<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 26 20 00</SCN><BRK/>
<BRK/>
<STL>INTERIOR DISTRIBUTION SYSTEM</STL><BRK/>
<DTE>08/08</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for the <SCP>procurement, 
installation, and testing of electrical wiring systems for construction projects</SCP>.  <BRK/>
<BRK/>
Telecommunications cabling is covered in Section <SRF>27 10 00</SRF>, BUILDING TELECOMMUNICATIONS 
CABLING SYSTEM.  These wiring systems primarily involve voltages of 1,000 volts 
and less and mainly involve interior systems.  When voltages greater than 1,000 
volts are brought into a facility, consult and use Section <SRF>33 71 02.00 20</SRF>, UNDERGROUND 
ELECTRICAL DISTRIBUTION; Section <SRF>26 11 16</SRF>, SECONDARY UNIT SUBSTATIONS; and Section 
<SRF>26 12 19.10</SRF>, PAD-MOUNTED TRANSFORMERS for Navy projects and Section 
<SRF>33 71 01</SRF>, UNDERGROUND ELECTRICAL DISTRIBUTION SYSTEM, AERIAL; Section 
<SRF>33 70 02.00 10</SRF>, UNDERGROUND ELECTRICAL DISTRIBUTION SYSTEM; and Section 
<SRF>26 11 14.00 10</SRF>, MAIN ELECTRIC SUPPLY STATION AND SUBSTATION on Army projects 
as required.  Requirements for materials and procedures for special or unusual 
design should be added as necessary to fit specific projects.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestion on this specification are welcome and should be directed 
to the technical proponent of the specification.  A listing of the <URL HREF="http://www.ccb.org/UFGS/ufgstoc.htm">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following information shall be shown on the project drawings:</NPR><BRK/>
<BRK/>
<NPR>1.  Location of equipment</NPR><BRK/>
<BRK/>
<NPR>2.  Single-line diagrams elevations, limiting dimensions, and equipment ratings 
which are not covered in the specifications</NPR><BRK/>
<BRK/>
<NPR>3.  Remote indicating or control requirements.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to in the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)</ORG><BRK/><BRK/><RID>ANSI C12.7</RID><RTL>(2005) Requirements for Watthour Meter Sockets</RTL><BRK/><BRK/></REF><REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM B 1</RID><RTL>(2001; R 2007) Standard Specification for Hard-Drawn Copper Wire</RTL><BRK/><BRK/><RID>ASTM B 8</RID><RTL>(2004) Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft</RTL><BRK/><BRK/><RID>ASTM D 709</RID><RTL>(2001; R 2007) Laminated Thermosetting Materials</RTL><BRK/><BRK/></REF><REF><ORG>INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)</ORG><BRK/><BRK/><RID>IEEE C2</RID><RTL>(2007; Errata 2007; INT 2008) National Electrical Safety Code</RTL><BRK/><BRK/><RID>IEEE Std 100</RID><RTL>(2000) The Authoritative Dictionary of IEEE Standards Terms</RTL><BRK/><BRK/><RID>IEEE Std 81</RID><RTL>(1983) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System (Part 1)Normal Measurements</RTL><BRK/><BRK/></REF><REF><ORG>INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)</ORG><BRK/><BRK/><RID>NETA ATS</RID><RTL>(2003) Acceptance Testing Specifications</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)</ORG><BRK/><BRK/><RID>NEMA 250</RID><RTL>(2003) Enclosures for Electrical Equipment (1000 Volts Maximum)</RTL><BRK/><BRK/><RID>NEMA BU 1.1</RID><RTL>(2005) General Instructions for Proper Handling, Installation, Operation, and Maintenance of Busway Rated 600 Volts or Less</RTL><BRK/><BRK/><RID>NEMA C12.1</RID><RTL>(2008) Electric Meters; Code for Electricity Metering</RTL><BRK/><BRK/><RID>NEMA C80.1</RID><RTL>(2005) Standard for Electrical Rigid Steel Conduit (ERSC)</RTL><BRK/><BRK/><RID>NEMA C80.3</RID><RTL>(2005) Standard for Electrical Metallic Tubing (EMT)</RTL><BRK/><BRK/><RID>NEMA C80.5</RID><RTL>(2005) Standard for Electrical Rigid Aluminum Conduit (ERAC)</RTL><BRK/><BRK/><RID>NEMA FU 1</RID><RTL>(2002; R 2007) Low Voltage Cartridge Fuses</RTL><BRK/><BRK/><RID>NEMA ICS 1</RID><RTL>(2000; R 2005; R 2008) Standard for Industrial Control and Systems General Requirements</RTL><BRK/><BRK/><RID>NEMA ICS 2</RID><RTL>(2000; Errata 2002; R 2005; Errata 2006) Standard for Industrial Control and Systems:  Controllers, Contractors, and Overload Relays Rated Not More than 2000 Volts AC or 750 Volts DC: Part 8 - Disconnect Devices for Use in Industrial Control Equipment</RTL><BRK/><BRK/><RID>NEMA ICS 3</RID><RTL>(2005) Standard for Industrial Control and Systems:  Medium Voltage Controllers Rated 2001 to 7200 Volts AC</RTL><BRK/><BRK/><RID>NEMA ICS 4</RID><RTL>(2005) Industrial Control and Systems: Terminal Blocks</RTL><BRK/><BRK/><RID>NEMA ICS 6</RID><RTL>(1993; R 2006) Standard for Industrial Controls and Systems Enclosures</RTL><BRK/><BRK/><RID>NEMA KS 1</RID><RTL>(2001; R 2006) Enclosed and Miscellaneous Distribution Equipment Switches (600 Volts Maximum)</RTL><BRK/><BRK/><RID>NEMA MG 1</RID><RTL>(2007; Errata 2008) Standard for Motors and Generators</RTL><BRK/><BRK/><RID>NEMA MG 10</RID><RTL>(2001; R 2007) Energy Management Guide for Selection and Use of Fixed Frequency Medium AC Squirrel-Cage Polyphase Induction Motors</RTL><BRK/><BRK/><RID>NEMA MG 11</RID><RTL>(1977; R 2007) Energy Management Guide for Selection and Use of Single Phase Motors</RTL><BRK/><BRK/><RID>NEMA RN 1</RID><RTL>(2005) Standard for Polyvinyl Chloride (PVC) Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit</RTL><BRK/><BRK/><RID>NEMA ST 20</RID><RTL>(1992; R 1997) Standard for Dry-Type Transformers for General Applications</RTL><BRK/><BRK/><RID>NEMA TC 14</RID><RTL>(2002) Standard for Reinforced Thermosetting Resin Conduit (RTRC) and Fittings</RTL><BRK/><BRK/><RID>NEMA TC 2</RID><RTL>(2003) Standard for Electrical Polyvinyl Chloride (PVC) Tubing and Conduit</RTL><BRK/><BRK/><RID>NEMA TC 3</RID><RTL>(2004) Standard for Polyvinyl Chloride PVC Fittings for Use With Rigid PVC Conduit and Tubing</RTL><BRK/><BRK/><RID>NEMA TP 1</RID><RTL>(2002) Guide for Determining Energy Efficiency for Distribution Transformers</RTL><BRK/><BRK/><RID>NEMA VE 1</RID><RTL>(2002) Standard for Metallic Cable Tray Systems</RTL><BRK/><BRK/><RID>NEMA WD 1</RID><RTL>(1999; R 2005) Standard for General Requirements for Wiring Devices</RTL><BRK/><BRK/><RID>NEMA WD 6</RID><RTL>(2002; R 2008) Standard for Wiring Devices - Dimensional Requirements</RTL><BRK/><BRK/><RID>NEMA Z535.4</RID><RTL>(2007; Errata 2007) Product Safety Signs and Labels</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/><RID>NFPA 70E</RID><RTL>(2008) Electrical Safety in the Workplace</RTL><BRK/><BRK/><RID>NFPA 780</RID><RTL>(2007) Standard for the Installation of Lightning Protection Systems</RTL><BRK/><BRK/></REF><REF><ORG>TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)</ORG><BRK/><BRK/><RID>TIA J-STD-607-A</RID><RTL>(2002) Commercial Building Grounding (Earthing)  and Bonding Requirements for Telecommunications</RTL><BRK/><BRK/><RID>TIA/EIA-568-B.1</RID><RTL>(2001 Addendums 2001, 2003, 2003, 2003, 2004, 2007) Commercial Building Telecommunications Cabling Standard - Part 1: General Requirements</RTL><BRK/><BRK/><RID>TIA/EIA-569-A</RID><RTL>(1998; Addenda 2000, 2001) Commercial Building Standards for Telecommunications Pathways and Spaces</RTL><BRK/><BRK/></REF><REF><ORG>U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)</ORG><BRK/><BRK/><RID>29 CFR 1910.147</RID><RTL>Control of Hazardous Energy (Lock Out/Tag Out)</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 1</RID><RTL>(2005; Rev thru Jul 2007) Standard for Flexible Metal Conduit</RTL><BRK/><BRK/><RID>UL 1010</RID><RTL>(2006) Receptacle-Plug Combinations for Use in Hazardous (Classified) Locations</RTL><BRK/><BRK/><RID>UL 1063</RID><RTL>(2006) Standard for Safety Machine-Tools Wires and Cables</RTL><BRK/><BRK/><RID>UL 1242</RID><RTL>(2006; Rev thru Jul 2007) Standard for Electrical Intermediate Metal Conduit -- Steel</RTL><BRK/><BRK/><RID>UL 1449</RID><RTL>(2006) Surge Protective Devices</RTL><BRK/><BRK/><RID>UL 1561</RID><RTL>(1999; Rev thru Sep 2005) Dry-Type General Purpose and Power Transformers</RTL><BRK/><BRK/><RID>UL 1569</RID><RTL>(1999; Rev thru Nov 2006) Metal-Clad Cables</RTL><BRK/><BRK/><RID>UL 1660</RID><RTL>(2004; Rev thru Jan 2005) Liquid-Tight Flexible Nonmetallic Conduit</RTL><BRK/><BRK/><RID>UL 1699</RID><RTL>(1999; Rev thru May 2003) Arc-Fault Circuit-Interrupters</RTL><BRK/><BRK/><RID>UL 198M</RID><RTL>(2003; Rev thru Oct 2007) Mine-Duty Fuses</RTL><BRK/><BRK/><RID>UL 20</RID><RTL>(2000 ; Rev thru Dec 2008) Standard for General-Use Snap Switches</RTL><BRK/><BRK/><RID>UL 2043</RID><RTL>(2008) Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces</RTL><BRK/><BRK/><RID>UL 360</RID><RTL>(2003; Rev thru Jul 2007) Liquid-Tight Flexible Steel Conduit</RTL><BRK/><BRK/><RID>UL 4</RID><RTL>(2004; Rev thru Oct 2008) Armored Cable</RTL><BRK/><BRK/><RID>UL 44</RID><RTL>(2005; Rev thru Nov 2005) Thermoset-Insulated Wires and Cables</RTL><BRK/><BRK/><RID>UL 467</RID><RTL>(2007) Standard for Grounding and Bonding Equipment</RTL><BRK/><BRK/><RID>UL 486A-486B</RID><RTL>(2003; Rev thru Aug 2006) Standard for Wire Connectors</RTL><BRK/><BRK/><RID>UL 486C</RID><RTL>(2004; Rev thru Aug 2006) Standard for Splicing Wire Connectors</RTL><BRK/><BRK/><RID>UL 489</RID><RTL>(2002; Rev thru Jun 2006) Standard for Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures</RTL><BRK/><BRK/><RID>UL 498</RID><RTL>(2001; Rev thru Oct 2008) Attachment Plugs and Receptacles</RTL><BRK/><BRK/><RID>UL 5</RID><RTL>(2004; Rev thru May 2007) Surface Metal Raceways and Fittings</RTL><BRK/><BRK/><RID>UL 50</RID><RTL>(2007) Standard for Enclosures for Electrical Equipment</RTL><BRK/><BRK/><RID>UL 506</RID><RTL>(2000; Rev thru May 2006) Standard for Specialty Transformers</RTL><BRK/><BRK/><RID>UL 508</RID><RTL>(1999; Rev thru Sep 2008) Standard for Industrial Control Equipment</RTL><BRK/><BRK/><RID>UL 510</RID><RTL>(2005; Rev thru Aug 2005) Polyvinyl Chloride, Polyethylene, and Rubber Insulating Tape</RTL><BRK/><BRK/><RID>UL 512</RID><RTL>(1993; Rev thru Jan 2008) Fuseholders</RTL><BRK/><BRK/><RID>UL 514A</RID><RTL>(2004; Rev thru Aug 2007) Standard for Metallic Outlet Boxes</RTL><BRK/><BRK/><RID>UL 514B</RID><RTL>(2004; Rev thru Aug 2007) Standard for Conduit, Tubing and Cable Fittings</RTL><BRK/><BRK/><RID>UL 514C</RID><RTL>(1996; Rev thru Dec 2008) Nonmetallic Outlet Boxes, Flush-Device Boxes, and Covers</RTL><BRK/><BRK/><RID>UL 5A</RID><RTL>(2003; Rev thru Aug 2008) Nonmetallic Surface Raceways and Fittings</RTL><BRK/><BRK/><RID>UL 6</RID><RTL>(2007) Standard for Electrical Rigid Metal Conduit-Steel</RTL><BRK/><BRK/><RID>UL 651</RID><RTL>(2005; Rev thru May 2007) Standard for Schedule 40 and 80 Rigid PVC Conduit and Fittings</RTL><BRK/><BRK/><RID>UL 67</RID><RTL>(1993; Rev thru Jul 2008) Standard for Panelboards</RTL><BRK/><BRK/><RID>UL 674</RID><RTL>(2003; Rev thru Aug 2008) Standard for Electric Motors and Generators for Use in Division 1 Hazardous (Classified) Locations</RTL><BRK/><BRK/><RID>UL 698</RID><RTL>(2006) Industrial Control Equipment for Hazardous (Classified) Locations</RTL><BRK/><BRK/><RID>UL 6A</RID><RTL>(2008) Electrical Rigid Metal Conduit - Aluminum, Red Brass, and Stainless Steel</RTL><BRK/><BRK/><RID>UL 719</RID><RTL>(2006; Rev thru Oct 2007) Nonmetallic-Sheathed Cables</RTL><BRK/><BRK/><RID>UL 797</RID><RTL>(2007) Standard for Electrical Metallic Tubing -- Steel</RTL><BRK/><BRK/><RID>UL 817</RID><RTL>(2001; Rev thru May 2007) Cord Sets and Power-Supply Cords</RTL><BRK/><BRK/><RID>UL 83</RID><RTL>(20086) Standard for Thermoplastic-Insulated Wires and Cables</RTL><BRK/><BRK/><RID>UL 845</RID><RTL>(2005; Rev thru Aug 2006) Standard for Motor Control Centers</RTL><BRK/><BRK/><RID>UL 854</RID><RTL>(2004; Rev thru Oct 2007) Service-Entrance Cables</RTL><BRK/><BRK/><RID>UL 857</RID><RTL>(2001; Rev thru Nov 2002) Busways</RTL><BRK/><BRK/><RID>UL 869A</RID><RTL>(2006) Reference Standard for Service Equipment</RTL><BRK/><BRK/><RID>UL 870</RID><RTL>(1995; Rev thru Jul 2003) Standard for Wireways, Auxiliary Gutters, and Associated Fittings</RTL><BRK/><BRK/><RID>UL 877</RID><RTL>(1993; Rev thru Nov 1999) Circuit Breakers and Circuit-Breaker Enclosures for Use in Hazardous (Classified) Locations</RTL><BRK/><BRK/><RID>UL 886</RID><RTL>(1994; Rev thru Nov 2005) Outlet Boxes and Fittings for Use in Hazardous (Classified) Locations</RTL><BRK/><BRK/><RID>UL 943</RID><RTL>(2006; Rev thru Feb 2008) Ground-Fault Circuit-Interrupters</RTL><BRK/><BRK/><RID>UL 984</RID><RTL>(1996; Rev thru Sept 2005) Hermetic Refrigerant Motor-Compressors</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   DEFINITIONS</TTL><BRK/>
<BRK/>
<TXT>Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on 
the drawings, shall be as defined in <RID>IEEE Std 100</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are[ for Contractor Quality Control approval][ for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government].  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Panelboards</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Transformers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Busway</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Cable trays</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Motor control centers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Include wiring diagrams and installation details of equipment indicating proposed location, 
layout and arrangement, control panels, accessories, piping, ductwork, and other items that 
must be shown to ensure a coordinated installation.  Wiring diagrams shall identify circuit 
terminals and indicate the internal wiring for each item of equipment and the interconnection 
between each item of equipment.  Drawings shall indicate adequate clearance for operation, maintenance, 
and replacement of operating equipment devices.</ITM><BRK/>
<BRK/>
<ITM><SUB>Wireways</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Load centers for housing units</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]]</ITM><BRK/>
<BRK/>
<ITM><SUB>Marking strips</SUB> drawings[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Receptacles</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Circuit breakers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Switches</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Transformers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Enclosed circuit breakers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Motor controllers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Combination motor controllers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Load centers for housing units</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]]</ITM><BRK/>
<BRK/>
<ITM><SUB>Manual motor starters</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Residential load centers</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Metering</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Meter base only</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]]</ITM><BRK/>
<BRK/>
<ITM><SUB>CATV outlets</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Telecommunications <SUB>Grounding Busbar</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Surge protective devices</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>Submittals shall include performance and characteristic curves.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>600-volt wiring test</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Grounding system test</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Transformer tests</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM><SUB>Ground-fault receptacle test</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Fuses</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<LST><SUB>SD-09 Manufacturer's Field Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Transformer factory tests</SUB></ITM><BRK/>
<BRK/>
[<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete SD-10 and its subparagraph on LANTNAVFACENGCOM projects unless 
"metering" or other special equipment is added to the section which requires 
O&amp;M manuals.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM><SUB>Electrical Systems</SUB>, Data Package 5[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>[<SUB>Metering</SUB>, Data Package 5[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]]</ITM><BRK/>
<BRK/>
<ITM>Submit operation and maintenance data in accordance with Section <SRF>01 78 23</SRF>, OPERATION AND MAINTENANCE 
DATA and as specified herein.</ITM><BRK/>
<BRK/>
]</SPT><SPT><TTL>1.4   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.4.1   Fuses</TTL><BRK/>
<BRK/>
<TXT>Submit coordination data as specified in paragraph, FUSES of this section.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.2   Regulatory Requirements</TTL><BRK/>
<BRK/>
<TXT>In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the 
word, "shall" had been substituted for "should" wherever it appears.  Interpret references in these publications 
to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer.  Equipment, 
materials, installation, and workmanship shall be in accordance with the mandatory and advisory provisions of <RID>
NFPA 70</RID> unless more stringent requirements are specified or indicated.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.3   Standard Products</TTL><BRK/>
<BRK/>
<TXT>Provide materials and equipment that are products of manufacturers regularly engaged in the production of such 
products which are of equal material, design and workmanship.  Products shall have been in satisfactory commercial 
or industrial use for 2 years prior to bid opening.  The 2-year period shall include applications of equipment 
and materials under similar circumstances and of similar size.  The product shall have been on sale on the commercial 
market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.  Where two or 
more items of the same class of equipment are required, these items shall be products of a single manufacturer; 
however, the component parts of the item need not be the products of the same manufacturer unless stated in this 
section.</TXT><BRK/>
<BRK/>
<SPT><TTL>1.4.3.1   Alternative Qualifications</TTL><BRK/>
<BRK/>
<TXT>Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory 
field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is 
furnished.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.3.2   Material and Equipment Manufacturing Date</TTL><BRK/>
<BRK/>
<TXT>Products manufactured more than 3 years prior to date of delivery to site shall not be used, unless specified 
otherwise.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>1.5   MAINTENANCE</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete subparagraph on LANTNAVFACENGCOM projects unless "metering" or 
other special equipment is added to the section which requires O&amp;M manuals.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT>[<TTL>1.5.1   <SUB>Electrical Systems</SUB></TTL><BRK/>
<BRK/>
<TXT>Submit operation and maintenance manuals for electrical systems that provide basic data relating to the design, 
operation, and maintenance of the electrical distribution system for the building.  This shall include:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Single line diagram of the "as-built" building electrical system.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Schematic diagram of electrical control system (other than HVAC, covered elsewhere).</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Manufacturers' operating and maintenance manuals on active electrical equipment.</ITM><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>1.6   WARRANTY</TTL><BRK/>
<BRK/>
<TXT>The equipment items shall be supported by service organizations which are reasonably convenient to the equipment 
installation in order to render satisfactory service to the equipment on a regular and emergency basis during 
the warranty period of the contract.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>1.7   SEISMIC REQUIREMENTS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Do not use this paragraph for Navy projects.  When directed to meet Seismic 
Requirements, Section 13080 and Section 16070A) must be edited to suit the project 
and be included in the contract documents.  Edit the following paragraph and 
include it in the project specification.  When a Government designer is the 
Engineer of Record, provide seismic requirements on the drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Seismic details shall[ conform to[ Section <SRF>13 48 00</SRF>, SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT][ and to][ 
Section <SRF>26 05 48.00 10</SRF>, SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT]][ be as indicated].</TXT><BRK/>
<BRK/>
]</SPT></PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   MATERIALS AND EQUIPMENT</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Choose the last bracketed sentence for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Materials, equipment, and devices shall, as a minimum, meet requirements of UL, where UL standards are established 
for those items, and requirements of <RID>NFPA 70</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2   CONDUIT AND FITTINGS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For Navy projects, do not use Electrical Nonmetallic Tubing (ENT) without 
specific written approval from the cognizant electrical design branch manager.<BRK/>
Malleable iron seal electrical fittings shall be used in fuel valve pits and 
similar locations where fittings are exposed to potential freeze thaw environments.  
Nonmetallic fittings have failed in these environments.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Shall conform to the following:</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.1   Rigid Metallic Conduit</TTL><BRK/>
<BRK/>
<SPT><TTL>2.2.1.1   Rigid, Threaded Zinc-Coated Steel Conduit</TTL><BRK/>
<BRK/>
<TXT><RID>NEMA C80.1</RID>, <RID>UL 6</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.1.2   Rigid Aluminum Conduit</TTL><BRK/>
<BRK/>
<TXT><RID>NEMA C80.5</RID>, <RID>UL 6A</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2.2   Rigid Nonmetallic Conduit</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Do not use fiberglass in buildings.  With advanced approval, for acceptable 
reasons, it may be used for service entrance or below grade use.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>PVC Type EPC-40[, and EPC-80] in accordance with <RID>NEMA TC 2</RID>,<RID>UL 651</RID>[, or fiberglass conduit, in accordance with <RID>
NEMA TC 14</RID>].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.3   Intermediate Metal Conduit (IMC)</TTL><BRK/>
<BRK/>
<TXT><RID>UL 1242</RID>, zinc-coated steel only.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.4   Electrical, Zinc-Coated Steel Metallic Tubing (EMT)</TTL><BRK/>
<BRK/>
<TXT><RID>UL 797</RID>, <RID>NEMA C80.3</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.5   Plastic-Coated Rigid Steel and IMC Conduit</TTL><BRK/>
<BRK/>
<TXT><RID>NEMA RN 1</RID>, Type 40(<MET> one millimeter (40 mils)</MET><ENG> 40 mils</ENG> thick).</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.6   Flexible Metal Conduit</TTL><BRK/>
<BRK/>
<TXT><RID>UL 1</RID>.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.6.1   Liquid-Tight Flexible Metal Conduit, Steel</TTL><BRK/>
<BRK/>
<TXT><RID>UL 360</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2.7   Fittings for Metal Conduit, EMT, and Flexible Metal Conduit</TTL><BRK/>
<BRK/>
<TXT><RID>UL 514B</RID>.  Ferrous fittings shall be cadmium- or zinc-coated in accordance with <RID>UL 514B</RID>.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.7.1   Fittings for Rigid Metal Conduit and IMC</TTL><BRK/>
<BRK/>
<TXT>Threaded-type.  Split couplings unacceptable.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.7.2   Fittings for EMT</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use steel for SOUTHNAVFACENGCOM projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Steel][Die cast] compression type.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2.8   Fittings for Rigid Nonmetallic Conduit</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Do not use fiberglass in buildings.  With advanced approval, for acceptable 
reasons, it may be used for service entrance or below grade use.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NEMA TC 3</RID> for PVC[ and <RID>NEMA TC 14</RID> for fiberglass], and <RID>UL 514B</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.9   Liquid-Tight Flexible Nonmetallic Conduit</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Do not use liquid-tight flexible nonmetallic conduits in Continental 
United States (CONUS).  In overseas locations, only use when allowed by the 
Authority Having Jurisdiction.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>UL 1660</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.3   SURFACE RACEWAY</TTL><BRK/>
<BRK/>
<SPT><TTL>2.3.1   Surface Metal Raceway</TTL><BRK/>
<BRK/>
<TXT><RID>UL 5</RID>, two-piece painted steel, totally enclosed, snap-cover type.[  Provide multiple outlet-type raceway with 
grounding-type receptacle where indicated.  Receptacles shall be as specified herein and shall be spaced minimum 
of one every<MET> [455] [_____] mm</MET><ENG> [18] [_____] inches</ENG>.][  Alternate receptacles shall be wired on different circuits.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.2   Surface Nonmetallic Raceway</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer should coordinate with the Authority Having Jurisdiction responsible 
for the construction contract regarding the use of this wiring method in the 
project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>UL 5A</RID>, nonmetallic totally enclosed, snap-cover type.[  Provide multiple outlet-type raceway with grounding-type 
receptacle where indicated.  Receptacles shall be as specified herein and shall be spaced minimum of one every<MET>
 [455] [_____] mm</MET><ENG> [18] [_____] inches</ENG>.][  Alternate receptacles shall be wired on different circuits.]</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.4   <SUB>BUSWAY</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Phase sequence of voltages, orientation, etc., should be indicated on 
the drawings for existing transformers, switchboards, switchgear, motor control 
centers, etc.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NEMA BU 1.1</RID>, <RID>UL 857</RID>.  Buses shall be[ copper][ or][ aluminum].  Busways shall be rated [_____] volts, [_____] 
continuous current amperes, three-phase,[ three-][ four-]wire, and include integral or internal[ 50-percent] 
ground bus.  Short circuit rating shall be[ [_____] root mean square (rms) symmetrical amperes minimum][ as indicated].[  
Busway systems shall be suitable for use indoors.]  Enclosures shall be[ steel][ aluminum] [ metallic].  Hardware 
shall be plated or otherwise protected to resist corrosion.  Joints shall be one-bolt type with through-bolts, 
which can be checked for tightness without deenergizing system.  Maximum hot spot temperature rise at any point 
in busway at continuous rated load shall not exceed 55 degrees C above maximum ambient temperature of 40 degrees 
C in any position. Provide internal barriers to prevent movement of superheated gases. Contractor shall coordinate 
proper voltage phasing of entire bus duct system, for example where busway interfaces with transformers, switchgear, 
switchboards, motor control centers, and other system components.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.4.1   Feeder Busways</TTL><BRK/>
<BRK/>
<TXT>Provide[ ventilated, except that vertical busways within<MET> 1830 mm</MET><ENG> 6 feet</ENG> of floors shall be unventilated,][ unventilated, 
totally enclosed] low-impedance busway.  Bus bars shall be fully covered with insulating material, except at 
stabs.  Entire busway system shall be polarized.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.2   Plug-In Busways</TTL><BRK/>
<BRK/>
<TXT>Unventilated type.  Plug-in units shall be[ fusible, handle-operated, switch type, horsepower-rated][ circuit 
breaker-type][ handle-operated, switch type, equipped with high interrupting-capacity, current-limiting fuses].  
Bus bars shall be covered with insulating material throughout, except at joints and other connection points. 
[  A hook stick of suitable length shall be provided for operating plug-in units from the floor.].</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.5   <SUB>CABLE TRAYS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Show cable tray layout on the drawings.  When using multiple types and 
sizes, indicate size and type of cable trays on the drawings.  When using "as 
indicated" option, insure information required is shown on the drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NEMA VE 1</RID>.  Cable trays shall form a wireway system, and shall be of nominal[<MET> [75] [100] [150] mm ([ 3][ 4][ 
6] inch)</MET><ENG> [3] [4] [6] inch</ENG>] depth[ as indicated].  Cable trays shall be constructed of[ aluminum][ copper-free 
aluminum][ steel that has been zinc-coated after fabrication].  Trays shall include splice and end plates, dropouts, 
and miscellaneous hardware.  Edges, fittings, and hardware shall be finished free from burrs and sharp edges.  
Fittings shall have not less than load-carrying ability of straight tray sections and shall have manufacturer's 
minimum standard radius.[  Radius of bends shall be<MET> [305] [610] [915] mm ([ 12][ 24][ 36] inches)</MET><ENG> [12] [24] [36] 
inches</ENG>.][  Radius of bends shall be as indicated.]</TXT><BRK/>
<BRK/>
<SPT><TTL>2.5.1   Basket-Type Cable Trays</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Basket cable tray is a fabricated structure consisting of wire mesh bottom 
and side rails.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide[ size as indicated][ of nominal<MET>[ 50,][ 100,][ 150,][ 200,][ 300,][ 450,][ and][ 600] mm ([2,][ 4,][ 6,][ 
8,][ 12,][ 18,][ and][ 24] inch)</MET><ENG>[ 2,][ 4,][ 6,][ 8,][ 12,][ 18,][ and][ 24] inch</ENG> width and <MET>[ 25,][ 50,][ and][ 
100] mm ([1,][ 2,][ and][ 4] inch)</MET><ENG>[ 1,][ 2,][ and][ 4] inch</ENG> depth] with maximum wire mesh spacing of<MET> 50 by 100 
mm (2 by 4 inch)</MET><ENG> 2 by 4 inch</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.2   Trough-Type Cable Trays</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Trough or ventilated cable tray is a fabricated structure consisting 
of integral or separate longitudinal rails and a bottom having openings sufficient 
for the passage of air and utilizing 75% or less of the plan area of the surface 
to support cables.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide[ size as indicated][ of nominal<MET> [150] [305] [455] [610] [760] [915] mm ([ 6][ 12][ 18][ 24][ 30][ 36] 
inch)</MET><ENG> [6] [12] [18] [24] [30] [36] inch</ENG> width].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.3   Ladder-Type Cable Trays</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Ladder cable tray is a fabricated structure consisting of two longitudinal 
side rails connected by individual transverse members (rungs).</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide[ size as indicated][ of nominal<MET> [150] [305] [455] [610] [760] [915] mm ([6] [12] [18] [24] [30] [36] 
inch)</MET><ENG> [6] [12] [18] [24] [30] [36] inch</ENG> width] with maximum rung spacing of<MET> [150] [225] [305] [455] mm ([6][9][12][18])</MET><ENG>
 [6] [9] [12] [18] inches</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.4   Channel-Type Cable Trays</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Channel cable tray is a fabricated structure consisting of a one-piece 
ventilated-bottom or solid-bottom channel section, not exceeding <MET>152 mm (6 inches)</MET><ENG>
6 inches</ENG> in width.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide [ size as indicated][ of nominal<MET> [75] [100] [150] mm ([3][4][6] inch)</MET><ENG> [3] [4] [6] inch</ENG> width].  Trays 
shall be one-piece construction having slots spaced not more than<MET> 115 mm (4 1/2 inches)</MET><ENG> 4 1/2 inches</ENG> on centers.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.5   Solid Bottom-Type Cable Trays</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Solid bottom or non-ventilated cable tray is a fabricated structure consisting 
of a bottom without ventilation openings within integral or separate longitudinal 
side rails.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide[ size as indicated][ of nominal<MET> [150] [305] [455] [610] [760] [915] mm ([6][12][18][24][30][36] inch)</MET><ENG>
 [6][12][18][24][30][36] inch</ENG> width].  Solid covers[ shall][ shall not] be provided.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.5.6   Cantilever</TTL><BRK/>
<BRK/>
<TXT>Cantilever-type, center-hung cable trays may be provided at the Contractor's option in lieu of other cable tray 
types specified.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT>[<TTL>2.6   OPEN TELECOMMUNICATIONS CABLE SUPPORT</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Do not use for Navy projects.  Navy does not allow the use of open-top 
cable supports (J-supports) or closed ring cable supports (D-rings) for telecommunications 
pathway.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.6.1   Open Top Cable Supports</TTL><BRK/>
<BRK/>
<TXT>Provide open top cable supports in accordance with <RID>UL 2043</RID>.  Open top cable supports shall be[[ galvanized][ 
zinc-coated] steel][ as indicated].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6.2   Closed Ring Cable Supports</TTL><BRK/>
<BRK/>
<TXT>Provide closed ring cable supports in accordance with <RID>UL 2043</RID>.  Closed ring cable supports shall be[[ galvanized][ 
zinc-coated] steel][ as indicated].</TXT><BRK/>
<BRK/></SPT>
]</SPT><SPT><TTL>2.7   OUTLET BOXES AND COVERS</TTL><BRK/>
<BRK/>
<TXT><RID>UL 514A</RID>, cadmium- or zinc-coated, if ferrous metal.  <RID>UL 514C</RID>, if nonmetallic.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.7.1   Floor Outlet Boxes</TTL><BRK/>
<BRK/>
<TXT>Boxes shall be[ adjustable][ nonadjustable] and concrete tight.  Each outlet shall consist of[ nonmetallic][  
or][ cast-metal] body with threaded openings,[ or sheet-steel body with knockouts] for conduits,[ adjustable 
][, ][ brass flange] ring, and cover plate with<MET> [19][25][31.75][53.92] mm ([3/4][1][1 1/4][2 1/8] inch)</MET><ENG> [3/4][1][1 
1/4][2 1/8] inch</ENG> threaded plug.  Telecommunications outlets shall consist of[ surface-mounted, horizontal][ flush], 
aluminum or stainless steel housing with a receptacle as specified and[<MET> 25 mm (one inch)</MET><ENG> one inch</ENG> bushed side 
opening][<MET> 19 mm (3/4 inch)</MET><ENG> 3/4 inch</ENG> top opening].  Receptacle outlets shall consist of[ surface-mounted, horizontal][ 
flush] aluminum or stainless steel housing with duplex-type receptacle as specified herein.  Provide gaskets 
where necessary to ensure watertight installation.[  Provide plugs with installation instructions to the Contracting 
Officer for[ 5][ ____] percent of outlet boxes for the capping of outlets upon removal of service fittings.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2   Outlet Boxes for Telecommunications System</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When using "as indicated" option, ensure information required is shown 
on the drawings.  Choose 100 mm (4 inch) square boxes for single gang, four 
outlet, copper telecommunications configurations that do not have provision 
for fiber optic cabling.  Choose 120 mm (4 11/16 inch) square boxes for 35 mm 
(1 1/4 inch) conduit installations and for outlet boxes that have or may require 
fiber optic cabling.  Larger boxes are required to meet bend radii requirements 
for fiber optic cable.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide standard type<MET>[ 100 mm square by 54 mm deep (4 inches square by 2 1/8 inches deep)][ 120 mm square by 
54 mm deep (4 11/16 inches square by 2 1/8 inches)]</MET><ENG>[ 4 inches square by 2 1/8 inches deep][ 4 11/16 inches square 
by 2 1/8 inches deep]</ENG>.[  Outlet boxes for wall-mounted telecommunications outlets shall be<MET> 100 by 54 by 54 mm 
(4 by 2 1/8 by 2 1/8 inches)</MET><ENG> 4 by 2 1/8 by 2 1/8 inches</ENG> deep.]  Depth of boxes shall be large enough to allow 
manufacturers' recommended conductor bend radii.[  Outlet boxes for fiber optic telecommunication outlets shall 
include a minimum<MET> 10 mm (3/8 inch)</MET><ENG> 3/8 inch</ENG> deep single or two gang plaster ring as shown and installed using 
a minimum<MET> 27 mm (1 inch)</MET><ENG> 1 inch</ENG> conduit system.][  Outlet boxes for handicapped telecommunications station shall 
be<MET> 100 by 54 by 54 mm (4 by 2 1/8 by 2 1/8 inches)</MET><ENG> 4 by 2 1/8 by 2 1/8 inches</ENG> deep.]</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.7.3   Clock Outlet for Use in Other Than Wired Clock System</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Battery-operated clocks are Navy standard.  Retain this paragraph only 
under special conditions.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide outlet box with plastic cover, where required, and single receptacle with clock outlet plate.  Receptacle 
shall be recessed sufficiently within box to allow complete insertion of standard cap, flush with plate.  Suitable 
clip or support for hanging clock shall be secured to top plate.  Material and finish of plate shall be as specified 
in paragraph DEVICE PLATES of this section.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>2.8   CABINETS, JUNCTION BOXES, AND PULL BOXES</TTL><BRK/>
<BRK/>
<TXT>Volume greater than<MET> 1640 mL</MET><ENG> 100 cubic inches</ENG>, <RID>UL 50</RID>, hot-dip, zinc-coated, if sheet steel.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9   WIRES AND CABLES</TTL><BRK/>
<BRK/>
<TXT>Wires and cables shall meet applicable requirements of <RID>NFPA 70</RID> and UL for type of insulation, jacket, and conductor 
specified or indicated.  Wires and cables manufactured more than 12 months prior to date of delivery to site 
shall not be used.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.9.1   Conductors</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  1.  For Navy projects, unless directed<BRK/>
       otherwise, do not specify the use of <BRK/>
       aluminum conductors for interior distribution<BRK/>
       circuits of 600 VAC or less.<BRK/>
<BRK/>
       2.  The use of aluminum conductors in mission<BRK/>
       critical facilities, dormitories, officers'<BRK/>
       housing, and transient living facilities is<BRK/>
       limited to service entrance conductors only,<BRK/>
       sizes No. 4 AWG and larger.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  In overseas locations, for conductors No. 10 AWG and smaller diameter, 
consideration may be given to the use of stranded wires, if suitable terminal 
devices can be applied which enable proper connection.  Also, stranded wires 
in sizes No. 10 AWG and smaller diameter may be required for projects involving 
uninterrupted power supply (UPS) installations.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Conductors No. 8 AWG and larger diameter shall be stranded.  Conductors No. 10 AWG and smaller diameter shall 
be solid, except that conductors for remote control, alarm, and signal circuits, classes 1, 2, and 3, shall be 
stranded unless specifically indicated otherwise.  Conductor sizes and capacities shown are based on copper, 
unless indicated otherwise.[  All conductors shall be copper.][  Conductors indicated to be No. 6 AWG or smaller 
diameter shall be copper.  Conductors indicated to be No. 4 AWG and larger diameter shall be either copper or 
aluminum, unless type of conductor material is specifically indicated, or specified, or required by equipment 
manufacturer.]</TXT><BRK/>
<BRK/>
<SPT>[<TTL>2.9.1.1   Equipment Manufacturer Requirements</TTL><BRK/>
 <NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use this paragraph only if aluminum conductors are allowed.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>When manufacturer's equipment requires copper conductors at the terminations or requires copper conductors to 
be provided between components of equipment, provide copper conductors or splices, splice boxes, and other work 
required to satisfy manufacturer's requirements.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.9.1.2   Aluminum Conductors</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  In certain instances it may be necessary to require compact stranding, 
i.e., when outside diameter of cable shall be limited.  When necessary, specify 
the following:  "Conductors shall be compact stranded utilizing method of stranding 
specified in ASTM B 400; however, conductor material shall be as specified herein."</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Aluminum conductors shall be AA-8000 series electrical grade aluminum alloy conductors.  Type EC/1350 aluminum 
is not acceptable.  Should Contractor choose to provide aluminum for conductors No. 4 AWG and larger diameter, 
Contractor shall be responsible for increasing conductor size to have same ampacity as copper size indicated; 
increasing conduit and pull box sizes to accommodate larger size aluminum conductors in accordance with <RID>NFPA 70</RID>
; ensuring that pulling tension rating of aluminum conductor is sufficient; providing panelboards[ and motor 
control centers] that are UL listed for use with aluminum, and so labeled; relocating equipment, modifying equipment 
terminations, resizing equipment; and resolving problems that are direct results of providing aluminum conductors 
in lieu of copper.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9.1.3   Minimum Conductor Sizes</TTL><BRK/>
<BRK/>
<TXT>Minimum size for branch circuits shall be No. 12 AWG; for Class 1 remote-control and signal circuits, No. 14 
AWG; for Class 2 low-energy, remote-control and signal circuits, No. 16 AWG; and for Class 3 low-energy, remote-control, 
alarm and signal circuits, No. 22 AWG.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.9.2   Color Coding</TTL><BRK/>
<BRK/>
<TXT>Provide for service, feeder, branch, control, and signaling circuit conductors.  Color shall be green for grounding 
conductors and white for neutrals; except where neutrals of more than one system are installed in same raceway 
or box, other neutrals shall be white with a different colored (not green) stripe for each.  Color of ungrounded 
conductors in different voltage systems shall be as follows:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  208/120 volt, three-phase</ITM><BRK/>
<BRK/>
<ITM>(1)  Phase A - black</ITM><BRK/>
<BRK/>
<ITM>(2)  Phase B - red</ITM><BRK/>
<BRK/>
<ITM>(3)  Phase C - blue</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  480/277 volt, three-phase</ITM><BRK/>
<BRK/>
<ITM>(1)  Phase A - brown</ITM><BRK/>
<BRK/>
<ITM>(2)  Phase B - orange</ITM><BRK/>
<BRK/>
<ITM>(3)  Phase C - yellow</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  120/240 volt, single phase:  Black and red</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">[d.  On three-phase, four-wire delta system, high leg shall be orange, as required by <RID>NFPA 70</RID>
.]</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9.3   Insulation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Be sure conduit fill calculations are based on largest diameter insulation 
type allowed.  Designer may select other insulation types which may be more 
suitable for a particular project.  For rewiring project where existing conduit 
is to be utilized, specify types THHN and THWN.  Designer should use THWN values 
(75 degrees C) for capacities of THWN/THHN.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Unless specified or indicated otherwise or required by <RID>NFPA 70</RID>, power and lighting wires shall be 600-volt,[  
Type THWN/THHN conforming to <RID>UL 83</RID>][ or][ Type[ XHHW][ or][ RHW] conforming to <RID>UL 44</RID>], except that grounding 
wire may be type TW conforming to <RID>UL 83</RID>; remote-control and signal circuits shall be Type TW or TF, conforming 
to <RID>UL 83</RID>.  Where lighting fixtures require 90-degree Centigrade (C) conductors, provide only conductors with 
90-degree C insulation or better.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9.4   Bonding Conductors</TTL><BRK/>
<BRK/>
<TXT><RID>ASTM B 1</RID>, solid bare copper wire for sizes No. 8 AWG and smaller diameter; <RID>ASTM B 8</RID>, Class B, stranded bare copper 
wire for sizes No. 6 AWG and larger diameter.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.9.4.1   Telecommunications Bonding Backbone (TBB)</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  A Telecommunication Bonding Backbone (TBB) is required between the telecommunications 
main grounding busbar (TMGB) and all telecommunications grounding busbars (TGBs).  
A TBB is not required for installation with only a single TGB or TMGB.<BRK/>
              Sizing of the TBB<BRK/>
<HL1>TBB length linear m (ft)          TBB Size (AWG)</HL1><BRK/>
 less than 4 (13)                     6<BRK/>
  4 - 6 (14 - 20)                     4<BRK/>
  6 - 8 (21 - 26)                     3<BRK/>
  8 - 10 (27 - 33)                    2<BRK/>
 10 - 13 (34 - 41)                    1<BRK/>
 13 - 16 (42 - 52)                  1/0<BRK/>
 16 - 20 (53 - 66)                  2/0<BRK/>
greater than 20 (66)                3/0<BRK/>
<BRK/>
Choose the second bracketed options where lightning protection system is provided 
in the job and specified in other sections.<BRK/>
<BRK/>
Choose insulated TBB when pathway is a dissimilar metal than copper.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide a copper conductor TBB in accordance with <RID>TIA J-STD-607-A</RID>.  The TBB shall be a minimum No. 6 AWG and 
be sized at 2 kcmil per linear foot of conductor length up to a maximum size of 3/0 AWG.[  Provide insulated 
TBB with insulation as specified in the paragraph INSULATION and meeting the fire ratings of its pathway.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9.4.2   Bonding Conductor for Telecommunications</TTL><BRK/>
<BRK/>
<TXT>Provide a copper conductor Bonding Conductor for Telecommunications between the telecommunications main grounding 
busbar (TMGB) and the electrical service ground in accordance with <RID>TIA J-STD-607-A</RID>.  The bonding conductor for 
telecommunications shall be sized the same as the TBB.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>2.9.5   Service Entrance Cables</TTL><BRK/>
<BRK/>
<TXT>Service Entrance (SE) and Underground Service Entrance (USE) Cables, <RID>UL 854</RID>.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.9.6   Nonmetallic Sheathed Cable</TTL><BRK/>
<BRK/>
<TXT><RID>UL 719</RID>, Type NM or NMC.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.9.7   Wire and Cable for 400 Hertz (Hz) Circuits</TTL><BRK/>
<BRK/>
<TXT>Insulated copper conductors.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.9.8   Metal-Clad Cable</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Type MC cable is UL listed and NFPA 70 recognized for most common building 
applications. Review NFPA 70.  MC cable does not protect conductors as well 
as rigid conduit but is more flexible to install and relocate.  For Navy projects, 
designer shall consult with NAVFAC cognizant EFD/EFA  electrical design branch 
manager and obtain written approval before specifying this wiring method.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>UL 1569</RID>; <RID>NFPA 70</RID>, Type MC cable.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.9.9   Armored Cable</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Type AC cable has more restricted applications than MC cable but offers 
the same advantages.  Review NFPA 70.  For Navy projects, consult with cognizant 
EFD/EFA electrical design branch manager and obtain written approval before 
specifying AC cable.  Do not use for EFA CHES projects without written approval.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>UL 4</RID>; <RID>NFPA 70</RID>, Type AC cable.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.9.10   Mineral-Insulated, Metal-Sheathed Cable</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Type MI cable is used for low temperature, high temperature, hazardous 
locations, life safety, and heating applications.  Refer to NFPA 70.  Drawings 
shall clearly show the MI cable. If MI cable utilized in hazardous areas is 
likely to be subject to high voltage surges, consider the use of surge suppressors 
in electrical panels serving the load from outside of the hazardous area.  Locate 
suppressors in appropriately rated enclosures within the hazardous area only 
if there is no other option.  MI cable is not available in ratings above 600 
volts.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>UL listed; <RID>NFPA 70</RID>, Type MI cable.  Sheathing containing asbestos fibers shall not be used.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.9.11   Flat Conductor Cable</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Type FCC cable has been listed by UL and recognized by NFPA 70 for under 
carpet tile applications.  Review NFPA 70.  FCC cable is available off the shelf 
for power and telecommunications transmission applications.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>UL listed; <RID>NFPA 70</RID>, Type FCC.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.9.12   Cable Tray Cable or Power Limited Tray Cable</TTL><BRK/>
<BRK/>
<TXT>UL listed; type TC or PLTC.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.9.13   Cord Sets and Power-Supply Cords</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include this paragraph when equipment utilizing cord sets is permanently 
connected to boxes in lieu of use of plug and receptacles.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>UL 817</RID>.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>2.10   SPLICES AND TERMINATION COMPONENTS</TTL><BRK/>
<BRK/>
<TXT><RID>UL 486A-486B</RID> for wire connectors and <RID>UL 510</RID> for insulating tapes.  Connectors for No. 10 AWG and smaller diameter 
wires shall be insulated, pressure-type in accordance with <RID>UL 486A-486B</RID> or <RID>UL 486C</RID> (twist-on splicing connector).  
Provide solderless terminal lugs on stranded conductors.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11   DEVICE PLATES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use last three sentences of paragraph for brig facilities only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide UL listed, one-piece device plates for outlets to suit the devices installed.  For metal outlet boxes, 
plates on unfinished walls shall be of zinc-coated sheet steel or cast metal having round or beveled edges.  
For nonmetallic boxes and fittings, other suitable plates may be provided.[  Plates on finished walls shall be 
nylon or lexan, minimum<MET> 0.792 mm</MET><ENG> 0.03 inch</ENG> wall thickness.  Plates shall be same color as receptacle or toggle 
switch with which they are mounted.][  Plates on finished walls shall be satin finish stainless steel or brushed-finish 
aluminum, minimum<MET> 0.792 mm</MET> <ENG>0.03 inch</ENG> thick.]  Screws shall be machine-type with countersunk heads in color to 
match finish of plate.  Sectional type device plates will not be permitted.  Plates installed in wet locations 
shall be gasketed and UL listed for "wet locations."[  Device plates in areas normally accessible to prisoners 
shall be brown or ivory finish nylon-device plates rated for high abuse.  <TST>Test device plates for compliance with <RID>
UL 514A</RID> and <RID>UL 514C</RID> for physical strength.</TST>  Attach device plates with spanner head bolts.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12   <SUB>SWITCHES</SUB></TTL><BRK/>
<BRK/>
<SPT><TTL>2.12.1   Toggle Switches</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Do not use solderless pressure type toggle switches on Navy projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NEMA WD 1</RID>,<RID> UL 20</RID>,[ single pole][, double pole][, three-way][, and four-way], totally enclosed with bodies of 
thermoplastic or thermoset plastic and mounting strap with grounding screw.  Handles shall be[ white][ ivory][ 
brown] thermoplastic.  Wiring terminals shall be screw-type, side-wired[ or of the solderless pressure type having 
suitable conductor-release arrangement].  Contacts shall be silver-cadmium and contact arm shall be one-piece 
copper alloy.  Switches shall be rated quiet-type ac only, 120/277 volts, with current rating and number of poles 
indicated.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12.2   Switch with Red Pilot Handle</TTL><BRK/>
<BRK/>
<TXT><RID>NEMA WD 1</RID>.  Provide pilot lights that are integrally constructed as a part of the switch's handle.  The pilot 
light shall be red and shall illuminate whenever the switch is closed or "on".  The pilot lighted switch shall 
be rated 20 amps and 120 volts or 277 volts as indicated.  Provide the circuit's neutral conductor to each switch 
with a pilot light.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12.3   Breakers Used as Switches</TTL><BRK/>
<BRK/>
<TXT>For 120- and 277-Volt fluorescent fixtures, mark breakers "SWD" in accordance with <RID>UL 489</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12.4   Disconnect Switches</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Switches requiring frequent operation should be the heavy duty-type and 
should be so indicated on the drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NEMA KS 1</RID>.  Provide heavy duty-type switches where indicated, where switches are rated higher than 240 volts, 
and for double-throw switches. Fused switches shall utilize Class R fuseholders and fuses, unless indicated otherwise.  
Switches serving as motor-disconnect means shall be horsepower rated.  Provide switches in NEMA[ 1][ 3R] [_____], 
enclosure[ as indicated] per <RID>NEMA ICS 6</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.13   <SUB>FUSES</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer shall determine the proper fuse class and type based on the 
requirements of the electrical system and the equipment serviced.  This note 
briefly summarizes some of the UL fuse standards and their application.  In 
addition to 200,000 ampere rms symmetrical UL listing, 300,000 ampere rms symmetrical 
special purpose rating has been witnessed on UL tested and certified Class RK1, 
J and Class L.</NPR><BRK/>
<BRK/>
<NPR>UL 198, Class R:  200,000 ampere, rms symmetrical interrupting rating, RK1 is 
labeled current limiting, and is available in dual-element time-delay and non-time-delay 
options.  RK5 fuses are dual-element time-delay and labeled current-limiting.  
Both RK1 and RK5 fuses are rejection type which should be used with rejection 
mounting on new equipment to satisfy high current interrupting listing by UL.  
However, these fuses may be used on existing equipment that is non-rejection 
type as a direct replacement for UL 198 fuses.</NPR><BRK/>
<BRK/>
<NPR>UL 198, Classes J, L, and CC:  200,000 ampere, rms symmetrical interrupting 
rating is available with time-delay option, is not interchangeable with any 
other UL fuse class, is labeled current-limiting, and is rated 600 volts ac.</NPR><BRK/>
<BRK/>
<NPR>UL 198, Class H:  Maximum 10,000 ampere, symmetrical interrupting rating.  Use 
only in existing equipment where the available fault is known to be less than 
10,000 amperes.</NPR><BRK/>
<BRK/>
<NPR>UL 198, Class T:  Maximum 200,000 ampere symmetrical interrupting rating.  Is 
not interchangeable with other UL fuse classes.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NEMA FU 1</RID>.  Provide complete set of fuses for each fusible[ switch][ panel][ and  control center].  Time-current 
characteristics curves of fuses serving motors or connected in series with circuit breakers[ or other circuit 
protective devices] shall be coordinated for proper operation. Submit coordination data for approval.  Fuses 
shall have voltage rating not less than circuit voltage.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.13.1   Fuseholders</TTL><BRK/>
<BRK/>
<TXT>Provide in accordance with <RID>UL 512</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.13.2   Cartridge Fuses, Current Limiting Type (Class R)</TTL><BRK/>
<BRK/>
<TXT><RID>UL 198M</RID>, Class[ RK-1][ RK-5][ time-delay type].  Associated fuseholders shall be Class R only.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.13.3   Cartridge Fuses, High-Interrupting Capacity, Current Limiting Type (Classes J, L, and CC)</TTL><BRK/>
<BRK/>
<TXT><RID>UL 198M</RID>, Class J for zero to 600 amperes, Class L for 601 to 6,000 amperes, and Class CC for zero to 30 amperes.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.13.4   Cartridge Fuses, Current Limiting Type (Class T)</TTL><BRK/>
<BRK/>
<TXT><RID>UL 198M</RID>, Class T for zero to 1,200 amperes, 300 volts; and zero to 800 amperes, 600 volts.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.14   <SUB>RECEPTACLES</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:1.  Designer will select the proper grade for the application.  Hard use 
receptacles are suitable for normal use and heavy use.  Use hospital grade receptacles 
only for those applications that exceed capabilities of hard use.<BRK/>
<BRK/>
2.  Do not use solderless pressure type receptacles on Navy projects.<BRK/>
<BRK/>
3.  Thermoplastic components provide superior resistance to impacts, chemicals 
and solvents as compared to thermoset materials.  Nylon, Polycarbonate, Polyester, 
Acrylic and Polypropylene are examples of thermoplastic material.  Phenolic. 
Urea and Melamine are examples of thermoset materials which do not provide high 
degrees of resistance to impact.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[<RID>UL 498</RID>, hard use, heavy-duty,][ <RID>UL 498</RID>, hospital grade,] grounding-type.  Ratings and configurations shall be 
as indicated.  Bodies shall be of[ white][ ivory][ brown] as per <RID>NEMA WD 1</RID>.  Face and body shall be thermoplastic 
supported on a metal mounting strap.  Dimensional requirements shall be per <RID>NEMA WD 6</RID>.  Provide screw-type, side-wired 
wiring terminals[ or of the solderless pressure type having suitable conductor-release arrangement].  Connect 
grounding pole to mounting strap.  The receptacle shall contain triple-wipe power contacts and double or triple-wipe 
ground contacts.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.14.1   Switched Duplex Receptacles</TTL><BRK/>
<BRK/>
<TXT>Provide separate terminals for each ungrounded pole.  Top receptacle shall be switched when installed.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.2   Weatherproof Receptacles</TTL><BRK/>
<BRK/>
<TXT>Provide in cast metal box with gasketed, weatherproof, cast-metal cover plate and gasketed cap over each receptacle 
opening.  Provide caps with a spring-hinged flap.  Receptacle shall be UL listed for use in "wet locations with 
plug in use."</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.3   Ground-Fault Circuit Interrupter Receptacles</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For LANTNAVFACENGCOM projects, use GFI terminology in lieu of GFCI.  
For child care center projects, coordinate project drawings and specifications 
to include GFCI/GFI for receptacles in bathrooms, kitchens, laundry facilities, 
exterior locations, and swimming pools.  NAVFACENGCOM has established these 
GFCI/GFI safety standards for child care centers at a higher level of protection 
than NFPA 70's minimum requirements as a result of a GAO report and DOD concern 
about health and safety at these facilities.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>UL 943</RID>, duplex type for mounting in standard outlet box.  Device shall be capable of detecting current leak of 
6 milliamperes or greater and tripping per requirements of <RID>UL 943</RID> for Class A[ GFCI][ GFI] devices.   Provide 
screw-type, side-wired wiring terminals or pre-wired (pigtail) leads.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.4   Special Purpose Receptacles</TTL><BRK/>
<BRK/>
<TXT>Receptacles serving [_____] are special purpose.[  Provide in ratings indicated.][  NEMA [_____] configuration, 
rated [_____] amperes, [_____] volts.][  Furnish one matching plug with each receptacle.]</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.14.5   Plugs</TTL><BRK/>
<BRK/>
<TXT>Provide heavy-duty, rubber-covered[ three-,][ four-,][ or][ five-]wire cord of required size, install plugs thereon, 
and attach to equipment.  Plugs shall be UL listed with receptacles, complete with grounding blades.  Where equipment 
is not available, turn over plugs and cord assemblies to the Government.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.14.6   Range Receptacles</TTL><BRK/>
<BRK/>
<TXT>NEMA 14-50 configuration,[ flush mounted for housing units,] rated 50 amperes, 125/250 volts.[  Furnish one matching 
plug with each receptacle.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.7   Dryer Receptacles</TTL><BRK/>
<BRK/>
<TXT>NEMA 14-30 configuration, rated 30 amperes, 125/250 volts.[  Furnish one matching plug with each receptacle.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.14.8   Tamper-Resistant Receptacles</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The NFPA 70 defines a tamper-resistant receptacle as one which by its 
construction limits improper access to its energized parts.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide duplex receptacle with mechanical sliding shutters that prevent the insertion of small objects into its 
contact slots.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.15   <SUB>PANELBOARDS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For residential applications, use paragraph RESIDENTIAL LOAD CENTERS 
or LOAD CENTERS FOR HOUSING UNITS instead of PANELBOARDS unless required by 
the local Activity. </NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For LANTNAVFACENGCOM projects, use the first bracketed paragraph.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[<RID>UL 67</RID> and <RID>UL 50</RID> having a short-circuit current rating[ as indicated][ of 10,000 amperes symmetrical minimum].  
Panelboards for use as service disconnecting means shall additionally conform to <RID>UL 869A</RID>.  Panelboards shall 
be circuit breaker-equipped[ unless indicated otherwise].  Design shall be such that individual breakers can 
be removed without disturbing adjacent units or without loosening or removing supplemental insulation supplied 
as means of obtaining clearances as required by UL.  "Specific breaker placement" is required in panelboards 
to match the breaker placement indicated in the panelboard schedule on the drawings.  Use of "Subfeed Breakers" 
is not acceptable unless specifically indicated otherwise.  Main breaker shall be "separately" mounted[ "above"][ 
or][ "below"] branch breakers.  Where "space only" is indicated, make provisions for future installation of breakers.  
Directories shall indicate load served by each circuit in panelboard.  Directories shall also indicate source 
of service to panelboard (e.g., Panel PA served from Panel MDP).[  Provide new directories for existing panels 
modified by this project as indicated.]  Type directories and mount in holder behind transparent protective covering.[  
Panelboards shall be listed and labeled for their intended use.]  Panelboard shall have nameplates in accordance 
with paragraph FIELD FABRICATED NAMEPLATES.]</TXT><BRK/>
<BRK/>
<TXT>[<RID>UL 67</RID> and <RID>UL 50</RID>.  Panelboards for use as service disconnecting means shall additionally conform to <RID>UL 869A</RID>.  
Panelboards shall be circuit breaker-equipped.  Design shall be such that individual breakers can be removed 
without disturbing adjacent units or without loosening or removing supplemental insulation supplied as means 
of obtaining clearances as required by UL.  Where "space only" is indicated, make provisions for future installation 
of breaker sized as indicated.  Directories shall indicate load served by each circuit of panelboard.  Directories 
shall also indicate source of service (upstream panel, switchboard, motor control center, etc.) to panelboard.  
Type directories and mount in holder behind transparent protective covering.  Panelboard shall have nameplates 
in accordance with paragraph FIELD FABRICATED NAMEPLATES.]</TXT><BRK/>
<BRK/>
<SPT><TTL>2.15.1   Enclosure</TTL><BRK/>
<BRK/>
<TXT>Enclosures shall meet the requirements of <RID>UL 50</RID>.  All cabinets shall be fabricated from sheet steel of not less 
than <MET>3.5 millimeters (No. 10 gauge</MET><ENG> No. 10 gauge</ENG> if flush-mounted or mounted outdoors, and not less than<MET> 2.7 millimeters 
(No. 12 gauge)</MET><ENG> No. 12 gauge</ENG> if surface-mounted indoors, with full seam-welded box ends.  Cabinets mounted outdoors 
or flush-mounted shall be hot-dipped galvanized after fabrication.  Cabinets shall be painted in accordance with 
paragraph PAINTING.  Outdoor cabinets shall be of NEMA 3R raintight with[ conduit hubs welded to the cabinet][ 
a removable steel plate<MET> 7 millimeters (1/4 inch)</MET><ENG> 1/4 inch</ENG> thick in the bottom for field drilling for conduit 
connections].  Front edges of cabinets shall be form-flanged or fitted with structural shapes welded or riveted 
to the sheet steel, for supporting the panelboard front.  All cabinets shall be so fabricated that no part of 
any surface on the finished cabinet shall deviate from a true plane by more than<MET> 3 millimeters (1/8 inch)</MET><ENG> 1/8 
inch</ENG>.  Holes shall be provided in the back of indoor surface-mounted cabinets, with outside spacers and inside 
stiffeners, for mounting the cabinets with a<MET> 15 millimeter (1/2 inch)</MET><ENG> 1/2 inch</ENG> clear space between the back of 
the cabinet and the wall surface.  Flush doors shall be mounted on hinges that expose only the hinge roll to 
view when the door is closed.  Each door shall be fitted with a combined catch and lock, except that doors over<MET>
 600 millimeters (24 inches)</MET><ENG> 24 inches</ENG> long shall be provided with a three-point latch having a knob with a T-handle, 
and a cylinder lock.  Two keys shall be provided with each lock, and all locks shall be keyed alike.  Finished-head 
cap screws shall be provided for mounting the panelboard fronts on the cabinets.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.2   Panelboard Buses</TTL><BRK/>
<BRK/>
<TXT>Support bus bars on bases independent of circuit breakers.  Main buses and back pans shall be designed so that 
breakers may be changed without machining, drilling, or tapping.  Provide isolated neutral bus in each panel 
for connection of circuit neutral conductors.  Provide separate ground bus identified as equipment grounding 
bus per <RID>UL 67</RID> for connecting grounding conductors; bond to steel cabinet.[  In addition to equipment grounding 
bus, provide second "isolated" ground bus, where indicated.]</TXT><BRK/>
<BRK/>
<SPT>[<TTL>2.15.2.1   Panelboard Neutrals for Non-Linear Loads</TTL><BRK/>
<BRK/>
<TXT>UL listed, and panelboard type shall have been specifically UL heat rise tested for use on non-linear loads.  
Panelboard shall be heat rise tested in accordance with <RID>UL 67</RID>, except with the neutral assembly installed and 
carrying 200 percent of the phase bus current during testing.  Verification of the testing procedure shall be 
provided upon request.  Two neutral assemblies paralleled together with cable is not acceptable.  Nameplates 
for panelboard rated for use on non-linear loads shall be marked "SUITABLE FOR NON-LINEAR LOADS"and shall be 
in accordance with paragraph FIELD FABRICATED NAMEPLATES.  Provide a neutral label with instructions for wiring 
the neutral of panelboards rated for use on non-linear loads.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>2.15.3   <SUB>Circuit Breakers</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For most applications, plug-in circuit breakers are not permitted, and 
the last sentence is required.</NPR><BRK/>
<BRK/>
<NPR>For residential applications, paragraph RESIDENTIAL LOAD CENTERS or LOAD CENTERS 
FOR HOUSING UNITS should be used instead of PANELBOARDS unless panelboards with 
bolt-on breakers are required by the local Activity.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For LANTNAVFACENGCOM projects, use the second bracketed last sentence 
of the paragraph.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>UL 489</RID>,[ thermal magnetic-type][ solid state-type] having a minimum short-circuit current rating equal to the 
short-circuit current rating of the panelboard in which the circuit breaker shall be mounted.  Breaker terminals 
shall be UL listed as suitable for type of conductor provided.[  Where indicated on the drawings, provide circuit 
breakers with shunt trip devices.][  Series rated circuit breakers and plug-in circuit breakers without a self-contained 
bracket and not secured by a positive locking device requiring mechanical release for removal are unacceptable.][  
Series rated circuit breakers and plug-in circuit breakers are unacceptable.]</TXT><BRK/>
<BRK/>
<SPT><TTL>2.15.3.1   Multipole Breakers</TTL><BRK/>
<BRK/>
<TXT>Provide common trip-type with single operating handle.  Breaker design shall be such that overload in one pole 
automatically causes all poles to open.  Maintain phase sequence throughout each panel so that any three adjacent 
breaker poles are connected to Phases A, B, and C, respectively.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.3.2   Circuit Breaker With[ GFCI][ GFI]</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For LANTNAVFACENGCOM projects, use GFI terminology in lieu of GFCI.  
For child care center projects, coordinate project drawings and specifications 
to include GFCI/GFI for receptacles in bathrooms, kitchens, laundry facilities, 
exterior locations, and swimming pools.  NAVFACENGCOM has established these 
GFCI/GFI safety standards for child care centers at a higher level of protection 
than NFPA 70's minimum requirements as a result of a GAO report and DOD concern 
about health and safety at these facilities.  NFPA requires GFCI/GFI equipment 
protection at a higher MA level on certain exterior circuits.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>UL 943</RID> and <RID>NFPA 70</RID>.  Provide with "push-to-test" button, visible indication of tripped condition, and ability 
to detect and trip on current imbalance of[ 6 milliamperes or greater per requirements of <RID>UL 943</RID> for Class A[ 
GFCI][ GFI] devices, for personnel protection,][ and][ 20 milliamperes or greater per requirements of <RID>UL 943</RID> 
for Class B[ GFCI][ GFI] per equipment protection.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.3.3   Circuit Breakers for HVAC Equipment</TTL><BRK/>
<BRK/>
<TXT>Circuit breakers for HVAC equipment having motors (group or individual) shall be marked for use with HACR type 
and UL listed as HACR type.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.15.3.4   Arc-Fault Circuit-Interrupters</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  NFPA 70 requires that all branch circuits that supply 125 volt, single 
phase, 15 and 20 ampere outlets (receptacles, luminaires, smoke detectors etc) 
installed in dwelling unit bedrooms shall be protected by an arc-fault circuit-interrupter 
to provide protection to the entire branch circuit.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The one pole arc-fault circuit-interrupter is not designed for use on 
circuits in which the neutral conductor is shared with other circuits (defined 
as a multiwire branch circuit in NFPA 70) and will nuisance trip on shared neutral 
circuits.  Provide and indicate on the drawings one pole arc-fault circuit-interrupter 
breakers for each circuit, and do not use shared neutral for these circuits 
in new construction projects.  Where wiring is existing and not replaced and 
where a shared neutral exists, a two pole, 120/240 volt arc-fault circuit-interrupter 
for shared neutral circuits may be required.  It may also be required in new 
construction if 120/240 volt equipment or circuit is located in the bedroom.  
Coordinate the requirement with the cognizant Activity or EFD/EFA.</NPR><BRK/>
<AST/><BRK/>
 </NTE><BRK/>
<TXT><RID>UL 489</RID>, <RID>UL 1699</RID> and <RID>NFPA 70</RID>.  Molded case circuit breaker shall be rated as indicated.[  Two pole arc-fault circuit-interrupters 
shall be rated 120/240 volts.  The provision of (two) one pole circuit breakers for shared neutral circuits in 
lieu of (one) two pole circuit breaker is unacceptable.]  Provide with "push-to-test" button.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>2.15.4   Fusible Switches for Panelboards</TTL><BRK/>
<BRK/>
<TXT><RID>NEMA KS 1</RID>, hinged door-type.  Switches serving as motor disconnect means shall be<MET> kilowatt (horsepower)</MET><ENG> horsepower</ENG>
 rated.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.15.5   400 Hz Panelboard and Breakers</TTL><BRK/>
<BRK/>
<TXT>Panelboards and breakers for use on 400 Hz systems shall be "400 Hz" rated and labeled.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT>[<TTL>2.16   <SUB>RESIDENTIAL LOAD CENTERS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use the following paragraph and subparagraphs in lieu of the paragraph 
PANELBOARD and its subparagraphs if designer has chosen to specify residential 
load centers in the design.  Load centers are permitted only for family housing 
construction/repair projects.  Delete for other projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide residential load centers (RLCs), conforming to <RID>UL 67</RID> and <RID>UL 50</RID>.  RLCs for use as service disconnecting 
means shall additionally conform to <RID>UL 869A</RID>.  RLCs shall be circuit breaker equipped.  Design shall be such that 
individual breakers can be removed without disturbing adjacent units or without loosening or removing supplemental 
insulation supplied as means of obtaining clearances as required by UL.  Where "space only" is indicated, make 
provisions for future installation of breakers sized as indicated.[  Load centers shall have keyed locks.]  Printed 
directories shall be provided.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.16.1   RLC Buses</TTL><BRK/>
<BRK/>
<TXT>Support bus bars on bases independent of circuit breakers.  Main buses and back pans shall be designed so that 
breakers may be changed without machining, drilling, or tapping.  Provide isolated groundable neutral bus in 
each panel for connection of circuit neutral conductors.  Provide separate ground bus identified as equipment 
grounding bus per <RID>UL 67</RID> for connecting grounding conductors; bond to steel cabinet.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.16.2   <SUB>Circuit Breakers</SUB></TTL><BRK/>
<BRK/>
<TXT><RID>UL 489</RID>, thermal magnetic-type with interrupting capacity[ as indicated][ of 10,000 minimum amperes rms symmetrical].  
Breaker terminals shall be UL listed as suitable for the type of conductor provided.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.16.2.1   Multipole Breakers</TTL><BRK/>
<BRK/>
<TXT>Provide common trip-type with single operating handle.  Breaker design shall be such that overload in one pole 
automatically causes all poles to open.  Maintain phase sequence throughout each panel so that any two adjacent 
breaker poles are connected to alternate phases in sequence.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.16.2.2   Circuit Breaker With[ GFCI][ GFI]</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include GFCI for receptacles in bathrooms, kitchens, garages, unfinished 
basements, and exterior locations in accordance with NFPA 70.  Use GFI terminology 
for LANTNAVFACENGCOM.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>UL 943</RID> and <RID>NFPA 70</RID>.  Provide with "push-to-test" button, visible indication of tripped condition, and ability 
to detect and trip on current imbalance of 6 milliamperes or greater per requirements of <RID>UL 943</RID> for Class A[  
GFCI][ GFI] devices.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.16.2.3   Arc-Fault Circuit-Interrupters</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  NFPA 70 requires that all branch circuits that supply 125 volt, single 
phase, 15 and 20 ampere outlets (receptacles, luminaires, smoke detectors etc) 
installed in dwelling unit bedrooms (family housing) shall be protected by an 
arc-fault circuit-interrupter to provide protection to the entire branch circuit.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The one pole arc-fault circuit-interrupter is not designed for use on 
circuits in which the neutral conductor is shared with other circuits (defined 
as a multiwire branch circuit in NFPA 70) and will nuisance trip on shared neutral 
circuits.  Provide and indicate on the drawings one pole arc-fault circuit-interrupter 
breakers for each circuit, and do not use shared neutral for these circuits 
in new construction projects.  Where wiring is existing and not replaced and 
where a shared neutral exists, a two pole, 120/240 volt arc-fault circuit-interrupter 
for shared neutral circuits may be required.  It may also be required in new 
construction if 120/240 volt equipment or circuit is located in the bedroom.  
Coordinate the requirement with the cognizant Activity or EFD/EFA.</NPR><BRK/>
<AST/><BRK/>
 </NTE><BRK/>
<TXT><RID>UL 489</RID>, <RID>UL 1699</RID> and <RID>NFPA 70</RID>.  Molded case circuit breaker shall be rated as indicated.[  Two pole arc-fault circuit-interrupters 
shall be rated 120/240 volts.  The provision of (two) one pole circuit breakers for shared neutral circuits in 
lieu of (one) two pole circuit breaker is unacceptable.]  Provide with "push-to-test" button.</TXT><BRK/>
<BRK/></SPT>
</SPT>]</SPT><SPT>[<TTL>2.17   <SUB>LOAD CENTERS FOR HOUSING UNITS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use the following only for single phase, residential panelboards on LANTNAVFACENGCOM 
projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Single-phase panelboards for housing units on this project shall be load center type, circuit breaker equipped, 
conforming to <RID>UL 67</RID> and <RID>UL 50</RID>.  Panelboards shall have a series short-circuit current rating of 22,000 amperes 
symmetrical minimum for the main breaker and the branch breakers.  Panelboards for use as service disconnecting 
means shall additionally conform to <RID>UL 869A</RID>.  Design shall be such that individual breakers can be removed without 
disturbing adjacent units or without loosening or removing supplemental insulation supplied as means of obtaining 
clearances as required by UL.  "Specific breaker placement" is required in panelboards to match the breaker placement 
indicated in the panelboard schedule on the drawings.  Where "space only" is indicated, make provisions for future 
installation of breakers.  Provide cover with latching door.  Directories shall indicate load served by each 
circuit in panelboard.  Directories shall also indicate source of service to panelboard (e.g., Panel PA served 
from panel MDP).  Type directories and mount behind transparent protective covering on inside of panel door in 
a manner approved by the Contracting Officer.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.17.1   Panelboard Buses</TTL><BRK/>
<BRK/>
<TXT>Support bus bars on bases independent of circuit breakers.  Main buses and back pans shall be designed so that 
breakers may be changed without machining, drilling, or tapping.  Bus bars shall be copper or aluminum, and shall 
be tin plated or silver plated.  Provide isolated neutral bus in each panel for connection of circuit neutral 
conductors.  Provide separate ground bus identified as equipment grounding bus per <RID>UL 67</RID> for connecting grounding 
conductors; bond to steel cabinet.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.17.2   <SUB>Circuit Breakers</SUB></TTL><BRK/>
<BRK/>
<TXT><RID>UL 489</RID> thermal magnetic type having a minimum short-circuit current rating equal to the short-circuit current 
rating of the panelboard in which the circuit breaker will be mounted.  Breaker terminals shall be UL listed 
as suitable for type of conductor provided.  Half-size and tandem breakers are not acceptable.  15 and 20 ampere 
breakers shall be switch duty rated.  Breakers shall not require use of panel trim to secure them to the bus.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.17.2.1   Multipole Breakers</TTL><BRK/>
<BRK/>
<TXT>Provide common trip-type with single operating handle.  Breaker design shall be such that overload in one pole 
automatically causes all poles to open.  Maintain phase sequence throughout each panel so that any two adjacent 
breaker poles are connected to Phases A and B respectively.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.17.2.2   Arc-Fault Circuit-Interrupters</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  NFPA 70 requires that all branch circuits that supply 125 volt, single 
phase, 15 and 20 ampere outlets (receptacles, luminaires, smoke detectors etc) 
installed in dwelling unit bedrooms (family housing) shall be protected by an 
arc-fault circuit-interrupter to provide protection to the entire branch circuit.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The one pole arc-fault circuit-interrupter is not designed for use on 
circuits in which the neutral conductor is shared with other circuits (defined 
as a multiwire branch circuit in NFPA 70) and will nuisance trip on shared neutral 
circuits.  Provide and indicate on the drawings one pole arc-fault circuit-interrupter 
breakers for each circuit, and do not use shared neutral for these circuits 
in new construction projects.  Where wiring is existing and not replaced and 
where a shared neutral exists, a two pole, 120/240 volt arc-fault circuit-interrupter 
for shared neutral circuits may be required.  It may also be required in new 
construction if 120/240 volt equipment or circuit is located in the bedroom.  
Coordinate the requirement with the cognizant Activity or EFD/EFA.</NPR><BRK/>
<AST/><BRK/>
 </NTE><BRK/>
<TXT><RID>UL 489</RID>, <RID>UL 1699</RID> and <RID>NFPA 70</RID>.  Molded case circuit breaker shall be rated as indicated.[  Two pole arc-fault circuit-interrupters 
shall be rated 120/240 volts.  The provision of (two) one pole circuit breakers for shared neutral circuits in 
lieu of (one) two pole circuit breaker is unacceptable.]  Provide with "push-to-test" button.</TXT><BRK/>
<BRK/></SPT>
</SPT>]</SPT><SPT><TTL>2.18   <SUB>ENCLOSED CIRCUIT BREAKERS</SUB></TTL><BRK/>
<BRK/>
<TXT><RID>UL 489</RID>.  Individual molded case circuit breakers with voltage and continuous current ratings, number of poles, 
overload trip setting, and short circuit current interrupting rating as indicated.  Enclosure type as indicated.[  
Provide solid neutral.]</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.19   MOTOR SHORT-CIRCUIT PROTECTOR (MSCP)</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  MSCPs, also called motor circuit protectors (MCPs), are components of 
combination motor controllers rather than fuses or circuit breakers and are 
permitted if the motor short-circuit protector is part of a listed combination 
motor controller.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Motor short-circuit protectors, also called motor circuit protectors (MCPs); shall conform to <RID>UL 508</RID> and <RID>UL 489</RID>
 and shall be provided as shown.  MSCPs shall consist of an adjustable instantaneous trip circuit breaker used 
only in conjunction with a combination motor controller which provides coordinated motor branch-circuit overload 
and short-circuit protection.  MSCPs shall be rated in accordance with the requirements of <RID>NFPA 70</RID>.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.20   <SUB>TRANSFORMERS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate the location of dry-type transformers with the mechanical 
designer to ensure adequate ventilation.  This specification does not apply 
to transformers over 500 kVA, substation transformers, and transformers rated 
greater than 600 volts; for these types, see Section 26 12 19.10 THREE-PHASE 
PAD-MOUNTED TRANSFORMERS, Section 26 12 19.20 SINGLE-PHASE PAD-MOUNTED TRANSFORMERS, 
or Section 26 11 16 SECONDARY UNIT SUBSTATION FOR ALL PROJECTS; or Section 26 
11 13.00 20 PRIMARY UNIT SUBSTATION for Navy projects; or Section 26 11 14.00 
10 MAIN ELECTRIC SUPPLY STATION AND SUBSTATION for Army projects. Specify 80 
C or 115 C transformers when transformer is loaded above 60 percent of nameplate 
and has continuous duty cycle.   Delete quiet type where noise level does not 
affect personnel.  Relative to noise: the least desirable location for the transformer 
is in a corner of a room, especially when there is a low ceiling.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NEMA ST 20</RID>, general purpose, dry-type, self-cooled,[ ventilated][ unventilated][ sealed].  Provide transformers 
in NEMA[ 1][ 3R][_____] enclosure.  Transformer shall have 220 degrees C insulation system for transformers 15 
kVA and greater, and shall have 180 degrees C insulation for transformers rated 10 kVA and less, with temperature 
rise not exceeding[ 150][ 115][ 80] degrees C under full-rated load in maximum ambient of 40 degrees C.[   Transformer 
of 150 degrees C temperature rise shall be capable of carrying continuously 100 percent of nameplate kVA without 
exceeding insulation rating.][  Transformer of 115 degrees C temperature rise shall be capable of carrying continuously 
115 percent of nameplate kVA without exceeding insulation rating.][  Transformer of 80 degrees C temperature 
rise shall be capable of carrying continuously 130 percent of nameplate kVA without exceeding insulation rating.][  
Transformers shall be quiet type with maximum sound level at least 3 decibels less than NEMA standard level for 
transformer ratings indicated.]</TXT><BRK/>
<BRK/>
<SPT><TTL>2.20.1   Specified Transformer Efficiency</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Energy Star or energy efficient transformers are generally only available 
in ventilated enclosures, and not available in K-rated or quiet types.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Transformers, indicated and specified with:  480V primary, 80 degrees C or 115 degrees C temperature rise, kVA 
ratings of 37.5 to 100 for single phase or 30 to 500 for three phase, shall be energy efficient type.  Minimum 
efficiency, based on factory test results, shall not be less than NEMA Class 1 efficiency as defined by <RID>NEMA TP 1</RID>
.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.20.2   Transformers With Non-Linear Loads</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Analysis of the connected loads shall be made to determine the harmonic 
contents and the appropriate K-Factor rating.  K-Factor is defined as the sum 
from h=1 to infinity of I<SBS>h</SBS>(pu)<SPS>2</SPS>h<SPS>2</SPS> where I<SBS>h</SBS>(pu) is the rms current at harmonic 
"h" (per unit of rated rms load current) and h is the harmonic order.  Use K-4 
rating when connected loads are comprised of a large number of 100 percent non-linear 
single phase electronic equipment.  Use K-13 rating when connected loads are 
comprised of single, large electronic loads, or small numbers of comparatively 
large single phase loads (i.e. mainframe computers or on-line UPS systems).  
Caution should be used in specifying K-ratings above K-13, as the impedance 
generally decreases as the K-ratings increase.  Impedances below 3 percent are 
not recommended for computer loads connected to transformers with high K-ratings, 
as even higher neutral currents could result and possibly cause malfunctions 
or damage sensitive load equipment.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Transformer insulation shall be a UL recognized 220 degrees C system.  Neither the primary nor the secondary 
temperature shall exceed 220 degrees C at any point in the coils while carrying their full rating of non-sinusoidal 
load.  Transformers are to be UL listed and labeled for[ K-4][ K-9][ K-13][ K-Factor rating as indicated] in 
accordance with <RID>UL 1561</RID>.  Transformers evaluated by the UL K-Factor evaluation shall be listed for[ 115][ 80] 
degrees C average temperature rise only.  Transformers with K-Factor ratings with temperature rise of 150 degrees 
C rise shall not be acceptable.  K-Factor rated transformers shall have an impedance range of 3 percent to 5 
percent, and shall have a minimum reactance of 2 percent to prevent excessive neutral current when supplying 
loads with large amounts of third harmonic.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>2.21   MOTORS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Motor and motor controller specifications shall be thoroughly coordinated 
with and cross-referenced in all affected mechanical sections. UFC 3-410-01FA, 
HEATING, VENTILATING, AND AIR CONDITIONING, provides application data on motors 
and controllers.<BRK/></NPR>
<BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NEMA MG 1</RID>[ except fire pump motors shall be as specified in Section <SRF>21 30 00</SRF>] FIRE PUMPS; hermetic-type sealed 
motor compressors shall also comply with <RID>UL 984</RID>.  Provide the size in terms of<MET> kW</MET><ENG> HP</ENG>, or kVA, or full-load current, 
or a combination of these characteristics, and other characteristics, of each motor as indicated or specified.  
Determine specific motor characteristics to ensure provision of correctly sized starters and overload heaters.  
Motors for operation on 208-volt, 3-phase circuits shall have terminal voltage rating of 200 volts, and those 
for operation on 480-volt, 3-phase circuits shall have terminal voltage rating of 460 volts.  Motors shall be 
designed to operate at full capacity with voltage variation of plus or minus 10 percent of motor voltage rating.  
Unless otherwise indicated, motors rated<MET> 745 Watts (1 HP)</MET><ENG> 1 HP</ENG> and above shall be continuous duty type.</TXT><BRK/>
<BRK/>
<TXT>Where fuse protection is specifically recommended by the equipment manufacturer, provide fused switches in lieu 
of non-fused switches indicated.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.21.1   High Efficiency Single-Phase Motors</TTL><BRK/>
<BRK/>
<TXT>Single-phase fractional-horsepower alternating-current motors shall be high efficiency types corresponding to 
the applications listed in <RID>NEMA MG 11</RID>.  In exception, for motor-driven equipment with a minimum seasonal or overall 
efficiency rating, such as a SEER rating, provide equipment with motor to meet the overall system rating indicated.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.21.2   Premium Efficiency Polyphase Motors</TTL><BRK/>
<BRK/>
<TXT>Polyphase motors shall be selected based on high efficiency characteristics relative to typical characteristics 
and applications as listed in <RID>NEMA MG 10</RID>.  In addition, continuous rated, polyphase squirrel-cage medium induction 
motors shall meet the requirements for premium efficiency electric motors in accordance with <RID>NEMA MG 1</RID>, including 
the NEMA full load efficiency ratings.  In exception, for motor-driven equipment with a minimum seasonal or overall 
efficiency rating, such as a SEER rating, provide equipment with motor to meet the overall system rating indicated.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.21.3   Motor Sizes</TTL><BRK/>
<BRK/>
<TXT>Provide size for duty to be performed, not exceeding the full-load nameplate current rating when driven equipment 
is operated at specified capacity under most severe conditions likely to be encountered.  When motor size provided 
differs from size indicated or specified, make adjustments to wiring, disconnect devices, and branch circuit 
protection to accommodate equipment actually provided.  Provide controllers for motors rated 1-hp and above with 
electronic phase-voltage monitors designed to protect motors from phase-loss, undervoltage, and overvoltage.  
Provide protection for motors from immediate restart by a time adjustable restart relay.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.21.4   Wiring and Conduit</TTL><BRK/>
<BRK/>
<TXT>Provide internal wiring for components of packaged equipment as an integral part of the equipment.  Provide power 
wiring and conduit for field-installed equipment[, and motor control equipment forming part of motor control 
centers or switchgear assemblies, the conduit and wiring connecting such centers, assemblies, or other power 
sources to equipment] as specified herein.  Power wiring and conduit shall conform to the requirements specified 
herein.  Control wiring shall be provided under, and conform to the requirements of the section specifying the 
associated equipment.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.22   <SUB>MOTOR CONTROLLERS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Motor and motor controller specifications shall be thoroughly coordinated 
with and cross-referenced in all affected mechanical sections.  UFC 3-410-01FA, 
HEATING, VENTILATING, AND AIR CONDITIONING provides application data on motors 
and controllers.  Indicate NEMA size of controller on mechanical drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>UL 508</RID>, <RID>NEMA ICS 1</RID>, and <RID>NEMA ICS 2</RID>,[ except fire pump controllers shall be as specified in Section <SRF>21 30 00</SRF> FIRE 
PUMPS].  Controllers shall have thermal overload protection in each phase and shall have one spare normally open 
and one spare normally closed auxiliary contact.  Provide controllers for motors rated 1-hp and above with electronic 
phase-voltage monitors designed to protect motors from phase-loss, undervoltage, and overvoltage.  Provide protection 
for motors from immediate restart by a time adjustable restart relay.  Magnetic-type motor controllers shall 
have undervoltage protection when used with momentary-contact pushbutton stations or switches and shall have 
undervoltage release when used with maintained-contact pushbutton stations or switches.  When used with pressure, 
float, or similar automatic-type or maintained-contact switch, controller shall have hand/off/automatic selector 
switch.  Connections to selector switch shall be such that only normal automatic regulatory control devices are 
bypassed when switch is in "hand" position.  Safety control devices, such as low and high pressure cutouts, high 
temperature cutouts, and motor overload protective devices, shall be connected in motor control circuit in "hand" 
and "automatic" positions.  Control circuit connections to hand/off/automatic selector switch or to more than 
one automatic regulatory control device shall be made in accordance with indicated or manufacturer's approved 
wiring diagram.[  Selector switch shall have means for locking in any position.]  For each motor not in sight 
of controller or where controller disconnecting means is not in sight of motor location and driven machinery 
location, controller disconnecting means shall be capable of being locked in open position.  As an alternative, 
provide a manually operated, lockable, nonfused switch which disconnects motor from supply source within sight 
of motor.  Overload protective devices shall provide adequate protection to motor windings; be thermal inverse-time-limit 
type; and include manual reset-type pushbutton on outside of motor controller case.  Cover of combination motor 
controller and manual switch or circuit breaker shall be interlocked with operating handle of switch or circuit 
breaker so that cover cannot be opened unless handle of switch or circuit breaker is in "off" position.[  Minimum 
short circuit withstand rating of combination motor controller shall be [_____] rms symmetrical amperes.][  Provide 
controllers in hazardous locations with classifications as indicated].</TXT><BRK/>
<BRK/>
<SPT><TTL>2.22.1   Control Wiring</TTL><BRK/>
<BRK/>
<TXT>All control wire shall be stranded tinned copper switchboard wire with 600-volt flame-retardant insulation Type 
SIS meeting <RID>UL 44</RID>, or Type MTW meeting <RID>UL 1063</RID>, and shall pass the VW-1 flame tests included in those standards.  
Hinge wire shall have Class K stranding.  Current transformer secondary leads shall be not smaller than No. 10 
AWG.  The minimum size of control wire shall be No. 14 AWG.  Power wiring for 480-volt circuits and below shall 
be of the same type as control wiring and the minimum size shall be No. 12 AWG.  Special attention shall be given 
to wiring and terminal arrangement on the terminal blocks to permit the individual conductors of each external 
cable to be terminated on adjacent terminal points.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.22.2   Control Circuit Terminal Blocks</TTL><BRK/>
<BRK/>
<TXT><RID>NEMA ICS 4</RID>.  Control circuit terminal blocks for control wiring shall be molded or fabricated type with barriers, 
rated not less than 600 volts.  The terminals shall be removable binding, fillister or washer head screw type, 
or of the stud type with contact and locking nuts.  The terminals shall be not less than No. 10 in size and shall 
have sufficient length and space for connecting at least two indented terminals for 10 AWG conductors to each 
terminal.  The terminal arrangement shall be subject to the approval of the Contracting Officer and not less 
than four (4) spare terminals or 10 percent, whichever is greater, shall be provided on each block or group of 
blocks.  Modular, pull apart, terminal blocks will be acceptable provided they are of the channel or rail-mounted 
type.  The Contractor shall submit data showing that the proposed alternate will accommodate the specified number 
of wires, are of adequate current-carrying capacity, and are constructed to assure positive contact between current-carrying 
parts.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.22.2.1   Types of Terminal Blocks</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Short-Circuiting Type:  Short-circuiting type terminal blocks shall be furnished for all 
current transformer secondary leads and shall have provision for shorting together all leads 
from each current transformer without first opening any circuit.  Terminal blocks shall meet 
the requirements of paragraph CONTROL CIRCUIT TERMINAL BLOCKS above.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Load Type:  Load terminal blocks rated not less than 600 volts and of adequate capacity 
shall be provided for the conductors for NEMA Size 3 and smaller motor controllers and for other 
power circuits, except those for feeder tap units.  The terminals shall be of either the stud 
type with contact nuts and locking nuts or of the removable screw type, having length and space 
for at least two indented terminals of the size required on the conductors to be terminated.  
For conductors rated more than 50 amperes, screws shall have hexagonal heads.  Conducting parts 
between connected terminals shall have adequate contact surface and cross-section to operate 
without overheating.  Each connected terminal shall have the circuit designation or wire number 
placed on or near the terminal in permanent contrasting color.</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.22.3   Control Circuits</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Choose one of the following options.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Control circuits shall have maximum voltage of 120 volts derived from control transformer in same enclosure.  
Transformers shall conform to <RID>UL 506</RID>, as applicable.  Transformers, other than transformers in bridge circuits, 
shall have primaries wound for voltage available and secondaries wound for correct control circuit voltage.  
Size transformers so that 80 percent of rated capacity equals connected load.  Provide disconnect switch on primary 
side.[  Provide fuses in each ungrounded primary feeder].  One secondary lead shall be fused; other shall be 
grounded.[  For designated systems, as indicated, provide backup power supply, including transformers connected 
to[ emergency power source][_____].  Provide for automatic switchover and alarm upon failure of primary control 
circuit.]]</TXT><BRK/>
<BRK/>
<TXT>[Control circuits shall have maximum voltage of 120 volts derived from a separate control source.  Provide terminals 
and terminal boards.  Provide separate control disconnect switch within controller.  One secondary lead shall 
be fused; other shall be grounded.[  For designated systems, as indicated, provide backup power supply, including 
connection to[ emergency power source][_____].  Provide for automatic switchover and alarm upon failure of primary 
control circuit.]]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.22.4   Enclosures for Motor Controllers</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Indicate NEMA type of enclosure on the mechanical drawing to suit the 
application.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NEMA ICS 6</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.22.5   Multiple-Speed Motor Controllers and Reversible Motor Controllers</TTL><BRK/>
<BRK/>
<TXT>Across-the-line-type, electrically and mechanically interlocked.  Multiple-speed controllers shall have compelling 
relays and shall be multiple-button, station-type with pilot lights for each speed.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.22.6   Pushbutton Stations</TTL><BRK/>
<BRK/>
<TXT>Provide with "start/stop" momentary contacts having one normally open and one normally closed set of contacts, 
and red lights to indicate when motor is running.  Stations shall be heavy duty, oil-tight design.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.22.7   Pilot and Indicating Lights</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Choose one of the following bracketed items.  LED cluster lamps have 
an approximate life of 20,000 hours and will fit incandescent lamp bases.  Incandescent 
lamps have an approximate life of 1,000 hours.  LED colors are red, amber, yellow, 
and green and are not available in clear or white.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Provide LED cluster lamps.][Provide transformer, resistor, or diode type.]</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.22.8   Reduced-Voltage Controllers</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The designer shall determine, based on the power system characteristics 
and motor usage, where reduced-voltage controllers shall be specified.  Refer 
to UFC 3-520-01, INTERIOR ELECTRICAL SYSTEMS, for detailed discussion of these 
reduced voltage starter types and for guidance in their selection and application.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide for polyphase motors [_____]<MET> kilowatt</MET><ENG> horsepower</ENG> and larger.  Reduced-voltage starters shall be single-step, 
closed transition[ autotransformer,][ reactor,][ primary resistor-type,][ solid state-type,] or as indicated, 
and shall have adjustable time interval between application of reduced and full voltages to motors.[  Wye-delta 
reduced voltage starter or part winding increment starter having adjustable time delay between application of 
voltage to first and second winding of motor may be used in lieu of the reduced-voltage starters for starting 
of[ motor-generator sets,][ centrifugally operated equipment,][ or][ reciprocating compressors provided with 
automatic unloaders].]</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>2.23   <SUB>MANUAL MOTOR STARTERS</SUB> (MOTOR RATED SWITCHES)</TTL><BRK/>
<BRK/>
<TXT>[Single][Double][Three] pole designed for[ flush][ surface] mounting with overload protection[ and pilot lights].</TXT><BRK/>
<BRK/>
<SPT><TTL>2.23.1   Pilot Lights</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Choose either the incandescent or LED bracketed sentence.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Provide yoke-mounted, seven element LED cluster light module.  Color shall be[ green][ red][ amber][ in accordance 
with <RID>NEMA ICS 2</RID>].][Provide yoke-mounted, candelabra-base sockets rated 125 volts and fitted with glass or plastic 
jewels.  Provide clear, 6 watt lamp in each pilot switch.  Jewels for use with switches controlling motors shall 
be green; jewels for other purposes shall be[ white][ red][ amber].]</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.24   <SUB>MOTOR CONTROL CENTERS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Motor control center should be specified for groups of large motors requiring 
coordinated control.  In other applications, individual controllers or motor 
control panelboards should be used.  Generally, motor control centers should 
be NEMA, Class I, Type B.  Coordinate controller specifications with the mechanical 
equipment requirements.</NPR><BRK/>
<BRK/>
<NPR>NOTE:  Class I motor control centers consist of mechanical groupings of combination 
motor-control units, feeder-tap units, other units and electrical devices arranged 
in a convenient assembly.<BRK/>
  Class II motor control centers are the same as Class I except with the addition 
of manufacturer-furnished electrical interlocking and wiring between units as 
specifically described by the designer on the construction drawings</NPR><BRK/>
<AST/><BRK/></NTE>
 <BRK/>
<TXT><RID>UL 845</RID>, <RID>NEMA ICS 2</RID>, <RID>NEMA ICS 3</RID>.  Wiring shall be Class[ I][ II], Type[ A][ B][ C], in NEMA Type[ 1][ 3R][ 12][_____] 
enclosure.  Provide control centers suitable for operation on [_____]-volt, [_____]-phase, [_____]-wire, [_____] 
Hz system and shall have minimum short-circuit withstand and interrupting rating of[ 100,000][ 65,000][ 42,000][ 
25,000][ _____] amperes rms symmetrical.  Incoming power feeder shall be[ bus duct][ cable] entering at the[ 
top][ bottom] of enclosure and terminating on[ terminal lugs][ main protective device].[  Main protective device 
shall be[ molded case circuit breaker][ low-voltage power circuit breaker][ fusible switch] rated at [_____] 
amperes rms symmetrical interrupting capacity.][  Arrange busing so that control center can be expanded from 
both ends.]  Interconnecting wires shall be copper.  Terminal blocks shall be plug-in-type so that controllers 
may be removed without disconnecting individual control wiring.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.24.1   Bus Systems</TTL><BRK/>
<BRK/>
<TXT>Provide the following bus systems.  Power bus shall be braced to withstand fault current of[ 100,000][ 65,000][ 
42,000][ 25,000][ _____] amperes rms symmetrical.  Wiring troughs shall be isolated from horizontal and vertical 
bus bars.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.24.1.1   Horizontal and Main Buses</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  1,600-ampere and 2,000-ampere ratings are also available.  However, equipment 
at those ratings may not be UL listed, and, thus, have not been included as 
an option.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  UFC 3-520-01, INTERIOR ELECTRICAL SYSTEMS, recommends the use of copper 
bus.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Horizontal bus shall have continuous current rating of[ 600][ 800][ 1000][ 1200] amperes.  Main bus shall be[ 
aluminum, tin-plated][ copper, silver-plated] enclosed in isolated compartment at top of each vertical section.  
Main bus shall be isolated from wire troughs, starters, and other areas.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.24.1.2   Vertical Bus</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  UFC 3-520-01, INTERIOR ELECTRICAL SYSTEMS, recommends the use of copper 
bus.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Vertical bus shall have continuous current rating of[ 300][ 450][ 600][ _____] amperes, and shall be[ aluminum, 
tin-plated][ copper, tin-plated][ copper, silver-plated].  Vertical bus shall be enclosed in flame-retardant, 
polyester glass "sandwich."</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.24.1.3   Ground Bus</TTL><BRK/>
<BRK/>
<TXT>Copper ground bus shall be provided full width of motor control center and shall be equipped with necessary lugs.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.24.1.4   Neutral Bus</TTL><BRK/>
<BRK/>
<TXT>Insulated neutral bus shall be provided continuous through the motor control center; neutral shall be full rated.  
Lugs of appropriate capacity shall be provided, as required.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>2.24.2   Motor Disconnecting Devices and Controllers</TTL><BRK/>
<BRK/>
<TXT>Shall comply with paragraph COMBINATION MOTOR CONTROLLERS.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.24.3   <SUB>Combination Motor Controllers</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Per LANTNAVFACENGCOM criteria, combination motor controllers are not 
normally used on LANTNAVFACENGCOM projects, except when MCC's are used.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>UL 508</RID> and other requirements in paragraph, MOTOR CONTROLLERS. Controller shall employ[ molded case circuit breaker][ 
fusible switch with clips for [_____]-type fuses for branch circuit protection].[  Minimum short circuit withstand 
rating of combination motor controller shall be [_____] rms symmetrical amperes.][  Circuit breakers for combination 
controllers shall be[ thermal magnetic][ magnetic only].]</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.24.4   Space Heaters</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Heaters should be connected to an external power source in installations 
where the motor control center will not be energized continuously.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Space heaters shall be provided where indicated on the drawings and shall be controlled using an adjustable 10 
to 35 degrees C (50 to 90 degree F) thermostat, magnetic contactor, and a molded-case circuit breaker[ and a 
480-120 volt single-phase transformer].  The space heaters shall be 250-watt, 240 volt strip elements operated 
at 120 volts and shall be[ supplied from the motor control center bus][ wired to terminal blocks for connection 
to 120-volt single-phase power sources located external to the control centers].  The contactors shall be open 
type, electrically-held, rated 30 amperes, 2-pole, with 120-volt ac coils.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>2.25   LOCKOUT REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Provide disconnecting means capable of being locked out for machines and other equipment to prevent unexpected 
startup or release of stored energy in accordance with <RID>29 CFR 1910.147</RID>.  Mechanical isolation of machines and 
other equipment shall be in accordance with requirements of Division 23, "Mechanical."</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.26   TELECOMMUNICATIONS SYSTEM</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph provides information related to telecommunications system 
requirements for pathway and electrical service..  Complete system cabling and 
interconnecting hardware are specified in Section 27 10 00, BUILDING TELECOMMUNICATIONS 
CABLING SYSTEM, and Section 33 82 00, TELECOMMUNICATIONS OUTSIDE PLANT.  Where 
Section 27 10 00 is not provided and an empty conduit system is required for 
telecommunications service, copy and paste the subparagraph BACKBOARDS under 
the major paragraph COMMUNITY ANTENNA TELEVISION (CATV) SYSTEM as a subparagraph 
to this paragraph.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide system of telecommunications wire-supporting structures (pathway), including: outlet boxes, conduits 
with pull wires[ wireways,][ cable trays,] and other accessories for telecommunications outlets and pathway in 
accordance with <RID>TIA/EIA-569-A</RID> and as specified herein.[  Additional telecommunications requirements are specified 
in Section <SRF>27 10 00</SRF>, BUILDING TELECOMMUNICATIONS CABLING SYSTEM.]</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.27   COMMUNITY ANTENNA TELEVISION (CATV) SYSTEM</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: 1.  Use paragraph CATV OUTLETS and CATV FACEPLATES for empty conduit systems 
only, where cable is not provided in the project.<BRK/>
      2.  Designer shall provide riser diagram of system on drawings and provide 
empty conduit to exterior location for CATV service entrance.<BRK/>
      3.  Choose Section 27 54 00.00 20, COMMUNITY ANTENNA TELEVISION (CATV) 
SYSTEMS for Navy projects and Section 16815A CABLE TELEVISION PREMISES DISTRIBUTION 
SYSTEM for Army projects where complete CATV system is provided.  Delete paragraphs 
CATV OUTLETS and CATV FACEPLATES when section 27 54 00.00 20 or section 16815A 
are used on the project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Additional CATV requirements are specified in[ Section <SRF>27 54 00.00 20</SRF>, COMMUNITY ANTENNA TELEVISION (CATV) SYSTEMS.][ 
Section <SRF>27 05 14.00 10</SRF>, CABLE TELEVISION PREMISES DISTRIBUTION SYSTEM.]]</TXT><BRK/>
<BRK/>
<SPT>[<TTL>2.27.1   <SUB>CATV Outlets</SUB></TTL><BRK/>
<BRK/>
<TXT>Provide flush mounted, 75-ohm, F-type connector outlet rated from 5 to 1000 MHz in standard electrical outlet 
boxes[ with isolation barrier] with mounting frame.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.27.2   CATV Faceplates</TTL><BRK/>
<BRK/>
<TXT>Provide modular faceplates for mounting of CATV Outlets.[  Faceplate shall include designation labels and label 
covers for circuit identification.]  Faceplate color shall match outlet and switch coverplates.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.27.3   Backboards</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Choose the first bracketed sentence when providing an empty conduit system 
or choose the second bracketed sentence when Section 27 10 00 is used.  When 
using "as indicated" option, ensure information required is shown on the drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Provide void-free, fire rated interior grade plywood,<MET> 19 mm (3/4 inch)</MET><ENG> 3/4 inch</ENG> thick,<MET>[ 1200 by 2400 mm (4 by 
8 feet)]</MET><ENG>[ 4 by 8 feet]</ENG>[ as indicated].  Do not cover the fire stamp on the backboard.][  Coordinate CATV backboard 
requirements with telecommunications backboard requirements as specified in Section <SRF>27 10 00</SRF>, BUILDING TELECOMMUNICATIONS 
CABLING.]</TXT><BRK/>
<BRK/>
]</SPT>]</SPT><SPT><TTL>2.28   GROUNDING AND BONDING EQUIPMENT</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For LANTNAVFACENGCOM projects, delete "sectional type" and "<MET> 6100 mm 
(20 foot)</MET><ENG> 20 foot length</ENG>," except for projects at Portsmouth Naval Hospital, 
Portsmouth, VA.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.28.1   Ground Rods</TTL><BRK/>
<BRK/>
<TXT><RID>UL 467</RID>.  Ground rods shall be[ sectional type,] copper-clad steel, with minimum diameter of<MET> 19 mm (3/4 inch)</MET><ENG> 
3/4 inch</ENG> and minimum length<MET>[ of 3050 mm (10 feet)][ of 6100 mm (20 feet)]</MET><ENG>[ of 10 feet][ of 20 feet]</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.28.2   Ground Bus</TTL><BRK/>
<BRK/>
<TXT>A copper ground bus shall be provided in the electrical equipment rooms as indicated.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.28.3   Telecommunications [and CATV]<SUB>Grounding Busbar</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: 1.  Minimum width for the telecommunications main grounding busbar (TMGB) 
is 100 mm (4 in) and for the telecommunications grounding busbar (TGB) is 50 
mm (2 in).  Telecommunications grounding busbar provides grounding termination 
for voice, data and video (CATV) systems.<BRK/>
<BRK/>
 2.  Choose the bracketed option for Telecommunication Grounding Busbars (TGB) 
when there are more than one telecommunications room or telecommunications equipment 
rooms included in the project.<BRK/></NPR>
<BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide corrosion-resistant grounding busbar suitable for[ indoor][ outdoor] installation in accordance with <RID>
TIA J-STD-607-A</RID>.  Busbars shall be  (IS THIS AN ENGINEERING TERM OR SHOULD IT BE ELECTRO-PLATED?)-plated for 
reduced contact resistance.  If not plated, the busbar shall be cleaned prior to fastening the conductors to 
the busbar, and an anti-oxidant shall be applied to the contact area to control corrosion and reduce contact 
resistance.  Provide a telecommunications main grounding busbar (TMGB) in the telecommunications entrance facility[ 
and a (TGB) in all other telecommunications rooms and equipment rooms].  The telecommunications main grounding 
busbar (TMGB)[ and the telecommunications grounding busbar (TGB)] shall be sized in accordance with the immediate 
application requirements and with consideration of future growth.  Provide telecommunications grounding busbars 
with the following:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Predrilled copper busbar provided with holes for use with standard sized lugs,</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Minimum dimensions of<MET> 6 mm (0.25 inch)</MET><ENG> 0.25 in</ENG> thick x<MET> 100 mm (4 in)</MET><ENG> 4 in</ENG> wide for the TMGB[ 
and <MET>50 mm (2 in)</MET><ENG>2 in</ENG> wide for TGBs] with length as indicated;</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Listed by a nationally recognized testing laboratory.</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>2.29   HAZARDOUS LOCATIONS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Indicate very clearly the limits of all hazardous locations.  Edit the 
last sentence for actual equipment required in hazardous locations.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Electrical materials, equipment, and devices for installation in hazardous locations, as defined by <RID>NFPA 70</RID>, 
shall be specifically approved by Underwriters' Laboratories, Inc., or Factory Mutual for particular "Class," 
"Division," and "Group" of hazardous locations involved.  Boundaries and classifications of hazardous locations 
shall be as indicated.  Equipment in hazardous locations shall comply with <RID>UL 877</RID> for circuit breakers, <RID>UL 886</RID>
 for outlet boxes and fittings, <RID>UL 1010</RID> for receptacles, <RID>UL 674</RID> for motors, and <RID>UL 698</RID> for industrial controls.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.30   MANUFACTURER'S NAMEPLATE</TTL><BRK/>
<BRK/>
<TXT>Each item of equipment shall have a nameplate bearing the manufacturer's name, address, model number, and serial 
number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.31   FIELD FABRICATED NAMEPLATES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use the following paragraph where nameplates are fabricated to identify 
specific equipment designated on the drawings.  Provide note on panelboard schedules 
to indicate where red labels are required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>ASTM D 709</RID>.  Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as 
specified or as indicated on the drawings.  Each nameplate inscription shall identify the function and, when 
applicable, the position.  Nameplates shall be melamine plastic,<MET> 3 mm (0.125 inch)</MET><ENG> 0.125 inch</ENG> thick, white with 
[black] [_____] center core.[  Provide red laminated plastic label with white center core where indicated.]  
Surface shall be matte finish.  Corners shall be square.  Accurately align lettering and engrave into the core.  
Minimum size of nameplates shall be<MET> 25 by 65 mm (one by 2.5 inches)</MET><ENG> one by 2.5 inches</ENG>.  Lettering shall be a 
minimum of<MET> 6.35 mm (0.25 inch)</MET><ENG> 0.25 inch</ENG> high normal block style.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.32   WARNING SIGNS</TTL><BRK/>
<BRK/>
<TXT>Provide warning signs for flash protection in accordance with <RID>NFPA 70E</RID> and <RID>NEMA Z535.4</RID> for switchboards, panelboards, 
industrial control panels, and motor control centers that are in other than dwelling occupancies and are likely 
to require examination, adjustment, servicing, or maintenance while energized.  Provide field installed signs 
to warn qualified persons of potential electric arc flash hazards when warning signs are not provided by the 
manufacturer.  The marking shall be clearly visible to qualified persons before examination, adjustment, servicing, 
or maintenance of the equipment.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.33   FIRESTOPPING MATERIALS</TTL><BRK/>
<BRK/>
<TXT>Provide firestopping around electrical penetrations in accordance with Section <SRF>07 84 00</SRF>, FIRESTOPPING .</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.34   <SUB>WIREWAYS</SUB></TTL><BRK/>
<TXT><BRK/>
<RID>UL 870</RID>.  Material shall be steel[ epoxy painted][ galvanized] 16 gauge for heights and depths up to<MET> 150 by 150 
mm (6 by 6 inches)</MET><ENG> 6 by 6 inches</ENG>, and 14 gauge for heights and depths up to<MET> 305 by 305 mm (12 by 12 inches)</MET><ENG> 12 
by 12 inches</ENG>.  Provide in length[ indicated][ required for the application] with[ hinged-][ screw-] cover NEMA[ 
1][ 3R][ 12] enclosure per <RID>NEMA ICS 6</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>2.35   <SUB>METERING</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include "metering" information when a single-phase self contained meter 
base is required.  Coordinate with Section 26 12 19.20, SINGLE-PHASE PAD-MOUNTED 
TRANSFORMER and Section 33 71 01, OVERHEAD TRANSMISSION AND DISTRIBUTION.  For 
LANTNAVFACENGCOM projects only:  If meter base is mounted more than 5 feet from 
the building, this specification section number and title should be changed 
to LANTDIV regional Section 16403, WIRING SYSTEMS. Appropriate verbiage should 
be added to identify the exterior equipment (such as metering, supports, and 
disconnect switches) that would then be covered by this section.  When a three-phase 
service is designed, modify meter requirements accordingly.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>NEMA C12.1</RID>.  Provide a self-contained, socket-mounted, electronic programmable outdoor watthour meter.  Meter 
shall either be programmed at the factory or shall be programmed in the field.  Turn field programming device 
over to the Contracting Officer at completion of project.  Meter shall be coordinated to system requirements.</TXT><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Form 2S, in text below, is for single-phase, three-wire systems, for 
other system configurations, designer shall determine the appropriate form designation.  
Class 200 meters are for 100A and 200A services.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<ITM INDENT="-0.33">a.  Design:  Provide watthour meter designed for use on a single-phase, three-wire,[ 240/120][ 
480/240] volt system.  Include necessary KYZ pulse initiation hardware for Energy Monitoring 
and Control System (EMCS).</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Class:  200; Form: [ 2S][ _____], accuracy:  +/- 1.0 percent; Finish:  Class II.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Cover:  Polycarbonate and lockable to prevent tampering and unauthorized removal.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Kilowatt-hour Register:  five digit electronic programmable type.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Demand Register:</ITM><BRK/>
<BRK/>
<ITM>(1)  Provide solid state.</ITM><BRK/>
<BRK/>
<ITM>(2)  Meter reading multiplier:  Indicate multiplier on the meter face.</ITM><BRK/>
<BRK/>
<ITM>(3)  Demand interval length:  Shall be programmed for[ 15][ 30][ 60] minutes with rolling demand 
up to six subintervals per interval.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Socket:  <RID>ANSI C12.7</RID>.  Provide NEMA Type 3R, box-mounted socket, ringless, having[ manual 
circuit-closing bypass and having] jaws compatible with requirements of the meter.  Provide 
manufacturers standard enclosure color unless otherwise indicated.</ITM><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.36   <SUB>METER BASE ONLY</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use METER BASE ONLY paragraph for projects where meters are not currently 
required, but may be required in the future, for example, military housing units.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><RID>ANSI C12.7</RID>.  Provide NEMA Type 3R, box-mounted socket, ringless, having jaws compatible with requirements of 
a class:  200 and Form: [ 2S][ _____] self contained watthour meter.  Provide gray plastic closing cover and 
bypass links.  Provide manufacturers standard enclosure color unless otherwise indicated.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.37   <SUB>SURGE PROTECTIVE DEVICES</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Surge protection should be provided for the following types of facilities:  
Medical facilities; Air navigation aids and facilities; Petroleum, oil and lubricant 
(POL) storage and dispensing facilities; Critical utility plants and systems; 
Communication facilities and telephone exchanges; Fire stations, including fire 
alarm, fire control and radio equipment; Critical computer automatic data processing 
facilities; Air traffic control facilities; Base weather stations; Surveillance 
and warning facilities; Command and control facilities; Weapon systems; Security 
lighting systems; Mission, property and life support facilities at remote and 
not readily accessible sites.<BRK/>
   Consider surge protection for all types of facilities located in regions 
with a high lightning strike probability (refer to IEEE C62.41.1 and C62.41.2) 
and facilities located near commercial utility systems with routine substation 
capacitor switching.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Whenever possible, connect surge protectors to a spare circuit breaker 
in the associated panel.  Locate the surge protectors immediately adjacent to 
the protected equipment.<BRK/>
  It is not necessary to provide surge protection on all panelboards; the selection 
of which panelboards should have surge protective devices depends on the importance 
of the loads served and the sensitivity of electronic equipment connected to 
the circuits.<BRK/>
  Switching loads such as motor control centers should have surge protection 
to limit the transmission of switching transients to the rest of the facility.<BRK/>
  HVAC equipment usually contain electronic controls that are sensitive to surges.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide parallel type surge protective devices which comply with <RID>UL 1449</RID> at the service entrance[, load centers] 
[, panelboards] [, MCC] [and] [____].  Provide surge protectors in a NEMA[ 1][ __] enclosure per <RID>NEMA ICS 6</RID>.  
Provide the following modes of protection:<BRK/>
<BRK/>
      FOR SINGLE PHASE AND THREE PHASE WYE CONNECTED SYSTEMS-<BRK/>
            Each phase to neutral ( L-N )<BRK/>
            Neutral to ground ( N-G )<BRK/>
            Phase to ground ( L-G )<BRK/>
[<BRK/>
      FOR DELTA CONNECTIONS-<BRK/>
            Phase to phase ( L-L )<BRK/>
            Phase to ground ( L-G )]<BRK/>
<BRK/>
Surge protective devices at the service entrance shall have a minimum surge current rating of 80,000 amperes 
per mode minimum[ and downstream protectors shall be rated 40,000 amperes per mode minimum].  The maximum line 
to neutral (L-N) Suppressed Voltage Rating (SVR) shall be:<BRK/>
<BRK/>
      [500V for 120V, single phase system]<BRK/>
      [500V for 120/240V, single phase system]<BRK/>
      [500V for 208Y/120V, three phase system]<BRK/>
      [900V for 480Y/277V, three phase system]<BRK/>
<BRK/>
The minimum MCOV (Maximum Continuous Operating Voltage) rating shall be:<BRK/>
<BRK/>
      [150V for 120V, single phase system]<BRK/>
      [300/150V for 120/240V, single phase system]<BRK/>
      [300/150V for 208Y/120V, three phase system]<BRK/>
      [600/320V for 480Y/277V, three phase system]</TXT><BRK/>
<BRK/>
<TXT>EMI/RFI filtering shall be provided for each mode with the capability to attenuate high frequency noise.  Minimum 
attenuation shall be 20db.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.38   FACTORY APPLIED FINISH</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph covers only the basic painting requirements for most electrical 
equipment.  Include any special finishes for high or low temperatures and corrosive 
atmospheres.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Electrical equipment shall have factory-applied painting systems which shall, as a minimum, meet the requirements 
of <RID>NEMA 250</RID> corrosion-resistance test and the additional requirements as specified herein.  Interior and exterior 
steel surfaces of equipment enclosures shall be thoroughly cleaned and then receive a rust-inhibitive phosphatizing 
or equivalent treatment prior to painting.  Exterior surfaces shall be free from holes, seams, dents, weld marks, 
loose scale or other imperfections.  Interior surfaces shall receive not less than one coat of corrosion-resisting 
paint in accordance with the manufacturer's standard practice.  Exterior surfaces shall be primed, filled where 
necessary, and given not less than two coats baked enamel with semigloss finish.  Equipment located indoors shall 
be ANSI Light Gray,[ and equipment located outdoors shall be ANSI[ Light Gray][ Dark Gray]].  Provide manufacturer's 
coatings for touch-up work and as specified in paragraph FIELD APPLIED PAINTING.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.39   SOURCE QUALITY CONTROL</TTL><BRK/>
<BRK/>
<SPT><TTL>2.39.1   <SUB>Transformer Factory Tests</SUB></TTL><BRK/>
<BRK/>
<TXT>Submittal shall include routine <RID>NEMA ST 20</RID> transformer test results on each transformer and also contain the 
results of NEMA "design" and "prototype" tests that were made on transformers electrically and mechanically equal 
to those specified.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>2.40   COORDINATED POWER SYSTEM PROTECTION</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Do not use on Navy projects.<BRK/>
<BRK/>
NOTE:  The requirement for studies in this paragraph depends on the complexity 
and extent of the power system.  Delete this requirement for projects of limited 
scope, projects having protective devices which are not adjustable or for which 
coordination is not possible (standard molded case circuit breakers); projects 
involving simple extension of 600 volt level service to a building or facility 
from an existing transformer (750 kVA or less); or projects involving simple 
extension of 600 volt level service to a building or facility from a new transformer 
(750 kVA or less).</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Analyses shall be prepared as specified in Section 16475A, COORDINATED POWER SYSTEM PROTECTION.</TXT><BRK/>
<BRK/>
]</SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Electrical installations, including weatherproof and hazardous locations and ducts, plenums and other air-handling 
spaces, shall conform to requirements of <RID>NFPA 70</RID> and <RID>IEEE C2</RID> and to requirements specified herein.</TXT><BRK/>
<BRK/>
<SPT>[<TTL>3.1.1   Underground Service</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Choose this paragraph or the paragraph, OVERHEAD SERVICE.  When using 
this paragraph, designer may insert additional details describing the specific 
project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Underground service conductors and associated conduit shall be continuous from service entrance equipment to 
outdoor power system connection.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.1.2   Overhead Service</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use Section 33 71 01, OVERHEAD TRANSMISSION AND DISTRIBUTION for overhead 
service requirements (typical throughout this section).</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Overhead service conductors into buildings shall terminate at service entrance fittings or weatherhead outside 
building.  Overhead service conductors and support bracket for overhead conductors are included in[ Section 
<SRF>33 71 01</SRF>, OVERHEAD TRANSMISSION AND DISTRIBUTION.]</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.1.3   Hazardous Locations</TTL><BRK/>
<BRK/>
<TXT>Work in hazardous locations, as defined by <RID>NFPA 70</RID>, shall be performed in strict accordance with <RID>NFPA 70</RID> for 
particular "Class," "Division," and "Group" of hazardous locations involved.  Provide conduit and cable seals 
where required by <RID>NFPA 70</RID>.  Conduit shall have tapered threads.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.1.4   Service Entrance Identification</TTL><BRK/>
<BRK/>
<TXT>Service entrance disconnect devices, switches, and enclosures shall be labeled and identified as such.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.1.4.1   Labels</TTL><BRK/>
<BRK/>
<TXT>Wherever work results in service entrance disconnect devices in more than one enclosure, as permitted by <RID>NFPA 70</RID>
, each enclosure, new and existing, shall be labeled as one of several enclosures containing service entrance 
disconnect devices.  Label, at minimum, shall indicate number of service disconnect devices housed by enclosure 
and shall indicate total number of enclosures that contain service disconnect devices.  Provide laminated plastic 
labels conforming to paragraph FIELD FABRICATED NAMEPLATES.  Use lettering of at least<MET> 6.35 mm</MET><ENG> 0.25 inch</ENG> in height, 
and engrave on black-on-white matte finish.  Service entrance disconnect devices in more than one enclosure, 
shall be provided only as permitted by <RID>NFPA 70</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.1.5   Wiring Methods</TTL><BRK/>
<BRK/>
<TXT>Provide insulated conductors installed in rigid steel conduit, IMC, rigid nonmetallic conduit, or EMT, except 
where specifically indicated or specified otherwise or required by <RID>NFPA 70</RID> to be installed otherwise.  Grounding 
conductor shall be separate from electrical system neutral conductor.  Provide insulated green equipment grounding 
conductor for circuit(s) installed in conduit and raceways.[  Shared neutral, or multi-wire branch circuits, 
are not permitted with arc-fault circuit interrupters.]  Minimum conduit size shall be<MET> 16 mm (1/2 inch)</MET><ENG> 1/2 inch</ENG>
 in diameter for low voltage lighting and power circuits.  Vertical distribution in multiple story buildings 
shall be made with metal conduit in fire-rated shafts.  Metal conduit shall extend through shafts for minimum 
distance of<MET> 150 mm (6 inches)</MET><ENG> 6 inches</ENG>.  Conduit which penetrates fire-rated walls, fire-rated partitions, or 
fire-rated floors shall be firestopped in accordance with Section <SRF>07 84 00</SRF>, FIRESTOPPING.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.1.5.1   Pull Wire</TTL><BRK/>
<BRK/>
<TXT>Install pull wires in empty conduits.  Pull wire shall be plastic having minimum<MET> 890-N (200-pound)</MET><ENG> 200-pound</ENG> 
force tensile strength.  Leave minimum<MET> 915 mm (36 inches)</MET><ENG> 36 inches</ENG> of slack at each end of pull wire.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.1.5.2   Metal Clad Cable</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Type MC cable is UL listed; NFPA 70 is recognized for most common building 
applications.  MC cable does not protect conductors as well as rigid conduit 
but is more flexible to install and relocate.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Install in accordance with <RID>NFPA 70</RID>, Type MC cable.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.1.5.3   Armored Cable</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Type AC cable has more restricted applications than MC cable but offers 
the same advantages.  Review NFPA 70.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Install in accordance with <RID>NFPA 70</RID>, Type AC cable.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.1.5.4   Flat Conductor Cable</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Type FCC cable has been listed by UL and recognized by NFPA 70 for under 
carpet tile applications.  FCC cable is available off the shelf for power, and 
telecommunications transmission applications.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Install in accordance with <RID>NFPA 70</RID>, Type FCC cable.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.1.6   Conduit Installation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where exposed conduit is installed and subject to vandalism or misuse, 
such as in toilet or locker rooms, do not allow perpendicular or right angle 
to ceiling structural members.  Provide details on drawings to identify special 
treatments or offsets as needed.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>Do not install exposed conduit systems in inmate housing areas and other areas 
normally accessible to inmates unless such installations are specifically indicated.  
Where exposed conduit is indicated, conduits shall be rigid metallic type and 
outlet boxes shall be cast metal-type with threaded hubs.  Install conduits 
flat against wall; offsets or "kicks" shall be permitted only to enter outlet 
box.  Support conduits on<MET> 1525 mm (5 foot)</MET><ENG> 5 foot</ENG> maximum centers and within<MET>
 305 mm (12 inches)</MET><ENG> 12 inches</ENG> of each outlet box using two-hole conduit straps 
attached to surface with nonremovable break off security type bolts.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Unless indicated otherwise, conceal conduit under floor slabs and within finished walls, ceilings, and floors.  
Keep conduit minimum <MET>150 mm (6 inches)</MET> <ENG>6 inches</ENG> away from parallel runs of flues and steam or hot water pipes.  
Install conduit parallel with or at right angles to ceilings, walls, and structural members where located above 
accessible ceilings and where conduit will be visible after completion of project.[  Run conduits[ in crawl space][ 
under floor slab] as if exposed.]</TXT><BRK/>
<BRK/>
<SPT><TTL>3.1.6.1   Restrictions Applicable to Aluminum Conduit</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Do not install underground or encase in concrete or masonry.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Do not use brass or bronze fittings.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Do not use when the enclosed conductors must be shielded from the effects of High-altitude 
Electromagnetic Pulse (HEMP).</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.6.2   Restrictions Applicable to EMT</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Do not install underground.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Do not encase in concrete, mortar, grout, or other cementitious materials.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Do not use in areas subject to severe physical damage including but not limited to equipment 
rooms where moving or replacing equipment could physically damage the EMT.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">d.  Do not use in hazardous areas.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">e.  Do not use outdoors.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">f.  Do not use in fire pump rooms.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">g.  Do not use when the enclosed conductors must be shielded from the effects of High-altitude 
Electromagnetic Pulse (HEMP).</ITM><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.1.6.3   Restrictions Applicable to Nonmetallic Conduit</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  PVC Schedule 40 and PVC Schedule 80</ITM><BRK/>
<BRK/>
<ITM>(1)  Do not use in areas where subject to severe physical damage, including but not limited 
to, mechanical equipment rooms, electrical equipment rooms, hospitals, power plants, missile 
magazines, and other such areas.</ITM><BRK/>
<BRK/>
<ITM>(2)  Do not use in hazardous (classified) areas.</ITM><BRK/>
<BRK/>
<ITM>(3)  Do not use in fire pump rooms.</ITM><BRK/>
<BRK/>
<ITM>(4)  Do not use in penetrating fire-rated walls or partitions, or fire-rated floors.</ITM><BRK/>
<BRK/>
<ITM>(5)  Do not use above grade, except where allowed in this section for rising through floor slab 
or indicated otherwise.</ITM><BRK/>
<BRK/>
<ITM>(6)  Do not use when the enclosed conductors must be shielded from the effects of High-altitude 
Electromagnetic Pulse (HEMP).</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Do not use ENT for NAVFACENGCOM projects without written approval from 
the NAVFAC EFD/EFA electrical design engineering branch manager.  NAVFAC EFD/EFA 
electrical design branch managers should consider the following information 
in evaluating ENT for specific projects.  ENT may be provided in walls, floors, 
and ceilings only when protected by thermal barriers identified as having minimum 
15-minute finish rating.  If ENT is used, the Contractor shall provide any required 
thermal barriers, whether indicated or not.  Include the following restrictions 
for ENT where ENT is allowed by the Authority Having Jurisdiction in overseas 
locations.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
[<ITM INDENT="-0.33">b.  Electrical Nonmetallic Tubing</ITM><BRK/>
<BRK/>
<ITM>(1)  Do not install underground.</ITM><BRK/>
<BRK/>
<ITM>(2)  Do not encase in concrete except when provided with fittings identified for this purpose 
are used for connections.</ITM><BRK/>
<BRK/>
<ITM>(3)  Do not use in areas where subject to severe physical damage, including but not limited 
to, mechanical equipment rooms, electrical equipment rooms, hospitals, power plants, missile 
magazines, and other such areas.</ITM><BRK/>
<BRK/>
<ITM>(4)  Do not use in hazardous areas.</ITM><BRK/>
<BRK/>
<ITM>(5)  Do not use outdoors.</ITM><BRK/>
<BRK/>
<ITM>(6)  Do not use in sizes larger than<MET> 53 mm (2 inch)</MET><ENG> 2 inch</ENG>.</ITM><BRK/>
<BRK/>
<ITM>(7)  Do not run exposed in buildings exceeding three floors above grade, where "first floor" 
is as defined in NFPA 70.]</ITM><BRK/>
<BRK/>
<ITM>(8)  Do not use when the enclosed conductors must be shielded from the effects of High-altitude 
Electromagnetic Pulse (HEMP).</ITM><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.1.6.4   Restrictions Applicable to Flexible Conduit</TTL><BRK/>
<BRK/>
<TXT>Use only as specified in paragraph FLEXIBLE CONNECTIONS.  Do not use when the enclosed conductors must be shielded 
from the effects of High-altitude Electromagnetic Pulse (HEMP).</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.6.5   Service Entrance Conduit, Overhead</TTL><BRK/>
<BRK/>
<TXT>Rigid steel or IMC from service entrance to service entrance fitting or weatherhead outside building.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.6.6   Service Entrance Conduit, Underground</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For CHESNAVFACENGCOM and PACNAVFACENGCOM projects, <HL1>DO NOT USE</HL1> PVC Type-EPC 
40 conduit.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>PVC, Type-EPC 40, galvanized rigid steel or steel IMC.  Underground portion shall be encased in minimum of<MET> 75 
mm</MET><ENG> 3 inches</ENG> of concrete and shall be installed minimum<MET> 460 mm</MET><ENG> 18 inches</ENG> below slab or grade.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.6.7   Underground Conduit Other Than Service Entrance</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Soil conditions in some locations require that underground conduit be 
supported to prevent damage due to settlement.  The designer shall determine 
if the problem exists, and, if so, determine the best method for supporting 
the conduit.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Plastic-coated rigid steel; plastic-coated steel IMC; PVC, Type EPC-40[; or fiberglass.  Convert nonmetallic 
conduit, other than PVC Schedule 40 or 80, to plastic-coated rigid, or IMC, steel conduit before rising through 
floor slab.]  Plastic coating shall extend minimum<MET> 150 mm</MET><ENG> 6 inches</ENG> above floor.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.1.6.8   Conduit Interior to Buildings for 400 Hz Circuits</TTL><BRK/>
<BRK/>
<TXT>Aluminum or nonmetallic.  Where 400-Hz circuit runs underground or through concrete, conduit shall be PVC Schedule[ 
40][ 80].</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.1.6.9   Conduit for Circuits Rated Greater Than 600 Volts</TTL><BRK/>
<BRK/>
<TXT>Rigid metal conduit or IMC only.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.6.10   Conduit Installed Under Floor Slabs</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer shall closely coordinate with the design of building floor slab 
and soil conditions and evaluate the acceptability of conduit being installed 
directly beneath the floor slab.  Consideration shall be given to support conduit 
in case of soil settlement problems and vapor barrier penetrations.  Provide 
details on the drawings to clarify specification.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Conduit run under floor slab shall be located a minimum of<MET> [305] [_____] mm ([12] [_____] inches)</MET><ENG> [12] [_____] 
inches</ENG> below the vapor barrier.  Seal around conduits at penetrations thru vapor barrier.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.6.11   Conduit Through Floor Slabs</TTL><BRK/>
<BRK/>
<TXT>Where conduits rise through floor slabs, curved portion of bends shall not be visible above finished slab.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.1.6.12   Conduit Installed in Concrete Floor Slabs</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When this option is included, (such as in BEQ's and similar projects 
with precast planks and topping slabs), indicate specific locations and provide 
installation details on the electrical drawings.  Electrical designer shall 
closely coordinate this information with the designer of the slab to ensure 
that slab thickness, conduit placement/separation, and reinforcement spacing 
is sufficient to meet requirements of this paragraph.  Do not specify metal 
conduit in concrete that contains coral aggregate or is made with salt or brackish 
water.  This type of concrete is rarely allowed.  For LANTNAVFACENGCOM projects, 
use second bracketed option for conduit type.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Rigid steel; steel IMC; fiberglass, or PVC, Type EPC-40.][PVC, Type EPC-40, unless indicated otherwise.]  Locate 
so as not to adversely affect structural strength of slabs.  Install conduit within middle one-third of concrete 
slab.[  Do not stack conduits.][  Do not stack conduits more than two diameters high with minimum vertical separation 
of [_____]<MET> mm (____ inches)</MET><ENG> inches</ENG>.]  Space conduits horizontally not closer than three diameters, except at 
cabinet locations.  Curved portions of bends shall not be visible above finish slab.  Increase slab thickness 
as necessary to provide minimum<MET> 25 mm</MET><ENG> one inch</ENG> cover over conduit.  Where embedded conduits cross building and/or 
expansion joints, provide suitable watertight expansion/deflection fittings and bonding jumpers.  Expansion/deflection 
fittings shall allow horizontal and vertical movement of raceway.  Conduit larger than<MET> 27 mm (one inch)</MET><ENG> one inch</ENG>
 trade size shall be parallel with or at right angles to main reinforcement; when at right angles to reinforcement, 
conduit shall be close to one of supports of slab.[  Where nonmetallic conduit is used, raceway shall be converted 
to plastic coated rigid steel or plastic coated  steel IMC before rising above floor, unless specifically indicated.]</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.1.6.13   Stub-Ups</TTL><BRK/>
<BRK/>
<TXT>Provide conduits stubbed up through concrete floor for connection to free-standing equipment with adjustable 
top or coupling threaded inside for plugs, set flush with finished floor.  Extend conductors to equipment in 
rigid steel conduit, except that flexible metal conduit may be used<MET> 150 mm (6 inches)</MET><ENG> 6 inches</ENG> above floor.  
Where no equipment connections are made, install screwdriver-operated threaded flush plugs in conduit end.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.6.14   Conduit Support</TTL><BRK/>
<BRK/>
<TXT>Support conduit by pipe straps, wall brackets, hangers, or ceiling trapeze. Fasten by wood screws to wood; by 
toggle bolts on hollow masonry units; by concrete inserts or expansion bolts on concrete or brick; and by machine 
screws, welded threaded studs, or spring-tension clamps on steel work. Threaded C-clamps may be used on rigid 
steel conduit only.  Do not weld conduits or pipe straps to steel structures.  Load applied to fasteners shall 
not exceed one-fourth proof test load.  Fasteners attached to concrete ceiling shall be vibration resistant and 
shock-resistant.  Holes cut to depth of more than<MET> 40 mm</MET><ENG> 1 1/2 inches</ENG> in reinforced concrete beams or to depth 
of more than<MET> 20 mm</MET><ENG> 3/4 inch</ENG> in concrete joints shall not cut main reinforcing bars.  Fill unused holes.  In partitions 
of light steel construction, use sheet metal screws.  In suspended-ceiling construction, run conduit above ceiling.  
Do not support conduit by ceiling support system.  Conduit and box systems shall be supported independently of 
both (a) tie wires supporting ceiling grid system, and (b) ceiling grid system into which ceiling panels are 
placed.  Supporting means shall not be shared between electrical raceways and mechanical piping or ducts.  Installation 
shall be coordinated with above-ceiling mechanical systems to assure maximum accessibility to all systems.  Spring-steel 
fasteners may be used for lighting branch circuit conduit supports in suspended ceilings in dry locations.[   
Support exposed risers in wire shafts of multistory buildings by U-clamp hangers at each floor level and at<MET> 3050 
mm</MET><ENG> 10 foot</ENG> maximum intervals.] Where conduit crosses building expansion joints, provide suitable[ watertight] 
expansion fitting that maintains conduit electrical continuity by bonding jumpers or other means.  For conduits 
greater than<MET> 63 mm (2 1/2 inches)</MET><ENG> 2 1/2 inches</ENG> inside diameter, provide supports to resist forces of 0.5 times 
the equipment weight in any direction and 1.5 times the equipment weight in the downward direction.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.6.15   Directional Changes in Conduit Runs</TTL><BRK/>
<BRK/>
<TXT>Make changes in direction of runs with symmetrical bends or cast-metal fittings.  Make field-made bends and offsets 
with hickey or conduit-bending machine.  Do not install crushed or deformed conduits.  Avoid trapped conduits.  
Prevent plaster, dirt, or trash from lodging in conduits, boxes, fittings, and equipment during construction.  
Free clogged conduits of obstructions.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.6.16   Locknuts and Bushings</TTL><BRK/>
<BRK/>
<TXT>Fasten conduits to sheet metal boxes and cabinets with two locknuts where required by <RID>NFPA 70</RID>, where insulated 
bushings are used, and where bushings cannot be brought into firm contact with the box; otherwise, use at least 
minimum single locknut and bushing.  Locknuts shall have sharp edges for digging into wall of metal enclosures.  
Install bushings on ends of conduits, and provide insulating type where required by <RID>NFPA 70</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.6.17   Flexible Connections</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For LANTNAVFACENGCOM projects, do not use flexible nonmetallic conduit.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide flexible steel conduit between<MET> 915 and 1830 mm (3 and 6 feet)</MET><ENG> 3 and 6 feet</ENG> in length for recessed and 
semirecessed lighting fixtures[; for equipment subject to vibration, noise transmission, or movement; and for 
motors].  Install flexible conduit to allow 20 percent slack.  Minimum flexible steel conduit size shall be <MET>16 
mm (1/2 inch)</MET><ENG> 1/2 inch</ENG> diameter.  Provide liquidtight flexible[ nonmetallic] conduit in wet and damp locations[ 
and in fire pump rooms] for equipment subject to vibration, noise transmission, movement or motors.  Provide 
separate ground conductor across flexible connections.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.6.18   Telecommunications and Signal System Pathway</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For guidelines on conduit sizing, see UFC-3-580-02, TELECOMMUNICATIONS 
BUILDING CABLING SYSTEM PLANNING, DESIGN, AND ESTIMATING and NFPA 70.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Install telecommunications pathway in accordance with <RID>TIA/EIA-569-A</RID>.</TXT><BRK/>
<BRK/>
<ITM>a.  Horizontal Pathway:  Telecommunications pathways from the work area to the telecommunications 
room shall be installed and cabling length requirements in accordance with <RID>TIA/EIA-568-B.1</RID>.  
Size conduits[, wireways][, and cable trays] in accordance with <RID>TIA/EIA-569-A</RID>[ and][ as indicated].</ITM><BRK/>
<BRK/>
<ITM>b.  Backbone Pathway:  Telecommunication pathways from the telecommunications entrance facility 
to telecommunications rooms, and, telecommunications equipment rooms (backbone cabling) shall 
be installed in accordance with <RID>TIA/EIA-569-A</RID>.  Size conduits[, wireways][, and cable trays] 
for telecommunications risers in accordance with <RID>TIA/EIA-569-A</RID>[ and][ as indicated].</ITM><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.1.6.19   Community Antenna Television (CATV) System Conduits</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Choose the bracketed item depending on the CATV system design.  Delete 
this paragraph if an empty conduit CATV system is not used.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Install a system of CATV wire-supporting structures (pathway), including: outlet boxes, conduits with pull wires[ 
wireways,][ cable trays,] and other accessories for CATV outlets and pathway in accordance with <RID>TIA/EIA-569-A</RID>
.  [Distribution system shall be star topology with empty conduit and pullwire from each outlet box to the tele 
communications  room and empty conduit and pullwire from each telecommunications room to the headend equipment 
location][Distribution system shall be star topology with empty conduit and pullwire from each outlet to the 
headend equipment location].</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.1.7   Busway Installation</TTL><BRK/>
<BRK/>
<TXT>Installation shall comply at minimum with <RID>NFPA 70</RID>.  Install busways parallel with or at right angles to ceilings, 
walls, and structural members.  Support busways at<MET> 1525 mm</MET><ENG> 5 foot</ENG> maximum intervals, and brace to prevent lateral 
movement.  Hinges provided on risers shall be fixed type; spring-type are unacceptable.  Provide flanges where 
busway makes penetrations through walls and floors, and seal to maintain smoke and fire ratings.  Provide waterproof 
curb where busway riser passes through floor.  Seal gaps with fire-rated foam and calk.  Provide expansion joints, 
but only where bus duct crosses building expansion joints.  Provide supports to resist forces of 0.5 times the 
equipment weight in any direction and 1.5 times the equipment weight in the downward direction.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.8   Cable Tray Installation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For LANTNAVFACENGCOM projects, use the second bracketed paragraph.  Include 
bracketed second sentence where cable tray is used for telecommunications system.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Install and ground in accordance with <RID>NFPA 70</RID>.[  In addition, install and ground telecommunications cable tray 
in accordance with <RID>TIA/EIA-569-A</RID>, and <RID>TIA J-STD-607-A</RID>].  Install cable trays parallel with or at right angles 
to ceilings, walls, and structural members.  Support[ in accordance with manufacturer recommendations but at 
not more than<MET> [1830] [_____] mm</MET><ENG> [6] [_____] foot</ENG> intervals][ as indicated].[  Contact surfaces of aluminum connections 
shall be coated with an antioxidant compound prior to assembly.]  Adjacent cable tray sections shall be bonded 
together by connector plates of an identical type as the cable tray sections.  For grounding of cable tray system 
provide No. 2 AWG bare copper wire throughout cable tray system, and bond to each section, except use No. 1/0 
aluminum wire if cable tray is aluminum.  Terminate cable trays<MET> 255 mm</MET><ENG> 10 inches</ENG> from both sides of smoke and 
fire partitions.  Conductors run through smoke and fire partitions shall be installed in<MET> 103 mm (4 inch)</MET><ENG> 4 inch</ENG>
 rigid steel conduits with grounding bushings, extending<MET> 305 mm</MET><ENG> 12 inches</ENG> beyond each side of partitions.  Seal 
conduit on both ends to maintain smoke and fire ratings of partitions.  Penetrations shall be firestopped in 
accordance with Section <SRF>07 84 00</SRF>, FIRESTOPPING.  Provide supports to resist forces of 0.5 times the equipment 
weight in any direction and 1.5 times the equipment weight in the downward direction. ]</TXT><BRK/>
<BRK/>
<TXT>[Install cable trays parallel with or at right angles to ceilings, walls, and structural members.  Support[ as 
indicated][ at maximum<MET> [1830] [_____] mm</MET><ENG> [6] [_____] foot</ENG>] intervals.[  In addition, install and ground telecommunications 
cable tray in accordance with <RID>TIA/EIA-569-A</RID>, and <RID>TIA J-STD-607-A</RID>][  Contact surfaces of aluminum connections 
shall be coated with an antioxidant compound prior to assembly.]  Edges, fittings, and hardware shall be finished 
free from burrs and sharp edges.  Provide No. 2 AWG bare copper wire throughout cable tray system, and bond to 
each section.  Use No. 1/0 aluminum wire if cable tray is aluminum.  Conductors that run though smoke and fire 
partitions shall be installed in<MET> 103 mm (4 inch)</MET><ENG> 4 inch</ENG> rigid steel conduits with grounding bushing, extending<MET>
 305 mm (12 inches)</MET><ENG> 12 inches</ENG> beyond each side of partitions.  Seal conduit on both ends to maintain smoke and 
fire ratings of partitions.  Provide supports to resist forces of 0.5 times the equipment weight in any direction 
and 1.5 times the equipment weight in the downward direction.]</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.1.9   Telecommunications Cable Support Installation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete for Navy projects.  Concern and some evidence exists that certain 
cable supports can have a detrimental effect on transmission performance of 
higher performance cabling systems.  Devices that have small surface areas to 
support the cable laying horizontally in them are the types of supports in question.  
When a choice exists, it would be prudent to select a cable support with a wider 
surface area to support the cable as a precaution against potential problems.  
Another precaution would be to reduce the distance between the cable supports.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Install open top and closed ring cable supports on<MET> 1.2 m</MET><ENG> 4 ft</ENG> to<MET> 1.5 m</MET><ENG> 5 ft</ENG> centers to adequately support and 
distribute the cable’s weight.  These types of supports shall be used to support a maximum of 50<MET> 6.4 mm (0.25 
in)</MET><ENG> 0.25 in</ENG> diameter cables.  Install suspended cables with at least<MET> 75 mm</MET><ENG> 3 in</ENG> of clear vertical space above 
the ceiling tiles and support channels (T-bars).  Open top and closed ring cable supports shall be suspended 
from or attached to the structural ceiling or walls with hardware or other installation aids specifically designed 
to support their weight.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.1.10   Boxes, Outlets, and Supports</TTL><BRK/>
<BRK/>
<TXT>Provide boxes in wiring and raceway systems wherever required for pulling of wires, making connections, and mounting 
of devices or fixtures.  Boxes for metallic raceways shall be cast-metal, hub-type when located in wet locations, 
when surface mounted on outside of exterior surfaces,[ when surface mounted on interior walls exposed up to<MET> 2135 
mm</MET><ENG> 7 feet</ENG> above floors and walkways,][ or when installed in hazardous areas] and when specifically indicated.  
Boxes in other locations shall be sheet steel, except that aluminum boxes may be used with aluminum conduit, 
and nonmetallic boxes may be used with nonmetallic[ sheathed cable] conduit system.  Each box shall have volume 
required by <RID>NFPA 70</RID> for number of conductors enclosed in box.  Boxes for mounting lighting fixtures shall be 
minimum<MET> 100 mm (4 inches)</MET><ENG> 4 inches</ENG> square, or octagonal, except that smaller boxes may be installed as required 
by fixture configurations, as approved.  Boxes for use in masonry-block or tile walls shall be square-cornered, 
tile-type, or standard boxes having square-cornered, tile-type covers.  Provide gaskets for cast-metal boxes 
installed in wet locations and boxes installed flush with outside of exterior surfaces.  Provide separate boxes 
for flush or recessed fixtures when required by fixture terminal operating temperature; fixtures shall be readily 
removable for access to boxes unless ceiling access panels are provided.  Support boxes and pendants for surface-mounted 
fixtures on suspended ceilings independently of ceiling supports.  Fasten boxes and supports with wood screws 
on wood, with bolts and expansion shields on concrete or brick, with toggle bolts on hollow masonry units, and 
with machine screws or welded studs on steel.[  Threaded studs driven in by powder charge and provided with lockwashers 
and nuts[ or nail-type nylon anchors] may be used in lieu of wood screws, expansion shields, or machine screws.]  
In open overhead spaces, cast boxes threaded to raceways need not be separately supported except where used for 
fixture support; support sheet metal boxes directly from building structure or by bar hangers.  Where bar hangers 
are used, attach bar to raceways on opposite sides of box, and support raceway with approved-type fastener maximum<MET>
 610 mm</MET><ENG> 24 inches</ENG> from box.  When penetrating reinforced concrete members, avoid cutting reinforcing steel.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.1.10.1   Boxes</TTL><BRK/>
<BRK/>
<TXT>Boxes for use with raceway systems shall be minimum<MET> 40 mm (1 1/2 inches)</MET><ENG> 1 1/2 inches</ENG> deep, except where shallower 
boxes required by structural conditions are approved.  Boxes for other than lighting fixture outlets shall be 
minimum <MET> 100 mm ( 4 inches)</MET><ENG> 4 inches</ENG> square, except that<MET> 100 by 50 mm (4 by 2 inch)</MET><ENG> 4 by 2 inch</ENG> boxes may be 
used where only one raceway enters outlet.  Telecommunications outlets shall be a minimum of<MET>[ 100 mm square by 
54 mm deep (4 inches square by 2 1/8 inches deep)][ 120 mm square by 54 mm deep (4 11/16 inches square by 2 1/8 
inches)]</MET><ENG>[ 4 inches square by 2 1/8 inches deep][ 4 11/16 inches square by 2 1/8 inches deep]</ENG>[, except for [wall 
mounted telephones] [and] [outlet boxes for handicap telephone stations]].  Mount outlet boxes flush in finished 
walls.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.10.2   Pull Boxes</TTL><BRK/>
<BRK/>
<TXT>Construct of at least minimum size required by <RID>NFPA 70</RID>[ of code-gauge aluminum or galvanized sheet steel,][  
and][ compatible with nonmetallic raceway systems,] except where cast-metal boxes are required in locations specified 
herein.  Provide boxes with screw-fastened covers.  Where several feeders pass through common pull box, tag feeders 
to indicate clearly electrical characteristics, circuit number, and panel designation.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.1.10.3   Extension Rings</TTL><BRK/>
<BRK/>
<TXT>Extension rings are not permitted for new construction.  Use only on existing boxes in concealed conduit systems 
where wall is furred out for new finish.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT><TTL>3.1.11   Mounting Heights</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  In Hazardous Areas extending up to<MET> 455 mm</MET><ENG> 18 inches</ENG> above the finished 
floor, the mounting height of receptacles that are not explosion-proof, must 
be measured to the bottom of the outlet box in lieu of to the center.  Coordinate 
the mounting height with the height indicated on the drawings and use the last 
bracketed sentence.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Mount panelboards,[ enclosed] circuit breakers,[ motor controller] and disconnecting switches so height of operating 
handle at its highest position is maximum<MET> 1980 mm</MET><ENG> 78 inches</ENG> above floor.  Mount lighting switches[ and handicapped 
telecommunications stations][<MET> 1220 mm</MET><ENG> 48 inches</ENG> above finished floor].  Mount receptacles[ and telecommunications 
outlets]<MET> 460 mm</MET><ENG> 18 inches</ENG> above finished floor[, unless otherwise indicated].[  Wall-mounted telecommunications 
outlets shall be mounted at height[<MET> 1525 mm</MET><ENG> 60 inches</ENG> above finished floor][ indicated].] [  Mount other devices 
as indicated.][  Measure mounting heights of wiring devices and outlets[ in non-hazardous areas ]to center of 
device or outlet.][  Measure mounting heights of receptacle outlet boxes in the[ hazardous area][ ________] to 
the bottom of the outlet box.]</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.1.12   Nonmetallic Sheathed Cable Installation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use this paragraph only when Type NM or NMC cable is indicated.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Where possible, install cables concealed behind ceiling or wall finish.  Thread cables through holes bored on 
approximate centerline of wood members; notching of end surfaces is not permitted.  Provide sleeves through concrete 
or masonry for threading cables.  Install exposed cables parallel to or at right angles to walls or structural 
members.  Protect exposed nonmetallic sheathed cables less than<MET> 1220 mm</MET><ENG> 4 feet</ENG> above floors from mechanical injury 
by installation in conduit or tubing.  When cable is used in metal stud construction, insert plastic stud grommets 
in studs at each point through which cable passes, prior to installation of cable.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.1.13   Mineral Insulated, Metal Sheathed (Type MI) Cable Installation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Type MI cable used for low temperature, high temperature, hazardous locations, 
life safety, and heating applications.  Refer to NFPA 70.  Drawings shall clearly 
show the MI cable. Surge suppressors should be considered in hazardous locations 
and where high voltage surges are likely. MI cable is not available in ratings 
above 600 volts.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Mineral-insulated, metal-sheathed cable system, Type MI, may be used in lieu of exposed conduit and wiring.  
Conductor sizes shall be not less than those indicated for the conduit installation.  Cables shall be fastened 
within<MET> 305 mm</MET><ENG> 12 inches</ENG> of each turn or offset and at<MET> 830 mm</MET><ENG> 33 inches</ENG> maximum intervals.  Make cable terminations 
in accordance with <RID>NFPA 70</RID> and cable manufacturer's recommendations.  Single-conductor cables of a circuit, having 
capacities of more than 50 amperes, shall terminate in a single box or cabinet opening.  Individual conductors 
in all outlets and cabinets shall be color-coded.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.1.14   Conductor Identification</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Reference the section providing details of identifying control circuit 
wiring.  Use Section 23 09 53.00 20, SPACE TEMPERATURE CONTROL SYSTEMS and Section 
23 09 54.00 20, DIRECT DIGITAL CONTROL SYSTEMS for Navy projects or Section 
23 09 23, DIRECT DIGITAL CONTROL FOR HVAC AND OTHER LOCAL BUILDING SYSTEMS on 
Army projects.  Choose the last bracketed sentence when a telecommunications 
system is provided in Section 27 10 00, BUILDING TELECOMMUNICATIONS CABLING 
SYSTEMS.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide conductor identification within each enclosure where tap, splice, or termination is made.  For conductors 
No. 6 AWG and smaller diameter, color coding shall be by factory-applied, color-impregnated insulation.  For 
conductors No. 4 AWG and larger diameter, color coding shall be by plastic-coated, self-sticking markers; colored 
nylon cable ties and plates; or heat shrink-type sleeves.  Identify control circuit terminations in accordance 
with[ Section <SRF>23 09 53.00 20</SRF>, SPACE TEMPERATURE CONTROL SYSTEMS.][ Section [_____], [_____]][ Section 
<SRF>23 09 23</SRF>, DIRECT DIGITAL CONTROL FOR HVAC AND OTHER LOCAL BUILDING SYSTEMS][ manufacturer's recommendations].[  
Provide telecommunications system conductor identification as specified in Section <SRF>27 10 00</SRF>, BUILDING TELECOMMUNICATIONS 
CABLING SYSTEMS.]</TXT><BRK/>
<BRK/>
<SPT><TTL>3.1.14.1   Marking Strips</TTL><BRK/>
<BRK/>
<TXT>White or other light-colored plastic marking strips, fastened by screws to each terminal block, shall be provided 
for wire designations.  The wire numbers shall be made with permanent ink.  The marking strips shall be reversible 
to permit marking both sides, or two marking strips shall be furnished with each block.  Marking strips shall 
accommodate the two sets of wire numbers.  Each device to which a connection is made shall be assigned a device 
designation in accordance with <RID>NEMA ICS 1</RID> and each device terminal to which a connection is made shall be marked 
with a distinct terminal marking corresponding to the wire designation used on the Contractor's schematic and 
connection diagrams.  The wire (terminal point) designations used on the Contractor's wiring diagrams and printed 
on terminal block marking strips may be according to the Contractor's standard practice; however, additional 
wire and cable designations for identification of remote (external) circuits shall be provided for the Government's 
wire designations.  Prints of the <SUB>marking strips</SUB> drawings submitted for approval will be so marked and returned 
to the Contractor for addition of the designations to the terminal strips and tracings, along with any rearrangement 
of points required.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.1.15   Splices</TTL><BRK/>
<BRK/>
<TXT>Make splices in accessible locations.  Make splices in conductors No. 10 AWG and smaller diameter with insulated, 
pressure-type connector.  Make splices in conductors No. 8 AWG and larger diameter with solderless connector, 
and cover with insulation material equivalent to conductor insulation.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.1.15.1   Splices of Aluminum Conductors</TTL><BRK/>
<BRK/>
<TXT>Make with solderless circumferential compression-type, aluminum-bodied connectors UL listed for AL/CU.  Remove 
surface oxides from aluminum conductors by wire brushing and immediately apply oxide-inhibiting joint compound 
and insert in connector.  After joint is made, wipe away excess joint compound, and insulate splice.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT>[<TTL>3.1.16   Terminating Aluminum Conductors</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1.16.1   Termination to Copper Bus</TTL><BRK/>
<BRK/>
<TXT>Terminate aluminum conductors to copper bus either by:  (a) inline splicing a copper pigtail, of ampacity at 
least that of aluminum conductor, or (b) utilizing circumferential, compression-type, aluminum-bodied terminal 
lug UL listed for AL/CU, and steel Belleville cadmium-plated hardened steel spring washers, flat washers, bolts, 
and nuts.  Carefully install Belleville spring washers with crown up toward nut or bolt head, with concave side 
of Belleville bearing on heavy-duty, wide series flat washer of larger diameter than Belleville.  Tighten nuts 
sufficiently to flatten Belleville, and leave in position.  Lubricate hardware with joint compound prior to making 
connection.  Wire brush and apply joint compound to conductor prior to inserting in lug.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.16.2   Termination to Aluminum Bus</TTL><BRK/>
<BRK/>
<TXT>Terminate aluminum conductors to aluminum bus by using aluminum nuts, bolts, washers, and compression lugs.  
Wire brush and apply joint compound to conductor prior to inserting in lug.  Lubricate hardware with joint compound 
prior to making connection.  When bus contact surface is unplated, scratch-brush and coat with joint compound, 
without grit.</TXT><BRK/>
<BRK/></SPT>
]</SPT><SPT><TTL>3.1.17   Covers and Device Plates</TTL><BRK/>
<BRK/>
<TXT>Install with edges in continuous contact with finished wall surfaces without use of mats or similar devices.  
Plaster fillings are not permitted.  Install plates with alignment tolerance of<MET> 0.58 mm (1/16 inch)</MET><ENG> 1/16 inch</ENG>
.  Use of sectional-type device plates are not permitted.  Provide gasket for plates installed in wet locations.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.18   Electrical Penetrations</TTL><BRK/>
<BRK/>
<TXT>Seal openings around electrical penetrations through fire resistance-rated walls, partitions, floors, or ceilings 
in accordance with Section <SRF>07 84 00</SRF>, FIRESTOPPING.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.19   Grounding and Bonding</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use reference to NFPA 780 and last bracketed sentence where lightning 
protection is provided.  In addition, size and indicate the grounding electrode 
conductor in accordance with NFPA 780.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide In accordance with <RID>NFPA 70</RID>[ and <RID>NFPA 780</RID>].  Ground exposed, non-current-carrying metallic parts of electrical 
equipment,[ access flooring support system,] metallic raceway systems, grounding conductor in metallic and nonmetallic 
raceways, telecommunications system grounds, [grounding conductor of nonmetallic sheathed cables, ]and neutral 
conductor of wiring systems.[  Make ground connection at main service equipment, and extend grounding conductor 
to point of entrance of metallic water service.  Make connection to water pipe by suitable ground clamp or lug 
connection to plugged tee. If flanged pipes are encountered, make connection with lug bolted to street side of 
flanged connection.  Supplement metallic water service grounding system with additional made electrode in compliance 
with <RID>NFPA 70</RID>.][  Make ground connection to driven ground rods on exterior of building.][  Interconnect all grounding 
media in or on the structure to provide a common ground potential.  This shall include lightning protection, 
electrical service, telecommunications system grounds, as well as underground metallic piping systems.  Interconnection 
to the gas line shall be made on the customer's side of the meter.  Use main size lightning conductors for interconnecting 
these grounding systems to the lightning protection system.]  In addition to the requirements specified herein, 
provide telecommunications grounding in accordance with <RID>TIA J-STD-607-A</RID>.  Where ground fault protection is employed, 
ensure that connection of ground and neutral does not interfere with correct operation of fault protection.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.1.19.1   Ground Rods</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For LANTNAVFACENGCOM Projects:  Use sectional type ground rods only on 
projects at Naval Hospital, Portsmouth, VA.  Do not use chemically charged ground 
rods for Navy projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide cone pointed ground rods.  The resistance to ground shall be measured using the fall-of-potential method 
described in <RID>IEEE Std 81</RID>.  The maximum resistance of a driven ground shall not exceed 25 ohms under normally 
dry conditions.  If this resistance cannot be obtained with a single rod,[ ______] additional rods not less than <MET>
1830 mm (6 feet)</MET><ENG>6 feet</ENG> on centers,[ or if sectional type rods are used,[ _____] additional sections may be coupled 
and driven with the first rod].[  In high-ground-resistance, UL listed chemically charged ground rods may be 
used.]  If the resultant resistance exceeds 25 ohms measured not less than 48 hours after rainfall, notify the 
Contracting Officer who will decide on the number of ground rods to add.</TXT><BRK/>
<BRK/>
 </SPT><SPT><TTL>3.1.19.2   Grounding Connections</TTL><BRK/>
<BRK/>
<TXT>Make grounding connections which are buried or otherwise normally inaccessible,[ excepting specifically those 
connections for which access for periodic testing is required,] by exothermic weld or compression connector.</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Make exothermic welds strictly in accordance with the weld manufacturer's written recommendations.  
Welds which are "puffed up" or which show convex surfaces indicating improper cleaning are not 
acceptable.  Mechanical connectors are not required at exothermic welds.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Make compression connections using a hydraulic compression tool to provide the correct circumferential 
pressure.  Tools and dies shall be as recommended by the manufacturer.  An embossing die code 
or other standard method shall provide visible indication that a connector has been adequately 
compressed on the ground wire.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.19.3   Ground Bus</TTL><BRK/>
<BRK/>
<TXT>A copper ground bus shall be provided in the electrical equipment rooms as indicated. Noncurrent-carrying metal 
parts of[ transformer neutrals and other electrical][ electrical] equipment shall be effectively grounded by 
bonding to the ground bus.  The ground bus shall be bonded to both the entrance ground, and to a ground rod or 
rods as specified above having the upper ends terminating approximately<MET> 100 mm (4 inches)</MET><ENG> 4 inches</ENG> above the 
floor.  Connections and splices shall be of the brazed, welded, bolted, or pressure-connector type, except that 
pressure connectors or bolted connections shall be used for connections to removable equipment.[  For raised 
floor equipment rooms in computer and data processing centers, a minimum of 4, one at each corner, ground buses 
shall be provided and connected to the building grounding system.  Connections shall be bolted type in lieu of 
thermoweld, so they can be changed as required by additions and/or alterations.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.19.4   Resistance</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If difficulties are encountered in obtaining the proper resistance, the 
Contracting Officer will make a decision on the number of ground rods to be 
used, based on local conditions and on the type and size of electrical installation 
in the project.   Insulated grounding conductors will be required where electrolytic 
corrosion may be encountered.   In most applications, it is desirable to have 
a maximum resistance of much less, typically 5 ohms or less.  NFPA 70, approves 
the use of a single made electrode for the system-grounding electrode, if its 
resistance does not exceed 25 ohms.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Maximum resistance-to-ground of grounding system shall not exceed[ 5][ _____] ohms under dry conditions.  Where 
resistance obtained exceeds[ 5][ _____] ohms, contact Contracting Officer for further instructions.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.19.5   Telecommunications System</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: 1.  Include this paragraph when telecommunications service is provided 
in job and specified in this section and other sections.<BRK/>
 2.  Choose the bracketed option for Telecommunication Grounding Busbars (TGB) 
when there are more than one telecommunications room or telecommunications equipment 
rooms included in the project.<BRK/>
 3.  Choose Telecommunications Bonding Conductors bracketed option when more 
than one telecommunications grounding busbar is installed as part of the project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide telecommunications grounding in accordance with the following:</TXT><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Telecommunications Grounding Busbars:  Provide a telecommunications main grounding busbar 
(TMGB) in the telecommunications entrance facility.  The TMGB shall be as close to the electrical 
service entrance grounding connection as practicable.[  Provide a telecommunications grounding 
busbar (TGB) in all other telecommunications rooms and telecommunications equipment rooms.  
The TGB shall be as close to the telecommunications room panelboard as practicable, when equipped.  
Where a panelboard for telecommunications equipment is not installed in the telecommunications 
room, the TGB shall be located near the backbone cabling and associated terminations. In addition, 
the TGB shall be placed to provide for the shortest and straightest routing of the grounding 
conductors.  Where a panelboard for telecommunications equipment is located within the same 
room or space as a TGB, that panelboard’s alternating current equipment ground (ACEG) bus (when 
equipped) or the panelboard enclosure shall be bonded to the TGB.]  Telecommunications grounding 
busbars shall be installed to maintain clearances as required by <RID>NFPA 70</RID> and shall be insulated 
from its support.  A minimum of<MET> 50 mm (2 inches)</MET><ENG> 2 inches</ENG> separation from the wall is recommended 
to allow access to the rear of the busbar and the mounting height shall be adjusted to accommodate 
overhead or underfloor cable routing.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Telecommunications Bonding Conductors:  Provide main telecommunications service equipment 
ground consisting of separate bonding conductor for telecommunications, between the TMGB and 
readily accessible grounding connection of the electrical service.  Grounding and bonding conductors 
should not be placed in ferrous metallic conduit.  If it is necessary to place grounding and 
bonding conductors in ferrous metallic conduit that exceeds <MET>1 m (3 feet)</MET><ENG>3 feet</ENG> in length, the 
conductors shall be bonded to each end of the conduit using a grounding bushing or a No. 6 AWG 
conductor, minimum.[  Provide a telecommunications bonding backbone (TBB) that originates at 
the TMGB extends throughout the building using the telecommunications backbone pathways, and 
connects to the TGBs in all telecommunications rooms and equipment rooms.  The TBB conductors 
shall be installed and protected from physical and mechanical damage.  The TBB conductors should 
be installed without splices and routed in the shortest possible straight-line path.  The bonding 
conductor between a TBB and a TGB shall be continuous.  Where splices are necessary, the number 
of splices should be a minimum and they shall be accessible and located in telecommunications 
spaces.  Joined segments of a TBB shall be connected using exothermic welding, irreversible 
compression-type connectors, or equivalent.  All joints shall be adequately supported and protected 
from damage.  Whenever two or more TBBs are used within a multistory building, the TBBs shall 
be bonded together with a grounding equalizer (GE) at the top floor and at a minimum of every 
third floor in between.  The TBB and GE shall not be connected to the pathway ground, except 
at the TMGB or the TGB.]</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">c.  Telecommunications Grounding Connections:  Telecommunications grounding connections to the 
TMGB[ or TGB] shall utilize listed compression two-hole lugs, exothermic welding, suitable and 
equivalent one hole non-twisting lugs, or other irreversible compression type connections.  
All metallic pathways, cabinets, and racks for telecommunications cabling and interconnecting 
hardware located within the same room or space as the TMGB[ or TGB] shall be bonded to the TMGB[ 
or TGB respectively].  In a metal frame (structural steel) building, where the steel framework 
is readily accessible within the room; each TMGB[ and TGB] shall be bonded to the vertical steel 
metal frame using a minimum No. 6 AWG conductor.  Where the metal frame is external to the room 
and readily accessible, the metal frame shall be bonded to the TGB or TMGB with a minimum No. 
6 AWG conductor.  When practicable because of shorter distances and, where horizontal steel 
members are permanently electrically bonded to vertical column members, the TGB may be bonded 
to these horizontal members in lieu of the vertical column members.  All connectors used for 
bonding to the metal frame of a building shall be listed for the intended purpose.</ITM><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.1.20   Equipment Connections</TTL><BRK/>
<BRK/>
<TXT>Provide power wiring for the connection of motors and control equipment under this section of the specification.  
Except as otherwise specifically noted or specified, automatic control wiring, control devices, and protective 
devices within the control circuitry are not included in this section of the specifications but shall be provided 
under the section specifying the associated equipment.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.21   Elevator</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  To achieve a complete specification, the electrical designer shall ensure 
that the controls for HVAC, fire alarm system, elevators, cranes, and special 
systems are definitely and properly covered by the other sections of the project 
specification.  Should controls appear in this section of the project specification, 
this paragraph shall be modified accordingly.  The drawings shall indicate required 
equipment connections.  Elevator paragraph shall be coordinated with Section 
14 21 00.00 20, ELECTRIC TRACTION ELEVATORS for Navy projects, Section 14 20 
00, ELEVATORS, ELECTRIC and Section 14 24 00, HYDRAULIC ELEVATORS for all projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
 <TXT>Provide circuit to line terminals of elevator controller, and disconnect switch on line side of controller, outlet 
for control power, outlet receptacle and work light at midheight of elevator shaft, and work light and outlet 
receptacle in elevator pit.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.1.22   Government-Furnished Equipment</TTL><BRK/>
<BRK/>
<TXT>Contractor[ shall rough-in for Government-furnished equipment][ shall make connections to Government-furnished 
equipment] to make equipment operate as intended, including providing miscellaneous items such as plugs, receptacles, 
wire, cable, conduit, flexible conduit, and outlet boxes or fittings.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.1.23   Repair of Existing Work</TTL><BRK/>
<BRK/>
<TXT>Repair of existing work[, demolition, and modification of existing electrical distribution systems] shall be 
performed as follows:</TXT><BRK/>
<BRK/>
<SPT><TTL>3.1.23.1   Workmanship</TTL><BRK/>
<BRK/>
<TXT>Lay out work in advance.  Exercise care where cutting, channeling, chasing, or drilling of floors, walls, partitions, 
ceilings, or other surfaces is necessary for proper installation, support, or anchorage of conduit, raceways, 
or other electrical work.  Repair damage to buildings, piping, and equipment using skilled craftsmen of trades 
involved.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.1.23.2   Existing Concealed Wiring to be Removed</TTL><BRK/>
<BRK/>
<TXT>Existing concealed wiring to be removed shall be disconnected from its source.  Remove conductors; cut conduit 
flush with floor, underside of floor, and through walls; and seal openings.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.1.23.3   Removal of Existing Electrical Distribution System</TTL><BRK/>
<BRK/>
<TXT>Removal of existing electrical distribution system equipment shall include equipment's associated wiring, including 
conductors, cables, exposed conduit, surface metal raceways, boxes, and fittings,[ back to equipment's power 
source] as indicated.</TXT><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>3.1.23.4   Continuation of Service</TTL><BRK/>
<BRK/>
<TXT>Maintain continuity of existing circuits of equipment to remain.  Existing circuits of equipment shall remain 
energized.  Circuits which are to remain but were disturbed during demolition shall have circuits wiring and 
power restored back to original condition.</TXT><BRK/>
<BRK/>
]</SPT></SPT><SPT>[<TTL>3.1.24   Watthour Meters</TTL><BRK/>
<BRK/>
<TXT><RID>NEMA C12.1</RID>.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>3.1.25   Surge Protective Devices</TTL><BRK/>
<BRK/>
<TXT>Connect the surge protective devices in parallel to the power source, keeping the conductors as short and straight 
as practically possible.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.2   FIELD FABRICATED NAMEPLATE MOUNTING</TTL><BRK/>
<BRK/>
<TXT>Provide number, location, and letter designation of nameplates as indicated.  Fasten nameplates to the device 
with a minimum of two sheet-metal screws or two rivets.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3   WARNING SIGN MOUNTING</TTL><BRK/>
<BRK/>
<TXT>Provide the number of signs required to be readable from each accessible side.  Space the signs in accordance 
with <RID>NFPA 70E</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4   FIELD APPLIED PAINTING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use and coordinate paint and coating requirements with Section 09 90 
00, PAINTS AND COATINGS when provided in the job.  Use the second bracketed 
option when Section 09 90 00 is not provided or when requirements are beyond 
what is specified in Section 09 90 00.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Paint electrical equipment as required to match finish of adjacent surfaces or to meet the indicated or specified 
safety criteria.  [Painting shall be as specified in Section <SRF>09 90 00</SRF>, PAINTS AND COATINGS.][Where field painting 
of enclosures for panelboards, load centers or the like is specified to match adjacent surfaces, to correct damage 
to the manufacturer's factory applied coatings, or to meet the indicated or specified safety criteria, provide 
manufacturer's recommended coatings and apply in accordance to manufacturer's instructions.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5   FIELD QUALITY CONTROL</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide any additional test requirements for equipment requiring running 
tests or tests that shall be coordinated with mechanical equipment.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Furnish test equipment and personnel and submit written copies of test results.  Give Contracting Officer[ 5][ 
_____] working days notice prior to[ each][ _____] test[s].</TXT><BRK/>
<BRK/>
<SPT><TTL>3.5.1   Devices Subject to Manual Operation</TTL><BRK/>
<BRK/>
<TXT><TST>Each device subject to manual operation shall be operated at least five times, demonstrating satisfactory operation 
each time.</TST></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.2   <SUB>600-Volt Wiring Test</SUB></TTL><BRK/>
<BRK/>
<TXT><TST>Test wiring rated 600 volt and less to verify that no short circuits or accidental grounds exist.  Perform insulation 
resistance tests on wiring No. 6 AWG and larger diameter using instrument which applies voltage of approximately 
500 volts to provide direct reading of resistance.</TST>  Minimum resistance shall be 250,000 ohms.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.3   <SUB>Transformer Tests</SUB></TTL><BRK/>
<BRK/>
<TXT>Perform the standard, not optional, tests in accordance with the Inspection and Test Procedures for transformers, 
dry type, air-cooled, 600 volt and below; as specified in <RID>NETA ATS</RID>.  Measure primary and secondary voltages for 
proper tap settings.  Tests need not be performed by a recognized independent testing firm or independent electrical 
consulting firm.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.4   <SUB>Ground-Fault Receptacle Test</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If Ground-Fault Receptacle "line" and "load" leads are reversed, "test" 
will trip downstream loads but not trip the receptacle.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT><TST>Test ground-fault receptacles with a "load" (such as a plug in light) to verify that the "line" and "load" leads 
are not reversed.</TST></TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.5   <SUB>Grounding System Test</SUB></TTL><BRK/>
<BRK/>
<TXT><TST>Test grounding system to ensure continuity, and that resistance to ground is not excessive.</TST>  Test each ground 
rod for resistance to ground before making connections to rod; tie grounding system together and test for resistance 
to ground.  Make resistance measurements in dry weather, not earlier than 48 hours after rainfall.  Submit written 
results of each test to Contracting Officer, and indicate location of rods as well as resistance and soil conditions 
at time measurements were made.</TXT><BRK/>
<BRK/></SPT>
<SPT>[<TTL>3.5.6   Watthour Meter</TTL><BRK/>
<BRK/>
<ITM INDENT="-0.33">a.  Visual and mechanical inspection</ITM><BRK/>
<BRK/>
<ITM>(1)  Examine for broken parts, shipping damage, and tightness of connections.</ITM><BRK/>
<BRK/>
<ITM>(2)  Verify that meter type, scales, and connections are in accordance with approved shop drawings.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">b.  Electrical tests</ITM><BRK/>
<BRK/>
<ITM>(1)  Determine accuracy of meter.</ITM><BRK/>
<BRK/>
<ITM>(2)  Calibrate watthour meters to one-half percent.</ITM><BRK/>
<BRK/>
<ITM>(3)  Verify that correct multiplier has been placed on face of meter, where applicable.</ITM><BRK/>
<BRK/>
]</SPT></SPT></PRT>    <END/><BRK/></SEC>