<SCN>SECTION 08 33 13</SCN><BRK/>
<BRK/>
<STL>METAL ROLLING COUNTER DOORS</STL><BRK/>
<DTE>07/07</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>metal rolling counter 
doors</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<BRK/>
<NPR>This guide specification includes tailoring options for rolling counter door 
(non-rated), fire-rated rolling counter door, integral frame rolling counter 
door, and automatic closing device.  Selection or deselection of a tailoring 
option will include or exclude that option in the section, but editing the resulting 
section to fit the project is still required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
<BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
<BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 240/A 240M</RID><RTL>(2008) Standard Specification for Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications</RTL><BRK/><BRK/><RID>ASTM A 653/A 653M</RID><RTL>(2008) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process</RTL><BRK/><BRK/><RID>ASTM B 209</RID><RTL>(2007) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate</RTL><BRK/><BRK/><RID>ASTM B 209M</RID><RTL>(2007) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate (Metric)</RTL><BRK/><BRK/><RID>ASTM B 221</RID><RTL>(2008) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes</RTL><BRK/><BRK/><RID>ASTM B 221M</RID><RTL>(2007) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric)</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 80</RID><RTL>(2006; Errata 2008) Standard for Fire Doors and Other Opening Protectives</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy, Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are for [Contractor Quality Control approval.][information only.  When used, a designation following the "G" 
designation identifies the office that will review the submittal for the Government.]  Submit the followingin 
accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Detail Drawings</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Detail drawings as specified.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Rolling Counter Doors</SUB></ITM><BRK/>
<BRK/>
<ITM>  Manufacturer's descriptive data and catalog cuts.</ITM><BRK/>
<BRK/>
<ITM><SUB>Installation</SUB></ITM><BRK/>
<ITM><SUB>Cleaning</SUB></ITM><BRK/>
<BRK/>
<ITM>  Manufacturer's preprinted installation and cleaning instructions.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Rolling Counter Door (Non-Rated)</SUB></ITM><BRK/>
<ITM><SUB>Fire-Rated Rolling Counter Door</SUB></ITM><BRK/>
<BRK/>
<ITM>  [Six] [_____] complete copies of Data Package 2 for Rolling Counter Doors (Non-Rated) and 
Fire-Rated Rolling Counter Doors in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE 
DATA.  Provide a list of the parts recommended by the manufacturer to be replaced after [1 year] 
[and] [3 years] of service.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   GENERAL REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Furnish <SUB>rolling counter doors</SUB> of the type, size, and design indicated on the drawings.  Provide the standard 
product of a manufacturer regularly engaged in the production of rolling counter doors.  Provide each door with 
a permanent label showing the manufacturer's name and address and the model number of the door.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   <SUB>DETAIL DRAWINGS</SUB></TTL><BRK/>
<BRK/>
<TXT>Submit drawings showing elevations of each door type, details of anchorage, details of construction, location 
and description of hardware, shape and thickness of materials, details of joints and connections, and details 
of guides and fittings.  Include a schedule showing the location of each counter door with the drawings.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5   DELIVERY AND STORAGE</TTL><BRK/>
<BRK/>
<TXT>Deliver rolling counter doors to the jobsite wrapped in a protective covering with the brands and names clearly 
marked thereon.  Store rolling counter doors in accordance with the manufacturer's instructions in a dry location 
that is adequately ventilated and free from dust, water, or other contaminants, and in a manner that permits 
easy access for inspecting and handling.  Handle doors carefully to prevent damage.  Replace damaged items that 
cannot be restored to like-new condition.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6   WARRANTY</TTL><BRK/>
<BRK/>
<TXT>Provide manufacturer's standard performance guarantees or warranties that extend beyond a 1 year period.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  These paragraphs will be edited to retain only the materials and finishes 
for the type of rolling counter door required for the project.  If finishes 
other than those specified are required, the specification will be revised accordingly.  
Generally G40 minimum galvanized coating with prime coat is sufficient for interior 
applications on most projects.  Aluminum or stainless steel should be selected 
for esthetics.  Aluminum should not be chosen for high use applications.  Fire 
rated doors should be constructed only of steel or stainless steel.<BRK/>
<BRK/>
Fire-rated doors are not normally available in sizes as large as non-rated doors.  
Coordinate with manufacturers on available heights and widths.</NPR><BRK/>
<BRK/>
<NPR>Add requirements for weatherstripping and weather-tight installation for rolling 
counter doors located on exterior walls.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.1   BASIC COMPONENTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1.1   Curtain</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Standard non-rated rolling counter doors may be constructed of aluminum, 
steel or stainless steel.  Fire rated counter doors must be constructed of steel.  
Edit the specification for the type or types of rolling doors required for the 
project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Fabricate the curtain of [extruded aluminum slats conforming to<MET> <RID>ASTM B 221M</RID></MET><ENG> <RID>ASTM B 221</RID></ENG>, Alloy 6063] [<MET>0.759 mm</MET><ENG>
 22 gauge</ENG> Type 304 stainless steel slats conforming to <RID>ASTM A 240/A 240M</RID>, Type 304 or Type 430] [or] [<MET>0.759 mm</MET><ENG>
 22 gauge</ENG> galvanized steel slats conforming to <RID>ASTM A 653/A 653M</RID>, Coating Designation [G60] [G90]].  Provide 
thickness of slat material as required by width of opening [or as required by specified fire-rating.]  Use slats 
approximately<MET> 32 to 38 mm</MET><ENG> 1-1/4 to 1-1/2 inch</ENG> wide with a depth of crown of<MET> 13 mm</MET><ENG> 1/2 inch</ENG>.  Fit alternate slats 
with end locks to maintain curtain alignment.  Provide bottom of curtain with angle or tubular bar reinforcement 
matching the curtain, and fitted with a resilient bottom seal.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   Jamb Guides</TTL><BRK/>
<BRK/>
<TXT>Furnish guides of [<MET>3 mm</MET><ENG> 1/8 inch</ENG> minimum thickness extruded aluminum conforming to<MET> <RID>ASTM B 221M</RID></MET><ENG> <RID>ASTM B 221</RID></ENG>, Alloy 
6063, and fitted with neoprene silencers or replaceable heavy nap striping to eliminate noise and dust infiltration.] 
[<MET>2.278 mm</MET><ENG> 13 gauge</ENG> minimum thickness stainless steel conforming to <RID>ASTM A 240/A 240M</RID>, Type 304 or Type 430.] 
[<MET>2.278 mm</MET><ENG> 13 gauge</ENG> minimum thickness galvanized steel angles conforming to <RID>ASTM A 653/A 653M</RID>, Coating Designation 
[G60] [G90].]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.3   Counterbalance Shaft Assembly</TTL><BRK/>
<BRK/>
<TXT>Furnish the curtain coiled around a steel tube of sufficient thickness and diameter to prevent deflection exceeding<MET>
 2.5 mm per meter</MET><ENG> 0.03 inch per foot</ENG>.  Provide a barrel containing oil tempered helical steel torsion springs 
capable of sufficient torque to counterbalance the weight of the curtain.  Calculate the springs to provide a 
minimum of [7,500] [_____] operating cycles (one complete cycle of door operation will begin with the door in 
the closed position, move to the full open position and return to the closed position).</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.4   Brackets</TTL><BRK/>
<BRK/>
<TXT>Furnish brackets of a minimum<MET> 2.657 mm</MET><ENG> 12 gauge</ENG> thickness steel if flat plate, or<MET> 1.519 mm</MET><ENG> 16 gauge</ENG> thickness 
if there are a minimum of 3 returns of<MET> 19 mm</MET><ENG> 3/4 inch</ENG> width.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.5   Hood</TTL><BRK/>
<BRK/>
<TXT>Provide a hood of [<MET>1.02 mm</MET><ENG> 0.040 inch</ENG> minimum thickness aluminum sheet conforming to<MET> <RID>ASTM B 209M</RID></MET><ENG> <RID>ASTM B 209</RID></ENG>, 
Alloy 5005.] [<MET>0.607 mm</MET><ENG> 24 gauge</ENG> stainless steel conforming to <RID>ASTM A 240/A 240M</RID>, Type 304 or Type 430.] [<MET>0.607 
mm</MET><ENG> 24 gauge</ENG> galvanized steel conforming to <RID>ASTM A 653/A 653M</RID>, Coating Designation [G60] [G90].]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.6   Locks</TTL><BRK/>
<BRK/>
<TXT>Lock the curtain at [each side of the bottom bar by an integral slide bolt suitable for padlocks by others] [both 
sides of bottom bar by a chrome-plated cylinder lock keyed into the building keying system].  Locate lock on 
the [_____] room side of the counter door.  [Provide [pad locks] [and] [keying] [conforming to Section 
<SRF>08 71 00</SRF> DOOR HARDWARE] [as shown].]</TXT><BRK/>
<BRK/></SPT>
</SPT><TAI OPT="ROLLING COUNTER DOOR (NON-RATED)"><SPT><TTL>2.2   <SUB>ROLLING COUNTER DOOR (NON-RATED)</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Standard non-rated rolling counter doors may be constructed of aluminum, 
steel or stainless steel.  Operation may be manual push-up, manual crank with 
removable handle, or motor operation.  Edit the specification for the type or 
types of rolling doors required for the project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Construct rolling counter doors, curtains, guides and hood components of [aluminum] [stainless steel] [galvanized 
steel] conforming to the requirements specified herein.</TXT><BRK/>
<BRK/></SPT>
</TAI><TAI OPT="FIRE-RATED ROLLING COUNTER DOOR"><SPT><TTL>2.3   <SUB>FIRE-RATED ROLLING COUNTER DOOR</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Fire-rated rolling counter doors are available with Class A (3 hr), Class 
B (1-1/2 hr), C (3/4 hr), or Class D (1-1/2 hr) label.  If only one class of 
rolling counter door is required for the project, the label requirement may 
be specified.  If the project requires more than one class of rolling counter 
door, the label requirements should be shown on the drawings.  If fire-rated 
rolling counter doors are not required, all references to fire-rating and label 
requirements will be deleted.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Furnish fire-rated rolling counter doors, [[Class A (3 hr.)] [Class B (1-1/2 hr.)] [Class C (3/4 hr.)] [Class 
D (1-1/2 hr.)] rated] [as shown] and conforming to the requirements specified and to <RID>NFPA 80</RID> for the class indicated.  
Provide labels of a recognized testing agency for the doors, indicating the applicable fire resistance rating.  
The construction details necessary for labeled rolling counter doors will take precedence over details indicated 
or specified herein.  Furnish door curtains, guides and hood of [stainless steel] [galvanized steel].  Provide 
fire-rated rolling counter doors complete with hardware, accessories, and automatic closing device.  Provide 
rolling counter doors, in exit corridor walls, with perimeter smoke and draft control gasketing.</TXT><BRK/>
<BRK/></SPT>
</TAI><TAI OPT="INTEGRAL FRAME ROLLING COUNTER DOOR"><SPT><TTL>2.4   INTEGRAL FRAME ROLLING COUNTER DOOR (RATED OR NON-RATED)</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Requirements for counter and frame construction will be shown on the 
drawings.  Integral frame units may be used where appropriate; however, the 
specification must be edited to incorporate the additional requirements for 
frame and counter.  Fire rated integral frame units are available with Class 
A (3 hr), Class B (1-1/2 hr), or Class C (3/4 hr), or Class D (1-1/2 hr) label.  
Integral frame doors are not available as split frame.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Furnish integral frame rolling counter door of [[aluminum] [stainless steel] [galvanized steel].] [[[Class A 
(3 hr.)] [Class B (1-1/2 hr.)] [Class C (3/4 hr.)] [Class D (1-1/2 hr.)]] [as shown], [stainless steel] [galvanized 
steel].]  Conform fire-rated doors to the requirements of <RID>NFPA 80</RID> for the Class indicated and bearing the labels 
of a recognized testing agency indicating the applicable fire resistance rating.  Form jambs to create guides 
for the curtain.  Provide head and jambs of<MET> 1.519 mm</MET><ENG> 16 gauge</ENG> thickness.  Provide counter of<MET> 1.894 mm</MET><ENG> 14 gauge</ENG>
 thickness.  Provide rolling counter doors, in exit corridor walls, with perimeter smoke and draft control gasketing.</TXT><BRK/>
<BRK/></SPT>
</TAI><SPT><TTL>2.5   OPERATION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Rolling counter doors over 3048 mm (10 feet) wide, or where the interior 
counter is over 380 mm (15 inches) deep, may use manual crank operation or electric 
operation.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.5.1   Manual Operation</TTL><BRK/>
<BRK/>
<TXT>Provide curtain operated by means of [manual push-up with lift handles or continuous full width lift bar] [manual 
crank with removable handle].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.2   Power Operation</TTL><BRK/>
<BRK/>
<TXT>Furnish a high-starting torque, reversible type motor of sufficient power and torque output to move the door 
in either direction from any position at the required speed.  Provide power operator with an emergency push-up 
operation, limit switch, three-button type control marked "OPEN", "CLOSE", and "STOP".  Provide control voltage 
of [24 vac] [120 vac].  Provide conduit and wiring necessary for proper operation in accordance with Section 
<SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM.</TXT><BRK/>
<BRK/></SPT>
</SPT><TAI OPT="AUTOMATIC CLOSING DEVICE"><SPT><TTL>2.6   AUTOMATIC CLOSING DEVICE</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Activation of the automatic closing device on fire rated counter doors 
shall be by the building's fire alarm system or smoke/heat detector system when 
counter doors are located in smoke barriers and fire barriers, or where life 
safety would be endangered by fire and smoke if the doors were left open.  Fusible 
link devices will only be used in those areas where protection of property from 
fire is the only consideration.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Equip fire-rated counter doors with an automatic closing device which operates upon [the fusing of a<MET> 74 degrees 
C</MET><ENG> 165 degree F</ENG> fusible link] [activation of the building's [fire alarm system] [smoke alarm system] [heat detector 
system].  Furnish fire and smoke doors that easily reset by the facility user after they have been released by 
the detection system.  Resetting the door must not require the use of special tools.]</TXT><BRK/>
<BRK/></SPT>
</TAI><SPT><TTL>2.7   FINISH</TTL><BRK/>
<BRK/>
<TXT>Exposed parts of the counter door, including the curtain, bottom rail, guides, and hood must be of uniform finish 
and appearance.  Furnish [aluminum with a clear anodized finish.] [stainless steel with a No. 4 finish.] [steel 
galvanized coating with a [prime coat] [and] [a baked-on or powder-coated Factory top coat finish].]  Give all 
other steel parts a shop coat of primer paint standard with the manufacturer.  Provide a factory coated color 
[in accordance with Section <SRF>09 06 90</SRF> COLOR SCHEDULE] [_____].</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   <SUB>INSTALLATION</SUB></TTL><BRK/>
<BRK/>
<TXT>Install doors in accordance with approved detail drawings and manufacturer's instructions.  Accurately locate 
anchors and inserts for guides, brackets, hardware, and other accessories.  Upon completion, doors shall be free 
from warp, twist, or distortion.  Lubricate, properly adjust, and demonstrate doors to operate freely.  <TAI OPT="FIRE-RATED ROLLING COUNTER DOOR">Conform 
fire-door installation with <RID>NFPA 80</RID> for the class indicated and the manufacturer's instructions.</TAI></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   FIELD FINISHING</TTL><BRK/>
<BRK/>
<TXT>Doors to receive field finishing shall be factory primed, as required, and then finished in accordance with Section 
<SRF>09 90 00</SRF> PAINTS AND COATINGS.  Provide color [in accordance with Section <SRF>09 06 90</SRF> COLOR SCHEDULE] [_____].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3   <SUB>CLEANING</SUB></TTL><BRK/>
<BRK/>
<TXT>Clean aluminum and stainless steel doors in accordance with manufacturer's approved instructions.</TXT><BRK/>
<BRK/></SPT>
<TAI OPT="AUTOMATIC CLOSING DEVICE"><SPT><TTL>3.4   TESTS</TTL><BRK/>
<BRK/>
<TXT>Drop-test the fire doors in accordance with <RID>NFPA 80</RID> to show proper operation and full automatic closure and reset 
in accordance with the manufacturer's instructions.  Provide a written record of initial test to the Contracting 
Officer.</TXT><BRK/>
<BRK/></SPT>