<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA               UFGS-13 49 19 (February 2009)<BRK/>
                                             -----------------------------<BRK/>
Preparing Activity:  <PRA>USACE</PRA>                   Superseding<BRK/>
                                             UFGS-13 49 19 (April 2006)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 13 49 19</SCN><BRK/>
<BRK/>
<STL>X-RAY SHIELDING</STL><BRK/>
<DTE>02/09</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>x-ray shielding 
for medical and dental radiological facilities</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This specification essentially implements the requirements of NCRP Reports 
35, 49 and 102; however, designers are cautioned to ensure that the requirements 
of TB MED 521 be met in addition to the requirements of applicable NCRP publications.  
In case of conflict between NCRP publications and TB MED 521, the more stringent 
requirements will be applied.</NPR><BRK/>
<BRK/>
<NPR>The installation systems given in this guide specification are the systems more 
commonly used.  Where details of construction require systems not included in 
this guide specification, the guide specification requirements will be revised 
to specify the required system.  Criteria for users on radiation protection 
surveys is contained in TB MED 521.<BRK/>
<BRK/>
Design or modification of diagnostic x-ray, therapeutic x-ray, or gamma-beam 
therapy facilities must only be undertaken by experts certified in radiological 
physics or therapeutic radio-logical physics by the American Board of Radiology 
or the American Board of Health Physics.</NPR><BRK/>
<BRK/>
<NPR>Where the increase in cost can be justified by substantial increases in flexibility 
of the facility, allow for future rearrangement of x-ray equipment and facilities 
by providing the maximum thickness of shielding which provides the minimum protection 
in all areas that could be covered by the primary beam.  In any case, lead thickness 
must be uniform for the entire wall, ceiling, floor or partition to which it 
is applied.</NPR><BRK/>
<BRK/>
<NPR>Department of the Army Technical manual 5-805-12, "X-Ray Shielding," has standard 
details.  It is included in the CCB.</NPR><BRK/>
<BRK/>
<NPR>Include on the drawings:</NPR><BRK/>
<BRK/>
<NPR>1. Extent of the shielding; length, width, and height of the lead sheeting.</NPR><BRK/>
<BRK/>
<NPR>2. Joint, opening, and corner details showing the method of continuation of 
protection.</NPR><BRK/>
<BRK/>
<NPR>3. Door and window details, including louvers and screens.</NPR><BRK/>
<BRK/>
<NPR>4. Pipe and conduit chases and penetration sleeves.</NPR><BRK/>
<BRK/>
<NPR>5. Location of all door and wall plaques.</NPR><BRK/>
<BRK/>
<NPR>6. Stud spacing for lead lined gypsum board or lath.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification.  The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM B 749</RID><RTL>(2003) Standard Specification for Lead and Lead Alloy Strip, Sheet and Plate Products</RTL><BRK/><BRK/><RID>ASTM C 129</RID><RTL>(2006) Standard Specification for Nonloadbearing Concrete Masonry Units</RTL><BRK/><BRK/><RID>ASTM C 1396/C 1396M</RID><RTL>(2006a) Standard Specification for Gypsum Board</RTL><BRK/><BRK/></REF><REF><ORG>HARDWOOD PLYWOOD AND VENEER ASSOCIATION (HPVA)</ORG><BRK/><BRK/><RID>HPVA HP-1</RID><RTL>(2004) American National Standard for Hardwood and Decorative Plywood</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL COUNCIL ON RADIATION PROTECTION AND MEASUREMENTS (NCRP)</ORG><BRK/><BRK/><RID>NCRP 144</RID><RTL>(2003) Radiation Protection for Particle Accelerator Facilities</RTL><BRK/><BRK/><RID>NCRP Rpt 102</RID><RTL>(1989) Medical X-Ray, Electron Beam and Gamma-Ray Protection for Energies up to 50 MeV (Equipment Design, Performance and Use)</RTL><BRK/><BRK/><RID>NCRP Rpt 35</RID><RTL>(1970) Dental X-Ray Protection</RTL><BRK/><BRK/><RID>NCRP Rpt 49</RID><RTL>(1976) Structural Shielding Design and Evaluation for Medical Use of X-Rays and Gamma Rays of Energies up to 10 MeV</RTL><BRK/><BRK/></REF><REF><ORG>STEEL DOOR INSTITUTE (SDI/DOOR)</ORG><BRK/><BRK/><RID>SDI/DOOR A250.8</RID><RTL>(2003) Recommended Specification for Standard Steel Doors and Frames</RTL><BRK/><BRK/></REF><REF><ORG>U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)</ORG><BRK/><BRK/><RID>29 CFR 1910.1025</RID><RTL>Lead</RTL><BRK/><BRK/></REF><REF><ORG>WINDOW AND DOOR MANUFACTURERS ASSOCIATION (WDMA)</ORG><BRK/><BRK/><RID>WDMA I.S. 1-A</RID><RTL>(1997) Architectural Wood Flush Doors</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   SYSTEM DESCRIPTION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For Navy projects, submit x-ray shielding designs and calculations to 
Chief, Bureau Medicine and Surgery, 2300 E Street NW, Washington, D.C.  20372-5000, 
for review and approval prior to design release.<BRK/>
<BRK/>
Coordinate work of this section with Sections <SRF>11 27 13</SRF> RADIOGRAPHIC DARKROOM 
EQUIPMENT and <SRF>11 70 00</SRF> GENERAL REQUIREMENTS FOR MEDICAL AND DENTAL EQUIPMENT.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Construct X-ray shielding unimpaired by joints, openings for ducts, pipes, or other openings through shielding, 
or conduits, service boxes, and other items embedded in the shielding.  The shielding shall appear to be continuous.  
Install lead patches, lead sleeves, and/or mazes as required to provide continuity of the shielding.  Minimum 
lead lap shall be<MET> 25 mm</MET><ENG> 1 inch</ENG>.  Sleeves shall be not less than<MET> 25 mm</MET><ENG> 1 inch</ENG> in length.  Thicknesses indicated 
for shielding are minimum acceptable thickness.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section <SRF>01 33 00</SRF> SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy, Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are for [Contractor Quality Control approval.] [information only.  When used, a designation following the "G" 
designation identifies the office that will review the submittal for the Government.]  Submit the following in 
accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<TXT><SUB>Materials</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</TXT><BRK/>
<BRK/>
<ITM>  Drawings indicating thickness of lead at all locations; construction at floor, walls, ceiling, 
and columns; details of lead laps and lap securing methods; fastenings, profiles, details of 
items and accessories penetrating the shielding materials; and any special method of construction.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Materials</SUB></ITM><BRK/>
<BRK/>
<ITM>  Manufacturer's catalog cuts, descriptive data, and installation instructions.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-04 Samples</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Lead-Lined Wood Panels</SUB></ITM><BRK/>
<BRK/>
<ITM>  <MET>200 by 250 mm</MET><ENG> 8 by 10 inch</ENG> sample of each specified panel.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Testing and Certification</SUB></ITM><BRK/>
<BRK/>
<ITM>  Copies of surveyor's reports.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Materials</SUB></ITM><BRK/>
<BRK/>
<ITM>  Certification indicating the shielding materials supplied comply with specified quality and 
thicknesses.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   QUALIFICATIONS</TTL><BRK/>
<BRK/>
<TXT>Work shall be performed by a company which specializes in the type of shielding work required by the Contract 
documents.  Company shall have a minimum of [5] [_____] years of documented successful experience.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5   DELIVERY, STORAGE, AND HANDLING</TTL><BRK/>
<BRK/>
<TXT>Deliver materials in the original containers bearing the name of the manufacturer and brand name.  Store shielding 
materials off the ground under watertight cover.  Handle materials preventing damage to edges, ends or surfaces 
in conformance with <RID>29 CFR 1910.1025</RID>.  Remove damaged materials from the premises.  [Leave protective paper on 
acrylic panels until installation is complete.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6   WARRANTY</TTL><BRK/>
<BRK/>
<TXT>Lead sheet shielding materials shall be warranted against sagging and curling for [10] [_____] years.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   LEAD SHEET</TTL><BRK/>
<BRK/>
<TXT>Provide Lead sheet shall conform to <RID>ASTM B 749</RID>, Grade C, thickness as shown.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2   LEAD-LINED CONCRETE MASONRY UNITS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate the requirements of this Section with Section <SRF>04 20 00</SRF> MASONRY.  
Lead-lined masonry units have a broad range of lead thicknesses.  Lead-lined 
masonry units offer the advantages that they are relatively simple to construct, 
provide considerable structural strength, and may be surfaced easily with plaster.  
However, the cost is considerably higher (up to a specific kV) than using lead-lined 
wallboard, lath, panels, concrete, or earth.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide lead-lined concrete masonry units conforming to <RID>ASTM C 129</RID>, Type 1.  Each unit shall have a single thickness 
of unpierced lead sheet bonded or anchored permanently in the center of the unit/block.  Construct blocks to 
provide an effective lead lap between adjoining blocks either by the overlapping of lead in adjoining blocks 
or by lead bars at block joints when erected.  Nominal dimensions for full-size units shall be<MET> 300 by 300 by 
[100] [150] mm</MET><ENG> 12 by 12 by [4] [6] inch</ENG>.  Nominal dimensions for half-size units shall be<MET> 150 by 300 by [100] 
[150] mm</MET><ENG> 6 by 12 by [4] [6] inch</ENG>.  Units<MET> 100 mm</MET><ENG> 4 inch</ENG> thick shall be used for shielding requirements up to<MET> 6 
mm</MET><ENG> 1/4 inch</ENG> of lead, and<MET> 150 mm</MET><ENG> 6 inch</ENG> thick units shall be used for shielding requirements above<MET> 6 mm</MET><ENG> 1/4 inch</ENG>
 of lead.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3   <SUB>LEAD-LINED WOOD PANELS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When a matching finish is not required, specify prefinished panels.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Lead-lined panels shall be unpierced sheet lead laminated to hardwood veneer plywood conforming to <RID>HPVA HP-1</RID>, 
not less than<MET> 9 mm</MET><ENG> 3/8 inch</ENG> thick.  The lead sheet shall extend the full height and width of the panels except 
for applications at corners, frames, and other similar locations.  The lead sheet may extend beyond the edge 
of the panels to form effective lead laps.  Face veneer shall be [birch] [mahogany] [red gum] [red oak] [white 
oak].  Face veneer shall [have an approved natural finish] [be polished sanded] [have a primary coat of varnish, 
lacquer, or synthetic coating].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4   LEAD-LINED LATH</TTL><BRK/>
<BRK/>
<TXT>Lead-lined lath shall have a single thickness unpierced sheet of lead laminated to gypsum lath, conforming to <RID>
ASTM C 1396/C 1396M</RID>, Type 1, Grade R, Class 1, Form a, Style 1, <MET>9 mm</MET><ENG> 3/8 inch</ENG> thick, so that the lead extends<MET>
 25 mm</MET><ENG> 1 inch</ENG> beyond lath on one long side and one short side.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5   LEAD-LINED GYPSUM WALLBOARD</TTL><BRK/>
<BRK/>
<TXT>Lead-lined gypsum wallboard shall be a single thickness of unpierced lead laminated to<MET> [13][16] mm</MET><ENG> [1/2][5/8] 
inch</ENG> thick gypsum board conforming to <RID>ASTM C 1396/C 1396M</RID>, Type III, Grade R, Class 1, Form a, [Style 1][Style 
3].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6   LEADED GLASS</TTL><BRK/>
<BRK/>
<TXT>Leaded glass shall be clear X-ray protective quality glass in single or multiple thicknesses.  Leaded glass shall 
have lead equivalence required for the shield wall, door, or partition in which the leaded glass is installed.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7   LEAD-HEADED NAILS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Lead-headed nails are seldom required; use if radiological calculations 
show a need for them.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Lead-headed nails may be used to accomplish shielding not less than that provided by the barrier.  The size, 
type and design shall be recommended by the manufacturer of material to be installed.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.8   LEAD TABS OR CLIPS</TTL><BRK/>
<BRK/>
<TXT>Lead tabs or clips shall be unpierced sheet lead not less than the thickness of lead in the barrier.  Prior to 
folding, the tabs shall be rectangular in shape and shall be the required size to provide an effective lead lap 
over an unleaded nail, screw, or tie wire penetration when folded.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9   LEAD-LINED WOOD DOORS</TTL><BRK/>
<BRK/>
<TXT>Lead-lined wood doors shall be [premium grade, book matched] [good grade], hardwood veneer, solid core, in accordance 
with <RID>WDMA I.S. 1-A</RID>.  Lead sheet shall extend to door edges and provide x-ray absorption equal to the partition 
in which the door is installed.  Face veneer for lead-lined doors shall be [birch] [mahogany] [red gum] [red 
oak] [white oak] [_____] finished with [an approved natural finish] [_____].  Doors shall have filler strips, 
crossbanding face veneers and hardwood edge strips glued under heavy pressure with contact adhesive.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.9.1   Shielding</TTL><BRK/>
<BRK/>
<TXT>Secure cores together with [poured lead fasteners] [or] [steel bolts], using washers under heads and nuts.  Bolts 
shall be spaced not more than<MET> 38 mm</MET><ENG> 1-1/2 inch</ENG> from edges around door perimeter and not more than<MET> 200 mm</MET><ENG> 8 inch</ENG>
 on centers in both directions.  Bolts shall be countersunk and have poured lead or lead dowels covering heads 
and nuts flush with face of core.  Door thickness shall be manufacturer's standard for lead thickness used, unless 
shown otherwise.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9.2   Painting and Sealing Doors</TTL><BRK/>
<BRK/>
<TXT>Top and bottom edges of doors to be painted shall receive two factory coats of spar varnish before shipment to 
jobsite.  Doors to be stained or have a natural finish shall receive two shop coats of water-resistant sealer 
before shipment to jobsite.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9.3   Door Hardware</TTL><BRK/>
<BRK/>
<TXT>Door hardware shall be as specified in Section <SRF>08 71 00</SRF> DOOR HARDWARE.  Mortises for floor hinge arms and top 
pivots with sheet lead and necessary lead plugs, sheet lead, stainless steel pans, bolts and screws shall be 
provided.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9.4   Thresholds</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Threshold construction is determined by radiographic equipment required, 
work load, and location of radiation source from the door (i.e., threshold may 
not be required for installation operating below 125 kVp if the primary beam 
does not strike the door area).</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Thresholds are specified in Section <SRF>08 71 00</SRF> DOOR HARDWARE.  Line thresholds with a single sheet of lead to provide 
required shielding.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.10   LEAD WINDOW FRAMES</TTL><BRK/>
<BRK/>
<TXT>Construct lead window frames for viewing windows mounted in lead-lined doors from [lead extrusion welded in one 
piece] [extruded aluminum alloy with concealed lead lining], splayed on four sides for wide-angle viewing.  Frames 
shall form a minimum overlap of<MET> 9 mm</MET><ENG> 3/8 inch</ENG> at the perimeter of the lead glass or twice the thickness of the 
shielding, whichever is greater.  Thickness of lead shall be the same as the lead in the barrier in which they 
occur.  Frames can be either solid or telescoping type.  Lead stops shall be provided for glass or acrylic installation.  
Clear acrylic panel shall be provided with lead equivalence [_____] [as required by unit in which panel is installed.] 
[  Provide a baffled slot for voice passage in the frame.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11   LEAD LIGHTPROOF LOUVERS</TTL><BRK/>
<BRK/>
<TXT>Lead lightproof louvers for doors shall be fabricated entirely of lead of not less than the thickness of lead 
in barrier in which they are installed.  Louvers shall be one-unit construction designed with a maze-type blade 
to exclude the passage of light.  Louvers shall allow 30 percent free area for air circulation.  Louvers shall 
be factory-fitted, boxed separately, and shipped with door or assembled before shipment.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12   LEAD-LINED STEEL DOORS AND FRAMES</TTL><BRK/>
<BRK/>
<SPT><TTL>2.12.1   Doors</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Threshold construction is determined by radiographic equipment required, 
work load, and location of radiation source from the door (i.e., threshold may 
not be required for installation operating below 125 kVp if the primary beam 
does not strike the door area).</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Doors shall conform to Section <SRF>08 11 13</SRF> STEEL DOORS AND FRAMES, in accordance with <RID>SDI/DOOR A250.8</RID>, Grade II, 
heavy duty, Model 1, minimum 18 gage faces with steel stiffeners throughout.  Apply unpierced lead sheet, of 
thickness equal to that used in the adjoining wall, in the center of the door between the two faces, continuously 
from top to bottom and edge to edge.  Shield cutouts for locksets with sheet lead of the same thickness as used 
in the door; lap lead lining of locksets and the door lining.  Prepare doors to receive viewing windows and louvers 
as indicated.  Provide removable stops for glazed openings.  Use Section <SRF>08 71 00</SRF> DOOR HARDWARE for protective 
hardware requirements.  Line thresholds with a single sheet of lead to provide required shielding.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12.2   Frames</TTL><BRK/>
<BRK/>
<TXT>Provide steel frames as specified in Section <SRF>08 11 13</SRF> STEEL DOORS AND FRAMES.  The inside of frames shall be 
lined with a single thickness of sheet lead.  The thickness of the lead lining shall be the same as the lead 
lining of the system in which the frames are used.  Linings shall be installed at the factory, and shall be continuous.  
Lining shall be formed to contour of frame.  Lead shields shall be formed around areas prepared to receive hardware.  
Each lining shall be wide enough to provide and maintain an effective lead lap with the lead of the adjoining 
shielding units.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.13   FILM CASSETTE TRANSFER CABINETS</TTL><BRK/>
<BRK/>
<TXT>Cassette transfer cabinet shall be double-wall steel cabinet divided into two compartments with doors of one 
cabinet plainly marked for exposed cassettes and doors of the other cabinet plainly marked for unexposed cassettes.  
Interlocking device shall prevent the doors on opposite ends of the cabinets from being opened at the same time.  
Sheet lead lining of cassette cabinet shall provide x-ray absorption equal to the X-ray absorption provided by 
partition in which the cabinet is installed.  Cabinets shall have identification marking.  Cabinet floor shall 
be corrugated rubber with chrome-plated door knobs.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14   OPERATORS PROTECTIVE SCREEN</TTL><BRK/>
<BRK/>
<TXT>Operators protective screen shall be constructed [of studs, surfaced with lead-lined [gypsum lath conform to <RID>
ASTM C 1396/C 1396M</RID>] [gypsum wallboard conforming to <RID>ASTM C 1396/C 1396M</RID>] secured to studs with appropriate fasteners, 
with lead washer or tabs.] [of sheet lead laminated between plywood panels, <MET>19 mm</MET><ENG> 3/4 inch</ENG> thick conforming to <RID>
HPVA HP-1</RID>.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15   DESIGNATING PLAQUES</TTL><BRK/>
<BRK/>
<SPT><TTL>2.15.1   Required Information</TTL><BRK/>
<BRK/>
<TXT>Furnish and install designating plaques as specified below in rooms and as indicated on the drawings.  Locations 
where shielding thickness changes, or is not continuous, shall be indicated on the plaque.  Plaque shall be of 
aluminum, plastic, bakelite, or other approved materials and shall be [_____]<MET> mm</MET><ENG> inch</ENG> high by [_____]<MET> mm</MET><ENG> inch</ENG>
 long to contain the required information as specified below.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.2   X-Ray and Examination Rooms</TTL><BRK/>
<BRK/>
<TXT>One sign shall be provided for [dental x-ray room] [x-ray] [and] [examination rooms] lettered as follows:</TXT><BRK/>
<BRK/>
<TXT>: "THE PARTITIONS, THE DOORS, AND THE LEAD-LINED SHIELD OF THIS ROOM HAVE BEEN INSULATED WITH SHEET LEAD [_____] 
mm THICK PROVIDING A TOTAL LEAD EQUIVALENT PROTECTION OF [_____] mm."</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.3   Radiographic, Fluoroscopic, and Cystoscopic Rooms</TTL><BRK/>
<BRK/>
<TXT>One sign shall be provided for each room insulated with sheet lead lettered as follows:</TXT><BRK/>
<BRK/>
<TXT>: "SURFACES OF THIS ROOM HAVE BEEN INSULATED WITH SHEET LEAD OF FOLLOWING THICKNESS TO A HEIGHT OF<MET>2.1 m</MET><ENG> 7 FEET</ENG>
 ABOVE FLOOR SLAB:</TXT><BRK/>
<TBL><THD><BRK/>
                                                     TOTAL LEAD<BRK/>
                                   LEAD              EQUIVALENT<BRK/>
                                   THICKNESS         PROTECTION<BRK/></THD>
<BRK/>
              DOORS                [_____] mm         [_____] mm<BRK/>
<BRK/>
              PARTITIONS           [_____] mm         [_____] mm<BRK/>
<BRK/>
              FLOORS               [_____] mm         [_____] mm"</TBL><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.4   Deep Therapy Room</TTL><BRK/>
<BRK/>
<TXT>One sign shall be provided for each deep therapy room lettered as follows:</TXT><BRK/>
<BRK/>
<TXT>"ALL SURFACES OF THIS ROOM HAVE BEEN SHIELDED WITH AN EQUIVALENT SHEET LEAD OF THE FOLLOWING THICKNESS:</TXT><BRK/>
<TBL><THD><BRK/>
                                                     TOTAL LEAD<BRK/>
                                                     EQUIVALENT<BRK/>
                                                     PROTECTION<BRK/></THD>
<BRK/>
              DOORS                                   [_____] mm<BRK/>
<BRK/>
              PARTITIONS                              [_____] mm<BRK/>
<BRK/>
              FLOOR                                   [_____] mm<BRK/>
<BRK/>
              CEILING                                 [_____] mm"</TBL><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.5   Rooms With Nonshielded Partitions</TTL><BRK/>
<BRK/>
<TXT>Provide one sign for each lead-shielded partition in a room for which all partitions are not shielded.  A sign 
shall be located on lead-insulated partition and lettered as follows:</TXT><BRK/>
<BRK/>
<TXT>: "THIS PARTITION HAS BEEN SHIELDED THE [FULL HEIGHT] [HEIGHT OF [_____]<MET> m</MET><ENG> FEET</ENG>] WITH SHEET LEAD [_____]<MET> mm</MET><ENG> INCH</ENG>
 THICK, PROVIDING A TOTAL LEAD EQUIVALENT PROTECTION OF [_____] mm."</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.6   Cardiac Fluoroscopy Room</TTL><BRK/>
<BRK/>
<TXT>One sign shall be provided for the door to cardiac fluoroscopy or other room to which only the door is shielded, 
lettered as follows:</TXT><BRK/>
<BRK/>
<TXT>: "THIS DOOR HAS BEEN SHIELDED WITH SHEET LEAD OF [_____] mm."</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.16   CONCRETE</TTL><BRK/>
<BRK/>
<TXT>[Concrete shielding material shall be uniform density of<MET> 2355 kg/cubic meter</MET><ENG> 147 pcf</ENG>] [High-density concrete 
shielding material shall be of uniform density in the range of<MET> 3045 to 3445 kg/cubic meter</MET><ENG> 190 to 340 pcf</ENG>].</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   INSTALLATION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  NCRP Reports 49, and 51 or 102 will be included for medical facilities.  
NCRP Report 35 will be included for dental clinics.  For facilities with both 
medical and dental x-ray construction, NCRP Reports 35, 49 and 51 or 102 will 
be included.  This Section is applicable only to the design of medical and dental 
facilities; other type facilities are required to meet different radiation protection 
standards, and must be coordinated with NAVSEASYSCOM Detachment, Radiological 
Affairs Support Office, Yorktown, VA 23691-5098 for Navy projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Perform installation of <SUB>materials</SUB> in accordance with drawings and approved manufacturer's recommendations and 
[<RID>NCRP Rpt 35</RID>] [<RID>NCRP Rpt 49</RID>] [<RID>NCRP Rpt 102</RID>] [or] [<RID>NCRP 144</RID>].</TXT><BRK/>
<BRK/>
<SPT><TTL>3.1.1   Workmanship</TTL><BRK/>
<BRK/>
<TXT>Install sheet lead free of waves, lumps, and wrinkles and with a minimum of joints.  Joints in sheet lead shall 
provide protection equivalent to the protection provided by the adjacent sheet lead.  Joints shall be finished 
smooth and neat.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.2   Protection</TTL><BRK/>
<BRK/>
<TXT>Use lead shields to maintain continuity of protection where unshielded built-in items penetrate lead linings.  
Where outlet boxes, junction boxes, ducts, conduits, and similar items prevent the use of shields, lead sleeves 
or lead lining shall be used.  Fasteners shall not disrupt the continuity of shielding.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.2   LEAD-LINING FOR CONCRETE FLOORS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  In rooms scheduled for sheet lead ceiling, the sheet lead lining shall 
be placed on top of the floor slab above the room protected, unless a suspended 
lead ceiling is required.  Vertical wall shieldings shall be erected on lead 
strips prior to the installation of floor linings in the shielded room.  Lead 
strips shall project approximately 75 mm (3 inches) into the shielded room area.  
Lead lining at the door sill opening shall be not less than 600 mm (2 feet) 
wider than the opening and shall extend not less then 300 mm (1 foot) beyond 
the door jamb openings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Surfaces of concrete floors receiving lead linings shall be clean, dry, and free of sharp projections that will 
damage or penetrate the sheet lead.  When necessary, a smooth screed coat of concrete shall be applied over rough 
concrete surfaces.  A coat of asphalt or latex paint shall be applied to the concrete surfaces prior to installation 
of the sheet lead.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.2.1   Shielding</TTL><BRK/>
<BRK/>
<TXT>Sheet lead less than<MET> 3 mm</MET><ENG> 1/8 inch</ENG> thick shall be applied in a single layer with a<MET> 38 mm</MET><ENG> 1-1/2 inch</ENG> minimum lap 
at joints.  Sheet lead more than<MET> 3 mm</MET><ENG> 1/8 inch</ENG> thick shall be applied in two or more layers<MET> 3 mm</MET><ENG> 1/8 inch</ENG> or 
less in thickness with<MET> 38 mm</MET><ENG> 1-1/2 inch</ENG> minimum lap at joints or shall be applied in a single layer with joints 
butted and covered with lead strips not less than the thickness required for floor lining and as detailed.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.2   Protection from Damage</TTL><BRK/>
<BRK/>
<TXT>Apply a coat of asphalt paint to the top surface of the sheet lead prior to application of concrete surfacing.  
Traffic or other work will not be permitted in the area until concrete is applied over lining.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.3   LEAD-LINED BLOCKS</TTL><BRK/>
<BRK/>
<TXT>Lead-lined blocks shall be laid in running bond courses with staggered vertical joints.  Blocks designed for 
lead laps at joints shall be erected to provide minimum<MET> 25 mm</MET><ENG> 1 inch</ENG> tight lead laps without soldering or burning 
or provide lead bars in vertical and horizontal joints.  Blocks designed to have lead bars in joints shall be 
erected to permit lead bars with a thickness not less than the lead sheet thickness in block to be inserted in 
horizontal and vertical joints.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.3.1   Joints</TTL><BRK/>
<BRK/>
<TXT>Mortar joints shall be<MET> 9 mm</MET><ENG> 3/8 inch</ENG> thick and shall be filled solid with Type N mortar as specified under Section 
<SRF>04 20 00</SRF> MASONRY.  Mortar between lead laps will not be permitted.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.2   Blocks</TTL><BRK/>
<BRK/>
<TXT>Extend blocks into frame openings, with lead projecting into rabbets of frames to effectively lap with lead frames 
of frame linings.  Voids around frames shall be filled with mortar.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.3   Pipe and Conduit Chases</TTL><BRK/>
<BRK/>
<TXT>Where pipe and conduit chases occur within the blocks, concrete may be removed from one side of the partition 
as required to permit pipe installation.  Where necessary to remove lead lining for pipe or conduit installations, 
continuous sheet lead shall be installed and overlapped on the adjoining construction.  Voids around pipe and 
conduit chases within the blocks shall be filled with mortar.  Voids shall be finished flush with the face of 
partition.  Pipe and conduit chases shall not be installed directly opposite each other within the same partition.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.4   LEAD-LINED PANELS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When the finish of the panels must match the finish of other woodwork, 
the polish sanding for finish on the job will be specified.  Length and width 
of panels and joint pattern will be indicated on the drawings and will be selected 
to keep weights of panels to reasonable minimums.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Lead-lined panels shall be applied over supports specified in Section <SRF>06 10 00</SRF> ROUGH CARPENTRY.  The method of 
predrilling or drilling pilot holes for fasteners shall prevent deformation of the fastener and shall prevent 
distortion of the panel.  Lead-lined panels shall be butt-jointed and shall be placed over supports with lead 
linings placed next to supports.  Effective lead laps at corners and around frames of openings shall be made 
with panels having lead extensions or with sheet-lead strips not less than the thickness of the lead in the panel.  
Fasteners shall be set<MET> 2 mm</MET><ENG> 1/16 inch</ENG> below the face of panel or joint strip.  Fasteners shall be finished with 
filler or plugs to match the panel.  Sides and ends of panels shall be secured at approximately<MET> 200 mm</MET><ENG> 8 inch</ENG>
 on centers with fasteners to penetrate<MET> 40 mm</MET><ENG> 1-1/2 inch</ENG> into supports.  At intermediate supports, panels shall 
be fastened in a uniform pattern at approximately<MET> 400 mm</MET><ENG> 16 inch</ENG> on centers.  Fastening at joints shall conform 
to one of the following methods:</TXT><BRK/>
<BRK/>
<SPT><TTL>3.4.1   Joints With Lead-Lined Joint Strips</TTL><BRK/>
<BRK/>
<TXT>Cover joints with sheet-lead strips not less than the panel thickness and not less than<MET> 50 mm</MET><ENG> 2 inch</ENG> wide.  Secure 
joint strips to supports with fasteners located in the center of joint strip at approximately<MET> 200 mm</MET><ENG> 8 inch</ENG> on 
center.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4.2   Joints Backed with Lead Strips</TTL><BRK/>
<BRK/>
<TXT>Sheet-lead strips not less than the panel thickness and not less than<MET> 40 mm</MET><ENG> 1-1/2 inch</ENG> wide shall be installed 
on supports at panel joints.  Lead strips shall be secured at outer edges of strips.  Finish molding strips shall 
match the panel finish.  Finish molding strips shall be installed to cover joints and shall be secured with fasteners 
at approximately<MET> 200 mm</MET><ENG> 8 inch</ENG> on centers.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.5   LEAD-LINED LATH</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Lead-lined lath with lead 8 mm (5/16 inch) thick or less will be 400 
x 1220 mm (16 x 48 inches) with lead extensions on two sides for lapping and 
installed with the long dimension at right angles to supports.  Lead-lined lath 
with lead over 8 mm (5/16 inch) thick will be 300 mm (12 inches) wide by manufacturer's 
standard length with lead cut the same size as the lath installed with the long 
dimension parallel to supports.  Drawings will indicate support spacing at 300 
mm (12 inches) on centers where the 300 mm (12 inch) wide lath is used.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Lead-lined lath shall be applied over supports specified in Section <SRF>06 10 00</SRF> ROUGH CARPENTRY and Section 
<SRF>09 22 00</SRF> METAL SUPPORT ASSEMBLIES.  The method of predrilling or drilling the pilot holes shall prevent deformation 
of the fastener and shall prevent distortion of the lath.  Lead-lined lath shall be applied with long edges at 
right angles to supports and with lead linings placed next to supports.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.5.1   Joints</TTL><BRK/>
<BRK/>
<TXT>[Place end joints over supports staggered in alternate courses.]  [Wall joints shall not coincide with the ceiling 
joints.]  [Each sheet shall overlap the lead extension on the adjacent sheet, providing an effective lead lap.]  
[Lead-lined lath shall be applied with long edges parallel to supports and with lead linings placed next to supports.  
Blocking shall be provided at end joints.  Sheet-lead strips, not less than the lath thickness and not less than<MET>
 40 mm</MET><ENG> 1-1/2 inch</ENG> wide, shall be applied on blocking and on supports at joints.  Lead strips shall be secured 
to blocking and supports at outer edges of strips.]  Lath shall be close fitted and uniformly secured to supports.  
Approximately<MET> 6 mm</MET><ENG> 1/4 inch</ENG> shall be allowed between horizontal joint to form key for plaster.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.2   Frames and Corners</TTL><BRK/>
<BRK/>
<TXT>Lath shall extend into frames of openings effectively lapping with lead frames or frame linings.  Unless otherwise 
approved, lath shall be arranged around openings such that neither horizontal nor vertical joints occur at corners 
of openings.  External corners shall be reinforced with corner bead.  Internal corners, except at unrestrained 
suspended ceilings, shall be reinforced as required and shall be installed with lead-headed nails or tie wires 
and lead tabs.  At unrestrained ceilings, square-nosed casing beads shall be installed at the junction of walls 
and suspended ceilings.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.3   Wood Supports</TTL><BRK/>
<BRK/>
<TXT>Lath shall be uniformly nailed to wood supports at approximately<MET> 175 mm</MET><ENG> 7 inch</ENG> on centers with lead-headed nails.  
Nail heads shall be flush with lath surface.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.4   Metal Supports</TTL><BRK/>
<BRK/>
<TXT>Lath shall be uniformly secured to [wood furring strips which are secured at right angles to the metal supports 
with bolts or screws.  Lath shall be secured with lead-headed nails with the nail heads flush with lath surface] 
[metal supports with<MET> 25 mm</MET><ENG> 1 inch</ENG> screws or tie wire and lead tabs folded over the fasteners].</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.6   LEAD-LINED GYPSUM WALLBOARD</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  A nonlead-lined finish ply of gypsum wallboard may be installed where 
required by design requirements.  Style 1, butt-joints, will be used for the 
base ply of two-ply construction.  The finish ply shall be bonded to the first 
ply with laminating adhesive applied as recommended by the manufacturer of the 
wallboard.  A shoring system shall be used to hold the finish ply in place during 
the adhesive drying period.  Shoring shall be left in place at least 24 hours.  
Nailing of the finish ply will not be permitted.  Joint and corner treatment 
shall be as specified in Section <SRF>09 29 00</SRF> GYPSUM BOARD.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Lead-lined gypsum wallboard shall be applied over supports specified in Section <SRF>06 10 00</SRF> ROUGH CARPENTRY and 
Section <SRF>09 22 00</SRF> METAL SUPPORT ASSEMBLIES.  Method of predrilling or drilling pilot holes shall not cause deformation 
of the fastener and shall not cause distortion of wallboard.  Wallboard shall be applied vertically, with long 
edges parallel to supports, and with lead linings placed next to supports.  Blocking shall be provided at end 
joints.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.6.1   Joints</TTL><BRK/>
<BRK/>
<TXT>Sheet-lead strips not less than the lead thickness used for wallboard and not less than<MET> 38 mm</MET><ENG> 1-1/2 inches</ENG> wide 
shall be installed on blocking and supports at all joints.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6.2   Corner Joints</TTL><BRK/>
<BRK/>
<TXT>Corner joints shall consist of<MET> 45 by 45 mm</MET><ENG> 1-3/4 by 1-3/4 inch</ENG> lead angle.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6.3   Wood Supports</TTL><BRK/>
<BRK/>
<TXT>The sheet-lead strips shall be secured to blocking and supports at outer edges with wire nails.  Edges of wallboard 
shall then be butt-jointed and fastened to supports with lead-headed nails at approximately<MET> 200 mm</MET><ENG> 8 inch</ENG> on 
centers at joints and<MET> 300 mm</MET><ENG> 12 inch</ENG> on center at intermediate supports with nail heads driven slightly below 
the surface of wallboard.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6.4   Metal Supports</TTL><BRK/>
<BRK/>
<TXT>Edges of gypsum wallboard at metal studs shall be fastened with<MET> 25 mm</MET><ENG> 1 inch</ENG> long lead-headed screws.  Heads 
shall be covered with<MET> 13 mm</MET><ENG> 1/2 inch</ENG> diameter lead disc cemented to wallboard and installed flush with surface 
of wallboard.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6.5   Finish Ply</TTL><BRK/>
<BRK/>
<TXT>Gypsum wallboard not scheduled to be plastered shall receive a finish ply of gypsum wallboard bonded to the first 
ply with laminating adhesive as recommended by the wallboard manufacturer.  Nailing the finish ply will not be 
permitted.  A shoring system shall be used to hold finish ply in place during adhesive drying period.  Shoring 
shall be left in place at least 24 hours.  Joint and corner treatment shall be as specified in Section 
<SRF>09 29 00</SRF> GYPSUM BOARD.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.7   SUSPENDED LEAD-LINED CEILINGS</TTL><BRK/>
<BRK/>
<TXT>Provide suspended lead-lined ceilings consisting of lead-lined lath, ceiling bars, and hangers.  Continuous bars 
shall be spaced approximately<MET> [315] [415] mm</MET><ENG> [12-1/2] [16-1/2] inch</ENG> on center and supported by steel hangers 
from overhead structure.  Lead in the ceiling shall lap lead in the wall by not less than<MET> 38 mm</MET><ENG> 1-1/2 inch</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8   LEAD DOOR THRESHOLDS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Drawings should indicate type of threshold for each specified radiographic 
or therapy room. Thresholds will be included in installations where floor lining 
is not installed and if required by design conditions.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Thresholds shall be installed in accordance with approved detail drawings.  Prior to installation, lead threshold 
surfaces in contact with concrete shall be painted with a coat of asphalt paint or latex material.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.9   LEAD-LINED WOOD DOORS</TTL><BRK/>
<BRK/>
<TXT>Doors shall be fit, hung, and trimmed as required.  Doors shall be installed with a clearance of<MET> 2 mm</MET><ENG> 1/16 inch</ENG>
 at sides and top and minimum adequate clearance at bottom.  Lock edge shall be beveled<MET> 3 mm</MET><ENG> 1/8 inch</ENG>, and hardware 
shall be adjusted as required.  Warp or twist of lead-lined doors after doors have been hung and finished shall 
not exceed<MET> 6 mm</MET><ENG> 1/4 inch</ENG> in any face dimension of door including full diagonal.  Cuts required for installation 
shall be sealed with a clear varnish or sealer.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.9.1   Door Hardware</TTL><BRK/>
<BRK/>
<TXT>Bolts and screws which penetrate lead lining shall be recessed on the side of the door opposite hardware and 
shall be plugged with lead plugs to match face of door.  Nuts for securing surface-applied hardware such as hinges, 
door closers and automatic door operators shall be countersunk and covered with lead-lined<MET> 1.59 mm</MET><ENG> 16 gauge</ENG> thick 
stainless steel pans.  Stainless steel pans shall be secured with round-head screws with dull chromium-plated 
finish.  Cutouts for lock sets and latch cases shall be patched with sheet lead.  Lead lining of the lock set 
and lead lining of the door shall be lapped to provide x-ray absorption equal to the door.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.9.2   View Windows</TTL><BRK/>
<BRK/>
<TXT>View windows shall be installed in doors with hardwood stops to match face veneer.  Stops shall be glued to door 
on corridor side and shall be fastened with countersunk oval head screws or finishing nails.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.9.3   Lead Louvers</TTL><BRK/>
<BRK/>
<TXT>Lead louvers shall be installed in doors with cadmium-plated or chromium-plated screws.  Fastenings shall not 
penetrate lead lining of the door.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.10   OPERATOR'S PROTECTIVE SCREEN</TTL><BRK/>
<BRK/>
<TXT>Finish plywood-hinged screens and fixed screens after installation in the same manner as that specified for doors.  
Edge strips are not required for fixed screens.  At corners or where screen abuts a wall or floor, provide a 
lap of lead.  [Build-in viewing window of lead glass or acrylic with lead equivalence [indicated.] [matching 
adjacent panel].]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.11   <TST><SUB>TESTING AND CERTIFICATION</SUB></TST></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  NCRP Reports 49, 51, and 102 will be included for surveying medical facilities.  
NCRP Report 35 will be included for surveying dental clinics.  For facilities 
incorporating medical and dental x-ray installations, NCRP Reports 35, 49 and 
51 or 102 will be included.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Before and after x-ray equipment has been installed and placed in operating condition, the x-ray installation 
shall be surveyed by a qualified expert as defined in [<RID>NCRP Rpt 35</RID>] [<RID>NCRP Rpt 49</RID>] [<RID>NCRP Rpt 102</RID>] [or] [<RID>NCRP 144</RID>
].  Survey shall be performed in accordance with [<RID>NCRP Rpt 35</RID>] [<RID>NCRP Rpt 49</RID>] [<RID>NCRP Rpt 102</RID>] [or] [<RID>NCRP 144</RID>].  
Four copies of surveyor's report shall be furnished to the Contracting Officer.  Any part of x-ray shielding 
work found to be defective shall be corrected or replaced, including all other work affected thereby.</TXT><BRK/>
<BRK/></SPT>
</PRT>    <END/><BRK/></SEC>