<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA   UFGS- 21 12 00 (April 2006)<BRK/>
                                 -------------------------------<BRK/>
Preparing Activity:  <PRA>NAVFAC</PRA>      Replacing without change<BRK/>
                                 UFGS-13975 (August 2004) <BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION  21 12 00</SCN><BRK/>
<BRK/>
<STL>STANDPIPE SYSTEMS </STL><BRK/>
<DTE>04/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>dry and wet standpipe 
and hose systems for fire extinguishing in multi-story and multi-level buildings</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Standpipe system requirements must conform to the current edition of 
UFC 3-600-01 Design: Fire Protection Engineering for Facilities and NFPA 14.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Project drawings should indicate the following information:</NPR><BRK/>
<BRK/>
<NPR>1.  Location and detail of each standpipe supply riser, alarm valve, water motor 
alarm, fire department inlet connection, pressure/flow switch, fused disconnect 
switch, and associated electrical connections;</NPR><BRK/>
<BRK/>
<NPR>2.  Location where each standpipe system begins including connection to water 
distribution system piping;</NPR><BRK/>
<BRK/>
<NPR>3.  Location of standpipe system control valves, post indicator valves, or wall 
indicator valves;</NPR><BRK/>
<BRK/>
<NPR>4.  Location of fire hose cabinets when required, also indicate when fire extinguishers 
will be stored within the fire hose cabinet;</NPR><BRK/>
<BRK/>
<NPR>5.  Details of anchoring piping, including pipe clamps and tie rods, or mechanical 
retainer glands.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>AMERICAN WATER WORKS ASSOCIATION (AWWA)</ORG><BRK/><BRK/><RID>AWWA C651</RID><RTL>(2005; Errata 2005) Standard for Disinfecting Water Mains</RTL><BRK/><BRK/></REF><REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM C 1036</RID><RTL>(2006) Standard Specification for Flat Glass</RTL><BRK/><BRK/></REF><REF><ORG>FM GLOBAL (FM)</ORG><BRK/><BRK/><RID>FM P7825</RID><RTL>(2005) Approval Guide</RTL><BRK/><BRK/></REF><REF><ORG>FOUNDATION FOR CROSS-CONNECTION CONTROL AND HYDRAULIC RESEARCH (FCCCHR)</ORG><BRK/><BRK/><RID>FCCCHR List</RID><RTL>(continuously updated) List of Approved Backflow Prevention Assemblies</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 13</RID><RTL>(2006; Errata 2007; Amendment 1 2008) Installation of Sprinkler Systems</RTL><BRK/><BRK/><RID>NFPA 14</RID><RTL>(2006) Standard for the Installation of Standpipe, Private Hydrants and Hose Systems</RTL><BRK/><BRK/><RID>NFPA 24</RID><RTL>(2006) Standard for the Installation of Private Fire Service Mains and Their Appurtenances</RTL><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/><RID>NFPA 72</RID><RTL>(2006) National Fire Alarm Code</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL Fire Prot Dir</RID><RTL>(2008) Fire Protection Equipment Directory</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   RELATED REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Section <SRF>23 03 00.00 20</SRF> BASIC MECHANICAL MATERIALS AND METHODS applies to this section with additions and modifications 
specified herein.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   SYSTEM DESCRIPTION</TTL><BRK/>
<BRK/>
<TXT>Design and provide new [manual dry Class I][combination] [automatic] [wet Class I] standpipe [and fire sprinkler] 
system[s] as shown.  </TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   SYSTEM DESCRIPTION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Design standpipe systems in accordance with the current edition of MIL-HDBK-1008 
and NFPA 14.  Provide pipe-sizing calculations to the Division Fire Protection 
Engineer (FPE) for review.  Class I standpipes are for fire department use only 
and will normally be the type provided.  Wet standpipes must be protected from 
freezing.  It is NAVFAC policy <HL1>not</HL1> to provide hose on standpipes except in unique 
situations as approved by the Division FPE.  In low and intermediate height 
buildings (up to 75-ft in height), use of manual-dry standpipes is normally 
dictated by economics.  In high rise buildings, the time required to fill the 
piping with water and the pressure involved normally dictate automatic standpipes.<BRK/>
<BRK/>
The following clarification is provided regarding the design of standpipe systems.  
The two primary factors to consider are type of system (manual vs. automatic) 
and system design pressures.  Unless otherwise directed by the Division FPE, 
standpipe systems shall be designed as follows:<BRK/>
<BRK/>
1.  For buildings less than 75-ft, standpipe systems shall be designed as “Manual 
Standpipe Systems” as defined in NFPA 14.  The system piping shall be hydraulically 
designed to provide the required flow rate at a minimum residual pressure of 
65 psi at the hydraulically most remote 2˝-inch hose connection.  In combination 
sprinkler-standpipe systems, necessary fire booster pumps shall be sized to 
support the sprinkler demand only.  The fire department shall supplement the 
standpipe system via the fire department connections to provide the necessary 
flow and pressure.  The water supply must be evaluated to ensure the available 
capacity will support the minimum standpipe system flow rates.<BRK/>
<BRK/>
2.  For buildings 75-ft up to 150-ft in height, standpipe systems shall be designed 
as “Automatic Standpipe Systems”as defined in NFPA 14.  Fire pumps shall be 
sized to consider the standpipe demand as specified in NFPA 14.  The system 
piping shall be hydraulically designed to provide the required flow rate at 
a minimum residual pressure of 65 psi at the hydraulically most remote 2˝-inch 
hose connection.  <BRK/>
<BRK/>
3.  In buildings 150-ft in height and greater, standpipe systems shall be designed 
as “Automatic Standpipe Systems”as defined in NFPA 14.  Fire pumps shall be 
sized to consider the standpipe demand as specified in NFPA 14.  The system 
piping shall be hydraulically designed to provide the required flow rate at 
a minimum residual pressure of 100-psi at the hydraulically most remote 2˝-inch 
hose connection.<BRK/></NPR>
<BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>System design and manufacturer's products shall be in accordance with the required and advisory provisions of <RID>
NFPA 14</RID> except as modified herein.  [Standpipe system shall be designed by hydraulic calculations.][Provide sprinkler 
portion of system under Section <SRF>21 13 13.00 20</SRF> WET PIPE SPRINKLER SYSTEM.]  Each system [shall be designed for 
earthquakes and ]shall include materials, accessories, and equipment inside and outside the building necessary 
to provide each system complete and ready for use.  Devices and equipment shall be <RID>UL Fire Prot Dir</RID> listed or <RID>
FM P7825</RID> approved for fire protection service.  In the publications referred to herein, the advisory provisions 
shall be considered to be mandatory, as though the word "shall" had been substituted for "should" wherever it 
appears; reference to the "authority having jurisdiction" shall be interpreted to mean the [[_____] Division] 
[Engineering Field Activity [_____]], Naval Facilities Engineering Command, Fire Protection Engineer.  [The work 
shall begin at [the points indicated][_____].]</TXT><BRK/>
<BRK/>
<SPT><TTL>1.4.1   Residual Pressure</TTL><BRK/>
<BRK/>
<TXT>The minimum residual pressure at the outlet of the most remote 64 mm hose connection shall be <MET>448.2 kPa</MET><ENG> 65 psig</ENG>
 [<MET> 689.5 kPa</MET><ENG> 100 psig</ENG>] while the system is discharging at the required design flow rates.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.2   Friction Losses</TTL><BRK/>
<BRK/>
<TXT>Calculate losses in piping in accordance with the Hazen-Williams formula with 'C' value of 120 for steel piping, 
150 for copper tubing, and 140 for cement-lined ductile-iron piping.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>1.4.3   Water Supply</TTL><BRK/>
<BRK/>
<TXT>Base hydraulic calculations on a static pressure of [_____] <MET> kPa</MET> psi (gage with [_____] <MET> L/m</MET><ENG> gpm</ENG> available at 
a residual pressure of [_____] <MET> kPa</MET><ENG> psi</ENG> (gage) at the [junction with the existing water distribution piping system.] 
[Base hydraulic calculations on operation of fire pump[s] provided in Section 13920, "Fire Pumps."]</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>1.4.4   <SUB>Standpipe System</SUB> Drawings</TTL><BRK/>
<BRK/>
<TXT>Prepare in accordance with the requirements for "Plans and Specifications" as specified in <RID>NFPA 14</RID>.  Each drawing 
shall be <MET>A1 841 by 594 mm</MET><ENG> 34 by 22 inches</ENG>.  Plans shall be drawn to a scale not less than <MET> 1 mm equals 100 mm</MET><ENG>
 1/8 inch scale</ENG>  Do not commence work until the design of each system and the various components have been approved.  
Show data essential for proper installation of each system.  Show details, plan view, elevations, and sections 
of the systems supply and piping.  Show piping schematic of systems supply, devices, valves, pipe, and fittings.  
[Submit drawings signed by a registered fire protection engineer.]  Show:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Room, space or area layout and include pipe supports and hangers.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Field wiring diagrams showing locations of devices and points of connection and terminals 
used for all electrical field connections in the system, with wiring color code scheme.</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.5   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<TXT>The fire protection engineer, [[_____] Division] [Engineering Field Activity [_____]], Naval Facilities Engineering 
Command will review any approve all submittals in this section requiring Government approval.</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Standpipe system</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM>Aboveground <SUB>Pipe and fittings</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Mechanical couplings</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Pipe hangers and supports</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Valves</SUB>, including gate, check, and hose[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Fire department connections</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
[<ITM><SUB>Alarm valves</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
[<ITM><SUB>Water motor alarms</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
[<ITM><SUB>Pressure switch</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
[<ITM><SUB>Waterflow detector</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
[<ITM><SUB>Fire hose cabinets</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
<ITM><SUB>Valve tamper switch</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
[<ITM><SUB>Backflow preventer</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
<ITM><SUB>Buried Pipe and fittings</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Data which describes more than one type of item shall be clearly marked to indicate which 
type the Contractor intends to provide.  Submit one original for each item and clear, legible, 
first-generation photocopies for the remainder of the specified copies.  Incomplete or illegible 
photocopies will not be accepted.  Partial submittals will not be accepted.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Preliminary tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Acceptance tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit for all inspections and tests specified under paragraph entitled "Field Quality Control."</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Qualifications of installer</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit installers qualifications as required under paragraph entitled "Qualifications of Installer."</ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Alarm valves</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Backflow preventer</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE DATA.  Furnish one complete 
package prior to the time that final acceptance tests are performed, and furnish the remaining 
before the contract is completed.  Inscribe the following identification on the cover:  the 
words OPERATION AND MAINTENANCE MANUAL, the location of the building, the name of the Contractor, 
system manufacturer and the contract number.  The instructions shall be legible and easily read, 
with large sheets of drawings folded in.  The package shall include:  schematic drawings showing 
piping; circuit drawings; installation instructions; maintenance instructions; safety precautions, 
diagrams, and illustrations; test procedures; performance data; and parts list.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-11 Closeout Submittals</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>System as-built drawings</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.6.1   <SUB>Qualifications of Installer</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The experience clause in this guide specification has been approved by 
a Level I, Contracting Officer in accordance with the requirements of NAVFAC 
P-68.  The paragraph in this guide specification may be used without further 
approval or request for waiver.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Prior to commencing work, submit data showing that the Contractor has successfully installed fire extinguishing 
standpipe systems of the same type and design as specified herein, or that he has a firm contractual agreement 
with a subcontractor having the required experience.  Include the names and locations of at least two installations 
where the Contractor, or the subcontractor referred to above, has installed such systems.  Indicate the type 
and design of each system, and certify that the system has performed satisfactorily for a period of at least 
18 months.<BRK/>
<BRK/>
Qualifications of System Technician:  Installation drawings, shop drawing and as-built drawings shall be prepared, 
by or under the supervision of, an individual who is experienced with the types of works specified herein, and 
is currently certified by the National Institute for Certification in Engineering Technologies (NICET) as an 
engineering technician with minimum Level-III certification in Automatic Sprinkler System program.  Contractor 
shall submit data for approval showing the name and certification of all involved individuals with such qualifications 
at or prior to submittal of drawings.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6.2   <SUB>System As-Built Drawings</SUB></TTL><BRK/>
<BRK/>
<TXT>Upon completion, and before final acceptance of the work, submit a complete set of as-built drawings of each 
system.  Submit<MET> A1 841 by 594 mm</MET><ENG> 34 by 22 inch</ENG> reproducible as-built drawings on mylar film with title block 
similar to full size contract drawings.  Furnish as-built(record) working drawings in addition to the as-built 
drawings required by Division 1, "General Requirements."</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.7   DELIVERY, STORAGE AND HANDLING</TTL><BRK/>
<BRK/>
<TXT>Protect stored equipment from weather, humidity and temperature variations, dirt, dust, and other contaminants.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   ABOVEGROUND PIPING SYSTEMS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include bracketed text for wet pipe systems only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide fittings for changes in direction of piping and for connections. Make changes in piping sizes through 
tapered reducing pipe fittings; bushings will not be permitted.  Perform welding in the shop; field welding will 
not be permitted.  [Conceal piping in areas with suspended ceiling.]</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.1   <SUB>Pipe and Fittings</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer shall consider specifying high-pressure fittings where applicable.  
Consult the Division FPE for guidance.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NFPA 14</RID>, except as modified herein.  Steel piping shall be Schedule 40 for sizes less than<MET> 200 mm</MET><ENG> 8 inches</ENG>, and 
Schedule 30 or 40 for sizes<MET> 200 mm</MET><ENG> 8 inches</ENG> and larger.  Fittings shall be welded, threaded, or grooved-end type.  
Plain-end fittings with mechanical couplings and fittings which use steel gripping devices to bite into the pipe 
when pressure is applied will not be permitted.  Rubber gasketed grooved-end pipe and fittings with <SUB>mechanical 
couplings</SUB> shall be permitted in pipe sizes<MET> 40 mm</MET><ENG> 1.5 inches</ENG> and larger.  Fittings shall be <RID>UL Fire Prot Dir</RID> listed 
or <RID>FM P7825</RID> approved for use in [dry] [wet] pipe sprinkler systems.  Fittings, mechanical couplings, and rubber 
gaskets shall be supplied by the same manufacturer.  Steel piping with wall thickness less than Schedule 30 shall 
not be threaded. [Side outlet tees using rubber gasketed fittings shall not be permitted.] Pipe and fittings 
shall be metal.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   <SUB>Pipe Hangers and Supports</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide in accordance with <RID>NFPA 14</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.3   <SUB>Valves</SUB></TTL><BRK/>
<BRK/>
<TXT><RID>NFPA 14</RID>.  Provide valves of types approved for fire service.  Hose and gate valves shall open by counterclockwise 
rotation.  Provide isolation and check valves as required by <RID>NFPA 14</RID>.  Isolation valves shall be OS&amp;Y type.  
Check valves shall be flanged clear opening swing-check type with flanged inspection and access cover plate for 
sizes<MET> 100 mm</MET><ENG> 4 inches</ENG> and larger.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.3.1   Hose Valves</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where nozzle pressures may exceed<MET> 862 kPa</MET><ENG> 125 psi</ENG> for Class I standpipes, 
specify pressure regulating valves.  Specify<MET> 690 kPa</MET><ENG> 100 psi</ENG> for all Class I 
standpipes unless otherwise requested by the Division FPE.  Indicate on drawings 
which valves are to be pressure regulating type.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide bronze [pressure regulating type] hose valve with<MET> 65 mm</MET><ENG> 2 1/2 inch</ENG> National Standard male hose threads, 
and<MET> 65 mm</MET><ENG> 2 1/2 inch</ENG> NH female by<MET> 40 mm</MET><ENG> 1 1/2 inch</ENG> IPT male reducer with cap and chain.  [Equip valve with a 
device to regulate pressure at the outlet to a pressure not exceeding<MET> [690] [_____] kPa</MET><ENG> [100] [_____] psi</ENG> [under 
both flow and no-flow conditions].]</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.1.4   Identification Signs</TTL><BRK/>
<BRK/>
<TXT><RID>NFPA 14</RID>.  Attach properly lettered and approved metal signs to each valve and alarm device.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.1.5   Waterflow Test Connection</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include for wet pipe systems only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide test connections approximately<MET> 1.83 m</MET><ENG> 6 feet</ENG> above the floor for each standpipe system or portion of 
each standpipe system equipped with an alarm device; locate downstream and adjacent to each alarm actuating device.  
Provide test connection piping to a location where the discharge will be readily visible and where water may 
be discharged without property damage.  Discharge to janitor sinks or similar fixtures shall not be permitted.  
Provide discharge orifice equivalent to<MET> 15 mm</MET><ENG> 1/2 inch</ENG> sprinkler orifice.  [The penetration of the exterior wall 
shall be no greater than [<ENG> 2 feet</ENG><MET> 0.61 meter</MET>] [_____] above finished grade.]</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.6   Main Drains</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include for wet pipe systems only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide separate drain piping to discharge at safe points outside each building or to sight cones attached to 
drains of adequate size to readily receive the full flow from each drain under maximum pressure.  Provide auxiliary 
drains as required by <RID>NFPA 13</RID> and <RID>NFPA 14</RID>.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.1.7   Pipe Sleeves</TTL><BRK/>
<BRK/>
<TXT>Provide where piping passes entirely through walls, floors, roofs and partitions.  Secure sleeves in position 
and location during construction. Provide sleeves of sufficient length to pass through entire thickness of walls, 
floors, roofs and partitions.  Provide one inch minimum clearance between exterior of piping and interior of 
sleeve or core-drilled hole.  Firmly pack space with mineral wool insulation.  Seal space at both ends of the 
sleeve or core-drilled hole with plastic waterproof cement which will dry to a firm but pliable mass, or provide 
a mechanically adjustable segmented elastomeric seal.  In fire walls and fire floors, seal both ends of pipe 
sleeves or core-drilled holes with UL listed fill, void, or cavity material.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.7.1   Sleeves in Masonry and Concrete Walls, Floors, and Roofs</TTL><BRK/>
<BRK/>
<TXT>Provide hot-dip galvanized steel, ductile-iron, or cast-iron sleeves.  Core drilling of masonry and concrete 
may be provided in lieu of pipe sleeves when cavities in the core-drilled hole are completely grouted smooth.  
Extend sleeves in floor slabs<MET> 76 mm</MET><ENG> 3 inches</ENG> above finished floors.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.7.2   Sleeves in Partitions</TTL><BRK/>
<BRK/>
<TXT>Provide 26 gage galvanized steel sheet.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.1.8   Escutcheon Plates</TTL><BRK/>
<BRK/>
<TXT>Provide one piece or split hinge type metal plates for piping passing through walls, floors, and ceilings in 
both exposed and concealed spaces.  Provide polished stainless steel plates or chromium-plated finish on copper 
alloy plates in finished spaces.  Provide paint finish on metal plates in unfinished spaces.  Securely anchor 
plates in place.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.9   <SUB>Fire Department Connections</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Consult Division FPE for diameter and thread type for fire department 
hose connections in use.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide connections approximately<MET> one meter</MET><ENG> 3 feet</ENG> above finish grade, of the approved two-way type with [<MET>[65] 
[_____] mm</MET><ENG>[2.5] [_____] inch</ENG> National Standard] female hose threads with plug, chain, and identifying fire department 
connection escutcheon plate.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.1.10   <SUB>Alarm Valves</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include for wet pipe systems only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide variable pressure type alarm valve complete with retarding chamber, alarm test valve, alarm shutoff valve, 
drain valve, pressure gages, accessories, and appurtenances for the proper operation of the system.  The alarm 
shut-off valve in the piping between the alarm valve and the alarm pressure switch shall be a UL listed electrically 
supervised quarter-turn valve.  Connection of switch shall be under Section [<SRF>28 31 74.00 20</SRF> INTERIOR FIRE DETECTION 
AND ALARM SYSTEM.]  [<SRF>28 31 63.00 20</SRF> ADDRESSABLE INTERIOR FIRE DETECTION AND ALARM SYSTEM.]</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.11   <SUB>Water Motor Alarms</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include for wet pipe systems only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide alarms of the approved weatherproof and guarded type, to sound locally on the flow of water in each corresponding 
standpipe.  Mount alarms on the outside of the outer walls of each building.  Provide separate drain piping directly 
to exterior of building.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.12   <SUB>Pressure Switch</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include for wet pipe systems only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide switch with circuit opener or closer [SPDT contacts] for the automatic transmittal of an alarm over the 
facility fire alarm system.  Connect into the building fire alarm system.  Alarm actuating device shall have 
mechanical diaphragm controlled retard device adjustable from 10 to 60 seconds and shall instantly recycle.  </TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.13   <SUB>Waterflow Detector</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include for wet pipe systems only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide vane-type waterflow detector.  Provide detector with adjustable retard feature to prevent false alarms 
caused by momentary water surges. Connect into the building fire alarm system.  [Alarm actuating device shall 
have mechanical diaphragm controlled retard device adjustable from 10 to 60 seconds and shall instantly recycle.]  
Provide detector [at the base of each standpipe riser above main check valve] [where indicated] in accordance 
with manufacturers instructions.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.14   <SUB>Fire Hose Cabinets</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide [recessed] [semi recessed] [surface]-mounted cabinets where indicated.  Cabinets shall be prime grade, 
cold-rolled, reannealed, process-leveled, furniture steel.  Fabricate cabinet from 20 gage steel and door and 
trim from 18 gage steel.  Provide fully welded joints ground smooth.  On each jamb, provide at least two anchors 
or reinforcements spaced approximately<MET> 610 mm</MET><ENG> 24 inches</ENG> apart for building in or attaching the cabinets to adjacent 
construction.  Doors shall be flush hollow metal type with fully welded joints ground smooth and full glazed 
opening.  Provide door with continuous hinge, latch and pull.  Hinge door for 180 degree opening.  Glass shall 
conform to <RID>ASTM C 1036</RID> and shall be Type II (flat wired glass), Class 1 (clear), Form 1 (wired, polished both 
sides), Quality q 8 (glazing quality), diamond or square wire mesh,<MET> 6.35 mm</MET><ENG> 1/4 inch</ENG> thick.  Factory finish cabinet 
inside and out with one coat of enamel applied over a primer.  Interior finish color shall be white.  Exterior 
finish color shall be [_____].  [Fabricate cabinet with sufficient interior space to store one fire extinguisher.]</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.15   <SUB>Valve Tamper Switch</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include for wet pipe systems only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide valve tamper switch(es) to monitor the open position of valve(s) controlling water supply to the standpipe 
system.  Switch contacts shall transfer from the normal (valve open) position to the off-normal (valve closed) 
position during the first two revolutions of the hand wheel or when the stem of the valve has moved not more 
than one-fifth of the distance from its normal position.  Switch shall be tamper resistant.  Removal of the cover 
shall cause switch to operate into the off-normal position.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.16   Fire Pumps</TTL><BRK/>
<BRK/>
<TXT>Provide as specified in Section <SRF>21 30 00</SRF> FIRE PUMPS.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.17   <SUB>Backflow Preventer</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide [reduced pressure principle] [double check] valve assembly backflow preventer with OS&amp;Y gate valve 
on both ends.  Each check valve shall have a drain.  Backflow prevention assemblies shall have current "Certificate 
of Approval from the Foundation for Cross-Connection Control and Hydraulic Research, <RID>FCCCHR List</RID>.  Listing of 
the specific make, model, design, and size in the <RID>FCCCHR List</RID> shall be acceptable as the required documentation."</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>2.2   BURIED PIPING SYSTEMS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.2.1   <SUB>Buried Pipe and Fittings</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For pipe sizes larger than<MET> 305 mm</MET><ENG> 12 inches</ENG>, method for pipe anchorage 
including pipe clamps and rods shall be shown on the drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Requirements for buried piping systems<MET> 1.52 m</MET><ENG> 5 feet</ENG> beyond the building 
walls shall be specified in Section 33 11 00 WATER DISTRIBUTION.  Careful coordination 
is required to insure that materials rated for fire service are specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NFPA 24</RID>, outside coated, cement lined, ductile iron pipe and fittings for piping under the building and to a 
point<MET> 1.52 m</MET><ENG> 5 feet</ENG> outside the building walls.  Anchor the joints in accordance with <RID>NFPA 24</RID> using pipe clamps 
and steel rods.  Minimum pipe size shall be<MET> 150 mm</MET><ENG> 6 inches</ENG>.  Minimum depth of cover shall be [_____]<MET> [one meter]</MET><ENG>
 [3] feet</ENG>.  Piping more than<MET> 1.52 m</MET><ENG> 5 feet</ENG> outside the building walls shall be provided under Section 
<SRF>33 11 00</SRF> WATER DISTRIBUTION.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.2   Buried Utility Warning and Identification Tape</TTL><BRK/>
<BRK/>
<TXT>Provide detectable tape in accordance with Section <SRF>31 00 00</SRF> EARTHWORK.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.3   ELECTRICAL WORK</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit Section 26 20 00, INTERIOR DISTRIBUTION SYSTEM and include as part 
of the project specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When project includes requirement for a building fire alarm system, include 
Section 28 31 74.00 20 , INTERIOR FIRE DETECTION AND ALARM SYSTEM, or Section 
28 31 63.00 20, ANALOG/ADDRESSABLE INTERIOR FIRE ALARM SYSTEM in the project 
specification.  When project requires only tying into an existing building fire 
alarm system, fire alarm wiring should be specified in this section.  Edit this 
paragraph to suit project requirements.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide electrical work associated with this section under Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM, except 
for fire alarm wiring.  Provide fire alarm wiring and connection to fire alarm systems under Section [
<SRF>28 31 74.00 20</SRF> INTERIOR FIRE DETECTION AND ALARM SYSTEM] [<SRF>28 31 63.00 20</SRF> ADDRESSABLE INTERIOR FIRE DETECTION 
AND ALARM SYSTEM.][this section in accordance with <RID>NFPA 70</RID> and <RID>NFPA 72</RID>].</TXT><BRK/>
<BRK/>
<SPT>[<TTL>2.3.1   Wiring</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete this paragraph if Section 28 31 74.00 20, INTERIOR FIRE DETECTION 
AND ALARM SYSTEM is included in the project specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide fire alarm wiring and connections to fire alarm systems, under this section and conforming to <RID>NFPA 70</RID>
, and <RID>NFPA 72</RID>.  Wire for 120 volt circuits shall be No. 12 AWG minimum solid conductor.  Wire for low voltage 
DC circuits shall be No. [14] [16] AWG minimum solid conductor.  All wiring shall be color coded.  Wiring, conduit 
and devices exposed to water or weather shall be weatherproof.  Wiring, conduit and devices located in hazardous 
atmospheres, as defined by <RID>NFPA 70</RID> [and as shown], shall be explosion proof.  All conduit shall be minimum<MET> 20 
mm</MET><ENG> 3/4 inch</ENG> size.  Identify circuit conductors within each enclosure where a tap, splice or termination is made.  
Identify conductors by plastic coated self sticking printed markers or by heat-shrink type sleeves.  Attach the 
markers in a manner that will not permit accidental detachment.</TXT><BRK/>
<BRK/>
]</SPT></SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   EXCAVATION, BACKFILLING, AND COMPACTING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit Section 31 00 00 EARTHWORK and include as part of the project specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide under this section as specified in Section <SRF>31 00 00</SRF> EARTHWORK.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   CONNECTIONS TO EXISTING WATER SUPPLY SYSTEMS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate with Section 33 11 00 WATER DISTRIBUTION for this work.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Connections to existing water supply system are specified in Section <SRF>33 11 00</SRF> WATER DISTRIBUTION.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3   STANDPIPE SYSTEM INSTALLATION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include bracketed text for wet pipe systems only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Equipment, materials, installation, workmanship, fabrication, assembly, erection, examination, inspection, and 
testing shall be in accordance with the NFPA standards referenced herein.  Install piping straight and true to 
bear evenly on hangers and supports.  [Conceal piping to the maximum extent possible.  Piping shall be inspected, 
tested and approved before being concealed.]  Provide fittings for changes in direction of piping and for all 
connections Make changes in piping sizes through standard reducing pipe fittings; do not use bushings.  Cut pipe 
accurately and work into place without springing or forcing.  Ream pipe ends and free pipe and fittings from 
burrs.  Clean with solvent to remove all varnish and cutting oil prior to assemble.  Make screw joints with PTFE 
tape applied to male thread only.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4   DISINFECTION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete this paragraph for dry pipe systems and when the water supply 
for a wet pipe system is non-potable water.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Disinfect new water piping from the point of connection at the water main and existing water piping affected 
by the Contractor's operation in accordance with <RID>AWWA C651</RID>.  Exercise caution when mixing chlorine disinfectant 
solutions.  Fill piping systems with solution containing minimum of 50 parts per million of free available chlorine 
and allow solution to stand for a minimum of 24 hours.  Flush solution from systems with clean water until maximum 
residual chlorine content is not greater than 0.2 parts per million.  Obtain at least two consecutive satisfactory 
bacteriological samples from new water piping, analyze by a certified laboratory, and submit results prior to 
new water piping being placed into service.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5   FIELD PAINTING</TTL><BRK/>
<BRK/>
<TXT>Field painting of fire extinguishing standpipe system shall be specified in Section <SRF>09 90 00</SRF> PAINTS AND COATINGS.  
Field painting requirements for "Fire Extinguishing Sprinkler Systems" shall apply.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.5.1   Piping Labels</TTL><BRK/>
<BRK/>
<TXT>Provide permanent labels in mechanical rooms, spaced at<MET> 6 meters</MET><ENG> 20 foot</ENG> maximum intervals along pipe, indicating 
"STANDPIPE."</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.6   ELECTRICAL WORK</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit Section 26 20 00, INTERIOR DISTRIBUTION SYSTEM and include as part 
of the project specification</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When project includes requirement for a building fire alarm system, include 
Section 28 31 74.00 20 , INTERIOR FIRE DETECTION AND ALARM SYSTEM, or Section 
28 31 63.00 20, ADDRESSABLE INTERIOR FIRE DETECTION AND ALARM SYSTEM  in the 
project specification.  When project requires only tying into an existing building 
fire alarm system, fire alarm wiring should be specified in this section.  Edit 
this paragraph to suit project requirements.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide electrical work associated with this section under Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM, except 
for fire alarm wiring.  Provide fire alarm wiring and connection to fire alarm systems under  Section [
<SRF>28 31 74.00 20</SRF> INTERIOR FIRE DETECTION AND ALARM SYSTEM] [<SRF>28 31 63.00 20</SRF> ADDRESSABLE INTERIOR FIRE DETECTION 
AND ALARM SYSTEM.] [this section in accordance with <RID>NFPA 70</RID> and <RID>NFPA 72</RID>].</TXT><BRK/>
<BRK/>
<SPT>[<TTL>3.6.1   Wiring</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete this paragraph if Section 28 31 74.00 20, INTERIOR FIRE DETECTION 
AND ALARM SYSTEM is included in the project specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide fire alarm wiring and connections to fire alarm systems, under this section in accordance with <RID>NFPA 70</RID>
, and <RID>NFPA 72</RID>.  Provide wiring in rigid metal conduit or intermediate metal conduit, except electrical metallic 
tubing may be used in dry locations not enclosed in concrete or where not subject to mechanical damage.  Do not 
run low voltage DC circuits in the same conduit with AC circuits.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.7   FLUSHING</TTL><BRK/>
<BRK/>
<TXT>Flush the piping system with potable water in accordance with <RID>NFPA 14</RID>.  Continue flushing operation until water 
is clear, but for not less than 10 minutes.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8   FIELD QUALITY CONTROL</TTL><BRK/>
<BRK/>
<TXT>Prior to initial operation, inspect equipment and piping systems for compliance with drawings, specifications, 
and manufacturer's submittals.  Perform tests in the presence of the Contracting Officer to determine conformance 
with the specified requirements.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.8.1   <SUB>Preliminary Tests</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify hydrostatic test not less than<MET> 1379 kPa or 345 kPa</MET><ENG> 200 psi or 
50 psi</ENG> above the maximum working pressure when the maximum working pressure 
is greater than<MET> 1034 kPa</MET><ENG> 150 psi</ENG>.  Include bracketed text for wet pipe systems 
only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><TST>Each piping system shall be hydrostatically tested at<MET> [1379] [_____] kPa (gage)</MET><ENG> [200] [_____] psig</ENG> in accordance 
with <RID>NFPA 14</RID> and <RID>NFPA 24</RID> and shall show no leakage or reduction in gauge pressure after 2 hours.  The Contractor 
shall conduct complete preliminary tests, which shall encompass all aspects of system operation.  [Individually 
test alarms, and all other components and accessories to demonstrate proper functioning.  Test water flow alarms 
by flowing water.] When tests have been completed and all necessary corrections made, submit to the Contracting 
Officer a signed and dated certificate, similar to that specified in <RID>NFPA 13</RID>, attesting to the satisfactory completion 
of all testing and stating that the system is in operating condition.  Also include a written request for a formal 
inspection and test.</TST></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.2   Formal Inspection and Tests (<SUB>Acceptance Tests</SUB>)</TTL><BRK/>
<BRK/>
<TXT>The [[_____] Division] [Engineering Field Activity [_____]], , Naval Facilities Engineering Command, Fire Protection 
Engineer, will witness formal tests and approve all systems before they are accepted.  The system shall be considered 
ready for such testing only after all necessary preliminary tests have been made and all deficiencies found have 
been corrected to the satisfaction of the Contracting Officer and written certification to this effect is received 
by the Division Fire Protection Engineer.  Submit the request for formal inspection at least 15 working days 
prior to the date the inspection is to take place.  Experienced technicians regularly employed by the Contractor 
in the installation of both the mechanical and electrical portions of such systems shall be present during the 
inspection and shall conduct the testing.  All instruments, personnel, appliances and equipment for testing shall 
be furnished by the Contractor.  [The Government will furnish water for the tests.]  All necessary tests encompassing 
all aspects of system operation shall be made including the following, and any deficiency found shall be corrected 
and the system retested at no cost to the Government.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.8.2.1   Flow Test</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include bracketed text for dry pipe systems only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><TST>Perform flow tests of each standpipe riser in accordance with NFPA 14.  Affix<MET> [0-1379] [0-2068] kPa</MET><ENG> [0-200] [0-300] 
psi</ENG> pressure gauges to lowest hose valve and next-to-highest hose valve.  Connect lined,<MET> 65 mm</MET><ENG> 2 1/2 inch</ENG> diameter 
fire hose with underwriter's playpipe to highest hose valve and flow at least<MET> 946 L/m</MET><ENG> 250 gpm</ENG> for 5 minutes from 
standpipe to a safe location outside the building.  [For dry pipe system, supply system through<MET> 65 mm</MET><ENG> 2 1/2 inch</ENG>
 fire hose connected to the nearest fire hydrant which is approximately [_____]<MET> meters</MET><ENG> feet</ENG> away.]  Furnish hose, 
nozzles and fittings required for this test.</TST></TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.8.2.2   Alarm Testing</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include for wet pipe systems only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TST><ITM INDENT="-0.33">a.  Each pressure switch, waterflow detector, and water motor gong shall be activated by flow 
of water.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Each valve tamper switch shall be activated by partially closing the associated control 
valve.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Alarm annunciation at the fire alarm control panel shall be verified.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Circuit supervision shall be demonstrated.</ITM></TST><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.8.3   Additional Tests</TTL><BRK/>
<BRK/>
<TXT><TST>When deficiencies, defects or malfunctions develop during the tests required, all further testing of the system 
shall be suspended until proper adjustments, corrections or revisions have been made to assure proper performance 
of the system.  If these revisions require more than a nominal delay, the Contracting Officer shall be notified 
when the additional work has been completed, to arrange a new inspection and test of the system.  All tests required 
shall be repeated prior to final acceptance, unless directed otherwise.</TST></TXT><BRK/>
<BRK/></SPT>
</SPT></PRT>    <END/><BRK/></SEC>