<SCN>SECTION 21 21 01.00 20</SCN><BRK/>
<BRK/>
<STL>CARBON DIOXIDE FIRE EXTINGUISHING (HIGH PRESSURE)</STL><BRK/>
<DTE>04/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>high-pressure carbon 
dioxide fire extinguishing systems for protection of data processing equipment 
and similar electronics occupancies?</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  System requirements must conform to Unified Facilities Criteria (UFC) 
3-600-01 Design: Fire Protection Engineering for Facilities and NFPA 12, "Carbon 
Dioxide Extinguishing Systems."</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  With minor changes, this guide specification can be adapted to other 
occupancies or needs, such as the protection of electric generators.  Total 
flooding carbon dioxide systems shall not be installed in normally occupied 
spaces. In other spaces, consideration must be given to the possibility that 
personnel could be trapped in an atmosphere made by the discharge of carbon 
dioxide. Lockout keyed switches or audible pre-discharge signals shall be provided.  
Provide a sufficient time delay to allow for evacuation under worst case conditions.  
Refer to safety cautions in NFPA 12. If there are questions concerning system 
design, the Engineering Field Division, Naval Facilities Engineering Command, 
Fire Protection Engineer, should be consulted.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ASME INTERNATIONAL (ASME)</ORG><BRK/><BRK/><RID>ASME B16.11</RID><RTL>(2005) Forged Fittings, Socket-Welding and Threaded</RTL><BRK/><BRK/><RID>ASME B16.3</RID><RTL>(2006) Malleable Iron Threaded Fittings, Classes 150 and 300</RTL><BRK/><BRK/><RID>ASME B16.39</RID><RTL>(1998; R 2006) Standard for Malleable Iron Threaded Pipe Unions; Classes 150, 250, and 300</RTL><BRK/><BRK/></REF><REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 106/A 106M</RID><RTL>(2008) Standard Specification for Seamless Carbon Steel Pipe for High-Temperature Service</RTL><BRK/><BRK/><RID>ASTM A 53/A 53M</RID><RTL>(2007) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless</RTL><BRK/><BRK/></REF><REF><ORG>FM GLOBAL (FM)</ORG><BRK/><BRK/><RID>FM P7825</RID><RTL>(2005) Approval Guide</RTL><BRK/><BRK/></REF><REF><ORG>MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS INDUSTRY (MSS)</ORG><BRK/><BRK/><RID>MSS SP-58</RID><RTL>(2002) Standard for Pipe Hangers and Supports - Materials, Design and Manufacture</RTL><BRK/><BRK/><RID>MSS SP-69</RID><RTL>(2003; R 2004) Standard for Pipe Hangers and Supports - Selection and Application</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 12</RID><RTL>(2007) Standard on Carbon Dioxide Extinguishing Systems</RTL><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/><RID>NFPA 72</RID><RTL>(2006) National Fire Alarm Code</RTL><BRK/><BRK/><RID>NFPA 75</RID><RTL>(2008) Protection of Information Technology Equipment</RTL><BRK/><BRK/><RID>NFPA 90A</RID><RTL>(2008) Standard for the Installation of Air Conditioning and Ventilating Systems</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL Fire Prot Dir</RID><RTL>(2008) Fire Protection Equipment Directory</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   DEFINITION</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Year 2000 compliant - means computer controlled facility components that accurately process 
date and time data (including, but not limited to, calculating, comparing, and sequencing) from, 
into, and between the twentieth and twenty-first centuries, and the years 1999 and 2000 and 
leap year calculations.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   SYSTEM DESCRIPTION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Identify the rooms, spaces, or areas, as appropriate, which are to be 
protected by each type of system.  If the volume of the space under raised floors 
does not exceed<MET> 56.60 cubic meters</MET><ENG> 2000 cubic feet</ENG>, total flooding system is 
not required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Design and provide [new and modify existing] high-pressure carbon dioxide [hose reel fire extinguishing systems 
for protection of [_____]] [and] [underfloor total flooding fire extinguishing systems for spaces under raised 
floors] for protection of [_____].  The system design and manufacturer's products including design, materials, 
fabrication, assembly, erection, examination, inspection, and testing shall be in strict accordance with the 
required and advisory provisions of <RID>NFPA 12</RID>, [<RID>NFPA 70</RID>,] [<RID>NFPA 72</RID>,] [<RID>NFPA 75</RID>,] [and] [<RID>NFPA 90A</RID>,] except as modified 
herein.  Each system [shall be designed for earthquakes and] shall include all materials, accessories, and equipment 
inside and outside the building to provide each system complete and ready for use.  Design and provide <SUB>piping 
layout</SUB> of each system to give full consideration to blind spaces, piping, electrical equipment, ductwork, and 
other construction and equipment in accordance with detail working drawings to be submitted for approval.  Devices 
and equipment for fire protection service shall be listed in <RID>UL Fire Prot Dir</RID> or approved by <RID>FM P7825</RID> for use 
in carbon dioxide fire extinguishing systems.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.3.1   Detail Drawings</TTL><BRK/>
<BRK/>
<TXT>Prepare<MET> A1 841 x 594 mm</MET><ENG> 24 by 36 inch</ENG> detail working drawings of carbon dioxide piping layout in accordance with <RID>
NFPA 12</RID> "Working Drawings (Plans)."  Show data essential for proper installation of each system.  Show details 
plan view, elevations, and sections of the systems supply and piping.  Show piping schematic of systems supply, 
devices, valves, pipe, and fittings.  Show point-to-point <SUB>electrical wiring diagrams</SUB>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3.2   <SUB>System Calculations</SUB></TTL><BRK/>
<BRK/>
<TXT>Submit calculations showing that <SUB>open-area smoke detectors calculations</SUB>comply with specified power consumption 
limitation requirements.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3.3   <SUB>As-Built Drawings of Each System</SUB></TTL><BRK/>
<BRK/>
<TXT>After completion, but before final acceptance of the work, submit a complete set of as-built working drawings 
of each system for record purposes.  Submit<MET> A1 841 x 594 mm</MET><ENG> 24 by 36 inches</ENG> reproducible mylar film with title 
block similar to full-size contract drawings.  Furnish the as-built (record) working drawings in addition to 
the as-built contract drawings required by Division 1, "General Requirements."</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.4   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
[<TXT>The [_____] Division, Naval Facilities Engineering Command, Fire Protection Engineer, will review and approve 
all submittals in this section requiring Government approval.</TXT>]<BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For projects administered by the Pacific Division, Naval Facilities Engineering 
Command, use the optional "SUBMITTALS" article immediately below and delete 
the general "SUBMITTALS" article above.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
[<TXT>The [_____] Division, Naval Facilities Engineering Command, Fire Protection Engineer delegates the authority 
to the Quality Control (QC) Representative's U.S. Registered Fire Protection Engineer for review and approval 
of submittals required by this section.  Submit to the [_____] Division, Naval Facilities Engineering Command, 
Fire Protection Engineer one set of all approved submittals and drawings immediately after approval but no more 
later than 15 working days prior to final inspection.</TXT>]<BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Piping layout</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Electrical wiring diagrams</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Storage cylinders</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Discharge head</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Manifolds</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Discharge alarm</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Pipe and fittings</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Pipe hangers and supports</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Actuating stations</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Pressure switch</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Control panel</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Smoke detectors</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Heat activated detectors</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Alarm horns</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Alarm bells</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>[Audio] <SUB>Visual alarms</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Dampers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Main and reserve switch</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Warning signs</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Storage batteries</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Battery charger</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Annotate descriptive data to show the specific model, type, and size of each item.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-05 Design Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>System calculations</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Calculations substantiating battery capacity</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Open-area smoke detectors calculations</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Preliminary tests</SUB> on piping systems[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit certificates for preliminary test on piping systems.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Qualifications of installer</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Discharge head</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Control panel</SUB>, Data Package 3[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Submit in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE DATA.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-11 Closeout Submittals</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>As-built drawings of each system</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.5.1   <SUB>Qualifications of Installer</SUB></TTL><BRK/>
<BRK/>
<TXT>Prior to installation, submit data showing that the Contractor has successfully installed high-pressure carbon 
dioxide fire extinguishing systems of the same type and design as specified herein, or that Contractor has a 
firm contractual agreement with a subcontractor having such required experience.  The data shall include the 
names and locations of at least two installations where the Contractor, or the subcontractor referred to above, 
has installed such systems.  Indicate the type and design of each system and certify that each system has performed 
satisfactorily for not less than 18 months.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For projects administered by the Pacific Division, Naval Facilities Engineering 
Command, include the following optional paragraph requiring the minimum qualification 
of a NICET Level-III technician for preparation of all fire protection system 
drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Qualifications of System Technician:  Installation drawings, shop drawing and as-built drawings shall be prepared, 
by or under the supervision of, an individual who is experienced with the types of works specified herein, and 
is currently certified by the National Institute for Certification in Engineering Technologies (NICET) as an 
engineering technician with minimum Level-III certification in Special Hazard System program.  Contractor shall 
submit data for approval showing the name and certification of all involved individuals with such qualifications 
at or prior to submittal of drawings.]</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.6   SPARE PARTS</TTL><BRK/>
<BRK/>
<TXT>Furnish the following spare parts:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Two of each type detector installed.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  One of each type of audible and visual alarm device installed.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Two of each type of fuse required by the system.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Five complete sets of system keys.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.7   ELECTRICAL WORK</TTL><BRK/>
<BRK/>
<TXT>Provide electrical work associated with this section under Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM, except 
for control [and fire alarm] wiring.  [Provide fire alarm system under Section <SRF>28 31 74.00 20</SRF> INTERIOR FIRE ALARM 
SYSTEM.]  Provide control [and fire alarm] wiring[, including connections to fire alarm systems,] under this 
section in accordance with <RID>NFPA 70</RID>.  Provide wiring in rigid metal conduit or intermediate metal conduit, except 
electrical metallic tubing conduit may be provided in dry locations not enclosed in concrete or where not subject 
to mechanical damage.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   DESIGN OF CARBON DIOXIDE FIRE EXTINGUISHING SYSTEMS</TTL><BRK/>
<BRK/>
<TXT><RID>NFPA 12</RID>, except as modified herein.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.1.1   Underfloor Total Flooding Systems</TTL><BRK/>
<BRK/>
<TXT>Provide uniform discharge to each raised floor space to achieve a factor of one pound of carbon dioxide for each 
[<MET>0.28 cubic meters</MET><ENG>10 cubic feet</ENG> of underfloor volume in one minute for underfloor volumes of<MET> 56.6 cubic meters</MET><ENG>
 2000 cubic feet</ENG> or less] [and] [<MET>0.34 cubic meter</MET><ENG>12 cubic feet</ENG> of underfloor volume in one minute for underfloor 
volumes greater than<MET> 56.6 cubic meters</MET><ENG> 2000 cubic feet</ENG>, except that minimum supply of carbon dioxide shall be<MET>
 91 kg</MET><ENG> 200 pounds</ENG>].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   Underfloor Total Flooding Systems Supply</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer must ensure that no suffocation hazard will exist in any rooms 
with underfloor total flooding systems or within any space to which the carbon 
dioxide might migrate after discharge.  Check with Fire Protection Engineer 
if in doubt.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When a single total flooding underfloor supply is to protect more than 
one underfloor zone, clearly indicate the requirements on the drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Supply shall include high-pressure <SUB>storage cylinders</SUB>, racks, <SUB>manifolds</SUB>, beam scales, and associated equipment. 
Supply shall consist of carbon dioxide in [_____]<MET> [34 kg]</MET><ENG> [75 pound]</ENG> cylinders.  Arrange the first [_____] cylinders 
for discharge upon activation of the main control, and the remaining [_____] cylinders for discharge upon activation 
of the reserve control.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2   <SUB>PIPE AND FITTINGS</SUB></TTL><BRK/>
<BRK/>
<SPT><TTL>2.2.1   Pipe</TTL><BRK/>
<BRK/>
<TXT>Threaded end connections, Schedule 80 or Weight Class XS (Extra Strong), except that sizes smaller than one inch 
may be Schedule 40 or Weight Class STD (Standard).</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  <RID>ASTM A 53/A 53M</RID>, Type E (electric-resistance welded, Grade A or Grade B) or Type S (seamless, 
Grade A or Grade B).</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  <RID>ASTM A 106/A 106M</RID>, Grade A or Grade B.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.2   Threaded Fittings</TTL><BRK/>
<BRK/>
<TXT><RID>ASME B16.11</RID>, except sizes<MET> 50 mm</MET><ENG> 2 inches</ENG> and smaller may conform to <RID>ASME B16.3</RID>, Class 300.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.3   Unions</TTL><BRK/>
<BRK/>
<TXT><RID>ASME B16.39</RID>, Class 300.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.3   PIPING ACCESSORIES</TTL><BRK/>
<BRK/>
<SPT><TTL>2.3.1   Escutcheon Plates</TTL><BRK/>
<BRK/>
<TXT>Provide split hinge metal plates for piping entering floors, walls, and ceilings in exposed spaces.  Provide 
polished stainless steel plates or chromium plated finish on copper alloy plates in finished spaces.  Provide 
paint finish on metal plates in unfinished spaces.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.2   Pipe Sleeves</TTL><BRK/>
<BRK/>
<TXT>Provide where piping passes entirely through walls, ceilings, roofs, and floors.  Provide sleeves of sufficient 
length to pass through entire thickness of walls, ceilings, roofs, and floors.  Provide<MET> 25 mm</MET><ENG> one inch</ENG> minimum 
clearance between exterior of piping and interior of sleeve or core-drilled hole.  Firmly pack space with mineral 
wool insulation and seal both ends of sleeve or core-drilled hole with plastic waterproof cement which will dry 
to a firm but pliable mass, or provide mechanically adjustable segmented elastomeric seal.  In fire walls and 
fire floors, seal both ends of sleeves or core-drilled holes with UL listed fill, void, or cavity material.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Sleeves in Masonry and Concrete:  Provide hot-dipped galvanized steel, ductile-iron, or 
cast iron sleeves at walls, ceilings, roofs, and floors.  Core-drilling of masonry and concrete 
may be provided in lieu of sleeves provided that cavities in the core-drilled holes are completely 
grouted smooth.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Sleeves in Other Than Masonry and Concrete:  Provide 26 gage galvanized steel sheets.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.3   <SUB>Pipe Hangers and Supports</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide <RID>MSS SP-58</RID> and <RID>MSS SP-69</RID>, Type 1, with adjustable type support rods, except as specified or indicated 
otherwise.  Attach to steel joists with Type 19 or 23 clamps and retaining straps.  Attach to steel W or S beams 
with Type 21, 28, 29, or 30 clamps.  Attach to steel angles and vertical web steel channels with Type 20 clamp 
with beam clamp channel adapter.  Attach to horizontal web steel channel and wood with drilled hole on centerline 
and double nut and washer.  Attach to concrete with Type 18 insert or drilled expansion anchor.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.4   PRESSURE RELIEF DEVICE</TTL><BRK/>
<BRK/>
<TXT>Provide each system with an approved device designed to operate between<MET> 16.50 and 20.70 MPa (gage)</MET><ENG> 2400 and 3000 
psig</ENG>.  Locate the device between the storage cylinder manifolds and normally closed valves.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5   SYSTEM CONTROL</TTL><BRK/>
<BRK/>
<TXT>Provide apparatus, accessories, components, and associated materials specified or required.  Provide [automatic] 
[and] [manual] [combination] [electric] [and] [pneumatic] [mechanical pull cable] type of <SUB>actuating stations</SUB> 
complete and ready for operation.  For electrically actuated systems, provide <SUB>main and reserve switch</SUB>.  Switch 
will select between main and reserve carbon dioxide supplies, located adjacent to the cylinder bank or at the 
control panel.  [Detection system shall be complete Class A electrically supervised, combination, automatic, 
and manual.  Automatic automation shall be accomplished by [smoke] [and] [heat] detectors.]</TXT><BRK/>
<BRK/>
<SPT><TTL>2.5.1   Manual Control Station for Underfloor Total Flooding System</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Omit if total flooding system for underfloor areas is not to be provided.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Provide stations [at the principal exits from each protected space] [_____].]  For systems that are mechanically 
or pneumatically activated, provide a separate station for main supply and for reserve supply of carbon dioxide 
at each location.  For electrically activated systems, provide one station at each location.  Mark each station 
to indicate its function.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.2   Sequence of Operation</TTL><BRK/>
<BRK/>
<TXT>Smoke detection system shall be [cross-zoned,] [priority matrix,] [or have common circuit individual detector 
verification capability].  [If a cross-zoned system is used, each protected area shall contain two smoke detection 
circuits (zones), with each circuit having an equal number of detectors connected thereto and no two adjacent 
detectors connected to the same zone.]  Upon activation of any smoke detector, the system shall simultaneously 
activate pre-discharge alarms in the protected areas, signal the building fire alarm control panels to activate 
the building fire evacuation alarms, and send a signal to the base fire department via the base fire alarm system.  
Upon activation of a second detector (on the opposite zone of a cross-zoned system), the systems shall immediately 
shut down [computer] [_____] equipment and air conditioning power, close fire dampers [and fire doors], activate 
the discharge alarms, and initiate an adjustable zero to 60 second discharge time delay.  At the end of the time 
delay, [computer power shall shut down,] [and] carbon dioxide shall discharge into the protected area [and post 
discharge visual alarms shall activate].</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Upon activation by a manual station, the system shall immediately perform the above listed 
alarm functions and shutdown functions, and initiate the adjustable time delay.  At the end 
of the delay, carbon dioxide shall discharge into the protected area.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[b.  Upon manual activation of the inhibit switch, time delay countdown, equipment shutdown, 
and agent discharge shall be delayed.  All other functions shall continue unimpeded.  Upon release 
of inhibit switch, shutdown and discharge functions shall resume.  Time delay shall not reset 
and shall resume countdown to discharge after release of switch.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[c.  Activation of the manual discharge lever on the cylinder master <SUB>discharge head</SUB> shall cause 
immediate agent discharge and immediate operation of all alarm and shutdown functions specified 
in paragraph entitled "Sequence of Operation."]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.3   Pressure-Operated Fire Alarm Switch</TTL><BRK/>
<BRK/>
<TXT>Provide a <SUB>pressure switch</SUB> to actuate the building interior fire alarm system upon the discharge of carbon dioxide.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.4   Pressure-Operated Equipment Switch</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Omit if there is no air handling system serving the underfloor areas.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>For each protected space, provide a switch to automatically shut down the air handling equipment upon the discharge 
of carbon dioxide.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.5   <SUB>Control Panel</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use only when electrical actuation is specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide modular type panel in a [flush] [surface] mounted steel cabinet with hinged door and cylinder lock.  
Switches and other controls shall not be accessible without the use of a key.  The control panel shall be a neat, 
compact, factory-wired assembly containing all parts and equipment required to provide specified operating and 
supervisory functions of the system. Panel cabinet shall be finished on the inside and outside with factory-applied 
enamel finish.  Provide separate alarm and trouble lamps located on the exterior of the cabinet door or visible 
through the cabinet door for each zone initiating circuit.  Provide prominent rigid plastic or metal identification 
plates for all lamps and switches.  [Provide a<MET> 100 mm</MET><ENG> 4 inch</ENG> remote system trouble bell, installed [in a constantly 
attended area] [where shown], arranged to operate in conjunction with the internal trouble signals of the panel.  
Provide remote bell with a rigid plastic or metal identification sign which reads "Carbon Dioxide System Trouble."  
Lettering on identification sign shall be a minimum of one inch high.]  System control panel shall be UL listed 
or FM approved for use in carbon dioxide fire extinguishing system control (releasing device service).  [Provide 
supervised isolation switch to permit testing or servicing of electrical control system without tripping of carbon 
dioxide system.]</TXT><BRK/>
<BRK/>
<SPT><TTL>2.5.5.1   Trouble Signals</TTL><BRK/>
<BRK/>
<TXT>A single open or ground fault condition in detection (initiating) circuit shall not result in any loss of system 
function, but shall cause the actuation of system trouble signals.  A ground fault condition or single break 
in any other circuit shall result in the activation of the system trouble signals.  [Supervision of wiring external 
to the control panel for mechanical equipment shutdown is not required, provided a break in such wiring will 
cause the associated mechanical equipment to shut down.]  Loss of AC power, a break in the standby battery power 
circuits, or abnormal AC power or low battery voltage shall also result in the operation of the system trouble 
signals.  The abnormal position of any system switch in the control panel shall also result in the operation 
of the system trouble signals.  Trouble signals shall operate continuously until the system has been restored 
to normal at the control panel.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.5.2   Panel Switches</TTL><BRK/>
<BRK/>
<TXT>Panel shall be provided with the following switches:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Trouble silencing switch which transfers trouble signals to an indicating lamp.  Upon correction 
of the trouble condition, audible signals shall again sound until the switch is returned to 
its normal position, or the trouble circuit shall be automatically restored to normal upon correction 
of the trouble condition.  The silencing switch shall be a momentary action, self-resetting 
type.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Evacuation alarm silence switch which when activated shall silence associated alarm devices 
and cause operation of system trouble signals.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Individual zone disconnect switches which when operated shall disable only their respective 
initiating circuit and cause operation of the system and zone trouble signals.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Reset switch which when activated shall restore the system to normal standby status after 
the cause of the alarm has been corrected.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Lamp test switch.</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.5.6   Secondary Power Supply</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use only when electrical actuation is specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide nickel cadmium, lead calcium, or sealed lead acid batteries and charger.  Dry cell batteries will not 
be permitted.  Provide steel cabinet with cylinder lock for batteries or house within control panel.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.5.6.1   <SUB>Storage Batteries</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use only when electrical actuation is specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide batteries of the proper ampere-hour rating to operate the system under standby conditions for [60] [24] 
hours and alarm conditions for an additional [30] [15] minutes.  Supervise batteries for low voltage and circuit 
continuity.  Provide <SUB>calculations substantiating battery capacity</SUB>.  Provide reliable separation between cells 
to prevent contact between terminals of adjacent cells and between battery terminals and other metal parts.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.6.2   <SUB>Battery Charger</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use only when electrical actuation is specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide automatic [high and low charging rate type] charger, capable of recovering batteries from full discharge 
to full charge in 48 hours or less.  [Provide an ammeter for recording rate of charge and a voltmeter to indicate 
the state of battery charge.]  Provide a red pilot light to indicate when batteries are manually placed on a 
high rate of charge as part of the unit assembly if high-rate switch is provided.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>2.6   DETECTOR</TTL><BRK/>
<BRK/>
<SPT><TTL>2.6.1   Open-Area (Spot-Type) <SUB>Smoke Detectors</SUB></TTL><BRK/>
<BRK/>
<TXT>Design for detection of abnormal smoke densities by the [ionization] [photoelectric] principle.  Provide control 
and power modules required for operation integral with the main control panel.  Detectors and associated modules 
shall be compatible with the main control panel and shall be suitable for use in a supervised circuit.  [Detector 
circuits shall be of the four-wire type whereby the detector operating power is transmitted over conductors separate 
from the initiating circuit.]  [As an alternate, detector circuits of the two-wire type whereby the detector 
operating power is transmitted over the initiating circuits are permitted if:]</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Detectors used are approved by the control panel manufacturer for use with the control panel 
provided.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  The detectors are UL listed or FM approved as being compatible with the control panel.</ITM><BRK/>
<BRK/>
<TXT>[When two-wire detectors are used, the total number of detectors on a detection circuit shall not exceed 50 percent 
of the maximum number of detectors allowed by the control panel manufacturer for that circuit and the standby 
current draw of the entire system shall not exceed 50 percent of the rated output of the system power supply 
modules.  Additional zones above those specified in the paragraph entitled "Annunciation Zones" shall be provided 
if required to meet the above requirements.  Calculations showing compliance with the specified power consumption 
limitation requirements shall be submitted.]  The manufacturer's data submitted under the paragraph entitled 
"Manufacturer's Catalog Data" shall clearly indicate the compatibility of the detectors with the control panel 
provided and the maximum number of detectors permitted per zone.  Malfunction of the electrical circuits to the 
detector or its control or power units shall result in the operation of the system trouble signals.  Each detector 
shall contain a visible indicator lamp that flashes when the detector is in the normal standby mode and glows 
continuously when the detector is activated. [Remote indicator lamp shall be provided for each detector located 
above ceilings, beneath raised floors, or otherwise concealed from view.]  Each detector shall be the plug-in 
type with tab-lock or twist-lock, quick disconnect head and separate base in which the detector base contains 
screw terminals for making wiring connections.  Detector head shall be removable from its base without disconnecting 
wires.  Removal without disconnecting any wires.  Removal of detector head from its base, shall cause activation 
of system trouble signals.  Each detector shall be screened to prevent the entrance of insects into the detection 
chambers.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.6.1.1   Ionization Detectors</TTL><BRK/>
<BRK/>
<TXT>Multiple chamber type which is responsive to both visible and invisible products of combustion.  Detectors shall 
not be susceptible to operation by changes in relative humidity.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6.1.2   Photoelectric Detectors</TTL><BRK/>
<BRK/>
<TXT>Operate on a multiple cell concept using a light-emitting diode (LED) light source.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.6.2   Spot <SUB>Heat Activated Detectors</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide detectors for [surface] [flush] outlet box mounting.  Support detectors independently of conduit, tubing, 
or wiring connections. Detectors shall be completely metal enclosed and shall be [combination fixed temperature 
and rate-of-rise] [fixed temperature and rate compensated] [_____] type.  Contacts shall be self-resetting after 
[response to rate-of-rise] actuation.  [Operation under fixed temperature actuation shall result in an indication 
which may be noted by external visual inspection of the detector, or the detector may be the self-resetting type.]  
Provide fixed temperature type detectors in areas subject to abnormal temperature changes.  [Furnish a portable 
electric device suitable for testing the detectors.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6.3   Detector Spacing and Location</TTL><BRK/>
<BRK/>
<TXT><RID>NFPA 72</RID>, the manufacturer's recommendations, and the requirements stated herein.  Spacing and location of detectors 
shall take into account the airflow into the room and supply diffusers.  Detectors shall not be placed closer 
than<MET> 1.50 meters</MET><ENG> 5 feet</ENG> from a discharge grill.  [Spacing of detectors under raised floors shall not exceed<MET> [23.20 
square meter]</MET><ENG> [250 square feet]</ENG> [_____] per detector.]  Detectors installed beneath raised floors shall be mounted 
with the detector base within<MET> 50 mm</MET><ENG> 2 inches</ENG> of the underside of the raised floor framing, with the detector 
facing downward.  Where the space under the raised floor is less than<MET> 305 mm</MET><ENG> 12 inches</ENG> in height, detectors shall 
be mounted with their bases in the upper half of the underfloor space.  Under no circumstances shall detectors 
be mounted facing upward.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.7   INHIBIT SWITCH</TTL><BRK/>
<BRK/>
<TXT>Provide one switch where indicated.  Activation of switch shall delay only time delay countdown, equipment shutdown, 
and agent discharge.  Switch shall be guarder, spring-loaded type which operates only when pressure is manually 
applied to the switch.  Upon release of manual pressure, switch shall deactivate allowing delayed functions to 
resume.  After start of agent discharge, switch shall have no effect.  Activation of switch during normal (non-alarm) 
conditions shall cause activation of system trouble signals.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.8   ALARM SIGNALLING DEVICES</TTL><BRK/>
<BRK/>
<TXT>Provide each protected area with audible and visual alarms located as shown.  Alarm circuits shall be electrically 
supervised.  Provide separate and distinct audible and visual pre-discharge and discharge signals.  Where the 
building is equipped with a separate fire evacuation alarm system, the discharge signals shall also be distinct 
from those used by the building fire evacuation system.  Each signal device shall be provided with a rigid plastic 
or metal identification sign with lettering a minimum of<MET> 40 mm</MET><ENG> 1.5 inches</ENG> high.  The pre-discharge alarm shall 
be labelled "FIRE" and the <SUB>discharge alarm</SUB> shall be labelled "CARBON DIOXIDE DISCHARGE." [Post-discharge visual 
alarms shall be located outside entrances to protected areas, and provided with <SUB>warning signs</SUB> reading "CARBON 
DIOXIDE DISCHARGED WHEN FLASHING - DO NOT ENTER."]</TXT><BRK/>
<BRK/>
<SPT><TTL>2.8.1   <SUB>Alarm Bells</SUB></TTL><BRK/>
<BRK/>
<TXT>[Surface mounted] [Recessed], [_____]<MET> [250 mm]</MET><ENG> [10 inch]</ENG> diameter with matching mounting back box.  Bells shall 
be of the vibrating type suitable for use in an electrically supervised circuit.  Bells shall be of the underdome 
type and produce a sound output rating of at least 90 decibels at<MET> 3 meters</MET><ENG> 10 feet</ENG>.  Bells shall be finished 
in red enamel.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.8.2   <SUB>Alarm Horns</SUB></TTL><BRK/>
<BRK/>
<TXT>[Surface mounted] [Recessed], vibrating type suitable for use in an electrically supervised circuit and with 
a sound output rating of at least 90 decibels at<MET> 3 meters</MET><ENG> 10 feet</ENG>.  Horns shall be finished in red enamel.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.8.3   <SUB>Visual Alarms</SUB></TTL><BRK/>
<BRK/>
<TXT>[Surface] [Flush] mounted lamp assembly suitable for use in an electrically supervised circuit.  Lamp shall be 
the flashing [stroboscopic] [incandescent] [rotary beacon] type and powered from the control panel alarm circuit.  
Lamps shall provide a minimum of 50 candle power.  Flash rate shall be between 60 and 120 flashes per minute.  
Lamps shall be protected by a thermoplastic lens, red for pre-discharge alarms and blue for discharge [and post-discharge] 
alarms.  [Visual alarms may be part of an audio-visual alarm assembly.]</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.9   MAIN ANNUNCIATOR</TTL><BRK/>
<BRK/>
<TXT>Annunciator shall be integral with the main control panel.  Provide separate alarm and trouble lamps for each 
zone alarm initiating circuit located on the exterior of the cabinet door or visible through the cabinet door.  
Supervision will not be required provided a fault in the annunciator circuits results only in loss of annunciation 
and will not affect the normal functional operation of the remainder of the system.  Each lamp shall provide 
specific identification of the [zone] [area] [device] by means of a permanent label.  In no case shall zone identification 
consist of such words as "Zone 1," "Zone 2," but shall consist of the description of the [zone] [area] [device].</TXT><BRK/>
<BRK/>
<SPT><TTL>2.9.1   Annunciation Zones</TTL><BRK/>
<BRK/>
<TXT>Arranged as follows:</TXT><BRK/>
<BRK/>
<SPT><TTL>2.9.1.1   Remote Annunciator Panel</TTL><BRK/>
<BRK/>
<TXT>Locate as shown.  Panel shall duplicate all requirements specified for the main control panel annunciator, except 
that in lieu of individual zone trouble lamps a single trouble lamp may be provided.  Panel shall have a lamp 
test switch.  Zone identification shall be by means of [permanently attached rigid plastic or metal plate(s)] 
[silk-screened labels attached to the reverse face of backlighted viewing window(s)].  Panel shall be of the 
[interior] [waterproof] type, [flush] [surface] [pedestal]-mounted.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9.1.2   Graphic Annunciator Panel</TTL><BRK/>
<BRK/>
<TXT>Locate as shown.  Panel shall be of the [interior] [weatherproof] type, [flush] [surface] [pedestal]-mounted.  
Panel shall be provided with the floor plan of the protected area(s), drawn to scale, with remote alarm lamps 
mounted to represent the location of each alarm initiating device. Panel graphic shall also show the location 
of the annunciator panel and control panel, and shall have a "you are here" arrow showing its location. Orient 
floor plan on graphic to location of person viewing the graphic; i.e., the direction the viewer is facing shall 
be towards the top of the graphic display.  Provide a North arrow.  [Principal rooms and areas shown shall be 
labeled with their room numbers or titles.]  The panel location shall be shown on the floor plan.  Detectors 
mounted on ceilings, [above ceilings,] and beneath raised floors [and different types of initiating devices] 
shall have different symbols or lamps of different colors for identification.  Lamps shall illuminate upon actuation 
of their corresponding device and remain illuminated until the system is reset. Panel shall have a lamp test 
switch.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>2.10   AUTOMATIC SMOKE-FIRE <SUB>DAMPERS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Insert appropriate Section number and title in blank below using format 
per UFC 1-300-02.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide automatic control of smoke-fire dampers in openings and ductwork penetrating the envelop of the protected 
area.  Smoke-fire dampers are specified in Section [<SRF>23 00 00</SRF> AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST 
SYSTEMS][_____].  Dampers shall close upon activation of second detector or upon activation of carbon dioxide 
manual discharge station.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11   SMOKE AND CARBON DIOXIDE EXHAUST SYSTEM</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Insert appropriate Section number and title in blank below using format 
per UFC 1-300-02.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide under Section [<SRF>23 00 00</SRF> AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS][_____] and as specified 
herein.  Provide a key-operated ON/OFF switch with red and green indicator lights for control of exhaust fans 
from each protected space.  Green light shall remain illuminated when exhaust system is in standby status.  Green 
light shall extinguish and red light shall illuminate when system is operating.  Provide an interlock from the 
carbon dioxide system to prevent operation of exhaust system during carbon dioxide system discharge and for a 
minimum of 10 minutes after carbon dioxide discharge.  Ten minutes after carbon dioxide discharge, exhaust system 
shall be operable by the key switch even if smoke detectors are still in alarm mode.  Locate switches outside 
the protected spaces.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12   OPERATING POWER</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete the first three sentences (in brackets) if electrical actuation 
systems are not specified.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Obtain AC operating power to control panel and battery charger from the line side of the incoming building power 
source ahead of all building services] [at the location indicated].  Provide independent, properly fused safety 
switch, with provisions for locking the cover and operating handle in the POWER ON position for these connections, 
and locate adjacent to the main distribution panel.  Paint switch box with red enamel and identify by a lettered 
designation.  Provide wiring in accordance with <RID>NFPA 70</RID>. Wiring for 120-volt circuits shall be No. 12 AWG minimum.  
Wiring for low-voltage DC circuits shall be No. 14 AWG minimum.  Wiring shall be color coded.  Provide wiring 
in metal conduit or electrical metallic tubing.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.13   CONDUCTOR IDENTIFICATION</TTL><BRK/>
<BRK/>
<TXT>Identify circuit conductors within each enclosure where a tap, splice, or termination is made.  Conductor identification 
shall be by plastic-coated, self-sticking printed markers or by heat-shrink type sleeves.  Attach the markers 
to prevent accidental detachment.  Identify control circuit terminations.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14   OPERATING INSTRUCTIONS</TTL><BRK/>
<BRK/>
<TXT>Provide at each remote control station.  Instructions shall clearly indicate steps for system operation.  The 
proposed legend for operating instructions shall be approved before installation.  Instructions shall be embossed 
white letters on red rigid plastic backgrounds.  Lettering shall be a minimum of<MET> 6.50 mm</MET><ENG> 0.25 inch</ENG> high for operating 
instructions and<MET> 25 mm</MET><ENG> 1 inch</ENG> high for identification of system operating devices and control valves.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Equipment, materials, installation, workmanship, fabrication, assembly, erection, examination, inspection, and 
testing shall be in accordance with <RID>NFPA 12</RID>, except as modified herein.  Install piping straight and true to 
bear evenly on hangers and supports.  Keep the interior and ends of new piping and existing piping affected by 
the Contractor's operations thoroughly cleaned of water and foreign matter.  Keep piping systems clean during 
installation by means of plugs or other approved methods.  When work is not in progress, securely close open 
ends of piping to prevent entry of water and foreign matter.  <TST>Inspect piping before placing into position.</TST></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   PIPE AND FITTINGS</TTL><BRK/>
<BRK/>
<TXT><TST>Test, inspect, and approve piping before concealing.</TST>  Provide fittings for direction changes in piping and for 
connections.  Jointing compound for pipe threads shall be Teflon pipe thread paste; apply only to male threads.  
Provide exposed ferrous pipe threads with one coat of zinc molybdate primer applied to minimum dry film thickness 
of<MET> 0.025 mm</MET><ENG> 1.0 mil</ENG>.     Pipe nipples<MET> 150 mm</MET><ENG> 6 inches</ENG> long and shorter shall be Schedule 80 steel pipe.  Provide 
tapered-reducing pipe fittings for changes in piping size; bushings will not be permitted.  Minimum pipe sizes 
for hose reel systems shall be<MET> 20 mm</MET><ENG> 0.75 inch</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3   PIPE HANGERS AND SUPPORTS</TTL><BRK/>
<BRK/>
<TXT>Provide additional supports for the concentrated loads in piping between hangers and supports, such as for valves.  
Support steel piping as follows:</TXT><BRK/>
<MET><TBL><THD><BRK/>
                           <HL4>MAXIMUM SPACING (METERS)</HL4><BRK/></THD>
<BRK/>
  __________________________________________________________________________<BRK/>
  Nominal Pipe   25.0 and<BRK/>
  <HL1>Size (mm)       Under     32    40    50    65    80    100   125   150</HL1><BRK/>
<BRK/>
  Steel Piping     2.10      2.40  2.75  3.00  3.40  3.70  4.30  4.60  5.20<BRK/>
  ___________________________________________________________________________<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
                           <HL4>MAXIMUM SPACING (FEET)</HL4><BRK/></THD>
<BRK/>
  __________________________________________________________________________<BRK/>
  Nominal Pipe      1.0 and<BRK/>
  <HL1>Size (Inches)     Under      1.25    1.5    2    2.5    3    4    5    6  </HL1><BRK/>
<BRK/>
  Steel Piping       7          8      9     10     11   12    14   15   17<BRK/>
  ___________________________________________________________________________<BRK/></TBL>
</ENG><BRK/></SPT>
<SPT><TTL>3.4   FIELD PAINTING</TTL><BRK/>
<BRK/>
<TXT>Clean, pretreat, prime, and paint new carbon dioxide fire extinguishing systems including valves, piping, conduit, 
hangers, supports, miscellaneous metalwork, and accessories.  Apply coatings to clean, dry surfaces, using clean 
brushes.  Clean surfaces to remove dust, dirt, rust, and loose mill scale.  Immediately after cleaning, provide 
the metal surfaces with one coat of pretreatment primer applied to a minimum dry film thickness of<MET> 0.076 mm</MET><ENG> 0.3 
mil</ENG>, and one coat of zinc molybdate primer applied to a minimum dry film thickness of<MET> 0.025 mm</MET><ENG> 1.0 mil</ENG>.  Shield 
operating devices with protective covering while painting is in process.  Upon completion of painting, remove 
protective covering from operating devices.  Remove devices which are painted and replace with new devices.  
Provide primed surfaces with the following:</TXT><BRK/>
<BRK/>
<SPT><TTL>3.4.1   Systems in Unfinished Areas</TTL><BRK/>
<BRK/>
<TXT>Unfinished areas are defined as attic spaces, spaces above suspended ceilings, crawl spaces, pipe chases, and 
spaces where walls or ceilings are not painted or not constructed of a prefinished material.  Provide primed 
surfaces with one coat of red alkyd gloss enamel applied to a minimum dry film thickness of<MET> 0.025 mm</MET><ENG> 1.0 mil</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4.2   Systems in Other Areas</TTL><BRK/>
<BRK/>
<TXT>Provide primed surfaces with two coats of paint to match adjacent surfaces, except provide valves and operating 
accessories with one coat of red alkyd gloss enamel applied to a minimum dry film thickness of<MET> 0.025 mm</MET><ENG> 1.0 mil</ENG>
.  Provide piping with<MET> 50 mm</MET><ENG> 2 inch</ENG> wide red enamel bands or self-adhering red plastic tape bands spaced at maximum 
of<MET> 6 meters</MET><ENG> 20 foot</ENG> intervals throughout the piping systems, except in finished areas, such as offices, the red 
bands may be deleted.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.5   FIELD QUALITY CONTROL</TTL><BRK/>
<BRK/>
<TXT>Perform tests to determine compliance with the specified requirements in the presence of the Contracting Officer.  
Test, inspect, and approve piping before covering or concealing.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.5.1   <SUB>Preliminary Tests</SUB></TTL><BRK/>
<BRK/>
<TXT><TST>Pneumatically test each piping system with carbon dioxide, nitrogen, or dry air at<MET> 1034 kPa (gage)</MET><ENG> 150 psig</ENG> for 
2 hours with no leakage or reduction in gage pressure.  Gages used shall be calibrated.  Upon completion and 
before final acceptance of the work, test each piping system by discharging a minimum of one<MET> 34 kg</MET><ENG> 75 pound</ENG> cylinder 
of carbon dioxide to demonstrate the reliability and proper functioning of each pressure-operated switch and 
the discharge of carbon dioxide gas from each system discharge nozzle.  After discharge, clean wire screens at 
nozzles if provided.  If screens or nozzles show evidence of plugging, discharge an additional cylinder with 
the nozzles removed.  Individually test remote control stations and other components and accessories to demonstrate 
proper functioning.</TST>  When tests have been completed and corrections made, submit a signed and dated certificate.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.2   Formal Inspection and Tests</TTL><BRK/>
<BRK/>
<TXT>Do not submit request for formal tests and inspection until preliminary tests and corrections are complete and 
approved.  The [_____] Division, Naval Facilities Engineering Command, Fire Protection Engineer, will witness 
formal tests and approve all systems before they are accepted.  Submit written request for formal inspection 
at least [_____] [15] working days prior to the inspection date.  An experienced technician regularly employed 
by the system installer shall be present during the inspection.  <TST>At this inspection, repeat the required tests 
as directed.</TST>  Furnish carbon dioxide, instruments, appliances, equipment, and personnel for the tests.</TXT><BRK/>
<BRK/></SPT>
</SPT><MET><SPT><TTL>3.6   SCHEDULE</TTL><BRK/>
<BRK/>
<TXT>Some metric measurements in this section are based on mathematical conversion of inch-pound measurement, and 
not on metric measurement commonly agreed to by the manufacturers or other parties.  The inch-pound and metric 
measurements shown are as follows:</TXT><BRK/>
<TBL><THD><BRK/>
     <HL1>Products</HL1>             <HL1>Inch-Pound</HL1>                 <HL1>Metric</HL1><BRK/></THD>
<BRK/>
     Alarm Bells          Diameter - 10 in.          Diameter - 250 mm<BRK/></TBL>
</SPT></MET><BRK/></PRT>