<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><BRK/>
<HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA         UFGS-21 13 18.00 10 (November 2008)<BRK/>
                                       -----------------------------------<BRK/>
Preparing Activity:  <PRA>USACE</PRA>             Superseding<BRK/>
                                       UFGS-21 13 18.00 10 (October 2007)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 21 13 18.00 10</SCN><BRK/>
<BRK/>
<STL>PREACTION AND DELUGE SPRINKLER SYSTEMS, FIRE PROTECTION</STL><BRK/>
<DTE>11/08</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>preaction and deluge 
fire protection sprinkler systems</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Because preaction systems are more costly, less reliable, and require 
more maintenance than wet-pipe systems, they should be used only where justified 
by occupancy conditions.  Deluge systems are "open head" systems which discharge 
all sprinklers upon system actuation.  The use of deluge systems should be limited 
to special hazard situations.<BRK/>
<BRK/>
The Designer will edit this specification section for either a performance-designed 
system or a fully designed system as applicable.<BRK/>
<BRK/>
This specification section is primarily intended for performance designed systems, 
i.e. systems where the size, layout, and support of branch lines and cross mains, 
and the layout of sprinkler heads will be designed by the Contractor.<BRK/>
<BRK/>
The Designer will provide the following information in the contract documents 
for performance designed systems.  This information will be in accordance with 
Military Handbook 1008C.<BRK/>
<BRK/>
(1) Show the layout and size of all piping and equipment from the point of connection 
to the water supply, to the sprinkler cross mains.  The contract drawings must 
include a detailed sprinkler riser diagram.  Water velocity in the piping should 
not exceed 6 m/s (20 ft/s).<BRK/>
<BRK/>
(2) Show location and size of service mains, interior feed mains, control valves, 
sprinkler risers, drain lines, sectional valves, and inspector's test valves 
and switches on the drawings.<BRK/>
<BRK/>
(3) Specify waterflow data including hydrant flow results, including the location 
where the hydrant flow test was conducted, the location and size of existing 
mains and new water supply lines that will serve the sprinkler system (including 
all supervisory valves), and the location and size of all risers.<BRK/>
<BRK/>
(4) Highlight or clearly indicate the area(s) to be protected by sprinklers 
on the drawings.<BRK/>
<BRK/>
(5) Specify waterflow requirements including the design density, design area, 
the hose stream demand (including location of the hose stream demand), the duration 
of supply, and sprinkler spacing and area of coverage in this section.<BRK/>
<BRK/>
(6) Show the location of the backflow preventer (including provisions for a 
drain and access for maintenance) where the potable water supply system is at 
risk of contamination by the sprinkler system on the drawings.<BRK/>
<BRK/>
(7) Show all provisions necessary for forward flow testing of the backflow preventer 
at system demand as required by NFPA 13 on the drawings.  Indicate location 
of all components and  required items including test ports for pressure measurements 
both upstream and downstream of the backflow preventer, a drain to the building 
exterior, and appropriate, permanent means of disposing of the large quantity 
of water that will be involved in the initial test and subsequent annual tests.<BRK/>
<BRK/>
(8) Air compressors, including controls and complete installation details, including 
piping, control valves, mounting base.<BRK/>
<BRK/>
(9) Highlight all concealed spaces on the drawings that require sprinkler protection, 
such as spaces above suspended ceilings that are either built of combustible 
material or are intended for storing combustible materials.<BRK/>
<BRK/>
(10) Provide details on the drawings of pipe restraints for underground piping.  
This includes details of pipe clamps, tie rods, mechanical retainer glands, 
and thrust blocks.<BRK/>
<BRK/>
When connecting to an existing water distribution system, waterflow tests will 
be conducted to determine available water supply for the sprinkler system.  
The Designer will either perform or witness the waterflow test.  The waterflow 
test results (including date test is performed) should be included in the Project 
Development Brochure; however it is critical that the waterflow test results 
be included in the design documents no later than the concept submission.  Note 
that the availability of and funding for the Designer to participate or witness 
the waterflow test will be necessary.  The need for fire pumps or a water tank 
can in many instances have a significant impact on the amount programmed for 
design and construction of a facility.<BRK/>
<BRK/>
A fully designed system will include the items listed above and all additional 
information required that is required by Military Handbook 1008C and NFPA 13 
for a fully operational system.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification.  The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
<BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
<BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>AMERICAN SOCIETY OF SANITARY ENGINEERING (ASSE)</ORG><BRK/><BRK/><RID>ASSE 1015</RID><RTL>(2005) Double Check Backflow Prevention Assemblies and Double Check Fire Protection Backflow Prevention Assemblies</RTL><BRK/><BRK/></REF><REF><ORG>AMERICAN WATER WORKS ASSOCIATION (AWWA)</ORG><BRK/><BRK/><RID>AWWA 10084</RID><RTL>(2005) Standard Methods for the Examination of Water and Wastewater</RTL><BRK/><BRK/><RID>AWWA B300</RID><RTL>(2004) Hypochlorites</RTL><BRK/><BRK/><RID>AWWA B301</RID><RTL>(2004) Liquid Chlorine</RTL><BRK/><BRK/><RID>AWWA C104/A21.4</RID><RTL>(2003) Cement-Mortar Lining for Ductile-Iron Pipe and Fittings for Water</RTL><BRK/><BRK/><RID>AWWA C110/A21.10</RID><RTL>(2008) Ductile-Iron and Gray-Iron Fittings for Water</RTL><BRK/><BRK/><RID>AWWA C111/A21.11</RID><RTL>(2000) Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings</RTL><BRK/><BRK/><RID>AWWA C151/A21.51</RID><RTL>(2002; Errata 2002) Ductile-Iron Pipe, Centrifugally Cast, for Water</RTL><BRK/><BRK/><RID>AWWA C203</RID><RTL>(2002) Coal-Tar Protective Coatings and Linings for Steel Water Pipelines - Enamel and Tape - Hot-Applied</RTL><BRK/><BRK/><RID>AWWA C651</RID><RTL>(2005; Errata 2005) Standard for Disinfecting Water Mains</RTL><BRK/><BRK/><RID>AWWA C652</RID><RTL>(2002) Disinfection of Water-Storage Facilities</RTL><BRK/><BRK/></REF><REF><ORG>ASME INTERNATIONAL (ASME)</ORG><BRK/><BRK/><RID>ASME B16.1</RID><RTL>(2005) Standard for Gray Iron Threaded Fittings; Classes 125 and 250</RTL><BRK/><BRK/><RID>ASME B16.11</RID><RTL>(2005) Forged Fittings, Socket-Welding and Threaded</RTL><BRK/><BRK/><RID>ASME B16.21</RID><RTL>(2005) Nonmetallic Flat Gaskets for Pipe Flanges</RTL><BRK/><BRK/><RID>ASME B16.9</RID><RTL>(2007) Standard for Factory-Made Wrought Steel Buttwelding Fittings</RTL><BRK/><BRK/><RID>ASME B18.2.2</RID><RTL>(1987; R 2005) Standard for Square and Hex Nuts</RTL><BRK/><BRK/></REF><REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 135/A 135M</RID><RTL>(2006) Standard Specification for Electric-Resistance-Welded Steel Pipe</RTL><BRK/><BRK/><RID>ASTM A 183</RID><RTL>(2003) Standard Specification for Carbon Steel Track Bolts and Nuts</RTL><BRK/><BRK/><RID>ASTM A 193/A 193M</RID><RTL>(2008b) Standard Specification for Alloy-Steel and Stainless Steel Bolting Materials for High-Temperature Service</RTL><BRK/><BRK/><RID>ASTM A 449</RID><RTL>(2007b) Specification for Hex Cap Screws, Bolts, and Studs, Steel, Heat Treated, 120/105/90 ksi Minimum Tensile Strength, General Use</RTL><BRK/><BRK/><RID>ASTM A 47/A 47M</RID><RTL>(1999; R 2004) Standard Specification for Steel Sheet, Aluminum-Coated, by the Hot-Dip Process</RTL><BRK/><BRK/><RID>ASTM A 53/A 53M</RID><RTL>(2007) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless</RTL><BRK/><BRK/><RID>ASTM A 536</RID><RTL>(1984e1; R 2004) Standard Specification for Ductile Iron Castings</RTL><BRK/><BRK/><RID>ASTM A 563</RID><RTL>(2007a) Standard Specification for Carbon and Alloy Steel Nuts</RTL><BRK/><BRK/><RID>ASTM A 563M</RID><RTL>(2007) Standard Specification for Carbon and Alloy Steel Nuts (Metric)</RTL><BRK/><BRK/><RID>ASTM A 795/A 795M</RID><RTL>(2008) Standard Specification for Black and Hot-Dipped Zinc-Coated (Galvanized) Welded and Seamless Steel Pipe for Fire Protection Use</RTL><BRK/><BRK/><RID>ASTM F 436</RID><RTL>(2007a) Hardened Steel Washers</RTL><BRK/><BRK/><RID>ASTM F 436M</RID><RTL>(2004) Hardened Steel Washers (Metric)</RTL><BRK/><BRK/></REF><REF><ORG>FM GLOBAL (FM)</ORG><BRK/><BRK/><RID>FM P7825a</RID><RTL>(2005) Approval Guide Fire Protection</RTL><BRK/><BRK/><RID>FM P7825b</RID><RTL>(2005) Approval Guide Electrical Equipment</RTL><BRK/><BRK/></REF><REF><ORG>INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)</ORG><BRK/><BRK/><RID>IEEE C62.41.1</RID><RTL>(2002) IEEE Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power Circuits</RTL><BRK/><BRK/><RID>IEEE C62.41.2</RID><RTL>(2002) IEEE Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits</RTL><BRK/><BRK/></REF><REF><ORG>MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS INDUSTRY (MSS)</ORG><BRK/><BRK/><RID>MSS SP-71</RID><RTL>(2005) Standard for Gray Iron Swing Check Valves, Flanged and Threaded Ends</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 101</RID><RTL>(2008) Life Safety Code, 2006 Edition</RTL><BRK/><BRK/><RID>NFPA 13</RID><RTL>(2006; Errata 2007; Amendment 1 2008) Installation of Sprinkler Systems</RTL><BRK/><BRK/><RID>NFPA 13D</RID><RTL>(2006) Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes</RTL><BRK/><BRK/><RID>NFPA 13R</RID><RTL>(2006) Installation of Sprinkler Systems in Residential Occupancies Up to and Including Four Stories in Height</RTL><BRK/><BRK/><RID>NFPA 1963</RID><RTL>(2003) Standard for Fire Hose Connections</RTL><BRK/><BRK/><RID>NFPA 24</RID><RTL>(2006) Standard for the Installation of Private Fire Service Mains and Their Appurtenances</RTL><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/><RID>NFPA 72</RID><RTL>(2006) National Fire Alarm Code</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET)</ORG><BRK/><BRK/><RID>NICET 1014-7</RID><RTL>(2003) Program Detail Manual for Certification in the Field of Fire Protection Engineering Technology (Field Code 003) Subfield of Automatic Sprinkler System Layout</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL Bld Mat Dir</RID><RTL>(2008) Building Materials Directory</RTL><BRK/><BRK/><RID>UL Fire Prot Dir</RID><RTL>(2008) Fire Protection Equipment Directory</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   SYSTEM DESCRIPTION</TTL><BRK/>
<BRK/>
<LST>a.  Furnish piping offsets, fittings, and any other accessories as required to provide a complete installation 
and to eliminate interference with other construction.  Install sprinkler over and under ducts, piping 
and platforms when such equipment can negatively affect or disrupt the sprinkler discharge pattern and 
coverage.</LST><BRK/>
<BRK/>
<LST>b.  Provide [preaction] [deluge] sprinkler system(s) in [areas indicated on the drawings] [_____].  The 
sprinkler system shall provide fire sprinkler protection for the entire area.  Except as modified herein, 
the system shall meet the requirements of <RID>NFPA 13</RID> and <RID>NFPA 72</RID>.  The sprinkler system shall be a single 
interlocked system that requires the actuation of an alarm initiating device to open the water control 
(deluge) valve.</LST><BRK/>
<BRK/>
<LST>c.  Design any portions of the sprinkler system that are not indicated on the drawings or are not specified 
herein, including locating sprinklers, piping, and equipment, and size piping and equipment.  Determine 
pipe sizes which are not indicated on the drawings by hydraulic calculations.</LST><BRK/>
<BRK/>
<SPT><TTL>1.2.1   Hydraulic Design</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Applications requiring multiple densities/design areas must be referred 
to and shown on the drawings.<BRK/>
<BRK/>
Systems covering 140 square meters (1500 square feet) or greater will be hydraulically 
designed.  Only systems less than 140 square meters (1500 square feet) may be 
designed using the pipe schedule method of NFPA 13.  This section must be edited 
if the system is to be designed using the pipe schedule method.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Hydraulically design the system to discharge a minimum density of [_____]<MET> L/min per square m</MET><ENG> gpm/square foot</ENG> 
over the hydraulically most demanding<MET> [280] [_____] square m</MET><ENG> [3,000] [_____] square feet</ENG> of floor area.  The 
minimum pipe size for branch lines in gridded systems shall be<MET> 32 mm</MET><ENG> 1-1/4 inch</ENG>.  Hydraulic calculations shall 
be in accordance with the Area/Density Method of <RID>NFPA 13</RID>.  Water velocity in the piping shall not exceed<MET> 6 m/s</MET><ENG>
 20 ft/s</ENG>.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.2.1.1   Hose Demand</TTL><BRK/>
<BRK/>
<TXT>Add an allowance for exterior hose streams of [_____]<MET> L/min</MET><ENG> gpm</ENG> to the sprinkler system demand [at the fire hydrant 
shown on the drawings closest to the point where the water service enters the building] [at the point of connection 
to the existing water system].  [An allowance for interior hose stations of [_____]<MET> L/min</MET><ENG> gpm</ENG> shall also be added 
to the sprinkler system demand.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.2.1.2   Basis for Calculations</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The design must include an adequate water supply to meet the sprinkler 
water demand.  The designer must provide water flow test results and hydraulic 
calculations to ensure that the system demand will be met.</NPR><BRK/>
<BRK/>
<NPR>Design Calculations:  The designer will provide detailed hydraulic calculations 
that clearly demonstrate that the water supply will meet the demand of the sprinkler 
system and hose streams.  Calculations will be submitted with the concept design 
submission.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Base the design of the system upon a water supply with a static pressure of [_____], and a flow of [_____] at 
a residual pressure of [_____].  Water supply shall be presumed available [at the point of connection to existing] 
[at the base of the riser] [_____].  Base hydraulic calculations [upon the Hazen-Williams formula with a "C" 
value of 120 for galvanized steel piping, 140 for new cement-lined ductile-iron piping, and [100] [_____] for 
existing underground piping] [on operation of the fire pump(s) provided in Section <SRF>21 30 00</SRF> FIRE PUMPS].</TXT><BRK/>
<BRK/>
<LST>a.  Outline <SUB>hydraulic calculations</SUB> as in <RID>NFPA 13</RID>, except that calculations shall be performed by computer 
using software intended specifically for fire protection system design using the design data shown on 
the drawings.  Software that uses k-factors for typical branch lines is not acceptable.  Calculations 
shall substantiate that the design area used in the calculations is the most demanding hydraulically.</LST><BRK/>
<BRK/>
<LST>b.  Plot water supply curves and system requirements on semi-logarithmic graph paper so as to present 
a summary of the complete hydraulic calculation.  Provide a summary sheet listing sprinklers in the design 
area and their respective hydraulic reference points, elevations, actual discharge pressures and actual 
flows.  Indicate elevations of hydraulic reference points (nodes).  Documentation shall identify each 
pipe individually and the nodes connected thereto.  Indicate for each pipe the diameter, length, flow, 
velocity, friction loss, number and type fittings, total friction loss in the pipe, equivalent pipe length 
and Hazen-Williams coefficient.</LST><BRK/>
<BRK/>
<LST>c.  For gridded systems, calculations shall show peaking of demand area friction loss to verify that 
the hydraulically most demanding area is being used.  Also for gridded systems, include a flow diagram 
indicating the quantity and direction of flows.  A drawing showing hydraulic reference points (nodes) 
and pipe designations used in the calculations shall be included and shall be independent of shop drawings.</LST><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.2.2   Sprinkler Coverage</TTL><BRK/>
<BRK/>
<TXT>Uniformly space sprinklers on branch lines.  In buildings protected by automatic sprinklers, provide coverage 
throughout 100 percent of the building.  This includes, but is not limited to, telephone rooms, electrical equipment 
rooms, boiler rooms, switchgear rooms, transformer rooms, and other electrical and mechanical spaces.  Coverage 
per sprinkler shall be in accordance with <RID>NFPA 13</RID>, but shall not exceed<MET> 9 square m</MET><ENG> 100 square feet</ENG> for extra 
hazard occupancies, <MET>12 square m</MET><ENG> 130 square feet</ENG> for ordinary hazard occupancies, and<MET> 21 square m</MET><ENG> 225 square feet</ENG>
 for light hazard occupancies.  Exceptions are as follows:</TXT><BRK/>
<BRK/>
<LST>a.  Facilities that are designed in accordance with <RID>NFPA 13R</RID> and <RID>NFPA 13D</RID>.</LST><BRK/>
<BRK/>
<LST>b.  Sprinklers may be omitted from small rooms which are exempted for specific occupancies in accordance 
with <RID>NFPA 101</RID>.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>1.2.3   Control System</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The drawings must show the following information relative to the control 
and detection system: preaction or deluge system control panel, source of power 
for control panel, fire protection valve actuation devices, detectors, manual 
actuation stations, waterflow pressure switches, supervisory switches; notification 
appliances; connection to the building fire alarm control panel or other remote 
monitoring systems, and all power, control, alarm, supervisory and interconnecting 
wiring.  The designer will indicate the complete zoning of initiating devices 
and specify the descriptive zone labeling for each corresponding system annunciator.</NPR><BRK/>
<BRK/>
<NPR>All areas to be protected with preaction sprinklers must be equipped with the 
detectors necessary to activate the sprinkler system.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The control system shall meet the requirements of <RID>NFPA 72</RID>.  The control panel shall be listed in <RID>UL Fire Prot Dir</RID>
 or <RID>FM P7825a</RID> and <RID>FM P7825b</RID> for "Releasing Device Service".  The control panel and the solenoid valve that activates 
the water control valves shall be compatible with each other.  Compatibility shall be in accordance with specific 
UL listing or FM approval of the control equipment.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.2.3.1   Power Supply</TTL><BRK/>
<BRK/>
<TXT>Provide the primary operating power from two single-phase 120 VAC circuits.  Transfer from normal to backup power 
and restoration from backup to normal power shall be fully automatic and shall not initiate a false alarm.  Loss 
of primary power shall not prevent actuation of the respective automatic water control valve upon activation 
of any alarm initiating device.  Provide backup power through use of rechargeable, sealed, lead calcium storage 
batteries.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.2.3.2   Circuit Requirements</TTL><BRK/>
<BRK/>
<TXT>Connect alarm initiating devices to initiating device circuits (IDC), Style [D] [_____] or to signal line circuits 
(SLC), Style [6] [_____], in accordance with <RID>NFPA 72</RID>.  Alarm notification or indicating appliances shall be connected 
to indicating appliance circuit (IAC), Style [W] [X] in accordance with <RID>NFPA 72</RID>.  Provide a separate circuit 
for actuation of each individual automatic water control valve.  Fully supervise the circuits that actuate the 
water control valves so that the occurrence of a single open or a single ground fault condition in the interconnecting 
conductors will be indicated at the control panel.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.2.4   System Operational Features</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete manual actuation stations when not required.  For deluge systems, 
delete requirements for supervisory air pressure.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Include in the system a heat detection system, manual actuation stations, supervisory and alarm switches, alarm 
notification appliances, control panel and associated equipment.  Provide preaction sprinkler system piping with 
supervisory air pressure not to exceed<MET> 210 kPa</MET><ENG> 30 psig</ENG>.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.2.4.1   System Actuation</TTL><BRK/>
<BRK/>
<TXT>Activation of any [single heat detector] [2 heat detectors] or a single manual actuation station shall actuate 
alarm zone circuits of the control panel that, in turn, shall actuate the corresponding automatic water control 
valve.  Actuation of the automatic water control valve shall cause water to [fill the preaction system piping 
and be discharged from fused sprinklers] [discharge from the open sprinklers of the deluge system].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.2.4.2   Alarm Functions</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Drawings must indicate and detail the connection of the system control 
panel to the building alarm system and/or to the base-wide fire reporting system.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Activation of any heat detector or sprinkler pressure alarm switch or manual actuation station shall cause the 
illumination of the respective zone annunciator, and [activation of the building fire alarm system] [transmission 
of the alarm to the base-wide fire reporting system].  Valve tamper alarm shall be monitored by the system control 
panel and transmitted to the building fire alarm system as a trouble alarm.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.2.4.3   Supervisory Functions</TTL><BRK/>
<BRK/>
<TXT>The reduction of supervisory air pressure within the sprinkler system piping to less than<MET> [70] [_____] kPa</MET><ENG> [10] 
[_____] psi</ENG> or the occurrence of a single open or a single ground fault in any alarm initiating device circuit, 
in the automatic water control valve actuation circuit, in any alarm indicating appliance circuit or in other 
electrically supervised circuit shall cause the individually labelled control panel trouble light to be illuminated, 
the audible trouble alarm to be activated, and a trouble alarm to be transmitted [to the building fire alarm 
control panel] [and] [to base-wide fire reporting system].</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>1.3   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section <SRF>01 33 00</SRF> SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy, Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are for [Contractor Quality Control approval.][information only.  When used, a designation following the "G" 
designation identifies the office that will review the submittal for the Government.]  Submit the following in 
accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Shop Drawings</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  [Three] [_____] copies of the Sprinkler System Drawings, no later than [21] [_____] days prior 
to the start of sprinkler system installation.  The drawings shall conform to the requirements 
established for working plans as prescribed in <RID>NFPA 13</RID>.  Drawings shall include plan and elevation 
views demonstrating that the equipment will fit the allotted spaces with clearance for installation 
and maintenance.</ITM><BRK/>
<BRK/>
<ITM><SUB>As-Built Drawings</SUB></ITM><BRK/>
<BRK/>
<ITM>  As-built drawings, at least [14] [_____] days after completion of the Final Tests.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Fire Protection Specialist</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  The name and documentation of certification of the proposed Fire Protection Specialists, no 
later than [14] [_____] days after the Notice to Proceed and prior to the submittal of the sprinkler 
system shop drawings and hydraulic calculations.</ITM><BRK/>
<BRK/>
<ITM><SUB>Installer Qualifications</SUB></ITM><BRK/>
<BRK/>
<ITM>  The name and documentation of certification of the proposed Sprinkler System Installer, concurrent 
with submittal of the Fire Protection Specialist Qualifications.</ITM><BRK/>
<BRK/>
<ITM><SUB>List of the Submittals</SUB></ITM><BRK/>
<BRK/>
<ITM>  A list of the Fire Protection Related Submittals, no later than [7] [_____] days after the 
approval of the Fire Protection Specialist.</ITM><BRK/>
<BRK/>
<ITM><SUB>Materials and Equipment</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Manufacturer's catalog data included with the Sprinkler System Drawings for all items specified 
herein.  Hhighlight the data to show model, size, options, etc., that are intended for consideration.  
Data shall be adequate to demonstrate compliance with all contract requirements. In addition, 
provide a complete equipment list that includes equipment description, model number and quantity.</ITM><BRK/>
<BRK/>
<ITM><SUB>Spare Parts</SUB></ITM><BRK/>
<BRK/>
<ITM>  Spare parts data for each different item of material and equipment specified.</ITM><BRK/>
<BRK/>
<ITM><SUB>OnSite Training</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Proposed Onsite Training schedule, at least [14] [_____] days prior to the start of related 
training.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-05 Design Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Sway Bracing</SUB></ITM><BRK/>
<BRK/>
<ITM>  For systems that are required to be protected against damage from earthquakes, load calculations 
for sizing of sway bracing.</ITM><BRK/>
<BRK/>
<ITM><SUB>Hydraulic Calculations</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Hydraulic calculations, including a drawing showing hydraulic reference points and pipe segments.</ITM><BRK/>
<BRK/>
<ITM><SUB>Storage Batteries</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Calculations to substantiate the total requirements for supervisory and alarm power.  Include 
ampere-hour requirements for each system component and each control panel component or module, 
under both normal and alarm conditions.  The battery recharging period shall be included with 
the calculations.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Preliminary Tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Proposed procedures for Preliminary Tests, no later than [14] [_____] days prior to the proposed 
start of the tests.  Proposed date and time to begin Preliminary Tests, submitted with the Preliminary 
Tests Procedures.</ITM><BRK/>
<BRK/>
<ITM>  [Three] [_____] copies of the completed Preliminary Tests Reports, no later that [7] [_____] 
days after the completion of the Preliminary Tests.  The Preliminary Tests Report shall include 
both the Contractor's Material and Test Certificate for Underground Piping and the Contractor's 
Material and Test Certificate for Aboveground Piping.  All items in the Preliminary Tests Report 
shall be signed by the Fire Protection Specialist.</ITM><BRK/>
<BRK/>
<ITM><SUB>Final Acceptance Tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Proposed procedures for Final Acceptance Tests, no later than [14] [_____] days prior to the 
proposed start of the tests.  Proposed date and time to begin Final Acceptance Tests, submitted 
with the Final Acceptance Test Procedures.  Notification shall be provided at least [14] [_____] 
days prior to the proposed start of the test.  Notification shall include a copy of the Contractor's 
Material &amp; Test Certificates.</ITM><BRK/>
<BRK/>
<ITM>  [Three] [_____] copies of the completed Final Acceptance Tests Reports, no later that [7] 
[_____] days after the completion of the Final Acceptance Tests.  All items in the Final Acceptance 
Report shall be signed by the Fire Protection Specialist</ITM>.<BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Inspection by Fire Protection Specialist</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Concurrent with the Final Acceptance Test Report, certification by the Fire Protection Specialist 
that the sprinkler system is installed in accordance with the contract requirements, including 
signed approval of the Preliminary, Detection and Control Systems, and Final Acceptance Test 
Reports.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Operating and Maintenance Instructions</SUB></ITM><BRK/>
<BRK/>
<ITM>  [Six] [_____] manuals listing step-by-step procedures required for system startup, operation, 
shutdown, and routine maintenance, at least [14] [_____] days prior to field training.  The 
manuals shall include the manufacturer's name, model number, parts list, list of parts and tools 
that should be kept in stock by the owner for routine maintenance including the name of a local 
supplier, simplified wiring and controls diagrams, troubleshooting guide, and recommended service 
organization (including address and telephone number) for each item of equipment.  [Each service 
organization submitted shall be capable of providing [4] [_____] hour onsite response to a service 
call on an emergency basis.]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<TXT>Compliance with referenced NFPA standards is mandatory.  This includes advisory provisions listed in the appendices 
of such standards, as though the word "shall" had been substituted for the word "should" wherever it appears.  
Applicable material and installation standards referenced in Appendix A of <RID>NFPA 13</RID> and <RID>NFPA 24</RID> shall be considered 
mandatory the same as if such referenced standards were specifically listed in this specification.  In the event 
of a conflict between specific provisions of this specification and applicable NFPA standards, this specification 
shall govern.  Incorporate all requirements that exceed the minimum requirements of <RID>NFPA 13</RID> into the design.  
Reference to "authority having jurisdiction" shall be interpreted to mean the Contracting Officer.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.4.1   <SUB>Fire Protection Specialist</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Level IV may be selected where warranted by system complexity.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Perform the work specified in this section under the supervision of and certified by the Fire Protection Specialist 
who is a registered professional engineer and a Full Member of the Society of Fire Protection Engineers or who 
is certified as a Level [III] [IV] Technician by National Institute for Certification in Engineering Technologies 
(NICET) in the Automatic Sprinkler System Layout subfield of Fire Protection Engineering Technology in accordance 
with <RID>NICET 1014-7</RID>.  The Fire Protection Specialist shall prepare a <SUB>list of the submittals</SUB> from the Contract Submittal 
Register that relate to the successful installation of the sprinkler systems(s).  The submittals identified on 
this list shall be accompanied by a letter of approval signed and dated by the Fire Protection Specialist when 
submitted to the Government.The Fire Protection Specialist shall be regularly engaged in the design and installation 
of the type and complexity of system specified in the Contract documents, and shall have served in a similar 
capacity for at least three systems that have performed in the manner intended for a period of not less than 
6 months.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.2   <SUB>Installer Qualifications</SUB></TTL><BRK/>
<BRK/>
<TXT>Work specified in this section shall be performed by the Sprinkler System Installer.  The Installer shall be 
regularly engaged in the installation of the type and complexity of system specified in the Contract documents, 
and shall have served in a similar capacity for at least three systems that have performed in the manner intended 
for a period of not less than 6 months.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.3   <SUB>Shop Drawings</SUB></TTL><BRK/>
<BRK/>
<TXT>Submit shop drawings, on reproducible full-size mylar film, as specified herein and in the Submittals paragraph; 
update the Shop Drawings to reflect as-built conditions after all related work is completed.  Each set of drawings 
shall include the following:</TXT><BRK/>
<BRK/>
<ITM>  a. Descriptive index of drawings in the submittal with drawings listed in sequence by drawing 
number.  A legend identifying device symbols, nomenclature, and conventions used.</ITM><BRK/>
<BRK/>
<ITM>  b. Floor plans drawn to a scale not less than<MET> 1:100</MET><ENG> 1/8" = 1'-0"</ENG> which clearly show locations 
of sprinklers, risers, pipe hangers, seismic separation assemblies, sway bracing, inspector's 
test connections, drains, and other applicable details necessary to clearly describe the proposed 
arrangement.  Indicate each type of fitting used and the locations of bushings, reducing couplings, 
and welded joints.</ITM><BRK/>
<BRK/>
<ITM>  c. Actual center-to-center dimensions between sprinklers on branch lines and between branch 
lines; from end sprinklers to adjacent walls; from walls to branch lines; from sprinkler feed 
mains, cross-mains and branch lines to finished floor and roof or ceiling.  A detail shall show 
the dimension from the sprinkler and sprinkler deflector to the ceiling in finished areas.</ITM><BRK/>
<BRK/>
<ITM>  d. Longitudinal and transverse building sections showing typical branch line and cross-main 
pipe routing as well as elevation of each typical sprinkler above finished floor.</ITM><BRK/>
<BRK/>
<ITM>  e. Details of each type of riser assembly; pipe hanger; sway bracing for earthquake protection, 
and restraint of underground water main at point-of-entry into the building, and electrical 
devices and interconnecting wiring.</ITM><BRK/>
<BRK/>
<ITM>  f. Complete point-to-point wiring diagram of the detection and control system.  Indicate the 
detailed interconnection of control panel modules to the devices, the number and size of conductors 
in each conduit, and size of conduit.  Connection points shall be indicated and coordinated 
with the terminal identification marked on the devices.  Provide complete internal wiring schematic 
of the control panel and each electrical device.  Detailed description of the functions of the 
control panel and each module shall be provided.</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.5   DELIVERY, STORAGE, AND HANDLING</TTL><BRK/>
<BRK/>
<TXT>All equipment delivered and placed in storage shall be housed in a manner to preclude any damage from the weather, 
humidity and temperature variations, dirt and dust, or other contaminants.  Additionally, all pipes shall either 
be capped or plugged until installed.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6   EXTRA MATERIALS</TTL><BRK/>
<BRK/>
<TXT>Submit <SUB>spare parts</SUB> data for each different item of material and equipment specified.   The data shall include 
a complete list of parts and supplies, with current unit prices and source of supply, and a list of parts recommended 
by the manufacturer to be replaced after 1 year and 3 years of service.  A list of special tools and test equipment 
required for maintenance and testing of the products supplied by the Contractor shall be included.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   STANDARD PRODUCTS</TTL><BRK/>
<BRK/>
<TXT>Provide <SUB>materials and equipment</SUB> which are standard products of a manufacturer regularly engaged in the manufacture 
of such products and that essentially duplicate items that have been in satisfactory use for at least 2 years 
prior to bid opening.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2   NAMEPLATES</TTL><BRK/>
<BRK/>
<TXT>All equipment shall have a nameplate that identifies the manufacturer's name, address, type or style, model or 
serial number, and catalog number.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3   REQUIREMENTS FOR FIRE PROTECTION SERVICE</TTL><BRK/>
<BRK/>
<TXT>Materials and equipment shall have been tested by Underwriters Laboratories, Inc. and listed in <RID>UL Fire Prot Dir</RID>
 or approved by Factory Mutual and listed in <RID>FM P7825a</RID> and <RID>FM P7825b</RID>.  Where the terms "listed" or "approved" 
appear in this specification, such shall mean listed in <RID>UL Fire Prot Dir</RID> or <RID>FM P7825a</RID> and <RID>FM P7825b</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4   UNDERGROUND PIPING SYSTEMS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The drawings must show the service connection details and the underground 
water mains for the sprinkler system and details of the water service point-of-entry 
into the building and through the floor slab, and underground piping restraints, 
including number and size of restraining rods and thrust blocks.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.4.1   Pipe</TTL><BRK/>
<BRK/>
<TXT>Piping from a point<MET> 150 mm</MET><ENG> 6 inches</ENG> above the floor to [a point<MET> 1500 mm</MET><ENG> 5 feet</ENG> outside the building wall] [the 
point of connection to the existing water mains] shall be ductile iron with a rated working pressure of<MET> [1034] 
[1207] [_____] kPa</MET><ENG> [150] [175] [_____] psi</ENG> conforming to <RID>AWWA C151/A21.51</RID>, with cement mortar lining conforming 
to <RID>AWWA C104/A21.4</RID>.  Piping more than<MET> 1500 mm</MET><ENG> 5 feet</ENG> outside the building walls shall comply with Section 
<SRF>33 11 00</SRF> WATER DISTRIBUTION.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.2   Fittings and Gaskets</TTL><BRK/>
<BRK/>
<TXT>Fittings shall be ductile iron conforming to <RID>AWWA C110/A21.10</RID>.  Gaskets shall be suitable in design and size 
for the pipe with which such gaskets are to be used.  Gaskets for ductile iron pipe joints shall conform to <RID>AWWA C111/A21.11</RID>
.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.3   Gate Valve and Indicator Posts</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph will be deleted if underground valves are either not required 
or are specified elsewhere.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Gate valves for underground installation shall be of the inside screw type with counter-clockwise rotation to 
open.  Where indicating type valves are shown or required, indicating valves shall be gate valves with an approved 
indicator post of a length to permit the top of the post to be located<MET> 900 mm</MET><ENG> 3 feet</ENG> above finished grade.  Gate 
valves and indicator posts shall be listed in <RID>UL Fire Prot Dir</RID> or <RID>FM P7825a</RID> and <RID>FM P7825b</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.5   ABOVEGROUND PIPING COMPONENTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.5.1   Steel Pipe</TTL><BRK/>
<BRK/>
<TXT>Except as modified herein, steel pipe shall be [black][galvanized][galvanized where indicated] as permitted by <RID>
NFPA 13</RID> and shall conform to applicable provisions of <RID>ASTM A 795/A 795M</RID>, <RID>ASTM A 53/A 53M</RID>, or <RID>ASTM A 135/A 135M</RID>
.  Pipe in which threads or grooves are cut or rolled formed shall be Schedule 40 or shall be listed by Underwriters' 
Laboratories to have a corrosion resistance ratio (CRR) of 1.0 or greater after threads or grooves are cut or 
rolled formed.  Pipe shall be marked with the name of the manufacturer, kind of pipe, and ASTM designation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.2   Fittings for Non-Grooved Steel Pipe</TTL><BRK/>
<BRK/>
<TXT>Fittings shall be galvanized steel conforming to <RID>ASME B16.9</RID> or <RID>ASME B16.11</RID>.  Fittings that sprinklers, drop nipples 
or riser nipples (sprigs) are screwed into shall be threaded type.  Plain-end fittings with mechanical couplings, 
fittings that use steel gripping devices to bite into the pipe and segmented welded fittings shall not be used.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.3   Grooved Mechanical Joints and Fittings</TTL><BRK/>
<BRK/>
<TXT>Joints and fittings shall be designed for not less than<MET> 1200 kPa</MET><ENG> 175 psi</ENG> service and shall be the product of 
the same manufacturer; segmented welded fittings shall not be used.  Fitting and coupling houses shall be malleable 
iron conforming to <RID>ASTM A 47/A 47M</RID>, Grade 32510; ductile iron conforming to <RID>ASTM A 536</RID>, Grade 65-45-12.  Gaskets 
shall be of silicon compound and approved for dry fire protection systems.  Gasket shall be the flush type that 
fills the entire cavity between the fitting and the pipe.  Nuts and bolts shall be heat-treated steel conforming 
to <RID>ASTM A 183</RID> and shall be cadmium plated or zinc electroplated.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.4   Flanges</TTL><BRK/>
<BRK/>
<TXT>Flanges shall conform to <RID>NFPA 13</RID> and <RID>ASME B16.1</RID>.  Gaskets shall be non-asbestos compressed material in accordance 
with <RID>ASME B16.21</RID>, <MET>1.6 mm</MET><ENG> 1/16 inch</ENG> thick, and full face or self-centering flat ring type.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.5.4.1   Bolts</TTL><BRK/>
<BRK/>
<TXT>Bolts shall be <RID>ASTM A 449</RID>, Type 1.  Bolts shall extend no less than three full threads beyond the nut with bolts 
tightened to the required torque.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.4.2   Nuts</TTL><BRK/>
<BRK/>
<TXT>Nuts shall be [hexagon type conforming to <RID>ASME B18.2.2</RID>] [<RID>ASTM A 193/A 193M</RID>, Grade 5] [<MET><RID>ASTM A 563M</RID></MET><ENG> <RID>ASTM A 563</RID></ENG>, 
Grade [C3] [DH3]].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.4.3   Washers</TTL><BRK/>
<BRK/>
<TXT>Washers shall meet the requirements of<MET> <RID>ASTM F 436M</RID></MET><ENG> <RID>ASTM F 436</RID></ENG>.  Flat circular washers shall be provided under 
all bolt heads and nuts.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.5.5   Pipe Hangers</TTL><BRK/>
<BRK/>
<TXT>Hangers shall be listed in <RID>UL Fire Prot Dir</RID> or <RID>FM P7825a</RID> and <RID>FM P7825b</RID> and of the type suitable for the application, 
construction, and pipe type and size to be supported.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.6   Valves</TTL><BRK/>
<BRK/>
<SPT><TTL>2.5.6.1   Control Valve and Gate Valve</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  A control valve is required for control of each individual sprinkler 
riser.  The type of such valves should be either the OS&amp;Y or wall type indicator 
post.  Where multiple risers are supplied from a single water service, riser 
control valves of the OS&amp;Y type should be located in a valve room with exterior 
access.  For more guidance on arrangement of sprinkler control valves, refer 
to NFPA 13, Appendix A</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Manually operated sprinkler control valve and gate valve shall be outside stem and yoke (OS&amp;Y) type and shall 
be listed in <RID>UL Bld Mat Dir</RID> or <RID>FM P7825a</RID> and <RID>FM P7825b</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.6.2   Check Valves</TTL><BRK/>
<BRK/>
<TXT>Check valve<MET> 50 mm</MET><ENG> 2 inches</ENG> and larger shall be listed in <RID>UL Bld Mat Dir</RID> or <RID>FM P7825a</RID> and <RID>FM P7825b</RID>.  Check valves<MET>
 100 mm</MET><ENG> 4 inches</ENG> and larger shall be of the swing type with flanged cast iron body and flanged inspection plate, 
shall have a clear waterway and shall meet the requirements of <RID>MSS SP-71</RID>, for Type 3 or 4.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>2.6   AUTOMATIC WATER CONTROL VALVE (DELUGE VALVE)</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  "Automatic water control valve" is a generic term synonymous with "deluge 
valve" and is used for both preaction and deluge systems.  "Automatic water 
control valve" is consistent with what is used in the UL Fire Protection Equipment 
Directory.  Delete reset capability when not required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Automatic water control valve (deluge valve) shall be electrically-actuated and rated for a working pressure 
of<MET> 1207 kPa</MET><ENG> 175 psi</ENG>.  Valve shall be capable of being reset without opening the valve.  Electrical solenoid valve 
used to actuate the water control valve shall be an integral component of the valve or shall be approved for 
use by the water control valve manufacturer.  Solenoid valve shall be rated at 24 volts direct current, and shall 
be normally closed type that operates when energized.  Solenoid valves shall be rated for a maximum pressure 
differential of<MET> 1207 kPa</MET><ENG> 175 psi</ENG>.  Water control valve shall be equipped with a means to prevent the valve from 
returning to the closed position until being manually reset.  Assembly shall be complete with the valve manufacturer's 
standard trim piping, drain and test valves, pressure gauges, and other required appurtenances.  Include with 
each assembly an emergency release device for manually tripping the water control valve in the event of a power 
or other system failure.  Device shall be a standard accessory component of the valve manufacturer and shall 
be labeled as to its function and method of operation.  Valves located in hazardous locations shall be approved 
for the hazard classification of the area where located.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7   SUPERVISORY AIR SYSTEM</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Supervisory air is not appropriate for deluge systems.  Delete this section 
and reference to supervisory air for deluge systems and for unsupervised preaction systems.<BRK/>
<BRK/>
Show the power supply to the air compressor and to the low air pressure alarm 
device on the drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.7.1   Air Compressor</TTL><BRK/>
<BRK/>
<TXT>Air compressor shall be single stage oil less type, air cooled, electric-motor driven, equipped with a check 
valve, centrifugal pressure and moisture unloader, pressure switch for automatic starting and stopping.  Pressure 
switch shall be set to start the compressor at<MET> [140] [_____] kPa</MET><ENG> [20] [_____] psi</ENG> and stop it at<MET> [200] [_____] 
kPa</MET><ENG> [30] [_____] psi</ENG>.  A safety relief valve, set to operate at<MET> [450] [_____] kPa</MET><ENG> [65] [_____] psi</ENG>, shall be 
provided.  The compressor shall be sized to pressurize the system to<MET> [200] [_____] kPa</MET><ENG> [30] [_____] psi</ENG> within 
30 minutes.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2   Air Pressure Maintenance Device</TTL><BRK/>
<BRK/>
<TXT>Device shall be a pressure regulator that automatically reduces supply air pressure to the minimum pressure required 
to be maintained in the piping system.  The device shall have a cast bronze body and valve housing complete with 
diaphragm assembly, spring, filter, ball check to prevent backflow, <MET>1.6 mm</MET><ENG> 1/16 inch</ENG> restriction to prevent rapid 
pressurization of the system, and adjustment screw.  The device shall be capable of reducing maximum inlet pressure 
of<MET> 680 kPa</MET><ENG> 100 psi</ENG> to a fixed outlet pressure adjustable to<MET> [70] [_____] kPa</MET><ENG> [10] [_____] psi</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.3   Air Supply Piping System</TTL><BRK/>
<BRK/>
<TXT>Each preaction system shall be equipped with a separate pressure maintenance device, shutoff valve, bypass valve 
and pressure gauge.  Piping shall be galvanized steel in accordance with <RID>ASTM A 795/A 795M</RID> or <RID>ASTM A 53/A 53M</RID>
.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.4   Low Air Pressure Switch</TTL><BRK/>
<BRK/>
<TXT>Each preaction system shall be provided with an air pressure switch connected to the control panel.  Upon reduction 
of supervisory air pressure to approximately<MET> [70] [_____] kPa</MET><ENG> [10] [_____] psi</ENG>, the low air pressure switch shall 
actuate the audible alarm device and a red low-air alarm light on the control panel annunciator.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.8   WATER MOTOR ALARM ASSEMBLY</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate this paragraph with paragraph Waterflow Alarm; delete parts 
not used.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Assembly shall include a body housing, impeller wheel, drive shaft, striker assembly, gong, wall plate and related 
components necessary for complete operation.  Minimum<MET>19 mm</MET><ENG> 3/4 inch</ENG> galvanized piping shall be provided between 
the housing and the automatic water control valve.  Drain piping from the body housing shall be minimum<MET> 25 mm</MET><ENG>
 1 inch</ENG> galvanized steel and shall be arranged to drain to the outside of the building.  Piping shall be galvanized 
both on the inside and on the outside surfaces.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9   FIRE DEPARTMENT CONNECTION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The designer will coordinate the desired location of the fire department 
connection with and verify the type of threads used by the fire department serving 
the building where the sprinkler system is being installed.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Fire department connection shall be [projecting] [flush] type with cast brass body, matching wall escutcheon 
lettered "Auto Spkr" with a [polished brass] [chromium plated] finish.  The connection shall have two inlets 
with individual self-closing clappers, caps with drip drains and chains.  Female inlets shall have<MET> 65 mm</MET><ENG> 2-1/2 
inch</ENG> diameter American National Fire Hose Connection Screw Threads (NH) in accordance with [<RID>NFPA 1963</RID>][_____].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.10   SPRINKLERS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The designer will indicate on the contract drawings the type of sprinkler 
heads for each area if more than one type of sprinklers is to be provided.  
Delete sprinkler types from this paragraph that are not intended for use in 
the system(s) used in the contract.</NPR><BRK/>
<BRK/>
<NPR>Areas that are classified as light hazard will be equipped with quick response 
sprinklers.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Sprinklers for preaction systems shall be automatic, fusible solder or glass bulb type; sprinklers for deluge 
systems shall be open type without the fusible element.  Sprinklers with internal O-rings shall not be used.  
Sprinklers shall be used in accordance with their listed coverage limitations.  Temperature classification shall 
be [ordinary] [intermediate] [_____] [as indicated].  Sprinklers in high heat areas including attic spaces or 
in close proximity to unit heaters shall have temperature classification in accordance with <RID>NFPA 13</RID>.  Extended 
coverage sprinklers shall not be used.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.10.1   Pendent Sprinkler</TTL><BRK/>
<BRK/>
<TXT>Pendent sprinkler shall be of the fusible strut or glass bulb type, [recessed] [quick-response] type with nominal 
[<MET>13 mm</MET><ENG> 1/2 inch</ENG>] [<MET>13.5 mm</MET><ENG> 17/32 inch</ENG>] orifice.  Pendent sprinklers shall have a [polished chrome] [stainless 
steel] [white polyester] [_____] finish.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.10.2   Upright Sprinkler</TTL><BRK/>
<BRK/>
<TXT>Upright sprinkler shall be [brass] [chrome-plated] [stainless steel] [white polyester] [quick-response type] 
[_____] and shall have a nominal [<MET>13 mm</MET><ENG> 1/2 inch</ENG>] [<MET>13.5 mm</MET><ENG> 17/32 inch</ENG>] orifice.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.10.3   Corrosion Resistant Sprinkler</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The use of corrosion resistant sprinklers is generally limited to industrial 
type occupancies such as electroplating, steam rooms, salt storage, and piers 
and wharves.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Corrosion resistant sprinkler shall be the [upright] [pendent] type installed in locations as indicated.  Corrosion 
resistant coatings shall be factory-applied by the sprinkler manufacturer.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.11   DISINFECTING MATERIALS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.11.1   Liquid Chlorine</TTL><BRK/>
<BRK/>
<TXT>Liquid chlorine shall conform to <RID>AWWA B301</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11.2   Hypochlorites</TTL><BRK/>
<BRK/>
<TXT>Calcium hypochlorite and sodium hypochlorite shall conform to <RID>AWWA B300</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.12   ACCESSORIES</TTL><BRK/>
<BRK/>
<SPT><TTL>2.12.1   Sprinkler Cabinet</TTL><BRK/>
<BRK/>
<TXT>Spare sprinklers shall be provided in accordance with <RID>NFPA 13</RID> and shall be packed in a suitable metal or plastic 
cabinet.  Spare sprinklers shall be representative of, and in proportion to, the number of each type and temperature 
rating of the sprinklers installed.  At least one wrench of each type required shall be provided.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12.2   Pendent Sprinkler Escutcheon</TTL><BRK/>
<BRK/>
<TXT>Escutcheon shall be one-piece metallic type with a depth of less than<MET> 19 mm</MET><ENG> 3/4 inch</ENG> and suitable for installation 
on pendent sprinklers.  The escutcheon shall have a factory finish that matches the pendent sprinkler heads.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12.3   Pipe Escutcheon</TTL><BRK/>
<BRK/>
<TXT>Escutcheon shall be polished chromium-plated zinc alloy, or polished chromium-plated copper alloy.  Escutcheons 
shall be either one-piece or split-pattern, held in place by internal spring tension or set screw.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12.4   Sprinkler Guard</TTL><BRK/>
<BRK/>
<TXT>Guard shall be a steel wire cage designed to encase the sprinkler and protect it from mechanical damage.  Guards 
shall be provided on sprinklers located [_____] [as indicated].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12.5   Identification Sign</TTL><BRK/>
<BRK/>
<TXT>Valve identification sign shall be minimum<MET> 150 mm wide by 50 mm high</MET><ENG> 6 inches wide by 2 inches high</ENG> with enamel 
baked finish on minimum<MET> 1.214 mm</MET><ENG> 18 gauge</ENG> steel or<MET> 0.6 mm</MET><ENG> 0.024 inch</ENG> aluminum with red letters on a white background 
or white letters on red background.  Wording of sign shall include, but not be limited to "main drain," "auxiliary 
drain," "inspector's test," "alarm test," "alarm line," and similar wording as required to identify operational 
components.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.13   DOUBLE-CHECK VALVE BACKFLOW PREVENTION ASSEMBLY</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Indicate piping, type of connection and equipment, such as a test header 
with hose valves, required for flow testing of the backflow preventer at full 
system demand as required by NFPA 13.  Arrangement of test assembly should be 
coordinated with the installation.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Double-check backflow prevention assembly shall comply with <RID>ASSE 1015</RID>.  The assembly shall have a bronze, cast-iron 
or stainless steel body with flanged ends.  The assembly shall include pressure test gauge ports and OS&amp;Y 
shutoff valves on the inlet and outlet, 2-positive-seating check valve for continuous pressure application, and 
four test cocks.  Assemblies shall be rated for working pressure of<MET> [1034] [1207] [_____] kPa</MET><ENG> [150] [175] [_____] 
psi</ENG>.  The maximum pressure loss shall be<MET> 40 kPa</MET><ENG> 6 psi</ENG> at a flow rate equal to the sprinkler water demand, at 
the location of the assembly.  A test port for a pressure gauge shall be provided both upstream and downstream 
of the double check backflow prevention assembly valves.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14   CONTROL PANEL</TTL><BRK/>
<BRK/>
<TXT>Panel shall be UL listed or FM approved for "Releasing Device Service" or shall have modules approved for this 
purpose.  Panel shall contain all components and equipment required to provide the specified operational and 
supervisory functions of the system.  House components in a [surface] [flush]-mounted steel cabinet with hinged 
door and cylinder lock.  Control panel shall be a clean, uncluttered, and orderly factory assembled and wired 
unit.  Panel shall include integral "power on," "alarm," and "trouble" lamps with annunciation of each alarm, 
supervisory and trouble signal.  The panel shall have prominent rigid plastic or metal identification plates 
for lamps, zones, controls, meters, fuses, and switches.  Nameplates for fuses shall also include ampere rating.  
Control panel switches shall be within the locked cabinet.  Provide a suitable means for testing the working 
condition and accuracy of the control panel visual indicating devices (meter and lamps).  Meters and lamps shall 
be plainly visible when the cabinet door is closed.  Signals shall be provided to indicate by zone any alarm, 
supervisory or trouble condition on the system.  Upon restoration of power, startup shall be automatic, and shall 
not require any manual operation.  The loss of primary power or the sequence of applying primary or emergency 
power shall not affect the transmission of alarm, supervisory or trouble signals.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.14.1   Zone Annunciator</TTL><BRK/>
<BRK/>
<TXT>Provide a separate alarm and trouble lamp for each active and spare zone located on exterior of cabinet door 
or visible through the cabinet door.  A minimum of [two] [_____] spare alarm zones that are fully operational 
shall be provided.  Each lamp shall provide specific identification of the zone by means of a permanently attached 
rigid plastic or metal sign with either raised or engraved letters.  Zone identification shall consist of a unique 
zone number as well as a word description of the zone.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.2   System Zoning</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  As a minimum, the system will be zoned by type of device and by floor 
or by specific location.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The system shall be zoned as follows:</TXT><BRK/>
<BRK/>
<ITM>ZONE NO.                          DESCRIPTION</ITM><BRK/>
<BRK/>
<ITM>[_____]                            [_____]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.3   Primary Power Supply</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The drawings will indicate a dedicated power supply circuit for each 
preaction and deluge sprinkler system control panel.  The power circuit will 
be arranged so that power and lighting system can be shutdown for building modifications 
without shutting down primary power to the control panel.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Primary power and trouble alarm power to the Control Panel shall be supplied from two 120 VAC circuits.  [Power 
to the control panel shall be as indicated.] [A [separate panel] [fused two-pole disconnect switch] connected 
ahead of [the main building panel] [indicated panel] shall be provided.] [Panel shall be equipped with [two] 
[_____] 20-amp circuit breakers for each control panel and with key lock.  [Panel] [Disconnect switch] shall 
be permanently marked "[PREACTION] [DELUGE] SPRINKLER SYSTEM".]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.4   Emergency Power Supply</TTL><BRK/>
<BRK/>
<TXT>Emergency power shall be provided for system operation in the event of failure of the primary power supply and 
shall consist of rechargeable storage battery system.  Transfer from normal to emergency power or restoration 
from emergency to normal power shall be automatic and shall not cause transmission of a false alarm.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.14.4.1   <SUB>Storage Batteries</SUB></TTL><BRK/>
<BRK/>
<TXT>Storage Batteries shall be sealed, lead-calcium type requiring no additional water.  The batteries shall have 
ample capacity, with primary power disconnected, to operate the system for a period of 90 hours.  Following this 
period of operation via batteries, the batteries shall have ample capacity to operate all alarm indicating devices 
in the alarm mode for a minimum period of [15] [_____] minutes.  Battery cabinet shall be a separate [compartment 
at the bottom of the control panel] [cabinet].  The battery cabinet shall have adequate space for spare duplicate 
storage batteries.  Batteries shall be mounted on a noncorrosive and nonconductive base or pad.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.4.2   Battery Charger</TTL><BRK/>
<BRK/>
<TXT>Battery charger shall be completely automatic, with high/low charging rate, capable of restoring the batteries 
from full discharge to full charge within [12 hours] [_____] using the high charging rate.  A separate ammeter 
shall be provided for indicating rate of charge.  A separate voltmeter shall be provided to indicate the state 
of the battery charge.  A pilot light indicating when batteries are manually placed on a high rate of charge 
shall be provided as part of the unit assembly.  The charger shall be located in control panel cabinet.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>2.15   ALARM INITIATING DEVICES</TTL><BRK/>
<BRK/>
<SPT><TTL>2.15.1   Heat Detectors</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The location and type of heat detectors and alarm devices must be indicated 
on project drawings.  Delete descriptive paragraphs of detectors types not used.  
Alarm indicator should be used only if necessary to meet project requirements.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Detectors located in areas subject to moisture, exterior atmospheric conditions or hazardous locations as defined 
in <RID>NFPA 70</RID> shall be approved for such locations.  Detectors shall be listed or approved for<MET> 15 m</MET><ENG> 50 foot</ENG> spacing 
between detectors.  The detector shall be equipped with an alarm indicating light in its base that lights when 
the detector is in an alarm condition.  [Five] [_____] spare detectors of each type and temperature rating shall 
be provided.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.15.1.1   Rate Compensation Detector</TTL><BRK/>
<BRK/>
<TXT>Detector shall be of the [vertical] [horizontal] spot type with a temperature classification rating of [ordinary] 
[intermediate] as defined by <RID>NFPA 72</RID>.  Detectors listed or approved as "rate anticipation" type will be accepted.  
Detector shall automatically reset when temperature drops below detector temperature rating.  Detector shall 
be hermetically sealed.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.1.2   Fixed-Temperature and Rate-of-Rise Heat Detector</TTL><BRK/>
<BRK/>
<TXT>Detector shall consist of two independently operated thermal elements.  The rate-of-rise portion of the detector 
shall consist of an air chamber, flexible metal diaphragm and a moisture-proof calibrated vent which will respond 
to a temperature rise exceeding<MET> 8 degrees C</MET><ENG> 15 degrees F</ENG> per minute.  This portion of the detector shall be self-restoring 
after actuation.  The fixed temperature portion of the detector shall consist of a fusible alloy that will melt 
and cause an alarm when the surrounding air rises above the temperature rating of the detector.  The detector 
shall provide an external indication when the fixed temperature portion of the detector actuates.  Detector shall 
have a temperature classification rating of [ordinary] [intermediate] as defined by <RID>NFPA 72</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.1.3   Fixed-Temperature Heat Detector</TTL><BRK/>
<BRK/>
<TXT>Detector shall have a fusible alloy that will melt and cause an alarm when the surrounding air rises above the 
temperature rating of the detector.  The detector shall provide an external indication upon actuation of the 
detector.  Detector shall provide a temperature classification rating of [ordinary] [intermediate] as defined 
by <RID>NFPA 72</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.15.2   Manual Actuation Station</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Manual actuation stations are needed for deluge systems only.  Delete 
this paragraph for preaction systems.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Station shall be mounted at<MET> 1000 mm</MET><ENG> 42 inches</ENG> above the floor, unless otherwise shown.  Station shall be arranged 
to activate the deluge system.  Station shall be dual-action type requiring two separate operations in order 
to cause system discharge.  Station shall be colored [lime yellow] [_____] [a unique color dissimilar to color 
used for manual fire alarm system].  Station shall be provided with a positive visible indication of operation 
of the station.  Station shall be weatherproof type and shall be provided with an engraved label indicating DELUGE 
SYSTEM.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.3   Sprinkler Pressure Alarm Switch </TTL><BRK/>
<BRK/>
<TXT>Pressure switch shall include a metal housing with a neoprene diaphragm, SPDT snap action switches.  The switch 
shall have a service pressure rating of<MET> 1200 kPa</MET><ENG> 175 psi</ENG>.  There shall be two SPDT (Form C) contacts factory 
adjusted to operate at<MET> 30 to 60 kPa</MET><ENG> 4 to 8 psi</ENG>.  The switch shall be capable of being mounted in any position 
in the alarm line trim piping of the alarm check valve.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.4   Waterflow Alarm</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Electric waterflow alarm bells are preferred.  Coordinate type and location 
of waterflow alarm with the electrical designer.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Electrically operated, exterior-mounted, waterflow alarm bell shall be provided and installed in accordance 
with <RID>NFPA 13</RID>.  Waterflow alarm bell shall be rated 24 VDC and shall be connected to the Fire Alarm Control Panel 
(FACP) in accordance with Section [<SRF>28 31 00.00 10</SRF> FIRE DETECTION AND ALARM SYSTEM, DIRECT CURRENT LOOP] [
<SRF>28 31 64.00 10</SRF> FIRE DETECTION AND ALARM SYSTEM, ADDRESSABLE]]. [Mechanically operated, exterior mounted, water 
motor alarm assembly shall be provided in accordance with <RID>NFPA 13</RID>.  Water motor alarm assembly shall include 
a body housing, impeller or pelton wheel, drive shaft, striker assembly, gong, wall plate and related components 
necessary for complete operation.  Minimum<MET> 19 mm</MET><ENG> 3/4 inch</ENG> galvanized piping from the body housing shall be provided 
between the housing and the alarm check valve.  Drain piping from the body housing shall be minimum<MET> 25 mm</MET><ENG> 1 inch</ENG>
 galvanized and shall be arranged to drain to the outside of the building.  Piping shall be galvanized both on 
the inside and outside surfaces.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.5   Valve Supervisory (Tamper) Switch</TTL><BRK/>
<BRK/>
<TXT>Switch shall be suitable for mounting to the type of control valve to be supervised open.  The switch shall be 
tamper resistant and contain one set of SPDT (Form C) contacts arranged to transfer upon removal of the housing 
cover or closure of the valve of more than two rotations of the valve stem.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.16   NOTIFICATION APPLIANCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The notification appliances are for providing local notification of a 
sprinkler system operation. These devices are not intended to provide general 
building fire alarm evacuation.  Fire alarm evacuation systems are addressed 
in Section <SRF>33 82 01</SRF> INTERCOMMUNICATION SYSTEM.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Notification appliances shall be suitable for connection to supervised alarm indicating circuits.  Appliance 
shall have a separate screw terminal for each conductor.  The surface of the appliance shall be red in color.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.16.1   Alarm Bell</TTL><BRK/>
<BRK/>
<TXT>Bell shall be<MET> 250 mm</MET><ENG> 10 inch</ENG> diameter, surface-mounted vibrating type with matching back box.  Sound output shall 
be a minimum of [85] [_____] DBA at<MET> 3000 mm</MET><ENG> 10 feet</ENG>.  Bell shall operate on nominal 24 VDC.  Bells shall have 
screw terminals for in-out wiring connection.  Bells used in exterior locations shall be specifically listed 
or approved for outdoor use and be provided with metal housing and protective grilles.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.16.2   Alarm Horn</TTL><BRK/>
<BRK/>
<TXT>Horn shall be surface mounted, with the matching mounting back box [surface mounted] [recessed] [[single] [double] 
projector,] [grill and] vibrating type suitable for use in an electrically supervised circuit.  Horns shall operate 
on nominal 24 VDC and have screw terminals for in-out wiring connection.  Sound output shall be a minimum of 
[85] [_____] DBA at<MET> 3000 mm</MET><ENG> 10 feet</ENG>.  Horns used in exterior locations shall be specifically listed or approved 
for outdoor use and be provided with metal housing and protective grills.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.17   WIRING</TTL><BRK/>
<BRK/>
<TXT>Wiring for alternating current (AC) circuits shall be 12 AWG minimum. Wiring for low voltage direct current (DC) 
circuits shall be No. [16] [14] AWG minimum.  Power wiring (over 28 volts) and control wiring shall be isolated.  
Wiring shall conform to <RID>NFPA 70</RID>.  System field wiring shall be solid copper and installed in electrical metallic 
tubing or in metallic conduit, except rigid plastic conduit may be used under slab-on-grade. Conductors shall 
be color coded.  Conductors used for the same function shall be similarly color coded.  Wiring color code shall 
remain uniform throughout the circuit.  Pigtail or T-tap connections to alarm initiating, alarm indicating, supervisory, 
and actuation circuits are prohibited.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   EXAMINATION</TTL><BRK/>
<BRK/>
<TXT>After becoming familiar with all details of the work, verify all dimensions in the field, and advise the Contracting 
Officer of any discrepancy before performing the work.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   EARTHWORK</TTL><BRK/>
<BRK/>
<TXT>Earthwork shall be performed in accordance with applicable provisions of Section <SRF>31 00 00</SRF> EARTHWORK.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3   INSTALLATION REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>The installation shall be in accordance with the applicable provisions of publications referenced herein.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4   <SUB>INSPECTION BY FIRE PROTECTION SPECIALIST</SUB> </TTL><BRK/>
<BRK/>
<TXT> The Fire Protection Specialist shall inspect the sprinkler system periodically during the installation to assure 
that the sprinkler system installed in accordance with the contract requirements.  The Fire Protection Specialist 
shall witness the preliminary and final tests, and shall sign the test results.  The Fire Protection Specialist, 
after completion of the system inspections and a successful final test, shall certify in writing that the system 
has been installed in accordance with the contract requirements.  Any discrepancy shall be brought to the attention 
of the Contracting Officer in writing, no later than three working days after the discrepancy is discovered.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5   ABOVEGROUND PIPING INSTALLATION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.5.1   Protection of Piping Against Earthquake Damage</TTL><BRK/>
<BRK/>
<TXT>Seismically protect the system piping against damage from earthquakes.  This requirement is not subject to determination 
under <RID>NFPA 13</RID>.  Install the seismic protection of the system piping, including <SUB>sway bracing</SUB> as required, in accordance 
with UFC 3-310-04, <RID>NFPA 13</RID> and Annex A.  Include the required features identified therein that are applicable 
to the specific piping system.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.2   Piping in Exposed Areas</TTL><BRK/>
<BRK/>
<TXT>Exposed piping shall be installed so as not diminish exit access widths, corridors, or equipment access.  Exposed 
horizontal piping, including drain piping, shall be installed to provide maximum headroom.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.3   Piping in Finished Areas</TTL><BRK/>
<BRK/>
<TXT>In areas with suspended or dropped ceilings and in areas with concealed spaces above the ceiling, piping shall 
be concealed above ceilings.  Piping shall be inspected, tested and approved before being concealed.  Risers 
and similar vertical runs of piping in finished areas shall be concealed.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.4   Pendent Sprinklers Locations</TTL><BRK/>
<BRK/>
<TXT>Sprinklers installed in the pendent position shall be of the listed dry pendent type, unless otherwise indicated.  
Dry pendent sprinklers shall be of the required length to permit the sprinkler to be threaded directly into a 
branch line tee.  Hangers shall be provided on arm-overs to drop nipples supplying pendent sprinklers when the 
arm-over exceeds<MET> 300 mm</MET><ENG> 12 inches</ENG> for steel pipe or <MET>150 mm</MET><ENG>6 inches</ENG> for copper tubing.  Dry pendent sprinkler 
assemblies shall be such that sprinkler ceiling plates or escutcheons are of the uniform depth throughout the 
finished space.  Pendent sprinklers in suspended ceilings shall be a minimum of<MET> 150 mm</MET><ENG> 6 inches</ENG> from ceiling 
grid.  Recessed pendent sprinklers shall be installed such that the distance from the sprinkler deflector to 
the underside of the ceiling shall not exceed the manufacturer's listed range and shall be of uniform depth throughout 
the finished area.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.5   Upright Sprinklers</TTL><BRK/>
<BRK/>
<TXT>Riser nipples or "sprigs" to upright sprinklers shall contain no fittings between the branch line tee and the 
reducing coupling at the sprinkler. Riser nipples exceeding<MET> 750 mm</MET><ENG> 30 inches</ENG> in length shall be individually 
supported.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.6   Pendent Sprinklers Locations</TTL><BRK/>
<BRK/>
<TXT>Sprinklers installed in the pendent position shall be of the listed dry pendent type, unless otherwise indicated.  
Dry pendent sprinklers shall be of the required length to permit the sprinkler to be threaded directly into a 
branch line tee.  Hangers shall be provided on arm-overs exceeding<MET> 300 mm</MET><ENG> 12 inches</ENG> in length.  Dry pendent sprinkler 
assemblies shall be such that sprinkler ceiling plates or escutcheons are of the uniform depth throughout the 
finished space.  Pendent sprinklers in suspended ceilings shall be a minimum of<MET> 150 mm</MET><ENG> 6 inches</ENG> from ceiling 
grid.  Recessed pendent sprinklers shall be installed such that the distance from the sprinkler deflector to 
the underside of the ceiling shall not exceed the manufacturer's listed range and shall be of uniform depth throughout 
the finished area.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.7   Pipe Joints</TTL><BRK/>
<BRK/>
<TXT>Pipe joints shall conform to <RID>NFPA 13</RID>, except as modified herein.  Not more than four threads shall show after 
joint is made up.  Welded joints will be permitted, only if welding operations are performed as required by <RID>NFPA 13</RID>
 at the Contractor's fabrication shop, not at the project construction site.  Flanged joints shall be provided 
where indicated or required by <RID>NFPA 13</RID>.  Grooved pipe and fittings shall be prepared in accordance with the manufacturer's 
latest published specification according to pipe material, wall thickness and size.  Grooved couplings and fittings 
shall be from the same manufacturer.  Grooved joints shall not be used in concealed locations, such as behind 
solid walls or ceilings, unless an access panel is shown on the drawings for servicing or adjusting the joint.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.8   Reducers</TTL><BRK/>
<BRK/>
<TXT>Reductions in pipe sizes shall be made with one-piece tapered reducing fittings.  The use of grooved-end or rubber-gasketed 
reducing couplings will not be permitted.  When standard fittings of the required size are not manufactured, 
single bushings of the face type will be permitted.  Where used, face bushings shall be installed with the outer 
face flush with the face of the fitting opening being reduced.  Bushings shall not be used in elbow fittings, 
in more than one outlet of a tee, in more than two outlets of a cross, or where the reduction in size is less 
than<MET> 13 mm</MET><ENG> 1/2 inch</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.9   Pipe Penetrations</TTL><BRK/>
<BRK/>
<TXT>Cutting structural members for passage of pipes or for pipe-hanger fastenings will not be permitted.  Pipes that 
must penetrate concrete or masonry walls or concrete floors shall be core-drilled and provided with pipe sleeves.  
Each sleeve shall be Schedule 40 galvanized steel, ductile iron or cast iron pipe and shall extend through its 
respective wall or floor and be cut flush with each wall surface.  Sleeves shall provide required clearance between 
the pipe and the sleeve in accordance with <RID>NFPA 13</RID>.  The space between the sleeve and the pipe shall be firmly 
packed with mineral wool insulation.  Where pipes penetrate fire walls, fire partitions, or floors, pipes shall 
be fire stopped in accordance with Section <SRF>07 84 00</SRF> FIRESTOPPING.  In penetrations that are not fire-rated or 
not a floor penetration, the space between the sleeve and the pipe shall be sealed at both ends with plastic 
waterproof cement that will dry to a firm but pliable mass or with a mechanically adjustable segmented elastomer 
seal.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.10   Escutcheons</TTL><BRK/>
<BRK/>
<TXT>Escutcheons shall be provided for pipe penetration of ceilings and walls. Escutcheons shall be securely fastened 
to the pipe at surfaces through which piping passes.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.11   Inspector's Test Connection</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer will indicate location of the inspector's test connections and 
all associated valves on the contract drawings, and will provide details of 
drain piping, if drain piping is needed.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Unless otherwise indicated, test connection shall consist of<MET> 25 mm</MET><ENG> 1 inch</ENG> pipe connected [to the remote branch 
line] [at the riser as a combination test and drain valve]; a test valve located approximately<MET> 2 m</MET><ENG> 7 feet</ENG> above 
the floor; a smooth bore brass outlet equivalent to the smallest orifice sprinkler used in the system; and a 
painted metal identification sign affixed to the valve with the words "Inspector's Test."  The discharge orifice 
shall be located outside the building wall directed so as not to cause damage to adjacent construction or landscaping 
during full flow discharge.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.12   Drains</TTL><BRK/>
<BRK/>
<TXT>Provide main drain piping to discharge [at a safe point outside the building] [at the location indicated].  Auxiliary 
drains shall be provided as indicated and as required by <RID>NFPA 13</RID>.  When the capacity of trapped sections of pipe 
is less than<MET> 11 L</MET><ENG> 3 gallons</ENG>, the auxiliary drain shall consist of a valve not smaller than<MET> 13 mm</MET><ENG> 1/2 inch</ENG> and 
a plug or nipple and cap.  When the capacity of trapped sections of piping is more than<MET> 11 L</MET><ENG> 3 gallons</ENG>, the auxiliary 
drain shall consist of two<MET> 25 mm</MET><ENG> 1 inch</ENG> valves and one<MET> 50 x 300 mm</MET><ENG> 2 x 12 inch</ENG> condensate nipple or equivalent, 
located in an accessible location.  Tie-in drains shall be provided for multiple adjacent trapped branch pipes 
and shall be a minimum of<MET> 25 mm</MET><ENG> 1 inch</ENG> in diameter.  Tie-in drain lines shall be pitched a minimum of<MET>13 mm per 
3 m</MET><ENG> 1/2 inch per 10 feet</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.13   Installation of Fire Department Connection</TTL><BRK/>
<BRK/>
<TXT>Connection shall be mounted [on the exterior wall approximately<MET> 900 mm</MET><ENG> 3 feet</ENG> above finished grade] [adjacent 
to and on the sprinkler system side of the backflow preventer].  The piping between the connection and the check 
valve shall be provided with an automatic drip in accordance with <RID>NFPA 13</RID> and arranged to drain to the outside.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.14   Identification Signs</TTL><BRK/>
<BRK/>
<TXT>Signs shall be affixed to each control valve, inspector test valve, main drain, auxiliary drain, test valve, 
and similar valves as appropriate or as required by <RID>NFPA 13</RID>.  Hydraulic design data nameplates shall be permanently 
affixed to each sprinkler riser as specified in <RID>NFPA 13</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.6   UNDERGROUND PIPING INSTALLATION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Restraint of the underground piping must be detailed on the drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The fire protection water main shall be laid, and joints anchored, in accordance with <RID>NFPA 24</RID>.  Minimum depth 
of cover shall be<MET> [900] [_____] mm</MET><ENG> [3] [_____] feet</ENG>.  The supply line shall terminate inside the building with 
a flanged piece, the bottom of which shall be set not less than<MET> 150 mm</MET><ENG> 6 inches</ENG> above the finished floor.  A 
blind flange shall be installed temporarily on top of the flanged piece to prevent the entrance of foreign matter 
into the supply line.  A concrete thrust block shall be provided at the elbow where the pipe turns up toward 
the floor.  In addition, joints shall be anchored in accordance with <RID>NFPA 24</RID> using pipe clamps and steel rods 
from the elbow to the flange above the floor and from the elbow to a pipe clamp in the horizontal run of pipe.  
Buried steel components shall be provided with a corrosion protective coating in accordance with <RID>AWWA C203</RID>.  
Piping more than<MET> 1500 mm</MET><ENG> 5 feet</ENG> outside the building walls shall meet the requirements of Section <SRF>33 11 00</SRF> WATER 
DISTRIBUTION.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7   ELECTRICAL WORK</TTL><BRK/>
<BRK/>
<TXT>Unless otherwise specified herein, power supply equipment and wiring shall be in accordance with Section 
<SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.7.1   Overcurrent and Surge Protection</TTL><BRK/>
<BRK/>
<TXT>All equipment connected to alternating current circuits shall be protected from surges in accordance with <RID>IEEE C62.41.1</RID>
, <RID>IEEE C62.41.2</RID> and <RID>NFPA 70</RID>.  Cables and conductors that serve as communications links, except fiber optics, 
shall have surge protection circuits installed at each end.  Fuses shall not be used for surge protection.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.2   Grounding</TTL><BRK/>
<BRK/>
<TXT>Grounding shall be provided to building ground.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.3   Wiring</TTL><BRK/>
<BRK/>
<TXT>System field wiring shall be installed in<MET> 19 mm</MET><ENG> 3/4 inch</ENG> minimum diameter electrical metallic tubing or metallic 
conduit.  Wiring for the sprinkler system fire detection and control system shall be installed in tubing or conduits 
dedicated for that use only and not installed in conduit, outlet boxes or junction boxes which contain lighting 
and power wiring or equipment.  Circuit conductors entering or leaving any mounting box, outlet box enclosure 
or cabinet shall be connected to screw terminals with each terminal marked and labeled in accordance with the 
wiring diagram.  No more than one conductor shall be installed under any screw terminal.  Connections and splices 
shall be made using screw terminal blocks.  The use of wire nut type connectors is not permitted.  Wiring within 
any control equipment shall be readily accessible without removing any component parts.  Conductors shall be 
color-coded and shall be identified within each enclosure where a connection or termination is made.  Conductor 
identification shall be by plastic-coated, self-sticking, printed markers or by heat-shrink type sleeves.  Circuits 
shall be wired to maintain electrical supervision so that removal of any single wire from any device shall cause 
a "trouble" condition on the control panel.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.4   Control Panel</TTL><BRK/>
<BRK/>
<TXT>The control panel and its assorted components shall be mounted so that no part of the enclosing cabinet is less 
than<MET> 600 mm</MET><ENG> 24 inches</ENG> and not more than<MET> 2000 mm</MET><ENG> 78 inches</ENG> above the finished floor.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.5   Detectors</TTL><BRK/>
<BRK/>
<TXT>Detectors shall be ceiling-mounted in accordance with <RID>NFPA 72</RID> and shall be at least<MET> 300 mm</MET><ENG> 12 inches</ENG> from any 
part of any lighting fixture.  Detectors shall be located at least<MET> 900 mm</MET><ENG> 3 feet</ENG> from diffusers of air handling 
systems.  Each detector shall be provided with appropriate mounting hardware as required by its mounting location.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.6   Manual Actuation Stations</TTL><BRK/>
<BRK/>
<TXT>Manual actuation stations shall be mounted readily accessible and<MET> 1060 mm</MET><ENG> 42 inches</ENG> above the finished floor.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.7   Notification Appliances</TTL><BRK/>
<BRK/>
<TXT>Notification appliances shall be mounted a minimum of<MET> 2400 mm</MET><ENG> 8 feet</ENG> above the finished floor unless limited 
by ceiling height.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.8   DISINFECTION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For modification of existing systems, provide specific procedures for 
disinfection of new equipment.  If sprinkler piping is isolated from the domestic 
water piping systems by means of a reduced pressure backflow prevention assembly 
or if sprinkler piping in not connected to the domestic water piping, this paragraph 
should be deleted.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>After all system components are installed and hydrostatic test(s) are successfully completed, each portion of 
the sprinkler system to be disinfected shall be thoroughly flushed with potable water until all entrained dirt 
and other foreign materials have been removed before introducing chlorinating material.  Flushing shall be conducted 
by removing the flushing fitting of the cross mains and of the grid branch lines, and then back-flushing through 
the sprinkler main drains.  The chlorinating material shall be hypochlorites or liquid chlorine.  Water chlorination 
procedure shall be in accordance with <RID>AWWA C651</RID> and <RID>AWWA C652</RID>.  The chlorinating material shall be fed into the 
sprinkler piping at a constant rate of 50 parts per million (ppm).  A properly adjusted hypochlorite solution 
injected into the system with a hypochlorinator, or liquid chlorine injected into the system through a solution-fed 
chlorinator and booster pump shall be used.  Chlorination application shall continue until the entire system 
if filled.  The water shall remain in the system for a minimum of 24 hours.  Each valve in the system shall be 
opened and closed several times to ensure its proper disinfection.  Following the 24-hour period, no less than 
25 ppm chlorine residual shall remain in the system.  The system shall then be flushed with clean water until 
the residual chlorine is reduced to less than one part per million.  Samples of water in disinfected containers 
for bacterial examination will be taken from several system locations which are approved by the Contracting Officer.  
Samples shall be tested for total coliform organisms (coliform bacteria, fecal coliform, streptococcal, and other 
bacteria) in accordance with <RID>AWWA 10084</RID>.  The testing method shall be either the multiple-tube fermentation technique 
or the membrane-filter technique.  The disinfection shall be repeated until tests indicate the absence of coliform 
organisms (zero mean coliform density per 100 milliliters) in the samples for at least 2 full days.  The system 
will not be accepted until satisfactory bacteriological results have been obtained.  After the successful completion, 
all sprinklers or plugs and gravity flush all drops or trapped piping.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.9   PIPE COLOR CODE MARKING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer will coordinate color code marking with Seciton <SRF>09 90 00</SRF> PAINTS 
AND COATINGS.  Color code marking for piping which are not listed in Table I 
of Paragraph 3.5 Pipe Color Code Marking of UFGS Section <SRF>09 90 00</SRF> will be added 
to the table.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Color code marking of piping shall be as specified in Section <SRF>09 90 00</SRF> PAINTS AND COATINGS.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.10   <SUB>PRELIMINARY TESTS</SUB></TTL><BRK/>
<BRK/>
<TXT>The system, including the underground water mains, the aboveground piping, detectors and control system and system 
components shall be tested to assure that equipment and components function as intended.  The underground and 
aboveground interior piping systems and attached appurtenances subjected to system working pressure shall be 
tested in accordance with <RID>NFPA 13</RID> and <RID>NFPA 24</RID>.  Upon completion of specified tests, complete certificates as 
specified in paragraph SUBMITTALS.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.10.1   Underground Piping</TTL><BRK/>
<BRK/>
<TXT>Underground piping shall be flushed in accordance with <RID>NFPA 24</RID>.  This includes the requirement to flush the lead-in 
connection to the fire protection system at a flow rate not less that the calculated maximum water demand rate 
of the system.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.10.2   Hydrostatic Testing</TTL><BRK/>
<BRK/>
<TXT>New underground piping shall be hydrostatically tested in accordance with <RID>NFPA 24</RID>.  The allowable leakage shall 
be measured at the specified test pressure by pumping from a calibrated container.  The amount of leakage at 
the joints shall not exceed<MET> 2 L</MET><ENG> 2 quarts</ENG> per hour per 100 gaskets or joints, regardless of pipe diameter.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.10.3   Aboveground Piping</TTL><BRK/>
<BRK/>
<SPT><TTL>3.10.3.1   Hydrostatic Testing</TTL><BRK/>
<BRK/>
<TXT>Aboveground piping shall be hydrostatically tested in accordance with <RID>NFPA 13</RID> at not less than<MET> 1400 kPa</MET><ENG> 200 psi</ENG>
 or<MET> 350 kPa</MET><ENG> 50 psi</ENG> in excess of maximum system operating pressure and shall maintain that pressure without loss 
for 2 hours.  There shall be no drop in gauge pressure or visible leakage when the system is subjected to the 
hydrostatic test.  The test pressure shall be read from a gauge located at the low elevation point of the system 
or portion being tested.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.10.3.2   Air Pressure Test</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete this paragraph for deluge system applications and preaction systems 
not requiring supervisory air.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>As specified in <RID>NFPA 13</RID>, an air pressure leakage test at<MET> 350 kPa</MET><ENG> 50 psi</ENG> shall be conducted for 24 hours.  There 
shall be no drop in gauge pressure in excess of<MET> 10 kPa</MET><ENG> 1.5 psi</ENG> for the 24 hours.  This air pressure test is in 
addition to the required hydrostatic test.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.10.3.3   Backflow Prevention Assembly Forward Flow Test</TTL><BRK/>
<BRK/>
<TXT>Each backflow prevention assembly shall be tested at system flow demand, including all applicable hose streams, 
as specified in <RID>NFPA 13</RID>.  Provide all equipment and instruments necessary to conduct a complete forward flow 
test, including<MET> 65 mm</MET><ENG> 2.5 inch</ENG> diameter hoses, playpipe nozzles, calibrated pressure gauges, and pitot tube gauge.  
Provide all necessary supports to safely secure hoses and nozzles during the test.  At the system demand flow, 
the pressure readings and pressure drop (friction) across the assembly shall be recorded.  A metal placard shall 
be provided on the backflow prevention assembly that lists the pressure readings both upstream and downstream 
of the assembly, total pressure drop, and the system test flow rate.  The pressure drop shall be compared to 
the manufacturer's data.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.10.4   Detection and Control System Tests</TTL><BRK/>
<BRK/>
<TXT>Upon completion of the installation, the detection and control system shall be subjected to functional and operational 
performance tests including tests of each installed initiating device, system actuation device and notification 
appliance.  The control system tests specified in paragraph FINAL ACCEPTANCE TESTS shall be conducted to ensure 
that the system is completely functional and that wiring has been properly connected.  If deficiencies are found, 
corrections shall be made and the system shall be retested to assure that the systems have no deficiencies.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.10.5   Automatic Water Control Valve Test</TTL><BRK/>
<BRK/>
<TXT>Each water control valve shall be independently trip-tested in accordance with the manufacturer's published instructions.  
Each valve shall be electrically trip-tested by actuating a respective heat detector and a manual actuation station 
connected to the control panel and a manual actuation device that is part of the valve trim.  A full-flow main 
drain test shall be made.  For preaction systems with supervisory air, the air pressure shall be reduced to verify 
proper operation of the air supply system and associated supervisory alarm devices.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.11   <SUB>FINAL ACCEPTANCE TESTS</SUB></TTL><BRK/>
<BRK/>
<TXT>Final Acceptance Test shall begin only when the Preliminary Test Report has been approved.  The Fire Protection 
Specialist shall conduct the Final Acceptance Test and shall provide a complete demonstration of the operation 
of the system.  This shall include operation of control valves and flowing of inspector's test connections to 
verify operation of associated waterflow alarm switches.  After operation of control valves has been completed, 
the main drain test shall be repeated to assure that control valves are in the open position.  Each system shall 
be completely drained after each trip test.  The system air supply system shall be tested to verify that system 
pressure is restored in the specified time.  In addition, the Fire Protection Specialist shall have available 
copies of <SUB>as-built drawings</SUB> and certificates of tests previously conducted.  The installation shall not be considered 
accepted until identified discrepancies have been corrected and test documentation is properly completed and 
received.  After the system has been tested and drained, the system shall be drained periodically for at least 
2 weeks until it can be assured that water from the system has been removed.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.11.1   Control System Test</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Listed tests are minimum required.  If additional tests are required, 
such tests must be added to the list.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Testing shall be in accordance with <RID>NFPA 72</RID>.  The test shall include the following:</TXT><BRK/>
<BRK/>
<LST>a.  Visual inspection of wiring connections.</LST><BRK/>
<BRK/>
<LST>b.  Opening the circuit at each alarm initiating device, solenoid valve, and notification appliance to 
test the wiring and supervisory features.</LST><BRK/>
<BRK/>
<LST>c.  Test of each function of the control panel.</LST><BRK/>
<BRK/>
<LST>d.  Test of each circuit in the normal, open and ground fault modes.</LST><BRK/>
<BRK/>
<LST>e.  Test of each initiating device in both normal and trouble conditions.</LST><BRK/>
<BRK/>
<LST>f.  Test of each control circuit and device.</LST><BRK/>
<BRK/>
<LST>g.  Test of each alarm notification appliance.</LST><BRK/>
<BRK/>
<LST>h.  Test of the battery charger and batteries.</LST><BRK/>
<BRK/>
<LST>i.  Operational tests under emergency power supply, including activation of connected alarm notification 
appliances for the specified time period.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>3.11.2   Trip-tests of Automatic Water Control Valves</TTL><BRK/>
<BRK/>
<TXT>Each water control valve shall be independently trip-tested in accordance with the manufacturer's published instructions.  
Each valve shall be electrically trip-tested by actuating a respective heat detector, a manual actuation station 
connected to the system control panel and the manual release which is part of the valve trim.  Each valve shall 
be returned to normal condition after each test.  Prior to trip testing sprinkler deluge system, precautionary 
steps shall be taken to prevent water damage to the building and equipment from sprinkler discharge.  [Control 
valves on deluge systems shall [be shut off immediately after automatic water control valve trips] [remain open 
until open sprinklers have discharged for a minimum of [10] [_____] seconds].] [Control valves on preaction systems 
shall remain open until piping is filled with water.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.11.3   Tests of Supervisory Air System</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete this paragraph for deluge system applications and preaction systems 
not requiring supervisory air.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Preaction system supervisory air pressure shall be reduced from the normal system pressure to the point at which 
a low-pressure alarm is sounded.  Air pressure shall be restored to verify trouble signal restoration.  Automatic 
start/stop features of air compressor shall be tested.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.12   <SUB>ONSITE TRAINING</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The number of hours of instruction should be determined based of the 
number and complexity of the systems specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The Fire Protection Specialist shall conduct a training course for operating and maintenance personnel as designated 
by the Contracting Officer.  Training shall be provided for a period of [_____] hours of normal working time 
and shall start after the system is functionally complete and after the Final Acceptance Test.  The Onsite Training 
shall cover all of the items contained in the approved <SUB>Operating and Maintenance Instructions</SUB>.</TXT><BRK/>
<BRK/></SPT>
</PRT>    <END/><BRK/></SEC>