<SCN>SECTION 11 44 00</SCN><BRK/>
<BRK/>
<STL>FOOD COOKING EQUIPMENT</STL><BRK/>
<DTE>01/08</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>commercial cooking 
equipment</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.<BRK/>
<BRK/>
This guide specification includes tailoring options for NAVFAC and USACE.  Selection 
or deselection of a tailoring option will include or exclude that option in 
the section, but editing the resulting section to fit the project is still required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification includes baking ovens, broilers, cooking ovens, 
exhaust hoods (and related fire suppression and grease extraction equipment, 
fryers, griddles, grills, holding ovens, kettles, microwave ovens, ranges, rotisseries, 
steamers, steam kettles, etc.</NPR><BRK/>
<BRK/>
<NPR>On the drawings, show:</NPR><BRK/>
<BRK/>
<NPR>1.  A 1:50 (1/4 inch) scale floor plan with layout of all food service equipment<TAI OPT="NAVFAC">
 and Naval Equipment Symbols</TAI>.</NPR><BRK/>
<BRK/>
<NPR>2.  Food Service Equipment Schedule laid out in accordance with <TAI OPT="NAVFAC">NAVFSSO</TAI><TAI OPT="USACE">current 
US Army Quartermaster Center and School equipment schedule</TAI> specified design 
requirements, including Energy Star qualified model list.</NPR><BRK/>
<BRK/>
<NPR>3.  Floor, wall, and ceiling penetrations.</NPR><BRK/>
<BRK/>
<NPR>4.  Raised bases, retainer curbs, or depressions.</NPR><BRK/>
<BRK/>
<NPR>5.  Recessed, grated floor drains required for equipment.</NPR><BRK/>
<BRK/>
<NPR>6.  Exhaust fan curbs, supply fan curbs, exhaust duct, supply duct, and ductwork 
material.</NPR><BRK/>
<BRK/>
<NPR>7.  Fire system CO2 tanks,actuating stations.</NPR><BRK/>
<BRK/>
<NPR>8.  Hoods, plumbing enclosure housing and control panel of automatic washdown 
system.</NPR><BRK/>
<BRK/>
<NPR>9.  Disconnect switches.</NPR><BRK/>
<BRK/>
<NPR>10.  Electrical chases and raceways and plumbing chases.</NPR><BRK/>
<BRK/>
<NPR>11.  Utility connections to building water, sanitary, electrical, and other 
utility systems.  Convenience outlets at point of use for plug-in equipment.</NPR><BRK/>
<BRK/>
<NPR>12.  All Contractor built-to-order items, per Food Service Equipment Schedule, 
shown and coordinated with the specifications.</NPR><BRK/>
<BRK/>
<NPR>14.  Utility connections to building water, sanitary, gas, electrical, sprinkler, 
fire alarm, oil, compressed air, steam, and other utility systems.  Convenience 
outlets at point of use for plug-in equipment.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>1.1   GENERAL RELATED SECTIONS AND STANDARDS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designate plumbing fixtures as "P" items on plumbing drawings with specific 
requirements added to Section <SRF>22 00 00</SRF> PLUMBING, GENERAL PURPOSE.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST>a.  Refer to section <SRF>11 05 40</SRF> COMMON WORK RESULTS FOR FOODSERVICE EQUIPMENT for general requirements.  
Provide detailed Food Service Equipment Schedule as specified in Section <SRF>11 06 40.13</SRF> FOOD SERVICE EQUIPMENT 
SCHEDULE.</LST><BRK/>
<BRK/>
<LST>b.  <TAI OPT="NAVFAC,USACE">Provide detailed Food Service Equipment Schedule conforming to <RID>DOD 4000.25-1-M</RID>.</TAI></LST><BRK/>
<BRK/>
<LST>c.  Gas-burning equipment must be designed for operation with the type of gas specified and be approved 
by CSA, conforming to <RID>CSA C22.2 No. 109</RID> and <RID>CSA Directory</RID>.</LST><BRK/>
<BRK/>
<LST>d.  All electrical work must conform to <RID>NFPA 70</RID>.</LST><BRK/>
<BRK/>
<LST>e.  <TAI OPT="USACE">Provide wet chemical fire extinguishing systems in accordance with Section <SRF>21 21 03.00 10</SRF> WET CHEMICAL 
FIRE EXTINGUISHING SYSTEM.</TAI></LST><BRK/>
<BRK/>
<LST>f.  <TAI OPT="NAVFAC">Provide connections as part of building sprinkler system, Section <SRF>21 13 13.00 20</SRF> WET PIPE SPRINKLER 
SYSTEM, FIRE PROTECTION.</TAI></LST><BRK/>
<BRK/>
<LST>g.  Grease extracting type hoods that have an internal hood fire protection system do not require wet 
chemical fire extinguishing protection for those components of the exhaust system, and for cooking equipment 
protected by a UL listed internal hood fire protection system complying to <RID>NFPA 96</RID>.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>1.2   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification.  The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
<BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
<BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>AMERICAN SOCIETY OF SANITARY ENGINEERING (ASSE)</ORG><BRK/><BRK/><RID>ASSE 1001</RID><RTL>(2008) Atmospheric Type Vacuum Breakers</RTL><BRK/><BRK/></REF><REF><ORG>AMERICAN WELDING SOCIETY (AWS)</ORG><BRK/><BRK/><RID>AWS A5.8/A5.8M</RID><RTL>(2004; Errata 2004) Specification for Filler Metals for Brazing and Braze Welding</RTL><BRK/><BRK/><RID>AWS D1.1/D1.1M</RID><RTL>(2008) Structural Welding Code - Steel</RTL><BRK/><BRK/><RID>AWS D10.4</RID><RTL>(1986; R 2000) Recommended Practices for Welding Austenitic Chromium-Nickel Stainless Steel Piping and Tubing</RTL><BRK/><BRK/><RID>AWS D9.1M/D9.1</RID><RTL>(2006) Sheet Metal Welding Code</RTL><BRK/><BRK/></REF><REF><ORG>CANADIAN STANDARDS ASSOCIATION (CSA)</ORG><BRK/><BRK/><RID>CSA C22.2 No. 109</RID><RTL>(1981; R 2004)Commercial Cooking Appliances - General Instruction No 1-3</RTL><BRK/><BRK/></REF><REF><ORG>CSA AMERICA, INC. (CSA/AM)</ORG><BRK/><BRK/><RID>CSA Directory</RID><RTL>(updated continuously online) Certified Products Listings</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 10</RID><RTL>(2007; Errata 2007; AMD 1 2007) Standard for Portable Fire Extinguishers</RTL><BRK/><BRK/><RID>NFPA 54</RID><RTL>(2008) National Fuel Gas Code</RTL><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/><RID>NFPA 96</RID><RTL>(2007) Ventilation Control and Fire Protection of Commercial Cooking Operations</RTL><BRK/><BRK/></REF><REF><ORG>NSF INTERNATIONAL (NSF)</ORG><BRK/><BRK/><RID>NSF 169</RID><RTL>(2007) Standard Specification for Special Purpose Food Equipment and Devices</RTL><BRK/><BRK/><RID>NSF 2</RID><RTL>(2008) Food Equipment</RTL><BRK/><BRK/><RID>NSF 4</RID><RTL>(2007) Standard for Commercial Cooking, Rethermalization and Powered Hot Food Holding and Transport Equipment</RTL><BRK/><BRK/><RID>NSF 51</RID><RTL>(2007) Food Equipment Materials</RTL><BRK/><BRK/><RID>NSF 52</RID><RTL>(2007e) Standard for Supplemental Flooring</RTL><BRK/><BRK/></REF><REF><ORG>SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION (SMACNA)</ORG><BRK/><BRK/><RID>SMACNA 1767</RID><RTL>(2001, 1st Ed) Kitchen Ventilation Systems and Food Service Equipment Guidelines</RTL><BRK/><BRK/><RID>SMACNA 1966</RID><RTL>(2005) HVAC Duct Construction Standards Metal and Flexible</RTL><BRK/><BRK/></REF><REF><ORG>U.S. DEPARTMENT OF DEFENSE (DOD)</ORG><BRK/><BRK/><RID>DOD 4000.25-1-M</RID><RTL>(2006; Notice 1) Requisitioning and Issue Procedures</RTL><BRK/><BRK/></REF><REF><ORG>U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)</ORG><BRK/><BRK/><RID>Energy Star</RID><RTL>(1992; R 2006) Energy Star Energy Efficiency Labeling System</RTL><BRK/><BRK/></REF><REF><ORG>U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)</ORG><BRK/><BRK/><RID>29 CFR 1910</RID><RTL>Occupational Safety and Health Standards</RTL><BRK/><BRK/><RID>29 CFR 1910-SUBPART D</RID><RTL>Walking - Working Surfaces</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 1598</RID><RTL>(2008; Rev thru Nov 2008) Luminaires</RTL><BRK/><BRK/><RID>UL 197</RID><RTL>(2003; Rev thru Mar 2006) Commercial Electric Cooking Appliances</RTL><BRK/><BRK/><RID>UL 489</RID><RTL>(2002; Rev thru Jun 2006) Standard for Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures</RTL><BRK/><BRK/><RID>UL 710</RID><RTL>(1995; Rev thru Feb 2007) Exhaust Hoods for Commercial Cooking Equipment</RTL><BRK/><BRK/><RID>UL 763</RID><RTL>(2000; Rev thru Dec 2007) Standard Specification for Motor-Operated Commercial Food Preparing Machines</RTL><BRK/><BRK/><RID>UL Elec Equip Dir</RID><RTL>(2008) Electrical Appliance and Utilization Equipment Directory</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.3   SYSTEM DESCRIPTION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Indicate the configuration and layout for all food preparation equipment, 
with interior elevations and equipment identified by number.  Show "Food Service 
Equipment Schedule" on the drawings using the same identification numbers<TAI OPT="USACE">[ and 
as indicated on the current US Army Quartermaster Center and School equipment 
schedule]</TAI>.  Ensure that all Contractor built-to-order items, per Food Service 
Equipment Schedule", are shown and coordinated with the specifications.</NPR><BRK/>
<BRK/>
<NPR>Designer must coordinate with other sections for final connection of equipment.</NPR><BRK/>
<BRK/>
<TAI OPT="NAVFAC"><NPR>Details of particular equipment and installations are provided on Naval Food 
Service Division drawings.  Use these NAVFSD drawings as a basis for the project 
details.  Contact NAVFSD at commercial telephone (717) 790-7580 or DSN 430-7580.</NPR></TAI><BRK/>
<BRK/>
<NPR>Indicate on drawings the location of each manual activation station.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The work includes [furnishing and] [installing] [and modifying existing] food service cooking equipment and related 
work.  Verify all existing dimensions, contract drawings, product data and all related conditions prior to commencing 
rough-in work.</TXT><BRK/>
<BRK/>
<LST>a.  Protect each exhaust hood system that serves cooking equipment, associated exhaust hood system ducts, 
and all cooking equipment served by the exhaust hood system with a wet chemical fire extinguishing system.</LST><BRK/>
<BRK/>
<LST>b.  Submit <SUB>detail drawings</SUB> for all food cooking equipment, <SUB>custom fabricated equipment</SUB>, along with equipment <SUB>
schedule</SUB>.  Drawings must be <MET> 1:50</MET><ENG> 1/4 inch</ENG> scale minimum.</LST><BRK/>
<BRK/>
<LST>c.  Include coordination of delivery through existing finished opening and vertical handling limitations 
within the building.  Advise the Contracting Officer of all discrepancies prior to ordering equipment.  
Submit <SUB>Contractor's Field Verification Data</SUB> prior to the preconstruction meeting.</LST><BRK/>
<BRK/>
<LST>d.Provide rough-in and connect <SUB>utilities</SUB> to equipment in accordance with requirements specified in other 
sections of this specification and in accordance with the physical dimensions, capacities, manufacturer's 
instructions, and other requirements of the equipment furnished.  Submit all <SUB>installation instructions 
and diagrams</SUB>.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review Submittal Description (SD) definitions in Section <SRF>01 33 00</SRF> SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy, Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are for [Contractor Quality Control approval.] [information only.  When used, a designation following the "G" 
designation identifies the office that will review the submittal for the Government.]  Submit the following in 
accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-01 Preconstruction Submittals</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Contractor's Field Verification Data</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Detail Drawings</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<ITM><SUB>Schedule</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Schedule in the same format as the equipment schedule on the drawings.</ITM><BRK/>
<BRK/>
<ITM><SUB>Energy Star qualified</SUB></ITM><BRK/>
<ITM><SUB>Exhaust Hoods Over Cooking Equipment</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<ITM><SUB>Utilities</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<ITM><SUB>Custom Fabricated Equipment</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<ITM><SUB>Installation Instructions and Diagrams</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Detail drawings, as specified,including insulation and utility requirements.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Commercial food cooking equipment</SUB></ITM><BRK/>
<ITM><SUB>Exhaust Hoods Over Cooking Equipment</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Field Test Reports</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<ITM><SUB>Exhaust Hood Air-Balance Report</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>NSF Certification</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<ITM><SUB>UL Certification</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<ITM><SUB>Energy Star Qualified</SUB></ITM><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   <SUB>EXHAUST HOODS OVER COOKING EQUIPMENT</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Seismic restraints for kitchen hoods must conform to Guidelines for Seismic 
Restraints of Kitchen Equipment (SMACNA Los Angeles Chapter).  See Appendix 
1 of SMACNA Fabrication Guidelines.  Include requirement in seismic zones 3 
and 4.</NPR><BRK/>
<BRK/>
<NPR>Hood design will be in accordance with NFPA 96, ASHRAE, and the ACGIH Industrial 
Ventilation Handbook.  Designer will indicate type, size, shape, make-up air, 
and detail of hoods and the required standard cubic meters per second (cubic 
feet per minute), meters per second (feet per minute) (velocity), static pressure, 
and duct collar size for exhaust/make-up air on the drawings.  Grease extracting 
automatic washdown hoods will be specified for new construction.  Filter type 
hoods may be used in existing facilities where conditions prevent the use of 
grease extractor hoods.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Conform to <RID>NFPA 96</RID> and <RID>UL 710</RID>.  Conform to <RID>SMACNA 1966</RID>.  [Provide seismic restraints in accordance with <RID>SMACNA 1767</RID>
.]  The hood shall not vary from design listing of air requirements or static pressure by more than five percent.  
Fabricate from<MET> 1.2 mm</MET><ENG> 18 gage</ENG> thick stainless steel.  Run electrical wiring in conduit or raceways.  When total 
hood length is more than<MET> 3600 mm</MET><ENG> 12 feet</ENG> long, provide hoods individually complete in all respects, of approximately 
equal length less than<MET> 3600 mm</MET><ENG> 12 feet</ENG> long, and mounted end to end.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.1   Centrifugal Grease-Extracting Hoods</TTL><BRK/>
<BRK/>
<TXT>Fabricate in factory.  Provide high-velocity type with average throat inlet air velocity of<MET> [5] [_____] mps</MET><ENG> [1,000] 
[_____] fpm</ENG> and duct velocity of<MET> [9] [_____] mps</MET><ENG> [1,800] [_____] fpm</ENG>.  Provide air inlet above and parallel to 
equipment for full length of hood.  Provide hood which will remove 95 percent of extraneous matter in air with 
non-removable grease-extracting baffles located in plenum chamber.  The use of filters, cartridges, rotating 
parts, removable parts, or constantly running water is not acceptable.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.1.1   Types of Hoods</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete types not indicated for the project.  If a type is not used, state 
"not used" at the subparagraph, to avoid renumbering.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide the following hood types as indicated:</TXT><BRK/>
<BRK/>
<LST>a.  Serve-Over Shelf<TAI OPT="NAVFAC">; Type l</TAI>:  Provide over [charbroilers,] [fryers,] [_____,] [and] [griddles] on serving 
lines.  Mount hood<MET> 1370 to 1450 mm</MET><ENG> 54 to 57 inches</ENG> above finished floor.</LST><BRK/>
<BRK/>
<LST>b.  Island<TAI OPT="NAVFAC">; Type 2</TAI>:  Provide over [steam-jacketed kettles,] [fry pans,] [ovens,] [broilers,] [_____,] 
[and] [steamers] located remote from walls.  Mount at height indicated.</LST><BRK/>
<BRK/>
<LST>c.  Wall-Mounted, Free-Standing<TAI OPT="NAVFAC">; Type 3</TAI>:  Provide over [ranges,] [_____,] [broilers,] [doughnut fryers,] 
[griddles,] [ovens,] [steam-jacketed kettles,] [and] [fryers] located along wall. Mount at height indicated.</LST><BRK/>
<BRK/>
<LST>d.  Low Ceiling<TAI OPT="NAVFAC">; Type 4</TAI>:  Provide over [_____] [and] [_____] where low ceiling restricts installation 
of Type 1, 2, or 3.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.1.2   Features</TTL><BRK/>
<BRK/>
<TXT>Provide the following:</TXT><BRK/>
<BRK/>
<LST>a.  Automatic washdown system.</LST><BRK/>
<BRK/>
<LST>b.  Fan control.</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete references to fire dampers in air inlet if fire dampers are included 
in exhaust ductwork connecting to hood.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST>c.  Damper controls.</LST><BRK/>
<BRK/>
<LST>d.  Fan control station and plumbing enclosure.</LST><BRK/>
<BRK/>
<LST>e.  Fire protection system, for hoods over [tilting frying pans,] [charbroilers,] [fryers,] [griddles,] 
[doughnut fryers,] [_____,] [deep-fat fryers,] [and] [broilers].</LST><BRK/>
<BRK/>
<LST>f.  Vapor-proof lights.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.1.3   Automatic Washdown System</TTL><BRK/>
<BRK/>
<TXT>Provide system that automatically washes internal portions of hood for an adjustable period of between 0 and 
15 minutes.  Provide for activation by time clock or upon operation of fire damper.</TXT><BRK/>
<BRK/>
<LST>a.  Features of Operation:</LST><BRK/>
<BRK/>
<ITM>(1)  Shut off supply and exhaust fans, if running, at beginning of cleaning cycle.</ITM><BRK/>
<BRK/>
<ITM>(2)  Subject accumulated contaminates on internal surfaces with water at<MET> [60] [82] degrees C</MET><ENG>
 [140] [180] degrees F</ENG> and a water pressure of<MET> 0.275 MPa</MET><ENG> 40 psi</ENG>.  Provide pressure reducing 
valve.</ITM><BRK/>
<BRK/>
<ITM>(3)  [Pump] [Inject] detergent into hot water supply line to create wash-water.</ITM><BRK/>
<BRK/>
<ITM>(4)  Provide scrubbing action by directing wash-water through manifolds and then through spray 
nozzles placed so that all internal surfaces are reached with streams of wash-water.</ITM><BRK/>
<BRK/>
<ITM>(5)  Collect wash-water and grease within hood and pipe to outside of hood to point indicated 
for indirect connection to building plumbing system.</ITM><BRK/>
<BRK/>
<ITM>(6)  End wash cycle by timer.</ITM><BRK/>
<BRK/>
<LST>b.  Plumbing Components:  Provide brass or stainless steel spray heads or nozzles and stainless steel 
distribution manifold in each hood.  Provide the following in fan control station and plumbing enclosure:</LST><BRK/>
<BRK/>
<ITM>(1)  Water solenoid valve</ITM><BRK/>
<BRK/>
<ITM>(2)  Shut-off valve</ITM><BRK/>
<BRK/>
<ITM>(3)  Shock absorber</ITM><BRK/>
<BRK/>
<ITM>(4)  Pressure gage</ITM><BRK/>
<BRK/>
<ITM>(5)  Temperature gage</ITM><BRK/>
<BRK/>
<ITM>(6)  Line strainer</ITM><BRK/>
<BRK/>
<ITM>(7)  Vacuum breaker, conforming to <RID>ASSE 1001</RID></ITM><BRK/>
<BRK/>
<ITM>(8)  Detergent reservoir, one gallon minimum</ITM><BRK/>
<BRK/>
<ITM>(9)  Detergent [pump] [injector]</ITM><BRK/>
<BRK/>
<ITM>(10)  Check valve</ITM><BRK/>
<BRK/>
<ITM>(11)  Timer</ITM><BRK/>
<BRK/>
<ITM>(12)  Pressure reducing valve</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.1.4   Fan Control</TTL><BRK/>
<BRK/>
<TXT>Locate in fan control station and plumbing enclosure.  Provide delay-time starter on starter leg of exhaust fan 
so supply fan starts first and run 5 seconds before exhaust fan starts, to insure the required balance in exhausted 
and make-up air flow.  Provide the following operations:</TXT><BRK/>
<BRK/>
<LST>a.  Interconnection with washdown system to effect shutoff.</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete references to fire dampers in air inlet if fire dampers are included 
in exhaust ductwork connecting to hood.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST>b.  Interconnection with fire dampers to effect shutoff of fans.</LST><BRK/>
<BRK/>
<LST>c.  Operation by time clock.</LST><BRK/>
<BRK/>
<LST>d.  Operation by manual push buttons labeled "start" and "stop".</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.1.5   Fire Damper</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete references to damper if fire dampers are included in exhaust ductwork 
connecting to hood.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide mechanically driven damper and damper control.  Activate by heat-sensing thermostat set to react to temperature 
of<MET> 176 degrees C</MET><ENG> 350 degrees F</ENG> in exhaust duct at hood.  Activation of damper must cause the following additional 
actions:</TXT><BRK/>
<BRK/>
<LST>a.  Shut off exhaust and supply fans of hood.</LST><BRK/>
<BRK/>
<LST>b.  Shut off fuel source and electric power to equipment under hood.</LST><BRK/>
<BRK/>
<LST>c.  Initiate automatic washdown system.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.1.6   Fan Control Station and Plumbing Enclosure</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Do not locate control cabinet for hoods on serving line tray slide support 
walls or on drop wall above serving line tray slide.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide flush-mounted enclosure.  Wire and plumb in factory.  Include the following:</TXT><BRK/>
<BRK/>
<LST>a.  Plumbing components of washdown system.</LST><BRK/>
<BRK/>
<LST>b.  Components required for fan control, including manual push buttons and interlocks with other systems.</LST><BRK/>
<BRK/>
<LST>c.  Components required to operate fire protection system.</LST><BRK/>
<BRK/>
<LST>d.  Time clock capable of being programmed by the week to operate fan system and automatic washdown system 
and of maintaining time cycle after being overridden by manual push buttons.</LST><BRK/>
<BRK/>
<LST>e.  Labeled light indicating when exhaust fan and supply fan are operating.</LST><BRK/>
<BRK/>
<LST>f.  Labeled light indicating when automatic washdown system is operating.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.1.7   Fire Protection Systems</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select fire protection system based on cost and local regulations.  If 
kitchen cannot tolerate time lost for clean-up in event of dry chemical release, 
or if kitchen return air is tied into building system return air, do not use 
that system.  Ensure that actuating systems are indicated on drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide a pre-engineered [[dry] [wet] chemical system in accordance with Division 21<TAI OPT="NAVFAC">, Section <SRF>21 23 00.00 20</SRF> 
DRY CHEMICAL FIRE EXTINGUISHING FOR KITCHEN CABINET</TAI>] [[liquid foam system] [water spray system] in accordance 
with <RID>NFPA 96</RID>].  [Include water spray in plenum of hood.]  Include micro-switch for electric power and fuel shut 
off to equipment under hood and a fuel shut-off and reset button.  Exposed piping under hood and surface nozzles 
to be stainless steel or chrome plated.  Paint exposed piping running to hood with rust-inhibiting aluminum paint.  
Provide electrical wiring, contactors, shunt breakers, electrical control for gas valves, and other electrical 
components required to install fire systems in accordance with Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM.</TXT><BRK/>
<BRK/>
<LST>a.  Actuating Stations.  Provide manual actuating station and remote manual actuating station as indicated.  
Clearly label actuating station as "Hood Fire Protection" and specific device protected.</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If water spray system is specified, make sure it is compatible with building 
sprinkler system.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST>b.  Water Spray Fire System In Grease-Extracting Type Hood:  Include wall-mounted control panel with 
pilot lights for indicating when system is operational, not operational, and on fire alert.  Provide 
audible fire alarm, unions, hand valve, valve switch, and pressure switch.  Include duct nozzles and 
plenum nozzles.  Provide water pipe to control panel and from control panel to hood.  Provide connections 
as part of building sprinkler system<TAI OPT="NAVFAC">, Section <SRF>21 13 13.00 20</SRF> WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION</TAI>
.</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If exhaust hood fire system is to be connected to building alarm system, 
the work must be included in other sections and coordinated.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">c.  Alarm Connection:  Provide capability to signal operational readiness and to generate electronic 
signal when hood fire system is activated.  Provide connection point for building alarm system. 
Provide system to connection point and connect in accordance with Section [_____]<TAI OPT="NAVFAC">[
<SRF>28 31 74.00 20</SRF> INTERIOR FIRE ALARM SYSTEM]</TAI>.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.1.8   Vapor proof Lights</TTL><BRK/>
<BRK/>
<TXT>Provide,<TAI OPT="NAVFAC">[ at Type 2 and Type 3 hoods,]</TAI> incandescent or fluorescent lights in accordance with <RID>UL 1598</RID> or <RID>UL 1598</RID>
.  Locate switches for operating hood lights on face of hood in lower [right] [_____] corner.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>2.2   <SUB>Commercial Food Cooking Equipment</SUB></TTL><BRK/>
<BRK/>
<LST>a.  All commercial cooking equipment shall conform to <RID>29 CFR 1910</RID>, CSA, NSF, UL and other related standards 
as stated herein and in Section <SRF>11 05 40</SRF> COMMON WORK RESULTS FOR FOODSERVICE EQUIPMENT.  Supply all gas 
fueled appliances with installed automatic shut-off device(s), as well as manual shut-offs device conforming 
to <RID>NFPA 96</RID>.</LST><BRK/>
<BRK/>
<LST>b.  Electrical cooking appliances must conform to <RID>UL 197</RID>, <RID>UL 489</RID>. <RID>UL 763</RID>, and <RID>UL Elec Equip Dir</RID>.</LST><BRK/>
<BRK/>
<LST>c.  [All commercial cooking equipment must conform to <RID>Energy Star</RID> labeling to confirm being <SUB>Energy Star 
Qualified</SUB>.  All equipment must bear <SUB>NSF Certification</SUB> and <SUB>UL Certification</SUB> labels.]</LST><BRK/>
<BRK/>
<SPT><TTL>2.2.1   Gas Burners</TTL><BRK/>
<BRK/>
<TXT>In accordance with <RID>NFPA 54</RID>, equip burners and pilots located in enclosed compartments with automatic shut off 
of gas supply if burners fail to ignite, or pilot is extinguished.</TXT><BRK/>
<BRK/></SPT>
[<SPT><TTL>2.2.2   Specialty Cooking Equipment</TTL><BRK/>
<BRK/>
<TXT>Conform to the requirements of <RID>NSF 169</RID>, <RID>NSF 2</RID>, <RID>NSF 4</RID>, and <RID>NSF 51</RID>.  Floor areas adjacent to cooking areas must 
conform to <RID>NSF 52</RID> and <RID>29 CFR 1910-SUBPART D</RID>.</TXT><BRK/>
<BRK/></SPT>
]</SPT>[<SPT><TTL>2.3   BAKING OVEN</TTL><BRK/>
<BRK/>
<TXT>[_____]</TXT><BRK/>
<BRK/></SPT>
][<SPT><TTL>2.4   BROILER</TTL><BRK/>
<BRK/>
<TXT>[_____]</TXT><BRK/>
<BRK/></SPT>
][<SPT><TTL>2.5   DEEP FRYERS</TTL><BRK/>
<BRK/>
<TXT>[_____]</TXT><BRK/>
<BRK/></SPT>
][<SPT><TTL>2.6   GRIDDLE</TTL><BRK/>
<BRK/>
<TXT>[_____]</TXT><BRK/>
<BRK/></SPT>
][<SPT><TTL>2.7   STEAM COOKERS</TTL><BRK/>
<BRK/>
<TXT>[_____], [3][4][5][6] pan</TXT><BRK/>
<BRK/></SPT>
]<SPT><TTL>2.8   PORTABLE FIRE EXTINGUISHER</TTL><BRK/>
<BRK/>
<TXT>Wall mount portable fire extinguisher conforming to <RID>NFPA 10</RID>, within [_____] feet of cooking area.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Perform installation in accordance with the manufacturer's printed instructions.  Refer to section <SRF>11 05 40</SRF> COMMON 
WORK RESULTS FOR FOODSERVICE EQUIPMENT for detailed installation, project closeout, and warranty requirements.  
Lay out work in advance to prevent damage to building, piping, wiring, or equipment as a result of cutting for 
installation.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.1.1   Setting and Connecting</TTL><BRK/>
<BRK/>
<TXT>Install equipment plumb and level.  Except for mobile and adjustable-leg equipment, securely anchor and attach 
items and accessories to walls, floors, or bases with stainless steel bolts.  Flash food service cabinets located 
in wall openings to the walls with<MET> 0.9 mm</MET><ENG> 20 gage</ENG> thick stainless steel.  Seal around equipment flashing and 
flanges, at walls, floor, and ceiling in accordance with Section <SRF>07 92 00</SRF> JOINT SEALANTS.  Fillers shall be continuous, 
without opening.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.2   Welding Field Joints</TTL><BRK/>
<BRK/>
<TXT>Weld stainless steel by the electric fusion method.  Provide where required by and in accordance with <RID>AWS A5.8/A5.8M</RID>
, <RID>AWS D1.1/D1.1M</RID>, <RID>AWS D10.4</RID>, AND <RID>AWS D9.1M/D9.1</RID>.  Accomplish brazing with silver solder for joining copper tubing 
to brass and bronze connection fitting and for no other purpose.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.3   Cleaning and Adjusting</TTL><BRK/>
<BRK/>
<TXT><TST>Test and adjust equipment for proper operation.  Test rotating components and motors for proper rotation.</TST>  Lubricate 
moving parts if suggested by manufacturer's literature.  Prior to acceptance of project, clean and sanitize equipment 
both inside and outside.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.4   Installation of Hoods</TTL><BRK/>
<BRK/>
<TXT>Install hoods in accordance with <RID>NFPA 96</RID> to remain free from vibration under all conditions of operation.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.2   FIELD INSPECTIONS AND TESTS</TTL><BRK/>
<BRK/>
<TXT><TST>Inspect equipment, fixtures, and material after installation for compliance with the applicable standards.</TST>  Upon 
completion of inspection<TST> perform operational tests on each piece of equipment to determine that equipment and 
components, including controls, safety devices, and attachments, operate as specified and are properly installed 
and adjusted.  Test all water, drain, gas, steam, oil, refrigerant, and liquid carrying components for leaks.  
Notify the Contracting Officer 14 calendar days prior to testing.  Submit <SUB>Field Test Reports</SUB> and [_____] copies 
of the <SUB>Exhaust Hood Air-Balance Report</SUB> to the Contracting Officer.</TST></TXT><BRK/>
<BRK/></SPT>
</PRT>    <END/><BRK/></SEC>