contact with seam tape as release paper is removed.  Roll the 
closed seam with a smooth silicone or steel hand roller, rolling first across the width of the seam then along 
the entire length, being careful not to damage the membrane.  Apply minimum<MET> 225 mm</MET><ENG> 9 inch</ENG> long strip of membrane-backed 
flashing tape over T-intersections of roof membrane.  Roll tape to ensure full adhesion and seal over T-joint.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.2.5   <SUB>Adhesive Seams / Lap Splices</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include the bracketed option in the first sentence as the norm.  Government 
approval required for adhesive formed seams in the field of the roof.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Use only field-applied adhesive formed seams [in flashing areas] where approved by the membrane manufacturer 
and the Contracting Officer.  Do not use adhesive formed seams for field of roof membrane seaming[, except as 
approved by the membrane manufacturer and the Contracting Officer].  Thoroughly and completely clean mating surfaces 
of materials throughout the lap area.  Remove all dirt, dust, and contaminants and allow to dry.</TXT><BRK/>
<BRK/>
<TXT>Apply primer as recommended by the membrane manufacturer.  Apply splice adhesive with a<MET> 75 mm to 100 mm</MET><ENG> 3 inch 
to 4 inch</ENG> wide,<MET> 13 mm</MET><ENG> 1/2 inch</ENG> thick, solvent-resistant brush in a smooth, even coat with long brush strokes.  
Bleed out brush marks.  Do not apply adhesive in a circular motion.  Simultaneously apply adhesive to both mating 
surfaces in an approximate<MET> 0.63 mm to 0.75 mm</MET><ENG> 0.025 to 0.030 inch</ENG> wet film thickness, or other thickness as recommended 
by the roof membrane manufacturer's printed instructions.</TXT><BRK/>
<BRK/>
<TXT>Allow the splice adhesive to set-up in accordance with membrane manufacturer's printed instructions.  Perform 
manufacturer recommended field check to test for adhesive readiness prior to closing seam.  Apply a<MET> 3 mm to 6 
mm</MET><ENG> 1/8 inch to 1/4 inch</ENG> bead of in-seam sealant approximately<MET> 13 mm</MET><ENG> 1/2 inch</ENG> from the inside edge of the lower 
membrane sheet prior to closing the seam.  Ensure the in-seam sealant does not extend onto the splice adhesive.  
Maintain the full adhered seam width required.  Roll the top membrane onto the mating surface.  Roll the seam 
area with a<MET> 50 mm to 75 mm</MET><ENG> 2 inch to 3 inch</ENG> wide, smooth silcone or steel hand roller.  A minimum of 2 hours 
after joining sheets and when the lap edge is dry, clean the lap edge with membrane manufacturer's recommended 
cleaner and apply a<MET> 6mm to 9 mm</MET><ENG> 1/4 inch to 3/8 inch</ENG> bead of lap sealant centered on the seam edge.  With a feathering 
tool, immediately feather the lap sealant to completely cover the splice edge, leaving a mound of sealant over 
the seam edge.  Apply lap sealant to all adhesive formed seams.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.2.6   <SUB>Perimeter Attachment</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  All application methods of EPDM membranes require mechanical fastening 
of the membrane to wood nailers at the roof perimeters, at angular penetrations, 
or at circular penetrations, except roof drains greater than 18 inch in diameter.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Adhesive bond or mechanically secure roof membrane sheet at roof perimeter in a manner to comply with wind resistance 
requirements and in accordance with membrane manufacturer's printed application instructions.  When adhesively 
bonding a mechanically fastened system in perimeter areas, the perimeter boundary of the adhesive bond must be 
the same as the boundary required for additional perimeter mechanical fastening to meet wind resistance requirements.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.7   Securement at Base Tie-In Conditions</TTL><BRK/>
<BRK/>
<TXT>Mechanically fasten the roof membrane at penetrations, at base of curbs and walls, and at all locations where 
the membrane turns and angle greater than 4 degrees (1:12).  Space <SUB>fasteners</SUB> a maximum of<MET> 300 mm</MET><ENG> 12 inch</ENG> on center, 
except where more frequent attachment is required to meet specified wind resistance or where recommended by the 
roof membrane manufacturer.  Flash over fasteners with a fully adhered layer of material as recommended by the 
roof membrane manufacturer's printed data.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.3   <SUB>FLASHINGS</SUB></TTL><BRK/>
<BRK/>
<SPT><TTL>3.3.1   General</TTL><BRK/>
<BRK/>
<TXT>Provide flashings in the angles formed at walls and other vertical surfaces and where required to make the work 
watertight, except where metal flashings are indicated.</TXT><BRK/>
<BRK/>
<TXT>Provide a one-ply flashing membrane, as specified for the system used, and install immediately after the roofing 
membrane is placed and prior to finish coating where a finish coating is required.  Flashings must be stepped 
where vertical surfaces abut sloped roof surfaces.  Provide sheet metal reglet in which sheet metal cap flashings 
are installed of not more than<MET> 400 mm</MET><ENG> 16 inch</ENG> nor less than<MET> 200 mm</MET><ENG> 8 inch</ENG> above the roofing surfaces. Exposed 
joints and end laps of flashing membrane must be made and sealed in the manner required for roofing membrane.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.2   <SUB>Membrane Flashing</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate flashing requirements with Section <SRF>07 60 00.00 40</SRF> FLASHING 
AND SHEET METAL and details.  Ensure Section <SRF>07 60 00.00 40</SRF> FLASHING AND SHEET 
METAL is properly edited for application to EPDM roofing systems and for inclusion 
of flashing conditions of the project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Install flashing and flashing accessories as the roof membrane is installed.  Apply flashing to cleaned surfaces 
and as recommended by the roof membrane manufacturer and as specified.  Utilize cured EPDM membrane flashing 
and prefabricated accessory flashings to the maximum extent recommended by the roof membrane manufacturer.  Limit 
uncured flashing material to reinforcing inside and outside corners and angle changes in plane of membrane, and 
to flashing scuppers, pourable sealer pockets, and other formed penetrations or unusually shaped conditions as 
recommended by the roof membrane manufacturer where the use of cured material is impractical.  Extend base flashing 
not less than<MET> 200 mm</MET><ENG> 8 inch</ENG> above roofing surface and as necessary to provide for seaming overlap on roof membrane 
as recommended by the roof membrane manufacturer.</TXT><BRK/>
<BRK/>
<TXT>Seal flashing membrane for a minimum of<MET> 75 mm</MET><ENG> 3 inch</ENG> on each side of fastening device used to anchor roof membrane 
to nailers.  Completely adhere flashing sheets in place.  Seam flashing membrane in the same manner as roof membrane, 
except as otherwise recommended by the membrane manufacturer's printed instructions and approved by the Contracting 
Officer.  Reinforce all corners and angle transitions by applying uncured membrane to the area in accordance 
with roof membrane manufacturer recommendations.  Mechanically fasten top edge of base flashing with manufacturer 
recommended termination bar fastened at maximum<MET> 300 mm</MET><ENG> 12 inch</ENG> on center.  Install sheet metal flashing over 
the termination bar in the completed work.  Mechanically fasten top edge of base flashing for all other terminations 
in a manner recommended by the roof membrane manufacturer.  Apply membrane liner over top of exposed nailers 
and blocking and to overlap top edge of base flashing installation at curbs, parapet walls, expansion joints 
and as otherwise indicated to serve as waterproof lining under sheet metal flashing components.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.3.3   Flashing at Roof Drain</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include this paragraph when roof drains are indicated.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide a tapered insulation sump into the drain bowl area.  Do not exceed tapered slope of<MET> (4:12)</MET><ENG> 18 degrees</ENG>
 for unreinforced membrane and<MET> (1:12)</MET><ENG> 5 degrees</ENG> for reinforced membrane.  Provide tapered insulation with surface 
suitable for adhering membrane in the drain sump area.  Avoid field seams running through or within<MET> 600 mm</MET><ENG> 24 
inch</ENG> of roof drain, or as otherwise recommended by the roof membrane manufacturer.  Adhere the membrane to the 
tapered in the drain sump area.  Apply water block mastic and extend membrane sheets over edge of drain bowl 
opening at the roof drain deck flange in accordance with membrane manufacturer's printed application instructions.  
Insure membrane free of wrinkles and folds in the drain area.  Securely clamp membrane in the flashing clamping 
ring.  Ensure membrane is cut to within<MET> 20 mm</MET><ENG> 3/4 inch</ENG> of inside rim of clamping ring to maintain drainage capacity.  
Do not cut back to bolt holes.  Retrofit roof drains must conform to <RID>ANSI/SPRI RD-1</RID>.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT>[<TTL>3.4   PRE-FABRICATED CURBS</TTL><BRK/>
<BRK/>
<TXT>Securely anchor prefabricated curbs to nailer or other base substrate and flashed with EPDM membrane flashing 
materials.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.4.1   Set-On Accessories</TTL><BRK/>
<BRK/>
<TXT>Where pipe or conduit blocking, supports and similar roof accessories, or isolated paver block, are set on the 
membrane, adhere reinforced membrane or walkpad material, as recommended by the roof membrane manufacturer, to 
bottom of accessories prior to setting on roofing membrane.  Specific method of installing set-on accessories 
must permit normal movement due to expansion, contraction, vibration, and similar occurrences without damaging 
roofing membrane.  Do not mechanically secure set-on accessories through roofing membrane into roof deck substrate.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4.2   Lightning Protection</TTL><BRK/>
<BRK/>
<TXT>Flash lightning protection system components or attach to the roof membrane in a manner acceptable to the roof 
membrane manufacturer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4.3   Roof Walkpads</TTL><BRK/>
<BRK/>
<TXT>Install walkpads at roof access points and where otherwise indicated for traffic areas and for access to mechanical 
equipment, in accordance with the roof membrane manufacturer's printed instructions.  Provide minimum<MET> 150 mm</MET><ENG> 
6 inch</ENG> separation between adjacent walkpads to accommodate drainage.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4.4   Elevated Metal [Walkways] [and] [Platforms]</TTL><BRK/>
<BRK/>
<TXT>Provide for protection of roof membrane by placing reinforced membrane or walkpad material, or other material 
approved by the Contracting Officer, at all surface bearing support locations.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.4.5   Isolated Paver Blocks</TTL><BRK/>
<BRK/>
<TXT>Install paver blocks where indicated and as necessary to support surface bearing items traversing the roof area.  
Set paver block on a layer of reinforced membrane or walkpad applied over the completed roof membrane.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.4.6   [Stone][Paver] <SUB>Ballast</SUB> [Paver System]</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Indicate the appropriate ballast type.  Indicate ballast weight required 
based on wind loading conditions.<BRK/>
<BRK/>
In some instances paver ballast may be used in perimeter and corner areas in 
combination with stone ballast in the field of the roof.  If so, include the 
[Paver] option in item "a".<BRK/>
<BRK/>
Where elevated paver system is required, refer to as "Paver System" in the paragraph 
title.  Delete bracketed options related to protection mat installation, stone 
ballast, and coverage rates.  The paver type and weight must be as specified 
in Part 2.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Complete all membrane and membrane flashing work, including inspection and repair of all membrane and seams in 
the area of [ballast][paver] application prior to applying [ballast][paver] system.  [Install protection mat 
over roof membrane in accordance with roof membrane manufacturer's recommendations.  Provide minimum<MET> 75 mm</MET><ENG> 3 
inch</ENG> side laps and<MET> 150 mm</MET><ENG> 6 inch</ENG> end laps.  Turn mat up vertical surfaces to extend<MET> 50 mm</MET><ENG> 2 inch</ENG> above ballast.  
Immediately after placement of protection mat,][Install and level pedestal system in accordance with manufacturer's 
requirements and] apply [stone][and][paver] [ballast][system.] [at the following coverage rates:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  [Pavers:  ][_____] pounds per square foot for perimeter and corner areas of roof.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  [_____] pounds per square foot for field of roof.</ITM><BRK/>
<BRK/>
<TXT>In no case apply ballast at a coverage rate less than 10 pounds per square foot or more than [_____] pounds per 
square foot.]</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.4.7   Correction of Deficiencies</TTL><BRK/>
<BRK/>
<TXT>Where any form of deficiency is found, additional measures must be taken as deemed necessary by the Contracting 
Officer to determine the extent of the deficiency and corrective actions must be as directed by the Contracting 
Officer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4.8   Clean Up</TTL><BRK/>
<BRK/>
<TXT>Remove debris, scraps, containers and other rubbish and trash resulting from installation of the roofing system 
from job site each day.</TXT><BRK/>
<BRK/></SPT>
]</SPT><SPT><TTL>3.5   PROTECTION OF APPLIED ROOFING</TTL><BRK/>
<BRK/>
<TXT>At the end of the day's work and when precipitation is imminent, protect applied membrane roofing system from 
water intrusion.</TXT><BRK/>
<BRK/>
<SPT>[<TTL>3.5.1   Water Cutoffs</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include this paragraph when roof insulation is a substrate for the EPDM 
sheet roofing.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Straighten insulation line using loose-laid cut insulation sheets and seal the terminated edge of the roof membrane 
system in an effective manner.  [Seal off flutes in metal decking along the cutoff edge.]  Remove the water cut-offs 
to expose the insulation when resuming work, and remove the insulation sheets used for fill-in.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.5.2   Temporary Flashing for Permanent Roofing</TTL><BRK/>
<BRK/>
<TXT>Provide temporary flashing at drains, curbs, walls and other penetrations and terminations of roofing sheets 
until permanent flashings can be applied.  Remove temporary flashing before applying permanent flashing.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.3   Temporary Walkways, Runways, and Platforms</TTL><BRK/>
<BRK/>
<TXT>Do not permit storing, walking, wheeling, and trucking directly on applied roofing materials.  Provide temporary 
walkways, runways, and platforms of smooth clean boards, mats or planks as necessary to avoid damage to applied 
roofing materials, and to distribute weight to conform to live load limits of roof construction.  Use rubber-tired 
equipment for roofing work.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.6   FIELD QUALITY CONTROL</TTL><BRK/>
<BRK/>
<SPT><TTL>3.6.1   Construction Monitoring</TTL><BRK/>
<BRK/>
<TXT>During progress of the roof work, Contractor must make visual inspections as necessary to ensure compliance with 
specified parameters. Additionally, verify the following:</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Equipment is in working order.  Metering devices are accurate.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Materials are not installed in adverse weather conditions.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Substrates are in acceptable condition, in compliance with specification, prior to application of 
subsequent materials.</LST><BRK/>
<BRK/>
<ITM>Nailers and blocking are provided where and as needed.</ITM><BRK/>
<BRK/>
<ITM>Insulation substrate is smooth, properly secured to its substrate, and without excessive gaps 
prior to membrane application.</ITM><BRK/>
<BRK/>
<ITM>The proper number, type, and spacing of fasteners are installed.</ITM><BRK/>
<BRK/>
<ITM>Materials comply with the specified requirements.</ITM><BRK/>
<BRK/>
<ITM>All materials are properly stored, handled and protected from moisture or other damages.  Liquid 
components are properly mixed prior to application.</ITM><BRK/>
<BRK/>
<ITM>Membrane is allowed to relax prior to seaming.  Adhesives are applied uniformly to both mating 
surfaces and checked for proper set prior to bonding mating materials.  Mechanical attachments 
are spaced as required[, including additional fastening of membrane in corner and perimeter 
areas as required.]</ITM><BRK/>
<BRK/>
<ITM>Membrane is properly overlapped.</ITM><BRK/>
<BRK/>
<ITM>Membrane seaming is as specified and seams are hand rolled to ensure full adhesion and bond 
width.  [In-seam sealant is applied when adhesive seams are used in the field of the roof.]  
All seams are checked at the end of each work day.</ITM><BRK/>
<BRK/>
<ITM>Applied membrane is inspected and repaired as necessary prior to ballast installation.</ITM><BRK/>
<BRK/>
<ITM>[Membrane is fully adhered without ridges, wrinkles, kinks, fishmouths.</ITM>]<BRK/>
<BRK/>
<ITM>Installer adheres to specified and detailed application parameters.</ITM><BRK/>
<BRK/>
<ITM>Associated flashings and sheet metal are installed in a timely manner in accord with the specified 
requirements.</ITM><BRK/>
<BRK/>
<ITM>Ballast is within the specified weight range.</ITM><BRK/>
<BRK/>
<ITM>Temporary protection measures are in place at the end of each work shift.</ITM><BRK/>
<BRK/></SPT>
[<SPT><TTL>3.6.2   Manufacturer's Inspection</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include this paragraph when manufacturer's inspection of work is required.  
Select desired frequency of manufacturer inspection and coordinate with text 
of optional 2<SPS>nd</SPS> and 3<SPS>rd</SPS> bracketed sentences.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Manufacturer's technical representative must visit the site a minimum of three [_____] times [once per week] 
during the installation for purposes of reviewing materials installation practices and adequacy of work in place.  
[Inspections must occur during the first 20 squares of membrane installation, at mid-point of the installation, 
and at substantial completion, at a minimum.  Do not exceed additional inspections one for each 100 squares of 
total roof area with the exception that follow-up inspections of previously noted deficiencies or application 
errors must be performed as requested by the Contracting Officer.]  After each inspection,  submit a report signed 
by the manufacturer's technical representative to the Contracting Officer within 3 working days.  Note overall 
quality of work, deficiencies and any other concerns, and recommended corrective action.</TXT><BRK/>
<BRK/></SPT>
][<SPT><TTL>3.6.3   Roof Drain Test</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include this paragraph when roof drains are required.  Consult with structural 
engineer to verify loading capability of roof structural system.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>After completing roofing but prior to Government acceptance, perform the following test for watertightness.  <TST>
Plug roof drains and fill with water to edge of drain sump for 8 hours.  Retrofit roof drains must conform to <RID>
ANSI/SPRI RD-1</RID>.  Do not plug secondary overflow drains at the same time as adjacent primary drain.  To ensure 
some drainage from roof, do not test all drains at same time.  Measure water at beginning and end of the test 
period.  When precipitation occurs during test period, repeat test.  When water level falls, remove water, thoroughly 
dry, and inspect installation; repair or replace roofing at drain to provide for a properly installed watertight 
flashing seal.  Repeat test until there is no water leakage.</TST></TXT><BRK/>
<BRK/></SPT>
]</SPT><SPT><TTL>3.7   <SUB>INSTRUCTIONS TO GOVERNMENT PERSONNEL</SUB></TTL><BRK/>
<BRK/>
<TXT>Furnish written and verbal instructions on proper maintenance procedures to designated Government personnel.  
Furnish instructions by a competent representative of the roof membrane manufacturer and include a minimum of 
4 hours on maintenance and emergency repair of the membrane.  Include a demonstration of membrane repair, and 
give sources of required special tools.  Furnish information on safety requirements during maintenance and emergency 
repair operations.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8   <SUB>INFORMATION CARD</SUB></TTL><BRK/>
<BRK/>
<TXT>For each roof, furnish a typewritten minimum<MET> 215 mm by 275 mm</MET><ENG> 8-1/2 inch by 11 inch </ENG>information card for facility 
records and a card laminated in plastic and framed for interior display at roof access point, or a photoengraved<MET>
 1 mm</MET><ENG> 0.032</ENG> inch thick aluminum card for exterior display.  Identify facility name and number; location; contract 
number; approximate roof area; detailed roof system description, including deck type, membrane, number of plies, 
method of application, manufacturer, insulation and cover board system and thickness; presence of tapered insulation 
for primary drainage, presence of vapor retarder; date of completion; installing contractor identification and 
contact information; membrane manufacturer warranty expiration, warranty reference number, and contact information.  
Install card at roof top or access location as directed by the Contracting Officer and provide a paper copy to 
the Contracting Officer.</TXT><BRK/>
<BRK/></SPT>
</PRT>    <END/><BRK/></SEC>