<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA   UFGS-21 13 20.00 20 (April 2006)<BRK/>
                                 ------------------------------<BRK/>
Preparing Activity:  <PRA>NAVFAC</PRA>      Replacing without change<BRK/>
                                 UFGS-13956N (September 1999)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 21 13 20.00 20</SCN><BRK/>
<BRK/>
<STL>FOAM FIRE EXTINGUISHING FOR AIRCRAFT HANGARS</STL><BRK/>
<DTE>04/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>automatic deluge, 
and pre-action fire extinguishing foam systems for aircraft hangars</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For fuel tank farm protection use Section 21 13 21.00 20 FOAM FIRE EXTINGUISHING 
FOR FUEL TANK PROTECTION. For hazardous and flammable handling and storage facilities 
such as truck or rail loading/unloading racks, hazardous/flammable liquid warehouses, 
fuel pump houses and laboratories, use Section 21 13 22.00 20 FOAM FIRE EXTINGUISHING 
FOR HAZ/FLAM MATERIAL FACILITY.  Choose the type of system most appropriate 
for the hazard.  Deluge systems are primarily intended for fire protection of 
aircraft hangar facilities.  Pre-action systems may be required for Air Force 
hangars even though NFPA 409 recommends deluge systems for aircraft hangars.  
Consult the current edition of AFR 88-15, "Criteria and Standards for Air Force 
Construction" for Air Force projects.  Pre-action systems provide added safety 
against accidental discharge by requiring both actuation of a detector and fusing 
of a sprinkler head before foam discharge will occur. Deluge systems provide 
the fastest fire extinguishment.  Areas larger than<MET> 279 sq meters</MET><ENG> 3,000 square 
feet</ENG> and all deluge systems must be hydraulically designed for uniform distribution.  
Assure that up to date reliable hydraulic data is used in design of the project.  
Do not show sprinkler piping layout and heads on project drawings.  System requirements 
must conform to the current edition of Unified Facilities Criteria (UFC) 3-600-01 
Design: Fire Protection Engineering for Facilities.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If there are questions concerning type of foam systems required, consult 
the Engineering Field Division, Naval Facilities Engineering Command.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following information shall be shown on the project drawings:</NPR><BRK/>
<BRK/>
<NPR>1.  Location and detail of each foam system supply riser, deluge, or pre-action 
valve, water motor alarm, fire department inlet connection, foam hydrant, hand 
hose station, monitor nozzle, air compressor(s), and associated electrical connections.</NPR><BRK/>
<BRK/>
<NPR>2.  Point of connection to the existing water distribution system.</NPR><BRK/>
<BRK/>
<NPR>3.  Location of foam system control valves and post indicator valves.</NPR><BRK/>
<BRK/>
<NPR>4.  Area(s) of foam system coverage, with zone designations (if multiple zones).  
Do not show piping layout.</NPR><BRK/>
<BRK/>
<NPR>5.  Location and design of draft curtains as required by NFPA 409 for aircraft 
hangar.</NPR><BRK/>
<BRK/>
<NPR>6.  For pipe larger than<MET> 305 mm</MET><ENG> 12 inches</ENG>, detail methods of anchoring pipe 
including pipe clamps and tie rods.</NPR><BRK/>
<BRK/>
<NPR>7.  Location of foam proportioning equipment and storage tank.</NPR><BRK/>
<BRK/>
<NPR>8.  Show locations of control panel, annunciator(s), alarm devices, manual actuation 
stations, point of connection to the building fire evacuation alarm system, 
remote trouble device, point of connection to the incoming power supply and 
fusible safety switch.  Do not show conduit sizes or number of conductors for 
DC circuits.  Do not show locations of detectors.</NPR><BRK/>
<BRK/>
<NPR>9.  Show single line riser diagram for all detection, activation, and alarm 
circuits. Connection of equipment shall be indicated by circuit runs and not 
conduit runs.  Do not indicate number and size of conductors for interconnection 
of fire alarm components.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>AMERICAN WATER WORKS ASSOCIATION (AWWA)</ORG><BRK/><BRK/><RID>AWWA C500</RID><RTL>(2002; R 2003) Metal-Seated Gate Valves for Water Supply Service</RTL><BRK/><BRK/><RID>AWWA C651</RID><RTL>(2005; Errata 2005) Standard for Disinfecting Water Mains</RTL><BRK/><BRK/></REF><REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 53/A 53M</RID><RTL>(2007) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless</RTL><BRK/><BRK/></REF><REF><ORG>FM GLOBAL (FM)</ORG><BRK/><BRK/><RID>FM P7825</RID><RTL>(2005) Approval Guide</RTL><BRK/><BRK/></REF><REF><ORG>FOUNDATION FOR CROSS-CONNECTION CONTROL AND HYDRAULIC RESEARCH (FCCCHR)</ORG><BRK/><BRK/><RID>FCCCHR List</RID><RTL>(continuously updated) List of Approved Backflow Prevention Assemblies</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 11</RID><RTL>(2005; Amendment 1 2006; Amendment 2 2007) Low-, Medium- and High- Expansion Foam Systems</RTL><BRK/><BRK/><RID>NFPA 13</RID><RTL>(2006; Errata 2007; Amendment 1 2008) Installation of Sprinkler Systems</RTL><BRK/><BRK/><RID>NFPA 14</RID><RTL>(2006) Standard for the Installation of Standpipe, Private Hydrants and Hose Systems</RTL><BRK/><BRK/><RID>NFPA 15</RID><RTL>(2006) Water Spray Fixed Systems for Fire Protection</RTL><BRK/><BRK/><RID>NFPA 16</RID><RTL>(2006) Installation of Foam-Water Sprinkler and Foam-Water Spray Systems</RTL><BRK/><BRK/><RID>NFPA 24</RID><RTL>(2006) Standard for the Installation of Private Fire Service Mains and Their Appurtenances</RTL><BRK/><BRK/><RID>NFPA 30</RID><RTL>(2007; Errata 2008) Flammable and Combustible Liquids Code</RTL><BRK/><BRK/><RID>NFPA 409</RID><RTL>(2004; TIA 2005; TIA 2006) Standard on Aircraft Hangers</RTL><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/><RID>NFPA 72</RID><RTL>(2006) National Fire Alarm Code</RTL><BRK/><BRK/></REF><REF><ORG>THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)</ORG><BRK/><BRK/><RID>SSPC Paint 22</RID><RTL>(1982; E 2004) Paint Specification No. 22 Epoxy-Polyamide Paints (Primer, Intermediate, and Topcoat)</RTL><BRK/><BRK/><RID>SSPC Paint 25</RID><RTL>(1997; E 2004) Paint Specification No. 25Zinc Oxide, Alkyd, Linseed Oil Primer for Use Over Hand Cleaned Steel Type I and Type II</RTL><BRK/><BRK/><RID>SSPC SP 11</RID><RTL>(1987; E 2004) Power Tool Cleaning to Bare Metal</RTL><BRK/><BRK/><RID>SSPC SP 3</RID><RTL>(2004; E 2004) Power Tool Cleaning</RTL><BRK/><BRK/><RID>SSPC SP 6</RID><RTL>(7) Commercial Blast Cleaning</RTL><BRK/><BRK/></REF><REF><ORG>U.S. DEPARTMENT OF DEFENSE (DOD)</ORG><BRK/><BRK/><RID>MIL-F-24385</RID><RTL>(Rev F; Am 1) Fire Extinguishing Agent, Aqueous Film Forming Foam (AFFF) Liquid Concentrate, for Fresh and Seawater</RTL><BRK/><BRK/><RID>MIL-P-24441</RID><RTL>(Rev C; Supp 1; INT Am 1) Paint, Epoxy-Polyamide</RTL><BRK/><BRK/></REF><REF><ORG>U.S. GENERAL SERVICES ADMINISTRATION (GSA)</ORG><BRK/><BRK/><RID>FS A-A-2962</RID><RTL>(Rev J) Enamel, Alkyd, Gloss, Low VOC Content</RTL><BRK/><BRK/><RID>FS A-A-58092</RID><RTL>(Basic) Tape, Antiseize, Polytetrafluoroethylene</RTL><BRK/><BRK/><RID>FS WW-S-2739</RID><RTL>(Basic) Strainers, Sediment:  Pipeline, Water, Air, Gas, Oil, or Steam</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 262</RID><RTL>(2004) Standard for Gate Valves for Fire-Protection Service</RTL><BRK/><BRK/><RID>UL 789</RID><RTL>(2004; Rev thru Aug 2008) Indicator Posts for Fire-Protection Service</RTL><BRK/><BRK/><RID>UL Fire Prot Dir</RID><RTL>(2008) Fire Protection Equipment Directory</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   DEFINITION</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Year 2000 compliant - means computer controlled facility components that accurately process 
date and time data (including, but not limited to, calculating, comparing, and sequencing) from, 
into, and between the twentieth and twenty-first centuries, and the years 1999 and 2000 and 
leap year calculations.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   RELATED REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Section <SRF>23 03 00.00 20</SRF> BASIC MECHANICAL MATERIALS AND METHODS, applies to this section, with the additions and 
modifications specified herein.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   SYSTEM DESCRIPTION</TTL><BRK/>
<BRK/>
<SPT><TTL>1.4.1   Design Requirements</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Identify the rooms, spaces or areas, as appropriate, which are to be 
protected by each system.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include only those NFPA codes applicable to the specific project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Design and [provide a new] [and] [modify an existing] automatic aqueous film forming foam (AFFF) [deluge] [pre-action] 
sprinkler system(s) [and under-wing supplemental protection system] for [_____].  System shall provide uniform 
distribution of AFFF solution to provide complete coverage throughout the [building] [areas indicated].  The 
design, equipment, materials, installation, and workmanship shall be in strict accordance with the required and 
advisory provisions of <RID>NFPA 11</RID>, <RID>NFPA 13</RID>, [<RID>NFPA 14</RID>,] [<RID>NFPA 15</RID>,] <RID>NFPA 16</RID>, [<RID>NFPA 24</RID>,] [<RID>NFPA 30</RID>,] <RID>NFPA 70</RID>, <RID>NFPA 72</RID>
, and <RID>NFPA 409</RID>, except as modified herein.  Each system [shall be designed for earthquakes and] shall include 
all materials, accessories and equipment necessary to provide each system complete and ready for use.  Design 
and install each system to give full consideration to blind spaces, piping, electrical equipment, ductwork, and 
all other construction and equipment to provide complete coverage in accordance with the drawings to be submitted 
for approval.  Devices and equipment for fire protection service shall be of a make and type listed by the Underwriter's 
Laboratories Inc. in the <RID>UL Fire Prot Dir</RID>, or approved by the Factory Mutual System and listed in <RID>FM P7825</RID>.  
In the publications referred to herein, the advisory provisions shall be considered to be mandatory, as though 
the word "shall" had been substituted for "should" wherever it appears; reference to the "authority having jurisdiction" 
shall be interpreted to mean the [[_____] Division, Naval Facilities Engineering Command Fire Protection Engineer] 
[Corps of Engineers Contracting Officer].  Begin work at the point indicated.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.4.1.1   Shop Drawings</TTL><BRK/>
<BRK/>
<TXT>Prepare shop drawings for <SUB>fire extinguishing system</SUB> in accordance with the requirements for "Plans" as specified 
in <RID>NFPA 11</RID> and "Working Plans" as specified in <RID>NFPA 13</RID>.  Each drawing shall be<MET> A1 841 x 594 mm</MET><ENG> 34 by 22 inches</ENG>
. Do not commence work until the design of each system and the various components have been approved.  Show:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Room, space or area layout and include data essential to the proper installation of each 
system</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Sprinkler heads, discharge nozzles and system piping layout annotated with reference points 
for design calculations</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Field wiring diagrams showing locations of devices and points of connection and terminals 
used for all electrical field connections in the system, with wiring color code scheme</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[d.  UV-IR detector manufacturer's recommended detector layout (plan view) including horizontal 
and vertical angles for correct aiming].</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.1.2   Calculations</TTL><BRK/>
<BRK/>
<TXT>Submit design calculations for the system.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  <SUB>Hydraulic calculations</SUB> showing basis for design in accordance with <RID>NFPA 11</RID> and <RID>NFPA 13</RID>.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  <SUB>Pressure discharge graphs or tables</SUB> showing pressure discharge relationship for sprinkler 
heads and discharge nozzles.</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Regarding the text below, consult with the Division Fire Protection Engineer 
before specifying 2-wire smoke detectors as a Contractor option.  2-wire detectors 
must be carefully matched to the control panel by the manufacturer, and are 
not universally interchangeable between systems for maintenance purposes.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">c.  Substantiating <SUB>battery standby power requirements calculations</SUB>showing battery capacity, 
supervisory and alarm power requirements.  [If 2-wire smoke detectors are proposed for use show 
comparison of the detector power requirements per zone versus the control panel smoke detector 
power output per zone in both the standby and alarm modes.]</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include the text below for Air Force Projects only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">[d.  <SUB>System surge analysis</SUB> showing surge pressure occurring throughout the system at both design 
flow and nonflow conditions.]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.1.3   <SUB>AFFF Containment and Disposal Plan</SUB></TTL><BRK/>
<BRK/>
<TXT>Submit AFFF containment and disposal plan as required under paragraph entitled "Environmental Protection."</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.1.4   <SUB>As-Built Drawings for the Fire Extinguishing System</SUB></TTL><BRK/>
<BRK/>
<TXT>Upon completion, and before final acceptance of the work, submit a complete set of as-built drawings for the 
fire extinguishing system [, including complete as-built circuit diagrams,].  Submit<MET> A1 841 x 594 mm</MET><ENG> 34 by 22 
inch</ENG> reproducible as-built drawings on mylar film with<MET> 200 by 100 mm</MET><ENG> 8 by 4 inch</ENG> title block similar to contract 
drawings.  Submit as-built drawings in addition to the record drawings required by Division 1.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.4.2   System Operation</TTL><BRK/>
<BRK/>
<TXT>Flow of water and AFFF shall be controlled by [deluge] [pre-action] valves.  Foam proportioning equipment shall 
activate automatically upon tripping of the [deluge] [pre-action] valve(s) for the corresponding foam system(s).  
[Deluge] [Pre-action] valves shall be tripped by independent detection systems.  No valve will be operated by 
the building fire evacuation alarm system.  Use of motor-operated valves is prohibited.  Once activated, system(s) 
shall operate until shut down manually.  Provide separate circuits from the control panel to each zone of initiating 
devices.  Transmission of signals from more than one zone over a common circuit is prohibited.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.4.2.1   Overhead Systems</TTL><BRK/>
<BRK/>
<TXT>Overhead systems shall be controlled by [deluge] [pre-action] valves operated by automatic detection systems 
and by remote manual release stations.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.2.2   Monitor System</TTL><BRK/>
<BRK/>
<TXT>Monitor nozzles shall be controlled by deluge valves operated by [the automatic detection systems and manual 
release stations which activate the corresponding overhead system(s)] [independent ultraviolet-infrared (UV-IR) 
optical detection systems and manual stations] [flow of AFFF solution in the overhead system].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.2.3   Hose System</TTL><BRK/>
<BRK/>
<TXT>Hose reels shall be controlled by deluge valves operated by remote manual release stations, separate from those 
used for overhead systems and monitor nozzles.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>1.5   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
[<TXT>The fire protection engineer, [_____] Division, Naval Facilities Engineering Command will review any approve 
all submittals in this section requiring Government approval.</TXT>]<BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For projects administered by the Pacific Division, Naval Facilities Engineering 
Command, use the optional "SUBMITTALS" article immediately below and delete 
the general "SUBMITTALS" article above.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
[<TXT>The [_____] Division, Naval Facilities Engineering Command, Fire Protection Engineer delegates the authority 
to the Quality Control (QC) Representative's U.S. Registered Fire Protection Engineer for review and approval 
of submittals required by this section.  Submit to the [_____] Division, Naval Facilities Engineering Command, 
Fire Protection Engineer one set of all approved submittals and drawings immediately after approval but no more 
later than 15 working days prior to final inspection.</TXT>]<BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Fire extinguishing system</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Pipe, fittings, and mechanical couplings</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>[Deluge] [Pre-action] valves</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Valves</SUB>, including gate, check, and globe[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Water motor alarms</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Sprinkler heads</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Monitor nozzles</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Hose and nozzles</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Pipe hangers and supports</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Pressure switch</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Fire department inlet connections</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Tank mounted air compressor</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Air pressure regulating device</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Air compressor</SUB> (pneumatic detection system)[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Low air pressure <SUB>trouble alarm</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Detection devices</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Storage batteries</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Alarm bells</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Alarm horns</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Annunciator panel</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Foam hydrants</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>AFFF concentrate storage tanks</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Proportioning equipment</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>AFFF concentrate</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
[<ITM><SUB>Strainers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
<ITM><SUB>Manual release stations</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Backflow preventers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Control panel</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Battery charger</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Data which describe more than one type of item shall be clearly marked to indicate which type 
the Contractor intends to provide.  Submit only originals.  Photocopies will not be accepted.  
Partial submittals will not be accepted.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-05 Design Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Hydraulic calculations</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Pressure discharge graphs or tables</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Battery standby power requirements calculations</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
[<ITM><SUB>System surge analysis</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM>]<BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Consult with the Division Fire Protection Engineer before specifying 
2-wire smoke detectors as a Contractor option.  2-wire detectors must be carefully 
matched to the control panel by the manufacturer, and are not universally interchangeable 
between systems for maintenance purposes.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM>Open-area (Spot-Type) <SUB>2-wire smoke detectors</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit copies of UL listing or FM approval data showing compatibility of the smoke detector 
model being provided with the control panel being provided, if 2-wire detectors are proposed 
for use.</ITM><BRK/>
<BRK/>
<ITM><SUB>Preliminary tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Acceptance tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit for all inspections and tests specified under paragraph entitled "Field Quality Control."</ITM><BRK/>
<BRK/>
<ITM>Hydrostatic testing of the <SUB>diaphragm pressure proportioning tanks</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Qualifications of installer</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit installers qualifications as required under paragraph entitled Qualifications of Installer."</ITM><BRK/>
<BRK/>
<ITM><SUB>AFFF containment and disposal plan</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Backflow preventers</SUB>; <SUB>G</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>[Deluge] [Pre-action] valves</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Tank mounted air compressor</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Proportioning equipment</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Control panel</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>AFFF concentrate storage tanks</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Monitor nozzles</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Instructions for operating the <SUB>fire extinguishing system</SUB>, Data Package 4[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE DATA.  Furnish one complete 
set of data prior to the time that final acceptance tests are performed, and furnish the remaining 
sets before the contract is completed.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-11 Closeout Submittals</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>As-built drawings for the fire extinguishing system</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.6   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.6.1   <SUB>Qualifications of Installer</SUB></TTL><BRK/>
<BRK/>
<TXT>Prior to commencing work, submit data showing that the Contractor has successfully installed automatic foam fire 
extinguishing sprinkler systems of the same type and design as specified herein, or that he has a firm contractual 
agreement with a subcontractor having the required experience.  Include the names and locations of at least two 
installations where the Contractor, or the subcontractor referred to above, has installed such systems.  Indicate 
the type and design of each system, and certify that the system has performed satisfactorily for a period of 
at least 18 months.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For projects administered by the Pacific Division, Naval Facilities Engineering 
Command, include the following optional paragraph requiring the minimum qualification 
of a NICET Level-III technician for preparation of all fire protection system 
drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Qualifications of System Technician:  Installation drawings, shop drawing and as-built drawings shall be prepared, 
by or under the supervision of, an individual who is experienced with the types of works specified herein, and 
is currently certified by the National Institute for Certification in Engineering Technologies (NICET) as an 
engineering technician with minimum Level-III certification in Special Hazard System program.  Contractor shall 
submit data for approval showing the name and certification of all involved individuals with such qualifications 
at or prior to submittal of drawings.]</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.7   SPARE PARTS</TTL><BRK/>
<BRK/>
<TXT>Furnish the following spare parts:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  2 of each type of detector installed.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  1 of each type of audible and/or visual alarm device installed.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  2 of each type of fuse required by the system.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  5 complete sets of system keys.</ITM><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   DESIGN OF FOAM SYSTEMS</TTL><BRK/>
<BRK/>
<TXT>Design of [deluge] [pre-action] fire extinguishing foam systems shall be by hydraulic calculations for uniform 
distribution of AFFF solution over the protected area and shall conform to the NFPA standards listed above and 
to the requirements as specified herein.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.1   <SUB>Sprinkler Heads</SUB></TTL><BRK/>
<BRK/>
<TXT>Heads shall have<MET> 15 [or 13.50] mm</MET><ENG> 1/2 [or 17/32] inch</ENG> orifice.  No o-rings will be permitted in sprinkler heads.  
[For deluge systems, provide open heads.]  [For pre-action systems, the release element of each head shall be 
of the ["intermediate"] ["high"] temperature rating or higher as suitable for the individual location installed.] 
Provide chromium plated ceiling plates and pendent sprinklers below suspended ceilings.  Provide corrosion resistant 
sprinkler heads and sprinkler head guards as required by <RID>NFPA 13</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   Cabinet</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Deluge systems do not require a sprinkler head cabinet.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide extra sprinkler heads and sprinkler head wrench in a metal cabinet adjacent to the pre-action valve within 
each building. The number and types of extra sprinkler heads shall be as specified in <RID>NFPA 13</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.3   <SUB>[Deluge] [Pre-Action] Valves</SUB></TTL><BRK/>
<BRK/>
<TXT>Valves shall be operated by a detection system listed for releasing service and independent of the building fire 
alarm system.  [[Deluge] [Pre-action] valve clappers shall incorporate a latching mechanism that will not be 
affected by changes of pressure in the water system.]  If<MET> 150 mm</MET><ENG> 6 inch</ENG> valves are used in<MET> 200 mm</MET><ENG> 8 inch</ENG> risers, 
provide smoothly tapered connections.  In addition to automatic operation, arrange each valve for manual release 
at the valve.  Provide pressure gages and other appurtenances at the [deluge] [pre-action] valves as required 
by <RID>NFPA 13</RID>.  Provide a detection device at the end of each actuation circuit to test the circuit and mount the 
device [adjacent to the valve] between<MET> 1.80 and 2.40 meters</MET><ENG> 6 and 8 feet</ENG> above the finish floor.  Label each 
testing device to indicate the valve it activates.  [Provide remote manual releases [at [_____]] [where shown].]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.4   AFFF Solution Distribution</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the first option for pre-action systems.  Select the second option 
for deluge systems. </NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Distribution shall be essentially uniform throughout the area in which it is assumed the sprinkler heads will 
open.  Variation in discharge from individual heads in the hydraulically most remote area shall be between 100 
and 115 percent of the specified density.]</TXT><BRK/>
<BRK/>
<TXT>[Distribution shall be essentially uniform throughout the area.  Variation in discharge from individual heads 
shall be between 100 and 115 percent of the specified density.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.5   AFFF Solution Application Density</TTL><BRK/>
<BRK/>
<TXT>Size system to provide the specified density when the system is discharging the specified total maximum required 
flow.  Application to horizontal surfaces below the ceiling sprinklers shall be<MET> 110 mL/sec per sq meter</MET><ENG> 0.16 
gallons per minute (gpm) per square foot</ENG> with simultaneous operation of [_____] operating foam monitor nozzles, 
[and] [_____] operating foam hose lines[, and with outside water hose stream requirements of [_____]<MET> mL/sec</MET><ENG> gpm</ENG>
].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.6   Sprinkler Discharge Area</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the first option for pre-action systems only and refer to MIL-HDBK-1008 
and the appropriate NFPA standard(s) governing the particular facility to determine 
the discharge area required.  Select the second option for deluge systems only 
and refer to NFPA 409 to determine the discharge area required for hangars.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Area shall be the hydraulically most remote [_____] square<MET> meter</MET><ENG> foot</ENG> area as defined by <RID>NFPA 13</RID>.]</TXT><BRK/>
<BRK/>
<TXT>[Area shall be [that protected by each riser] [based on the<MET> [15.25] [22.75] [30.50] meter</MET><ENG> [50] [75] [100] foot</ENG>
 radius rule as determined in accordance with <RID>NFPA 409</RID> for Type I aircraft hangars].]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.7   Friction Losses</TTL><BRK/>
<BRK/>
<TXT>Calculate losses in pipe in accordance with the Hazen-Williams Formula with 'C' value of 100 for steel pipe [except 
120 for steel pipe used in deluge systems], 150 for copper tube, and 140 for cement lined ductile iron pipe.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.8   Location of Sprinkler Heads</TTL><BRK/>
<BRK/>
<TXT>Location of heads in relation to the ceiling and spacing of sprinkler heads shall conform to <RID>NFPA 13</RID> for extra 
hazard occupancy.  The spacing of sprinklers on the branch lines shall be essentially uniform.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.9   Water Supply</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select first option if the water supply is provided directly from the 
base water distribution system and show or specify the point of connection. 
Select second option if the water supply is provided from fire pumps dedicated 
to the AFFF system, which are taking suction from a static water source. Select 
third option if the water supply is provided from booster fire pumps being supplied 
from the base water distribution system, and show or specify the point of connection 
to the base system.  Edit Section 13920, "Fire Pumps" and include as part of 
the project specification when using the second or third option.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Base hydraulic calculations on a static pressure of [_____]<MET> kPa (gage) with [_____] L/m</MET><ENG> pounds per square inch 
gage (psig) with [_____] gpm</ENG> being available at a residual pressure of [_____]<MET> kPa (gage)</MET><ENG> psig</ENG> at the point [indicated] 
[of connection with the base water distribution system].]</TXT><BRK/>
<BRK/>
<TXT>[Base hydraulic calculations on [_____] fire pump(s) running.  Provide fire pumps as specified in Section 
<SRF>21 30 00</SRF> FIRE PUMPS.]</TXT><BRK/>
<BRK/>
<TXT>[Base hydraulic calculations on [_____] fire pump(s) running, with a suction supply having a static pressure 
of [_____]<MET> kPa (gage)</MET><ENG> psig</ENG> with [_____]<MET> L/m</MET><ENG> gpm</ENG> being available at a residual pressure of [_____]<MET> kPa (gage)</MET><ENG> 
psig</ENG> at the point [indicated] [of connection with the base water distribution system].  Provide fire pumps as 
specified in Section <SRF>21 30 00</SRF> FIRE PUMPS].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.10   Duration of Discharge</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For sprinkler and monitors discharge duration, consult NFPA 409.  For 
hose station discharge duration, consult NFPA 30 and NFPA 409.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>System shall apply foam solution over the sprinkler discharge area for a minimum of [10] [_____] minutes while 
simultaneously discharging foam solution through monitors for a minimum of [10] [_____] minutes.  Hose station 
discharge time shall be a minimum of [20] [_____] minutes. Reduction of the discharge duration based on a discharge 
rate higher than the specified minimum is not permitted.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2   ELECTRIC <SUB>DETECTION DEVICES</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Electric detection system may be used with all detector types specified 
in this guide specification and are necessary for complex controls. </NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide electric [heat detectors,] [and] [smoke detectors,] [and] [combination ultraviolet-infrared detectors].  
All wiring shall be supervised and installed in protective metal conduit or tubing.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.1   <SUB>Control Panel</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select either "Class B" or Class A" supervision ("Style B" or "Style 
D" as defined by NFPA 72).  "Class B" supervision which will normally be used, 
provides a trouble indication when a failure occurs in a circuit.  "Class A" 
supervision provides a trouble indication when a fault occurs in a circuit and 
at the same time allows continued operation of that circuit.  "Class A" supervision 
should be used for strategically critical facilities.  Select first ("Class 
B") or second ("Class A") supervisory option accordingly.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide a remote trouble bell or buzzer in a constantly attended area 
if the control panel is not so located.  Provide a trouble bell at the control 
panel if the panel is located in a high noise area. Coordinate location of remote 
trouble bell and remote annunciator panel when both are provided.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Modular type panel installed in a [flush] [surface] mounted steel cabinet with hinged door and cylinder lock.  
Switches and other controls shall not be accessible without the use of a key.  The control panel shall be a neat, 
compact, factory-wired assembly containing all parts and equipment required to provide specified operating and 
supervisory functions of the system. Panel cabinet shall be finished on the inside and outside with factory-applied 
enamel finish.  Provide main annunciator located on the exterior of the cabinet door or visible through the cabinet 
door.  Provide audible trouble signal.  Provide prominent engraved rigid plastic or metal identification plates, 
or silk-screened labels attached to the rear face of the panel viewing window, for all lamps and switches.  System 
power shall be 120 volts AC service, transformed through a two winding isolation transformer and rectified to 
24 volts DC for operation of all system initiating, actuating, signal sounding, trouble signal and fire alarm 
tripping circuits.  System shall be electrically supervised on all circuits.  [A ground fault condition or a 
single break in any circuit which prevents the required operation of the system shall result in the operation 
of the system trouble signal.]  [A single open or ground fault condition in any detection (initiating) [or signaling] 
circuit shall not result in any loss of system function, but shall cause the actuation of system trouble signals.  
A ground fault condition or single break in any other circuit shall result in the activation of the system trouble 
signals.]  Loss of AC power, a break in the standby battery power circuits, or abnormal AC power or low battery 
voltage shall result in the operation of the system trouble signals.  The abnormal position of any system switch 
in the control panel shall result in the operation of the system trouble signals.  Trouble signals shall operate 
continuously until the system has been restored to normal at the control panel.  System trouble shall also be 
annunciated on the appropriate zone of the building fire alarm panel.  [Provide a<MET> 100 mm</MET><ENG> 4 inch</ENG> remote system 
trouble bell [or buzzer], installed [in a constantly attended area] [where shown], arranged to operate in conjunction 
with the integral trouble signals of the panel.  Provide remote bell [or buzzer] with a rigid plastic or metal 
identification sign which reads "Foam System Trouble."  Lettering on identification sign shall be a minimum of<MET>
 25 mm</MET><ENG> one inch</ENG> high.]  Control panel, batteries, and battery charger shall be weatherproof type or located in 
an area not subject to water damage.  System control panel shall be UL listed or FM approved for extinguishing 
system control (releasing device service).  Permanently label all switches.  Provide panel with the following 
switches:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Trouble silencing switch which transfers audible trouble signals (including remote trouble 
devices, if provided) to an indicating lamp.  Upon correction of the trouble condition, audible 
signals will again sound until the switch is returned to its normal position, or the trouble 
signal circuit shall be automatically restored to normal upon correction of the trouble condition.  
The silencing switch may be a momentary action, self-resetting type.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Alarm silencing switch which when activated will silence all associated alarm devices without 
resetting the panel, and cause operation of system trouble signals.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Individual zone disconnect switches which when operated will disable only their respective 
initiating circuit and cause operation of the system and zone trouble signals.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Reset switch which when activated will restore the system to normal standby status after 
the cause of the alarm has been corrected, and all activated initiating devices reset.  [Operation 
of reset switch shall restore activated smoke detectors to normal standby status.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Lamp test switch.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[f.  City disconnect switch which when activated will disconnect the coded device and cause 
operation of the system trouble signal.]</ITM><BRK/>
<BRK/>
<SPT><TTL>2.2.1.1   Main Annunciator</TTL><BRK/>
<BRK/>
<TXT>Provide integral with the main control panel.  Provide separate alarm and trouble lamps for each zone alarm initiating 
circuit as indicated below, located on the exterior of the cabinet door or visible through the cabinet door.  
Lamps shall be LED (Light Emitting Diode) type.  Supervision will not be required provided a fault in the annunciator 
circuits results only in loss of annunciation and will not affect the normal functional operation of the remainder 
of the system.  Each lamp shall provide specific identification of the [zone] [area] [device] by means of a permanent 
label. In no case shall zone identification consist of the words "Zone 1," "Zone 2," etc., but shall consist 
of the description of the [zone] [area] [device].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.1.2   Initiating Zones</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  List zones from 1 to x, with a brief description of each zone; e.g. "Zone 
1:  Hangar Bay No. 1".  Expand this list as necessary to identify all the zones 
required for the building.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Shall be arranged as follows:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">Zone 1:  [_____]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">Zone 2:  [_____]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">Zone 3:  [_____]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">Zone x:  [_____]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.1.3   Remote <SUB>Annunciator Panel</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate location of remote trouble bell and remote annunciator panel 
when both are provided. Locate panel at or near the building entrance to allow 
fire department quick access to panel.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Locate as shown.  Panel shall duplicate all requirements specified for the main control panel annunciator, except 
that in lieu of individual zone trouble lamps a single common system trouble lamp may be provided.  Lamps shall 
be LED (Light Emitting Diode) type, except lamps used in backlit panels shall be LED or neon type.  Panel shall 
have a lamp test switch. Zone identification shall be by means of [permanently attached rigid plastic or metal 
plate(s)] [silk-screened labels attached to the reverse face of backlighted viewing window(s)].  Panel shall 
be of the [interior] [weatherproof] type, [flush] [surface] [pedestal]-mounted.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2.2   Auxiliary Power Supply</TTL><BRK/>
<BRK/>
<SPT><TTL>2.2.2.1   <SUB>Storage Batteries</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Consult the Public Works Department for battery preference.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide [sealed lead calcium,] [or] [sealed lead acid,] [or] [vented wet cell nickel cadmium,] batteries and 
charger.  Drycell batteries are not acceptable.  House batteries in the control panel or in a well constructed 
vented steel cabinet with cylinder lock, non-corrosive base, and louvered vents.  Provide batteries of adequate 
ampere-hour rating to operate the system under supervisory conditions for 60 hours, at the end of which time 
batteries shall be capable of operating the entire system in a full alarm condition for not less than [30] [15] 
minutes.  Provide calculations substantiating the battery capacity.  Provide reliable separation between cells 
to prevent contact between terminals of adjacent cells and between battery terminals and other metal parts.  
Provide batteries with post-and-nut, "L"-blade, or similar terminals.  Slip-on tab type terminals are not acceptable.  
When a separate battery cabinet is used, provide a fuse block for battery leads within the cabinets.  Finish 
the cabinet on the inside and outside with enamel paint.  Locate the top of the battery cabinet not more than<MET>
 1.20 meters</MET><ENG> 4 feet</ENG> above floor level.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.2.2   <SUB>Battery Charger</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide completely automatic high/low charging rate type charger capable of recovery of the batteries from full 
discharge to full charge in 24 hours or less.  Provide an ammeter for recording rate of charge and a voltmeter 
to indicate the state of battery charge under load.  Meters shall be factory installed, or factory-supplied plug-in 
modules.  Field installation of meters other than the panel manufacturer's plug-in modules is prohibited. Provide 
a trouble light to indicate when batteries are manually placed on a high rate of charge as part of the unit assembly 
if a high-rate switch is provided.  House charger in the control panel or battery cabinet.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>2.3   PNEUMATIC DETECTION SYSTEM</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Pneumatic detection system may be used only with single acting rate-of-rise 
heat detectors. Consult with the Division Fire Protection Engineer for guidance 
on use of pneumatic detection systems.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide pneumatic single acting rate-of-rise heat detectors.  All tubing shall be supervised and installed in 
protective metal conduit or tubing.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.3.1   <SUB>Air Compressor</SUB></TTL><BRK/>
<BRK/>
<TXT>Shall be automatic, electric motor driven and include piping, pressure switch, regulator, and tank if required.  
Provide compressor with a minimum capacity capable of charging the pneumatic detection system to normal system 
pressure in 15 minutes and shall include all controls necessary to maintain the system fully charged.  [Provide 
at least one compressor for every [_____] detection circuits.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.2   Piping and Control Panel</TTL><BRK/>
<BRK/>
<TXT>Provide copper piping.  Provide a control panel or equivalent device(s) to automatically maintain the required 
pneumatic pressure in the detection system, and limit the quantity of air that enters the detection/release system.  
Provide supply air and system air pressure gages.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.4   PIPING SUPERVISION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include for projects involving pre-action sprinkler piping systems or 
pneumatic detection systems only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Pre-action sprinkler piping] [and] [pneumatic detection system] shall be supervised.  A break in the piping 
or tubing systems resulting in loss of pneumatic pressure shall result in the activation of a trouble signal. 
Provide a silencing switch which transfers trouble signals to an indicating lamp and arrange so that correction 
of the trouble condition will automatically transfer the trouble signal from the indicating lamp back to the 
trouble signal until the switch is restored to normal position.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5   <SUB>MANUAL RELEASE STATIONS</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide [combined] overhead system, and monitor nozzle release stations where shown, and separate hose station 
release stations at each hose station.  Stations shall be of a type not subject to operation by jarring or vibration.  
Stations shall have a dual action release configuration to prevent accidental system discharge.  Break-glass-front 
stations are not permitted; however a pull lever break-glass-rod type is acceptable. Station color shall be red.  
Station shall provide positive visible indication of operation.  Restoration shall require use of a key or special 
tool.  Place warning signs at each station indicating that operation of the station will cause immediate AFFF 
discharge.  Where a building fire alarm pull station is also mounted in the vicinity of a foam release station, 
separate the stations by at least<MET> one meter</MET><ENG> 3 feet</ENG> horizontally.  Provided permanent engraved rigid plastic or 
metal labels to clearly distinguish foam release stations from building fire alarm stations, and to indicate 
the function of each foam release station.  Stations shall be weatherproof type.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6   HEAT DETECTORS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the type of heat detector most suited for application or design.  
Do not use rate-of-rise detectors in areas subject to rapid temperature changes 
(e.g. near main hangar doors, unit heaters, etc.).  Consult the Division Fire 
Protection Engineer.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Designed for detection of fire by [combination fixed temperature rate-of-rise] [rate compensating] principle.  
Locate detectors in accordance with their listing by UL or FM and the requirements of <RID>NFPA 72</RID>, except provide 
at least two detectors in all rooms of<MET> 56 sq meters</MET><ENG> 600 square feet</ENG> or larger in area.  Temperature rating of 
detectors shall be in accordance with <RID>NFPA 72</RID>.  Reduce heat detector spacing in areas with ceiling heights exceeding<MET>
 3 meters</MET><ENG> 10 feet</ENG>, in accordance with <RID>NFPA 72</RID>.  No detector shall be located closer than<MET> 305 mm</MET><ENG> 12 inches</ENG> to 
any part of any lighting fixture nor closer than<MET> 610 mm</MET><ENG> 24 inches</ENG> to any part of an air supply diffuser.  Detectors, 
located in hazardous locations as defined by <RID>NFPA 70</RID>, shall be types approved for such locations.  Provide with 
terminal screw type connections.  Removal of detector head from its base shall cause activation of system trouble 
signal.  Detectors shall be weatherproof type.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.6.1   Combination Fixed Temperature Rate-of-Rise Detectors</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Only single acting rate-of-rise heat detectors may be specified for use 
with a pneumatic detection system.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Designed for [surface] [semi-flush] outlet box mounting and supported independently of conduit, tubing or wiring 
connections.  Contacts shall be</TXT><BRK/>
<TXT>self-resetting after response to rate-of-rise actuation.  Operation under fixed temperature actuation shall result 
in an external indication. Detector units located in areas subject to abnormal temperature changes shall operate 
on fixed temperature principle only.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6.2   Rate Compensating Detector</TTL><BRK/>
<BRK/>
<TXT>Designed for [surface] [flush] [vertical unit] outlet box mounting and supported independently of conduit, tubing 
or wiring connections. Detectors shall be hermetically sealed and automatically resetting type which will operate 
when ambient air temperature reaches detector setting regardless of rate of temperature rise.  Detector operation 
shall not be subject to thermal time lag.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.7   OPEN-AREA (SPOT-TYPE) SMOKE DETECTORS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Consult with the Division Fire Protection Engineer before specifying 
2 wire smoke detectors as a Contractor option.  2 wire detectors must be carefully 
matched to the control panel by the manufacturer, and are not universally interchangeable 
between systems for maintenance purposes.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Designed for detection of abnormal smoke densities by the [ionization] [or] [photoelectric] principle.  Provide 
necessary control and power modules required for operation integral with the main control panel.  Provide detectors 
and associated modules which are compatible with the main control panel and suitable for use in a supervised 
circuit.  Detector circuits shall be of the 4 wire type whereby the detector operating power is transmitted over 
conductors separate from the initiating circuit.  Provide a separate, fused, power circuit for each smoke detection 
initiating circuit (zone).  Failure of the power circuit shall be indicated as a trouble condition on the corresponding 
initiating circuit.  [As an alternate, detector circuits of the 2-wire type whereby the detector operating power 
is transmitted over the initiating circuit are permitted, provided the detectors used are approved by the control 
panel manufacturer for use with the control panel provided and are UL listed or FM approved as being compatible 
with the control panel (copies of the UL or FM listings showing compatibility shall be submitted).  When <SUB>2-wire 
smoke detectors</SUB>are used, the total number of detectors on any detection circuit shall not exceed 80 percent of 
the maximum number of detectors allowed by the control panel manufacturer for that circuit and the standby current 
draw of the entire system shall not exceed 80 percent of the rated output of the system power supply module(s).  
Provide additional zones above those specified in the paragraph entitled "Initiating Zones" if required to meet 
the above requirements.  Calculations showing compliance with the power consumption limitation requirements specified 
above shall be submitted with the calculations required by the paragraph entitled "Design Data."  The data submitted 
under the paragraph entitled "Test Reports" shall clearly indicate the compatibility of the detectors with the 
control panel provided and the maximum number of detectors permitted per zone.]  Malfunction of the electrical 
circuits to the detector or its control or power units shall result in the operation of the system trouble signals.  
Equip each detector with a visible indicator lamp that flashes when the detector is in the normal standby mode 
and glows continuously when the detector is activated. [Provide remote indicator lamps for each detector that 
is concealed from view.]  Provide plug-in type detectors with tab-lock or twist-lock, quick disconnect head and 
separate base in which the detector base contains screw terminals for making all wiring connections.  Detector 
head shall be removable from its base without disconnecting any wires.  Removal of detector head from its base 
shall cause activation of system trouble signals.  Provide each detector with an integral screen to prevent entrance 
of insects into the detection chamber(s).</TXT><BRK/>
<BRK/>
<SPT><TTL>2.7.1   Ionization Detectors</TTL><BRK/>
<BRK/>
<TXT>Multiple chamber type which is responsive to both visible and invisible particles of combustion.  Detectors shall 
not be susceptible to operation by changes in relative humidity.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2   Photoelectric Detectors</TTL><BRK/>
<BRK/>
<TXT>Operate on a multiple cell concept using an infra-red light-emitting diode (LED) light source.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.3   Detector Spacing and Location</TTL><BRK/>
<BRK/>
<TXT><RID>NFPA 72</RID>, the manufacturer's recommendations and the requirements stated herein, however, in no case shall spacing 
exceed<MET> 9 by 9 meters</MET><ENG> 30 by 30 feet</ENG> per detector, and<MET> 9 lineal meter</MET><ENG> 30 lineal feet</ENG> per detector along corridors.  
Detectors shall not be placed closer than<MET> [1] [1.50] meter</MET><ENG> [3] [5] feet</ENG> from any air discharge or return grille, 
nor closer than<MET> 305 mm</MET><ENG> 12 inches</ENG> to any part of any lighting fixture.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.8   COMBINATION ULTRAVIOLET-INFRARED FLAME DETECTORS</TTL><BRK/>
<BRK/>
<TXT>Flame detectors shall operate on the dual spectrum ultraviolet-infrared (UV-IR) principle.  Detector shall employ 
a solar-blind UV sensor with a high signal-to-noise ratio, and a narrow band IR sensor.  Detector logic shall 
require UV and IR signals to be present, in the proper ratio or signature as emitted by a hydrocarbon fire, before 
the detector initiates an alarm.  [Detectors shall respond within 5 seconds to a JP-4 fire<MET> 3 meters</MET><ENG> 10 feet</ENG> square,<MET>
 46 meters</MET><ENG> 150 feet</ENG> from the detector.] Detector shall not be activated by non-fire sources such as continuous 
or intermittent direct or reflected solar radiation, arc-welding, lightning, radiant heat, x-rays, artificial 
lighting, radio transmissions, and normal jet engine functions.  Detector shall have an automatic through-the-lens 
self-testing feature.  Malfunction of the detector circuitry, or degradation of the sensors' lens cleanliness 
to the point where the detector will not detect the design fire signature, shall cause operation of the system 
trouble signals.  Logic circuits necessary for operation of the detector shall be integral to the detector or 
located in separate flame detector control panel(s) located adjacent to the foam system control panel(s).  Each 
detector in alarm shall be individually annunciated by an LED on the detector or at the detector control panel.  
Primary and auxiliary power supply shall be taken from the foam system control panel(s).  Detectors, and associated 
control panels if required, shall be compatible with the foam system control panel(s). Detectors and associated 
control panels shall be weatherproof, or housed in weatherproof enclosure(s) when in an area subject to system 
discharge and shall also be explosion-proof when located in hazardous areas as defined by <RID>NFPA 70</RID>.  Detector 
spacing and location shall be in accordance with <RID>NFPA 72</RID>, their UL listing or FM approval, and the manufacturer's 
recommendations.  The detector manufacturer shall determine or approve the detector layout.  Detector layout 
drawings shall include horizontal and vertical angles for correct aiming.  Locate detectors so that every portion 
of the protected [floor] area is within the field of view of at least [two] [three] detectors, taking into account 
fixed obstructions.  Provide detectors with manufacturer's swivel mounting bracket.  Provide a permanent engraved 
rigid plastic or metal label at each detector location with detector aiming information (degrees horizontal and 
vertical) for the corresponding detector.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9   ELECTRICAL WORK</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit Section 26 20 00, INTERIOR DISTRIBUTION SYSTEM and include as part 
of the project specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When project includes requirement for a building fire alarm system, include 
Section 28 31 74.00 20 in the project specification.  When project requires 
only tying into an existing building fire alarm system, fire alarm wiring should 
be specified in this section.  Select the first 28 31 74.00 20 Section title 
when using the basic NAVFAC guide specification covering the subject work or 
select the second title when using the EFD regional guide specification covering 
the subject work.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Electrical work is specified in Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM, except for control [and fire alarm] 
wiring.  [Fire alarm system is specified in Section [<SRF>28 31 74.00 20</SRF> INTERIOR FIRE ALARM SYSTEM] ["Fire Alarm 
and Fire Detecting Systems (Local)"]].</TXT><BRK/>
<BRK/>
<SPT><TTL>2.9.1   Wiring</TTL><BRK/>
<BRK/>
<TXT>Provide control wiring and connections to fire alarm systems, under this section and conforming to <RID>NFPA 70</RID> and <RID>
NFPA 72</RID>.  Wire for 120 volt circuits shall be No. 12 AWG minimum solid conductor.  Wire for low voltage DC circuits 
shall be No. [14] [16] AWG minimum solid conductor [, except wire to remote annunciators, if provided, may be 
18 AWG minimum solid conductor].  All wiring shall be color coded.  Wiring, conduit and devices exposed to water 
or foam discharge shall be weatherproof.  Wiring, conduit and devices located in hazardous atmospheres, as defined 
by <RID>NFPA 70</RID>[and as shown], shall be explosion proof.  All conduit shall be minimum<MET> 20 mm</MET><ENG> 3/4 inch</ENG> size.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9.2   Operating Power</TTL><BRK/>
<BRK/>
<TXT>Power shall be 120 volts AC service, transformed through a two winding isolation type transformer and rectified 
to 24 volts DC for operation of all signal initiating, signal sounding, trouble signal, and actuating (releasing) 
circuits.  Provide secondary DC power supply for operation of system in the event of failure of the AC supply.  
Transfer from normal to emergency power or restoration from emergency to normal power shall be fully automatic 
and shall not cause transmission of a false alarm.  Obtain AC operating power for control panel, [and] battery 
charger [, and air compressor] from the line side of the incoming building power source ahead of all building 
services.  Provide independent properly fused safety switch, with provisions for locking the cover and operating 
handle in the "POWER ON" position for these connections and locate adjacent to the main distribution panel.  
Paint switch box red and suitably identify by a lettered designation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9.3   Conductor Identification</TTL><BRK/>
<BRK/>
<TXT>Identify circuit conductors within each enclosure where a tap, splice or termination is made.  Identify conductors 
by plastic coated self sticking printed markers or by heat-shrink type sleeves.  Attach the markers in a manner 
that will not permit accidental detachment.  Properly identify control circuit terminations.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.10   SYSTEM ACTIVATION</TTL><BRK/>
<BRK/>
<SPT><TTL>2.10.1   Overhead System Activation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide one or more risers per hangar bay as required by NFPA 409 based 
on size of bay.  Overhead systems, monitor systems and hose systems shall be 
served by separate risers.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Each zone shall encompass the area [protected by each riser] [of one hangar bay].  Upon activation of the detection 
system or overhead system manual release station(s), the corresponding overhead system protecting that area shall 
activate.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.10.2   Monitor System Activation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Overhead systems, monitor systems and hose systems shall be served by 
separate risers.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Each zone shall encompass [one hangar bay] [the monitors indicated].  Upon activation of [[detectors for] the 
overhead system] [two UV-IR detectors for more than 5 seconds] or activation of a manual release station, all 
monitors in that zone shall be activated.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.10.3   Hose System Activation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Overhead systems, monitor systems and hose systems shall be served by 
separate risers.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Each] [The] zone shall encompass [all hose stations] [the hose stations indicated].  Hose stations shall be 
activated upon activation of a hose station manual release station.  Provide a manual release station at each 
hose station.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.11   ALARMS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.11.1   <SUB>Water Motor Alarms</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide weatherproof and guarded type alarm for each [group of] [deluge] [pre-action] valve(s).  Alarms shall 
sound locally on the flow of foam solution in each system to which it is connected.  Mount alarms on the outside 
of the outer walls of each building, at locations indicated.  When more than one alarm gong is provided, provide 
permanent engraved rigid plastic or metal signs indicating to which system each gong is connected.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11.2   Local Alarm</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete if a building fire alarm system exists in the building or is being 
provided under this project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide electric [<SUB>alarm horns</SUB>] [<SUB>alarm bells</SUB>] to sound locally on operation of any system, regardless of whether 
water flows or not.  When more than one alarm is provided, provide permanent engraved rigid plastic or metal 
signs indicating to which system each alarm is connected.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11.3   Fire Alarm</TTL><BRK/>
<BRK/>
<TXT>Provide equipment for the automatic transmittal of an alarm over the building fire alarm system.  Arrange so 
that the detection system and the flow of solution in each system will actuate the alarm.  [Activation of a single 
UV-IR detector shall not cause activation of the foam system but shall cause activation of the fire alarm system].</TXT><BRK/>
<BRK/>
<SPT><TTL>2.11.3.1   <SUB>Pressure Switch</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide switch with SPDT contacts to automatically transmit alarms upon flow of water or AFFF.  Alarm actuating 
device shall [have mechanical diaphragm controlled retard device adjustable from 10 to 60 seconds and shall] 
instantly recycle.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.11.4   <SUB>Trouble Alarm</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete if a building fire alarm system exists in the building or is being 
provided under this project.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Pre-action sprinkler piping systems require supervision.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide local [<MET>100 mm</MET><ENG>4 inch</ENG>] electric alarm [bell] [horn] [_____] to indicate trouble [or failure of the [detection 
system] [or] [pre-action sprinkler piping system]].  Also connect trouble alarm into the building fire alarm 
control panel to indicate "trouble" on a separate zone labelled "Foam System Trouble".</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.12   <SUB>TANK MOUNTED AIR COMPRESSOR</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include for projects involving pre-action sprinkler piping systems only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide an approved automatic type electric motor driven air compressor including pressure switch, air piping, 
and<MET> [38 liter]</MET><ENG> [10 gallon]</ENG>[_____] minimum capacity tank.  Compressor shall have a minimum capacity capable of 
charging the complete sprinkler system to normal system air pressure within 30 minutes.  Provide each system 
with an approved automatic <SUB>air pressure regulating device</SUB>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.13   <SUB>AFFF CONCENTRATE</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Consult the facility fire department and the Division Fire Protection 
Engineer to determine percentage.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>MIL-F-24385</RID>, [3] [6] percent.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.13.1   Concentrate Fill Pump</TTL><BRK/>
<BRK/>
<TXT>Provide one pump to fill foam system tank.  Pump shall have a minimum flow rate of<MET> 27 L/m</MET><ENG> 7 gpm</ENG>.  Pump shall 
be complete with 115 VAC motor, fused switch, power cord with plug and<MET> 3 meters</MET><ENG> 10 foot</ENG> minimum suction and clear 
discharge hoses.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.14   DIAPHRAGM PRESSURE <SUB>PROPORTIONING EQUIPMENT</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the method of proportioning best suited for the project.  For 
hangars, NFPA 409 requires dual pumps (main and reserve) for each system.</NPR><BRK/>
<BRK/>
<NPR>Diaphragm pressure proportioning systems operate by water pressure, require 
no electrical power, and minimal control circuitry for automatic operation. 
Maintenance requirements are minimal, however refilling the tank is a difficult 
operation requiring the services of a qualified technician to avoid rupturing 
the diaphragm.</NPR><BRK/>
<BRK/>
<NPR>Balanced pressure proportioning systems require reliable electrical power and 
more complex control circuitry for automatic operation.  In some cases an emergency 
generator will be required.  The primary advantage of the non-diaphragm systems 
is the ease in refilling the tanks.  Tanks may be refilled even while the system 
is in operation, if necessary.</NPR><BRK/>
<BRK/>
<NPR>Skid-mounted balanced pressure proportioning systems perform proportioning at 
a central location, avoiding long runs of concentrate lines.  They are well 
suited for systems such as deluge sprinklers and monitor nozzles which have 
a relative narrow range of flow rates.</NPR><BRK/>
<BRK/>
<NPR>In-line balanced pressure proportioning is useful when there are multiple hazards 
with widely varying discharge rates which are to be supplied from the same proportioning 
system, and any time it is desired to proportion foam remotely at risers or 
discharge devices instead of at the pump room. Their disadvantage is the need 
for much more concentrate piping in the field.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Foam solution shall be produced by introducing AFFF concentrate into the water stream by the balanced pressure 
proportioning method using a diaphragm pressure tank and ratio controller.  [Provide proportioning system and 
storage tanks for hose lines independent of main proportioning system and tanks.]</TXT><BRK/>
<BRK/>
<SPT><TTL>2.14.1   <SUB>Diaphragm Pressure Proportioning Tanks</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When large quantities of AFFF concentrate are required, consider two 
or more tanks in parallel vs one large tank.  (This is in addition to reserve 
tanks.)  Approved diaphragm tanks larger than<MET> 9.50 - 11.40 cu meters</MET><ENG> 2,500 - 
3,000 gallons</ENG> are not readily available.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer must calculate foam tank capacity based on maximum flow for 
maximum duration to determine size of tank and space required.  Do not label 
foam tank capacity on drawing.  Exact tank size (which may be larger) will be 
determined by Contractor's hydraulic calculations.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Tanks shall be cylindrical steel ASME pressure vessels with a full Buna-N impregnated nylon inner tank or bladder 
designed to contain AFFF concentrate and to be used in conjunction with the concentrate ratio controller.  Tanks 
shall be designed for working pressure of<MET> [1206 kPa (gage)]</MET><ENG> [175 psig]</ENG> [_____] and hydrostatically tested at 
1.5 times the working pressure in accordance with ASME standards at the factory.  Tanks shall have UL or FM label 
and ASME stamp affixed to the vessel.  Size tank to provide sufficient AFFF concentrate for the time specified 
when the system is discharging foam solution at total maximum system flow.  Also provide connected reserve tanks(s) 
of equal capacity.  Permanently label each tank with its capacity, type and percentage of concentrate, which 
system(s) it serves, and whether it is a main or reserve tank.  Conspicuously post filling instructions near 
each group of tanks.  Provide a gage or unbreakable sight glass to permit visual determination of level of tank 
contents.  Prior to shop painting, abrasive blast clean tank exterior surface in accordance with <RID>SSPC SP 6</RID> to 
a surface profile not to exceed<MET> 0.05 mm</MET><ENG> 2.0 mils</ENG> and provide a <RID>MIL-P-24441</RID> or SSPC coating system to the tank 
exterior.  Prime tank exterior with one coat of <RID>MIL-P-24441</RID>/1, Formula 150 or <RID>SSPC Paint 22</RID> primer applied to 
a dry film thickness of<MET> 0.076 mm</MET><ENG> 3 mils</ENG> and topcoat with one coat of <RID>MIL-P-24441</RID>/7 Formula 156 (red) or <RID>SSPC Paint 22</RID>
 topcoat (red) applied to a dry film thickness of<MET> 0.076 mm</MET><ENG> 3 mils</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.2   Concentrate Ratio Controller</TTL><BRK/>
<BRK/>
<TXT>Ratio controller shall be a modified venturi device with AFFF concentrate feed line from diaphragm tank(s), and 
integral concentrate metering orifice.  Size for specified flow rate(s).</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.15   BALANCED PRESSURE PROPORTIONING SYSTEM</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the method of proportioning best suited for the project.  For 
hangars, NFPA 409 requires dual pumps (main and reserve) for each system.</NPR><BRK/>
<BRK/>
<NPR>Diaphragm pressure proportioning systems operate by water pressure, require 
no electrical power, and minimal control circuitry for automatic operation. 
Maintenance requirements are minimal, however refilling the tank is a difficult 
operation requiring the services of a qualified technician to avoid rupturing 
the diaphragm.</NPR><BRK/>
<BRK/>
<NPR>Balanced pressure proportioning systems require reliable electrical power and 
more complex control circuitry for automatic operation.  In some cases an emergency 
generator will be required.  The primary advantage of the non-diaphragm systems 
is the ease in refilling the tanks.  Tanks may be refilled even while the system 
is in operation, if necessary.</NPR><BRK/>
<BRK/>
<NPR>Skid-mounted balanced pressure proportioning systems perform proportioning at 
a central location, avoiding long runs of concentrate lines.  They are well 
suited for systems such as deluge sprinklers and monitor nozzles which have 
a relative narrow range of flow rates.</NPR><BRK/>
<BRK/>
<NPR>In-line balanced pressure proportioning is useful when there are multiple hazards 
with widely varying discharge rates which are to be supplied from the same proportioning 
system, and any time it is desired to proportion foam remotely at risers or 
discharge devices instead of at the pump room. Their disadvantage is the need 
for much more concentrate piping in the field.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Foam solution shall be produced by introducing AFFF concentrate into the water stream by the balanced pressure 
proportioning method using a pump and proportioner.  [Provide proportioning system and storage tanks for hose 
lines independent of main proportioning system and tanks.]</TXT><BRK/>
<BRK/>
<SPT>[<TTL>2.15.1   Skid-Mounted Balanced Pressure Proportioning System</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Choose this paragraph or the paragraph below, entitled "In-Line Balanced 
Pressure Proportioning System."</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Self-contained, skid-mounted system, fully assembled at the factory and delivered complete and ready for use.  
Field connections shall be limited to water, electrical, and AFFF concentrate inputs, foam solution output, and 
foam concentrate return line to storage tank.  Size system for required flow rate(s).  The concentrate pump and 
all piping, valves, and fittings in contact with foam concentrate shall be of materials resistant to the corrosive 
effects of the AFFF concentrate.  Concentrate pump shall be electric motor driven, drip proof, 240/480 volts, 
60 Hz AC.  Activation and operation of system shall be fully automatic, with manual over-ride and manual shut-down.  
Provide permanent engraved rigid plastic or corrosion resistant metal instruction plate for emergency manual 
operation, along with a similarly constructed label for each control device.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.15.2   In-Line Balanced Pressure Proportioning System</TTL><BRK/>
<BRK/>
<TXT>Size system for required flow rates.  AFFF concentrate pump shall be positive displacement, electric motor driven, 
drip proof, 240/480 volts, 60 Hz AC.  System operation shall be fully automatic, with manual over-ride and manual 
shut-down.  Provide a pressure regulating device in the AFFF concentrate pump return line to maintain constant 
pressure on the concentrate piping system at all AFFF solution flow rates.  Provide an in-line balanced pressure 
proportioning device at each system riser to automatically balance the AFFF concentrate pressure with the water 
pressure at the riser to provide correct proportioning over the range of flow rates calculated for that riser.  
The pump and all piping, valves, and fittings in contact with the foam concentrate shall be of materials resistant 
to the corrosive effects of the AFFF concentrate.  Provide permanent engraved rigid plastic or corrosion-resistant 
metal instruction plate for emergency manual operation, along with a similarly constructed label for each control 
device.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.15.3   <SUB>AFFF Concentrate Storage Tanks</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer must calculate foam tank capacity based on maximum flow for 
maximum duration to determine size of tank and space required.  Do not label 
foam tank capacity on drawing.  Exact tank size (which may be larger) will be 
determined by Contractor's hydraulic calculations.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Tank shall be designed for storage of AFFF concentrate at atmospheric pressure, and shall be [horizontal] [or] 
[vertical] cylindrical, fiberglass or polyethylene construction.  Tank shall have the following:  Drain valve 
located at the lowest point in the tank, connections for concentrate supply and return lines to the proportioners, 
top-mounted fill connections and inspection hatch, and a pressure/vacuum relief vent.  All openings and tank 
connections shall be installed at the factory, no holes shall be made in the tank shell in the field.  Tank shall 
include all necessary supports for free-standing installation.  Provide a gage or unbreakable sight glass to 
permit visual determination of level of tank contents, unless liquid level is clearly visible through shell of 
tank.  Size tank to provide sufficient AFFF concentrate for the time specified when the system is discharging 
foam solution at total maximum system flow.  Also provide connected reserve tank(s) of equal capacity.  Permanently 
label each tank with its capacity, type and percentage of concentrate, which system it serves, and whether it 
is a main or reserve tank.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.16   OSCILLATING <SUB>MONITOR NOZZLES</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Refer to MIL-HDBK-1008 and the appropriate NFPA standard(s) governing 
the particular facility to determine the density required.  Consult the activity 
for the floor area under the wings and fuselage.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Fixed, water motor operated, [with] [without] override to allow manual aiming.  Oscillation arc shall be adjustable 
from at least 0 to<MET> 2.88 radian</MET><ENG> 165 degrees</ENG>.  Oscillation speed shall be adjustable from 0 -<MET> 0.52 radian</MET><ENG> 30 degrees</ENG>
 per second.  Nozzle shall be adjustable while in operation from<MET> 0.52 radian</MET><ENG> 30 degrees</ENG> below to<MET>1.40 radian</MET><ENG> 80 
degrees</ENG> above horizontal, with lock or latching mechanism.  Nozzle shall be [non aspirating] [air aspirating] 
type, adjustable while in operation from straight stream to fan-spray.  Nozzle shall be capable of retaining 
the adjusted setting once the desired pattern has been set.  [Nozzle shall produce a straight stream of<MET> 46 meters</MET><ENG>
 150 feet</ENG> at<MET> [1920 L/m]</MET><ENG> [500 gpm]</ENG> [_____] and <MET>[690 kPa (gage)]</MET> <ENG>[100 psig]</ENG> [_____].]  [Nozzles shall provide a 
minimum application rate of<MET> [4.2] [_____] L/m per sq meter</MET><ENG> [0.10] [_____] gpm per square foot</ENG> over [the entire 
floor area] [[_____] square<MET> meter</MET><ENG> feet</ENG> of floor area underneath the aircraft wings and fuselage]].  Provide normally 
open 0S&amp;Y gate valve in supply line at each monitor location.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.17   HAND HOSE LINES</TTL><BRK/>
<BRK/>
<TXT>Provide each hose station with flow-through reel and [_____]<MET> meter of 40 mm</MET><ENG> feet of 1 1/2 inch</ENG> hard rubber <SUB>hose 
and nozzles</SUB>.  Nozzle shall have pistol-grip ball shutoff valve.  Nozzle shall be [non aspirating] [air aspirating] 
type.  Provide normally closed quarter-turn ball valve in supply line at each hose station.  Nozzle flow rate 
shall be<MET> [228 L/m]</MET><ENG> [60 gpm]</ENG> [_____] minimum.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.18   WALL <SUB>FOAM HYDRANTS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide wall foam hydrants for testing of proportioners on pre-action 
systems or where additional foam hand hose lines are required. Determine number 
of outlet connections based upon a ratio of one outlet for each<MET> 948 L/m</MET><ENG> 250 
gpm</ENG> of design flow, up to a maximum of 8 outlets.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide [dual] [triple] [_____] outlet connections with integral gate valves and locate about<MET> one meter</MET><ENG> 3 feet</ENG>
 above grade.  Provide each outlet with<MET> 65 mm</MET><ENG> 2 1/2 inch</ENG> male National Standard hose threads with cap and chain.  
Hydrant shall be controlled by 0S&amp;Y gate valve located inside foam room.  Provide wall escutcheon plate with 
"FOAM HYDRANT" in raised letters cast in plate. [Hydrant shall permit testing of each pre-action system riser 
at full design flow without charging the system supplied by the riser.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.19   ABOVEGROUND PIPING SYSTEMS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.19.1   <SUB>Pipe, Fittings, and Mechanical Couplings</SUB></TTL><BRK/>
<BRK/>
<TXT><RID>NFPA 13</RID>, except steel piping shall be Schedule 40 for sizes smaller than<MET> 200 mm</MET><ENG> 8 inches</ENG>, and Schedule 30 or 
40 for sizes<MET> 200 mm</MET><ENG> 8 inches</ENG> and larger.  Pipe nipples<MET> 150 mm</MET><ENG> 6 inches</ENG> long and shorter shall be Schedule 80 
steel pipe.  Water motor alarm piping shall be zinc-coated steel pipe and fittings.  Rubber gasketed grooved-end 
pipe and fittings with mechanical couplings shall only be permitted in pipe sizes<MET> 40 mm</MET><ENG> 1 1/2 inches</ENG> and larger.  
Rubber gaskets shall be UL listed for use in dry-pipe sprinkler systems.  Use of restriction orifices, reducing 
flanges, and plain-end fittings with mechanical couplings (which utilize steel gripping devices to bite into 
the pipe when pressure is applied) are not permitted.  Pipe and fittings in contact with AFFF concentrate shall 
be [material resistant to the corrosive effects of AFFF concentrate as approved by the manufacturer of the proportioning 
system] [stainless steel].  [Fittings on concentrate lines shall be flanged or welded only.  Screwed or mechanical 
fittings will not be permitted.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.19.2   Jointing Material</TTL><BRK/>
<TXT><BRK/>
<RID>FS A-A-58092</RID>, Polytetrafluoroethylene (PTFE) tape.  Pipe joint compound (pipe dope) is not acceptable.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.19.3   Duplex Basket <SUB>Strainers</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include for deluge systems with high volume flow, and for untreated water 
supply.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>FS WW-S-2739</RID>, Style Y (Y pattern).  Provide duplex basket strainers with removable screens having standard perforations,<MET>
 3 mm</MET><ENG> 0.125 inch</ENG> in diameter in the riser beneath the deluge valves.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.19.4   <SUB>Pipe Hangers and Supports</SUB></TTL><BRK/>
<BRK/>
<TXT><RID>NFPA 13</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.19.5   <SUB>Valves</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide valves as required by <RID>NFPA 13</RID> and of types approved for fire service.  Gate valves shall open by counterclockwise 
rotation.  Check valves shall be flanged clear opening swing check type with flanged inspection and access cover 
plate for sizes<MET> 100 mm</MET><ENG> 4 inches</ENG> and larger.  Provide an OS&amp;Y valve beneath each [deluge] [pre-action] valve 
in each riser, when more than one valve is supplied from the same water supply pipe.  Butterfly valves are not 
acceptable.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.19.6   Identification Signs</TTL><BRK/>
<BRK/>
<TXT>Attach properly lettered approved metal signs conforming to <RID>NFPA 13</RID> to each valve and alarm device.  Permanently 
affix design data nameplates to the riser of each system.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.19.7   Inspector's Test Connection</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include for pre-action systems.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide test connections about<MET> 2 meters</MET><ENG> 6 feet</ENG> above the floor for each sprinkler system and locate at the hydraulically 
most remote part of each system. Provide test connection piping to a location where the discharge will be readily 
visible and where water may be discharged without damage.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.19.8   Main Drains</TTL><BRK/>
<BRK/>
<TXT>Provide drain piping to discharge at safe points outside each building or to sight cones attached to drains of 
adequate size to readily receive the full flow from each drain under maximum pressure.  Provide auxiliary drains 
as required by <RID>NFPA 13</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.19.9   Pipe Sleeves</TTL><BRK/>
<BRK/>
<TXT>Provide where piping passes through walls, floors, roofs, and partitions. Secure sleeves in proper position and 
location during construction. Provide sleeves of sufficient length to pass through entire thickness of walls, 
floors, roofs, and partitions.  Provide not less than<MET> 6 mm</MET><ENG> 1/4 inch</ENG> space between exterior of piping and interior 
of sleeve.  Firmly pack space with insulation and calk at both ends of the sleeve with plastic waterproof cement.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.19.9.1   Sleeves in Masonry and Concrete Walls, Floors, Roofs</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM A 53/A 53M</RID>, schedule 40 or standard weight, zinc-coated steel pipe sleeves.  Extend sleeves in floor slabs<MET>
 80 mm</MET><ENG> 3 inches</ENG> above the finished floor.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.19.9.2   Sleeves in Partitions</TTL><BRK/>
<BRK/>
<TXT>Provide zinc-coated steel sheet having a nominal weight of not less than<MET> 4.40 kg per sq meter</MET><ENG> 0.90 pounds per 
square foot</ENG>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.19.10   Escutcheon Plates</TTL><BRK/>
<BRK/>
<TXT>Provide one piece or split hinge type plates for piping passing through floors, walls and ceilings, in both exposed 
and concealed areas.  Provide chromium plated metal plates where pipe passes through finished ceilings. Provide 
other plates of steel or cast iron with aluminum paint finish. Securely anchor plates in place.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.19.11   <SUB>Fire Department Inlet Connections</SUB></TTL><BRK/>
<BRK/>
<TXT>[Two] [Three] way type with<MET> 65 mm</MET><ENG> 2 1/2 inch</ENG> National Standard female hose threads with plug, chain, and identifying 
fire department connection escutcheon plate.  Provide inlet connections about<MET> one meter</MET><ENG> 3 feet</ENG> above grade.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.19.12   <SUB>Backflow Preventers</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When the water supply for the AFFF system is non-potable water delete 
this paragraph.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Reduced pressure principle type.  Proof shall be furnished that each make, model/design, and size of backflow 
preventer being furnished for the project is approved by and has a current "Certificate of Approval" from the <RID>
FCCCHR List</RID>.  Listing of the particular make, model/design, and size in the current <RID>FCCCHR List</RID> will be acceptable 
as the required proof.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.20   BURIED PIPING SYSTEMS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.20.1   Pipe and Fittings</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For pipe sizes larger than<MET> 305 mm</MET><ENG> 12 inches</ENG>, method for pipe anchorage 
including pipe clamps and the rods shall be shown on the drawings.  Avoid velocities 
greater than<MET> 4.60 meters per sec</MET><ENG> 15 ft./sec</ENG>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select first bracketed phrase for connection to an existing water distribution 
system located a short distance from the building.  Select second bracketed 
phrase when a new water distribution line is being provided as part of this 
project.  For new water distribution system, select and edit Section 33 11 00 
WATER DISTRIBUTION and include as part of the project specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NFPA 24</RID>, outside coated cement lined ductile iron pipe and fittings for piping under the building and to a point<MET>
 1.50 meters</MET><ENG> 5 feet</ENG> outside the building walls.  Anchor the joints in accordance with <RID>NFPA 24</RID> using pipe clamps 
and steel rods.  Minimum pipe size shall be<MET> 150 mm</MET><ENG> 6 inches</ENG>.  Minimum depth of cover shall be [_____]<MET> [one meter]</MET>
 <ENG> [3 feet]</ENG>.  Piping more than<MET> 1.50 meters</MET><ENG> 5 feet</ENG> outside the building walls shall be [outside coated cement lined 
ductile iron pipe and fittings conforming to <RID>NFPA 24</RID>] [provided under Section <SRF>33 11 00</SRF> WATER DISTRIBUTION].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.20.2   Valves</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If Section 33 11 00 WATER DISTRIBUTION is included as part of the project 
specification, requirements for buried gate valves, post indicator valves, and 
valve boxes may be deleted here and specified in Section 33 11 00.  Careful 
coordination is required to insure that materials rated for fire service are 
specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide as required by <RID>NFPA 24</RID> for fire service.  Gate valves shall conform to <RID>AWWA C500</RID> or <RID>UL 262</RID> with cast 
iron body and bronze trim, and shall open by counterclockwise rotation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.20.3   Post Indicator Valves</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If Section 33 11 00 WATER DISTRIBUTION is included as part of the project 
specification, requirements for buried gate valves, post indicator valves, and 
valve boxes may be deleted here and specified in Section 33 11 00.  Careful 
coordination is required to insure that materials rated for fire service are 
specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide with operating nut located about<MET> one meter</MET><ENG> 3 feet</ENG> above grade.  Gate valves for use with indicator post 
shall conform to <RID>UL 262</RID>.  Indicator posts shall conform to <RID>UL 789</RID>.  Paint each indicator post with one coat of 
primer and two coats of red enamel paint.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.20.4   Valve Boxes</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If Section 33 11 00 WATER DISTRIBUTION is included as part of the project 
specification, requirements for buried gate valves, post indicator valves, and 
valve boxes may be deleted here and specified in Section 33 11 00.  Careful 
coordination is required to insure that materials rated for fire service are 
specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Except where indicator posts are provided, provide each gate valve in buried piping with an adjustable cast-iron 
valve box of a size suitable for the valve on which it is to be used.  Boxes outside of paved areas may be of 
Acrylonitrile-Butadiene-Styrene (ABS) plastic or of inorganic fiber reinforced black polyolefin plastic.  The 
head shall be round and the lid shall have the word WATER cast on it.  The least diameter of the shaft of the 
box shall be<MET> 133 mm</MET><ENG> 5 1/4 inches</ENG>.  Coat each cast-iron box with bituminous paint.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.20.5   Buried Utility Warning and Identification Tape</TTL><BRK/>
<BRK/>
<TXT>Provide detectable aluminum foil plastic-backed tape or detectable magnetic plastic tape manufactured specifically 
for warning and identification of buried piping.  Tape shall be detectable by an electronic detection instrument.  
Provide tape in rolls,<MET> 76 mm</MET><ENG> 3 inches</ENG> minimum width, color coded for the utility involved, with warning and identification 
imprinted in bold black letters continuously and repeatedly over entire tape length.  Warning and identification 
shall be CAUTION BURIED WATER PIPING BELOW or similar. Use permanent code and letter coloring unaffected by moisture 
and other substances contained in trench backfill material.  Bury tape with the printed side up at a depth of<MET>
 305 mm</MET><ENG> 12 inches</ENG> below the top surface of earth or the top surface of the subgrade under pavements.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   EXCAVATION, BACKFILLING, AND COMPACTING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select and edit Section 02302, "Excavation, Backfilling, and Compacting 
for Utilities" and include as part of the project specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide under this section as specified in Section <SRF>31 00 00</SRF> EARTHWORK.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   CONNECTIONS TO EXISTING WATER SUPPLY SYSTEMS</TTL><BRK/>
<BRK/>
<TXT>Use tapping or drilling machine valve and mechanical joint type sleeves for connections to be made under pressure.  
Bolt sleeves around the mains; bolt valve conforming to <RID>AWWA C500</RID> or <RID>UL 262</RID> to the branch.  Open valve, attach 
drilling machine, make tap, close valve, and remove drilling machine, all without interruption of service.  Notify 
the Contracting Officer in writing at least [_____] [15] calendar days prior to the date the connections are 
required; approval shall be received before any service is interrupted.  Furnish all material required to make 
connections into the existing water supply systems, and perform all excavating, backfilling, and other incidental 
labor as required.  [Furnish] [Government will furnish only] the labor and the tapping or drilling machine for 
making the actual connections to the existing systems.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3   AFFF SYSTEM INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Equipment, materials, installation, workmanship, fabrication, assembly, erection, examination, inspection, and 
testing shall be in accordance with the NFPA standards referenced herein.  Install piping straight and true to 
bear evenly on hangers and supports.  Conceal piping to the maximum extent possible.  Piping shall be inspected, 
tested and approved before being concealed.  Provide fittings for changes in direction of piping and for all 
connections.  Make changes in piping sizes through standard reducing pipe fittings; do not use bushings.  Cut 
pipe accurately and work into place without springing or forcing.  Ream pipe ends and free pipe and fittings 
from burrs.  Clean with solvent to remove all varnish and cutting oil prior to assembly.  Make screw joints with 
PTFE tape applied to male thread only.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4   DISINFECTION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When the water supply for the AFFF system is non-potable water delete 
this paragraph.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Disinfect new water piping from the system control valve to the point of connection at the water main and existing 
water piping affected by the Contractor's operation in accordance with <RID>AWWA C651</RID>.  Fill piping systems with solution 
containing minimum of 50<MET> mg/kg</MET><ENG> parts per million (ppm)</ENG> of free available chlorine and allow solution to stand 
for minimum of 24 hours. Flush solution from systems with clean water until maximum residual chlorine content 
is not greater than 0.2<MET> mg/kg</MET><ENG> ppm</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5   FIELD PAINTING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For facilities located in a marine environment specify SSPC SP 11 cleaning 
and specify a second topcoat.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Clean, prime, and paint new foam systems including valves, piping, conduit, hangers, miscellaneous metal work, 
and accessories.  Apply coatings to clean dry surfaces using clean brushes.  Clean the surfaces in accordance 
with [<RID>SSPC SP 3</RID>] [<RID>SSPC SP 11</RID>].  Immediately after cleaning, prime the metal surfaces with one coat of <RID>SSPC Paint 25</RID>
 or <RID>SSPC Paint 25</RID>primer applied to a minimum dry film thickness of<MET> 0.04 mm</MET><ENG> 1.5 mils</ENG>.  Exercise care to avoid 
the painting of sprinkler heads and operating devices.  Upon completion of painting, remove materials which were 
used to protect sprinkler heads and operating devices while painting is in process.  Remove sprinkler heads and 
operating devices which have been inadvertently painted and provide new clean sprinkler heads and operating devices 
of the proper type.  Finish primed surfaces as follows:</TXT><BRK/>
<BRK/>
<SPT><TTL>3.5.1   Foam Systems in Unfinished Areas</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For facilities located in a marine environment specify SSPC SP 11 cleaning 
and specify a second topcoat.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Unfinished areas are defined as attic spaces, spaces above suspended ceilings, crawl spaces, foam rooms, pump 
rooms, pipe chases, and other spaces where ceilings are not painted or not constructed of a prefinished material.  
Paint primed surfaces with [one] [two] coat[s] of <RID>FS A-A-2962</RID> red enamel applied to a minimum dry film thickness 
of<MET> 0.04 mm</MET><ENG> 1.5 mils</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.2   Foam Systems in All Other Areas</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For facilities located in a marine environment specify SSPC SP 11 cleaning 
and specify a second topcoat.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Paint primed surfaces with two coats of paint to match adjacent surfaces, except paint valves and operating accessories 
with [one] [two] coat[s] of <RID>FS A-A-2962</RID> red enamel applied to a minimum dry film thickness of<MET> 0.04 mm</MET><ENG> 1.5 mils</ENG>
.  Provide piping with<MET> 50 mm</MET><ENG> 2 inch</ENG> wide red bands spaced at maximum<MET> 6 meters</MET><ENG> 20 foot</ENG> intervals throughout the 
piping systems.  Bands shall be red enamel or self adhering red plastic tape.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.3   Piping Labels</TTL><BRK/>
<BRK/>
<TXT>Provide permanent labels in foam rooms, spaced at<MET> 6 meters</MET><ENG> 20 foot</ENG> maximum intervals along pipe, indicating "WATER", 
"FOAM CONCENTRATE", and "FOAM SOLUTION" on corresponding piping.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.4   Field Touch-Up</TTL><BRK/>
<BRK/>
<TXT>Clean damaged areas of shop coated tanks in accordance with <RID>SSPC SP 11</RID> and coat cleaned areas with the same materials 
used for the shop applied coating system.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.6   ELECTRICAL WORK</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Edit Section 26 20 00, INTERIOR DISTRIBUTION SYSTEM and include as part 
of the project specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When project includes requirement for a building fire alarm system, include 
Section 28 31 74.00 20 in the project specification.  When project requires 
only tying into an existing building fire alarm system, fire alarm wiring should 
be specified in this section.  Select the first 28 31 74.00 20 Section title 
when using the basic NAVFAC guide specification covering the subject work or 
select the second title when using the EFD regional guide specification covering 
the subject work.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Electrical work is specified in Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM, except for control [and fire alarm] 
wiring.  [Fire alarm system is specified in Section [<SRF>28 31 74.00 20</SRF> INTERIOR FIRE ALARM SYSTEM] ["Fire Alarm 
and Fire Detecting Systems (Local)"]].</TXT><BRK/>
<BRK/>
<SPT><TTL>3.6.1   Wiring</TTL><BRK/>
<BRK/>
<TXT>Provide control wiring, and connections to fire alarm systems, under this section in accordance with <RID>NFPA 70</RID> 
and <RID>NFPA 72</RID>.  Provide wiring in rigid metal conduit or intermediate metal conduit, except electrical metallic 
tubing may be used in dry locations not enclosed in concrete or where not subject to mechanical damage.  Do not 
run low voltage DC circuits in the same conduit with AC circuits.  [Run wiring to UV-IR detectors alone in separate 
conduit if required by the detector manufacturer.]</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.7   FLUSHING</TTL><BRK/>
<BRK/>
<TXT>Flush the piping system with potable water in accordance with <RID>NFPA 13</RID>. Continue flushing operation until water 
is clear, but for not less than 10 minutes.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8   FIELD QUALITY CONTROL</TTL><BRK/>
<BRK/>
<TXT>Prior to initial operation, inspect equipment and piping systems for compliance with drawings, specifications, 
and manufacturer's submittals. Perform tests in the presence of the Contracting Officer to determine conformance 
with the specified requirements.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.8.1   <SUB>Preliminary Tests</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify hydrostatic test not less than<MET> 1379 kPa</MET><ENG> 200 psi</ENG> or<MET> 345 kPa</MET><ENG> 50 
psi</ENG> above the maximum working pressure when the maximum working pressure is 
greater than<MET> 1034 kPa</MET><ENG> 150 psi</ENG>.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><TST>Each piping system shall be hydrostatically tested at<MET> [1379 kPa (gage)]</MET><ENG> [200 psig]</ENG> [_____] in accordance with <RID>
NFPA 13</RID> and shall show no leakage or reduction in gage pressure after 2 hours.  The Contractor shall conduct 
complete preliminary tests, which shall encompass all aspects of system operation. Individually test all detectors, 
manual actuation stations, alarms, control panels, and all other components and accessories to demonstrate proper 
functioning.  Test water flow alarms by flowing water through the inspector's test connection.  When tests have 
been completed and all necessary corrections made, submit to the Contracting Officer a signed and dated certificate, 
similar to that specified in <RID>NFPA 13</RID>, attesting to the satisfactory completion of all testing and stating that 
the system is in operating condition.  Also include a written request for a formal inspection and test.</TST></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.2   Formal Inspection and Tests (<SUB>Acceptance Tests</SUB>)</TTL><BRK/>
<BRK/>
<TXT>The [_____] Division, Naval Facilities Engineering Command Fire Protection Engineer, will witness formal tests 
and approve all systems before they are accepted.  The system shall be considered ready for such testing only 
after all necessary preliminary tests have been made and all deficiencies found have been corrected to the satisfaction 
of the equipment manufacturer's technical representative and written certification to this effect is received 
by the Division Fire Protection Engineer.  Submit the request for formal inspection at least 15 working days 
prior to the date the inspection is to take place.  The control panel(s) and detection system(s) shall be in 
continuous service for a "break-in" period of at least 15 consecutive days prior to the formal inspection.  Experienced 
technicians regularly employed by the Contractor in the installation of both the mechanical and electrical portions 
of such systems shall be present during the inspection and shall conduct the testing.  All AFFF concentrate, 
instruments, [including UV-IR detector test lamp and function test kit,] personnel, appliances and equipment 
for testing shall be furnished by the Contractor.  All necessary tests encompassing all aspects of system operation 
shall be made including the following, and any deficiency found shall be corrected and the system retested at 
no cost to the Government.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.8.2.1   Systems and Device Testing</TTL><BRK/>
<BRK/>
<TST><TXT>The entire initiating, alarm, actuation systems shall be operated.  As a minimum, operation and supervision of 
the following functions and devices shall be demonstrated:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  All operational and supervisory functions of the control and annunciator panels.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Each manual actuation station and associated circuit(s).</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  All detectors and associated circuits.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  All alarms and associated circuits.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  All actuator circuits and system control valve(s) (without foam discharge).</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Activation of the building fire evacuation alarm system.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Activation of the Base fire alarm system (receipt of fire alarm at alarm office).</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">h.  All of the above tests shall then be repeated with the system on battery power only.</ITM></TST><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.2.2   AFFF Discharge and Concentration Testing</TTL><BRK/>
<BRK/>
<TST><TXT>When all of the initiating, alarm, actuation, and supervisory functions of the system operate to the satisfaction 
of the system manufacturer's technical representative and the Division Fire Protection Engineer, a complete discharge 
test of each system shall be performed to demonstrate satisfactory performance, proper AFFF concentration, mechanical 
operation and operation of valves, release devices, alarms, and interlocks which control the protected areas.  
These tests shall be conducted by experienced personnel according to the equipment and AFFF manufacturers' recommendations.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">[a. Test each deluge system by full flow of foam solution from the individual systems or combination 
of systems to achieve maximum design flow rate for at least 60 seconds.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b. Test each pre-action system at their design flow rate for at least 60 seconds with temporary 
hose lines and nozzles connected to a test header.  Furnish hose and nozzles required for tests.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c. Test all hose lines and monitor nozzles by full flow of foam solution for at least 60 seconds.</ITM><BRK/>
<BRK/>
<TXT>The manufacturer's representative shall test samples of foam solution taken from each system to ensure proper 
AFFF concentration.  Provide protection for all electrical fixtures and equipment exposed to possible damage 
during tests and protect doors and other openings leading from the protected area(s), to prevent migration of 
foam solution into other areas or spaces.</TXT></TST><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.2.3   Flushing and Rinsing</TTL><BRK/>
<BRK/>
<TXT>After completion of tests flush all piping carrying AFFF concentrate and solution with fresh water.  Piping normally 
containing AFFF concentrate when the system is in standby mode need not be flushed.  Rinse with fresh water all 
equipment and building surfaces exposed to AFFF discharge.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.8.3   Environmental Protection</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Consult facility and the Division or District environmental officials 
to determine local requirements for containment and disposal of discharged AFFF.  
In sufficient concentrations, AFFF may cause disruption of processes in sewage 
treatment plants and damage to fisheries.  Edit the paragraph as appropriate.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide temporary measures to prevent AFFF from entering storm drains, [sanitary sewers,] drainage ditches, streams 
and water courses.  [Do not allow AFFF concentrate or solution to come in contact with earth.  Contain all discharged 
AFFF on paved surfaces.]  [Collect all discharged AFFF and rinse and flushing water and dispose of it in an EPA 
- approved waste-water treatment facility which provides secondary (biological) treatment].  At least 15 days 
prior to the date flow testing is to take place, submit written plan for AFFF containment [and disposal] methods(s) 
to the Contracting Officer for approval.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.4   Additional Tests</TTL><BRK/>
<BRK/>
<TXT><TST>When deficiencies, defects or malfunctions develop during the tests required, all further testing of the system 
shall be suspended until proper adjustments, corrections or revisions have been made to assure proper performance 
of the system.  If these revisions require more than a nominal delay, the Contracting Officer shall be notified 
when the additional work has been completed, to arrange a new inspection and test of the system. All tests required 
shall be repeated prior to final acceptance, unless directed otherwise.</TST></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.5   AFFF Concentrate Storage Tanks Fill-Up</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Consult facility to determine whether the Government or the Contractor 
will furnish the initial fill-up of AFFF concentrate.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Fill storage tanks including reserve tanks and piping normally containing concentrate when the system is in standby 
mode with [Contractor] [Government] furnished AFFF concentrate after acceptance of the system.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.6   Manufacturer's Representative</TTL><BRK/>
<BRK/>
<TXT>Provide the services of representatives or technicians from the manufacturers of the foam system, [and] control 
panel [, and UV-IR detectors], experienced in the installation and operation of the type of system being provided, 
to supervise installation, adjustment, preliminary testing, and final testing of the system and to provide instruction 
to Government personnel.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.9   OPERATING INSTRUCTIONS</TTL><BRK/>
<BRK/>
<TXT>Provide operating instructions at control equipment and at each remote control station.  Instructions shall clearly 
indicate all necessary steps for the operation of the system.  Submit the proposed legend for operating instructions 
for approval prior to installation.  Instructions shall be in engraved white letters on red rigid plastic or 
red enameled steel backgrounds and shall be of adequate size to permit them to be easily read.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.10   TRAINING REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Prior to final acceptance, the Contractor shall provide two sessions of 4 hours each of operation and maintenance 
training to the Base Fire Department and [Public Works] [Civil Engineering] personnel on two different days to 
accommodate both shifts of the Base Fire Department. Each training session shall include emergency procedures, 
and unique maintenance and safety requirements.  Training areas will be provided by the Government in the same 
building as the protected areas.  The training conducted shall use operation and maintenance manuals specified 
in paragraph entitled "Operations and Maintenance Manuals".  Dates and times of the training period shall be 
coordinated through the Contracting Officer not less than two weeks prior to the session.</TXT><BRK/>
<BRK/></SPT>
<MET><SPT><TTL>3.11   SCHEDULE</TTL><BRK/>
<BRK/>
<TXT>Some metric measurements in this section are based on mathematical conversion of inch-pound measurement, and 
not on metric measurement commonly agreed to by the manufacturers or other parties.  The inch-pound and metric 
measurements shown are as follows:</TXT><BRK/>
<TBL><THD><BRK/>
     <HL1>  Products</HL1>                   <HL1>Inch-Pound</HL1>          <HL1>Metric</HL1><BRK/></THD>
<BRK/>
   a.  Air Compressor<BRK/>
         Tank Capacity            = 10 gallons        = 38 liters<BRK/>
<BRK/>
   b.  Concentrate Fill Pump<BRK/>
         Flow Rate                = 7 gpm             = 27 L/m<BRK/>
<BRK/>
   c.  Diaphragm Pressure<BRK/>
         Proportioning Tanks<BRK/>
         Working Pressure         = 175 psig          = 1206 kPa (gage)<BRK/></TBL>
</SPT></MET><BRK/></PRT>
    <END/><BRK/></SEC>