<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA      UFGS-26 36 23.00 20 (April 2006)<BRK/>
                                    ------------------------------<BRK/>
Preparing Activity:  <PRA>NAVFAC</PRA>         Replacing without change<BRK/>
                                    UFGS-16410N (February 2003)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 26 36 23.00 20</SCN><BRK/>
<BRK/>
<STL>AUTOMATIC TRANSFER SWITCHES</STL><BRK/>
<DTE>04/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>automatic transfer 
switches intended for use in Emergency Electrical Power Systems meeting requirements 
of NFPA 70, NFPA 99, and MIL-HDBK-1191</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following system design requirements shall be adhered to when providing 
automatic transfer switches:<BRK/>
<BRK/>
1.   Provide four-pole transfer switches.  The neutral conductor for each source 
of supply, including the neutral on separately derived systems, shall be switched 
by the transfer switch.<BRK/>
<BRK/>
2.   Do not install transfer switches on the supply side of service equipment.  
When the transfer switch is to be located on the supply side of service loads, 
provide an independent service overcurrent protection device on the supply side 
of the transfer switch.<BRK/>
<BRK/>
3.   Do not use open type transfer switches installed in other equipment such 
as switchboards, or as part of the service equipment.</NPR><BRK/>
<AST/><BRK/></NTE>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following information shall be shown on the project drawings:</NPR><BRK/>
<BRK/>
<NPR>1.  The available fault current at the bus feeding the automatic transfer switch.</NPR><BRK/>
<BRK/>
<NPR>2.  The rating of the overcurrent device protecting the automatic transfer switch.</NPR><BRK/>
<BRK/>
<NPR>3.  Identify automatic transfer switches to be provided with By-pass/Isolation 
Switches, when applicable.</NPR><BRK/>
<BRK/>
<NPR>4.  Identify control type, i.e., Utility-Generator, Preferred Utility Source, 
or Generator-Generator, for each automatic transfer switch.</NPR><BRK/>
<BRK/>
<NPR>5.  Identify automatic transfer switches to be provided with "transfer time 
delay" and "time delay transition" or "in-phase monitor" features, where applicable.</NPR><BRK/>
<BRK/>
<NPR>6.  Identify automatic transfer switches to be used for fire pump service, when 
applicable.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification. The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
 <BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
 <BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)</ORG><BRK/><BRK/><RID>NETA ATS</RID><RTL>(2003) Acceptance Testing Specifications</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 1008</RID><RTL>(1996; Rev thru Dec 2007) Standard for Transfer Switch Equipment</RTL><BRK/><BRK/><RID>UL 508</RID><RTL>(1999; Rev thru Sep 2008) Standard for Industrial Control Equipment</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   RELATED REQUIREMENTS</TTL><BRK/>
<BRK/>
<TXT>Section <SRF>26 00 00.00 20</SRF> BASIC ELECTRICAL MATERIALS AND METHODS, and Section <SRF>26 08 00</SRF> APPARATUS INSPECTION AND 
TESTING, apply to this section, with the additions and modifications specified herein.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy,  Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are [for Contractor Quality Control approval.][for information only.  When used, a designation following the 
"G" designation identifies the office that will review the submittal for the Government.]  The following shall 
be submitted in accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Automatic Transfer Switch Drawings</SUB>; <SUB>G</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB> Automatic Transfer Switches</SUB>; <SUB>G</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Acceptance Checks and Tests</SUB>; <SUB>G</SUB></ITM><BRK/>
<BRK/>
<ITM><SUB>Functional Acceptance Tests</SUB>; <SUB>G</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Proof of Listing</SUB>; <SUB>G</SUB></ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Automatic Transfer Switches</SUB>, Data Package 5; <SUB>G</SUB></ITM><BRK/>
<BRK/>
<ITM>  Submit in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE DATA.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.4.1   <SUB>Proof of Listing</SUB></TTL><BRK/>
<BRK/>
<TXT>Submit proof of listing by <RID>UL 1008</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4.2   <SUB>Automatic Transfer Switch Drawings</SUB></TTL><BRK/>
<BRK/>
<TXT>Drawings shall include outline, arrangement, and detail drawings.  Detail drawings shall include manufacturer's 
name and catalog number, electrical ratings, total system transfer statement, reduced normal supply voltage at 
which transfer to the alternate supply is initiated, transfer delay times, short-circuit current rating, wiring 
diagram, description of interconnections, testing instructions, acceptable conductor type for terminals, tightening 
torque for each wire connector, and other required <RID>UL 1008</RID> markings.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   <SUB>AUTOMATIC TRANSFER SWITCHES</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the following options for switches to be installed in facilities 
complying with MIL-HDBK-1191, DOD Medical and Dental Treatment Facilities Design 
and Construction Guide: (a) "Switches utilizing circuit breakers are not acceptable"; 
(b) "Automatic Transfer Switches provided with a by-pass/isolation switch shall 
be mounted on a drawout mechanism so that the automatic transfer switch can 
be removed from the enclosure".</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide four-pole, automatic transfer switches for use in emergency systems in accordance with <RID>UL 1008</RID>.  Each 
automatic transfer switch shall be rated for total system transfer and have the current and voltage ratings as 
indicated.  The rating of the switch shall be adequate for withstanding the effects of the indicated RMS symmetrical 
fault current when protected by the indicated overcurrent device without contact welding.  The switch operating 
mechanism shall be electrically operated from the source to which it is transferring, shall have quick-make, 
quick-break, load break contacts, and shall be mechanically held in both positions.  [Switches utilizing circuit 
breakers are not acceptable.]  Non-fire pump service transfer switches shall have manual operating means provided 
for maintenance and servicing accessible only by opening the enclosure.  [Transfer switches for fire pump service 
shall have manual operating means externally operable without opening the enclosure.]  The manual operating means 
shall affect the opening and closing of the switch contacts at the same rate of speed as that caused by the automatic 
operation of the switch.  [Automatic transfer switches provided with by-pass/isolation switches shall be mounted 
on a drawout mechanism so that the automatic transfer switch can be removed from the enclosure.]  [The switch 
enclosure shall comply with <RID>UL 508</RID>, NEMA Type [1], [12],[____], and shall be equipped with an equipment ground 
lug.]</TXT><BRK/>
<BRK/>
<SPT>[<TTL>2.1.1   By-Pass/Isolation Switches</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE: Include by-pass/isolation switches only where the nature of the loads 
make continuance of power essential when the associated ATS switch is disconnected 
for repairs, preventive maintenance, or testing.  Provide by-pass/isolation 
switches for automatic transfer switches to be installed in facilities complying 
with MIL-HDBK-1191, DOD Medical and Dental treatment Facilities Design and Construction 
Guide.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Include by-pass/isolation switches for the indicated automatic transfer switches.  Provide by-pass/isolation 
switches in accordance with <RID>UL 1008</RID> that can be used to manually select an available power source to feed load 
circuits and to permit total isolation of the automatic transfer switch.  The by-pass/isolation switch shall 
be rated for total system transfer and have the same current rating, voltage rating, number of poles, and withstand 
and closing rating as the associated automatic transfer switch.</TXT><BRK/>
<BRK/>
]</SPT><SPT><TTL>2.1.2   Automatic Transfer Switch Controls</TTL><BRK/>
<BRK/>
<SPT>[<TTL>2.1.2.1   Controls for Utility-Generator Automatic Transfer Switch</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following paragraph is intended for use when the automatic transfer 
switch is to be used for transferring loads to an emergency generator upon loss 
of the normal (utility) source.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide all necessary controls to start the generator set upon loss of the normal (utility) source, transfer 
the load to the generator set upon reaching rated voltage and frequency, re-transfer the load when the normal 
(utility) source returns, and stop the generator set.</TXT><BRK/>
<BRK/>
<TXT>The switch shall include the following control features.</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Three-phase normal source voltage sensing circuit with adjustable dropout, 75-93 percent of nominal, 
and pickup, 85-100 percent of nominal.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Engine starting control contacts with adjustable commit-to-start delay circuit, 0.5-6.0 seconds.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Voltage/frequency sensing circuit, set for 80 percent of nominal, for enabling load transfer to emergency 
source.</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide transfer to emergency source time delay for the transfer switches 
requiring delayed-automatic operation.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">[d.  Transfer to emergency source time delay for transfer switches as indicated, adjustable 0-5 minutes.]</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">e.  Re-transfer to normal source time delay, adjustable 1-30 minutes.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">f.  Programmable exerciser to allow automatic starting of the generator set and subsequent load transfer.  
Exercise periods shall be selectable for 1 to 24 hours per day for 0 to 7 days a week.</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When the transferred load includes motors (over 50 HP or over 5 HP without 
significant resistive loads), select the following option.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">[g.  Adjustable time delay transition or in-phase monitor feature for indicated transfer switches to 
allow safe transfer of highly inductive loads between two non-synchronized sources.]</LST><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.2.2   Controls for Generator - Generator Source Automatic Transfer Switch</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following paragraph is intended for use when a second automatic transfer 
switch is to be used to select between two generators in a three source (utility-generator-generator) 
system.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide all necessary controls to start both generator sets upon loss of the normal utility source, transfer 
the load to the first generator set to reach rated voltage and frequency, shutdown the second generator set upon 
transferring the load to the first generator set, restarting and transferring the load to the second generator 
if at any time the first generator set fails, re-transfer the load when the normal (utility) source returns, 
and shut down the generator set.  The switch shall include the following control features;</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Engine starting control contacts.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Voltage/frequency sensing circuit, set for 80 percent of nominal for enabling load transfer to emergency 
source.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Programmable exerciser time to allow automatic starting of the generator sets and subsequent load 
transfer to each generator set. Exercise periods shall be selectable for 1 to 24 hours per day for 0 
to 7 days a week.</LST><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.2.3   Controls for Preferred Utility Source Automatic Transfer Switch</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following paragraph is intended for use when the automatic transfer 
switch is to be used for selecting between two utility sources (preferred and 
alternate).</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide all the necessary controls to transfer the load to the alternate utility source upon loss of the preferred 
utility source and re-transfer the load to the preferred utility source when the preferred utility source returns.  
The switch shall include the following control features.</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Three-phase preferred and alternate source voltage sensing circuit with adjustable dropout, 75-98 
percent of nominal, and pick-up, 85-100 percent of nominal.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Re-transfer to normal source time delay, adjustable 1-30 minutes.</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  When the transferred load includes motors(over 50 HP or over 5 HP without 
significant resistive loads) select the following option.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">[c.  Adjustable time delay transition or in-phase monitor feature for indicated transfer switches to 
allow safe transfer of highly inductive loads between two non-synchronized sources.]</LST><BRK/>
<BRK/>
]</SPT><SPT>[<TTL>2.1.2.4   Controls for Fire Pump Service Automatic Transfer Switch</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following  paragraph is intended for use when the automatic transfer 
switch is to be used for fire pump service.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide the following additional controls features:</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Phase reversal of the normal source shall initiate transfer to the emergency/alternate source.]</LST><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.1.3   Front Panel Devices</TTL><BRK/>
<BRK/>
<TXT>Provide devices mounted on cabinet front consisting of:</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Mode selector switch with the following positions and associated functions;</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  TEST - Simulates loss of normal/preferred source system operation.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  NORMAL - Transfers system to normal/preferred source bypassing re-transfer time delay.</ITM><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Lamps for indicating connected source and normal/preferred source is available.</LST><BRK/>
<BRK/>
<LST INDENT="-0.33">c.  Auxiliary contacts for indicating connected source and normal/preferred source available.</LST><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select option for preferred source selector switch when specifying preferred 
utility source automatic transfer switches.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">[d.  Source selector switch with the following positions and associated functions.</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Source 1 - Selects Source 1 as the source to which the automatic transfer switch will transfer 
if that source is available.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  Source 2 - Selects source 2 as the source to which the automatic transfer switch will transfer 
if that source is available.]</ITM><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the following option when specifying by-pass/isolation switches.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<LST INDENT="-0.33">[e.  Lamps for indicating that the by-pass/isolation switch is in the "normal by-pass", "alternate by-pass", 
or "isolated" position.</LST><BRK/>
<BRK/>
]</SPT></SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   INSTALLATION</TTL><BRK/>
<BRK/>
<TXT>Installation shall conform to the requirements of <RID>NFPA 70</RID> and manufacturer's recommendation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   PREREQUISITES FOR FUNCTIONAL ACCEPTANCE TESTING</TTL><BRK/>
<BRK/>
<TXT>Completion of the following requirements is mandatory prior to scheduling functional acceptance tests for the 
automatic transfer switch.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.2.1   Performance of Acceptance Checks and tests</TTL><BRK/>
<BRK/>
<TXT>Complete as specified in paragraph entitled "Acceptance Checks and Tests".  The Acceptance Checks and Tests shall 
be accomplished by the Testing organization as described in Section <SRF>26 08 00</SRF> APPARATUS INSPECTION AND TESTING.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.2   Manufacturers O&amp;M Information</TTL><BRK/>
<BRK/>
<TXT>The manufacturers O&amp;M information required by the paragraph entitled "SD-10 Operation and Maintenance Data", 
shall have been submitted to and approved by the Contracting Officer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.3   Test Equipment</TTL><BRK/>
<BRK/>
<TXT>All test equipment and instruments shall be on hand prior to scheduling field tests, or subject to Contracting 
Officer's approval, evidence shall be provided to show that arrangements have been made to have the necessary 
equipment and instruments on site prior to field testing.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.3   FIELD QUALITY CONTROL</TTL><BRK/>
<BRK/>
<TXT>Give Contracting Officer 15 days notice of dates and times scheduled for tests which require the presence of 
the Contracting Officer.  The Contracting Officer will coordinate with the using activity and schedule a time 
that will eliminate or minimize interruptions and interference with the activity operations.  The contractor 
shall be responsible for costs associated with conducting tests outside of normal working hours and with incorporating 
special arrangements and procedures, including temporary power conditions.  The contractor shall provide labor, 
equipment, apparatus, including test load, and consumables required for the specified tests.  Calibration of 
all measuring devices and indicating devices shall be certified.  The test load shall be a cataloged product 
in accordance with Section <SRF>26 00 00.00 20</SRF> BASIC ELECTRICAL MATERIALS AND METHODS.  Perform the following field 
tests in accordance with the manufacturer's recommendations and include the following visual and mechanical inspections 
and electrical tests, performed in accordance with <RID>NETA ATS</RID>.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.3.1   Automatic Transfer Switch <SUB>Acceptance Checks and Tests</SUB></TTL><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Visual and Mechanical Inspection</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Compare equipment nameplate data with specifications and approved shop drawings.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  Inspect physical and mechanical condition.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Confirm correct application of manufacturer's recommended lubricants.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">4.  Verify that manual transfer warnings are attached and visible.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">5.  Verify tightness of all control connections.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">6.  Verify tightness of accessible bolted connections by calibrated torque-wrench method.  Thermographic 
survey is not required. </ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">7.  Perform manual transfer operation.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">8.  Verify positive mechanical interlocking between normal and alternate sources.</ITM><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Electrical Tests</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Measure contact-resistance.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  Perform insulation-resistance on each pole, phase-to-phase and phase-to-ground with switch 
closed, and across each open pole for one minute.  Perform tests in both source positions.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Verify settings and operations of control devices.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">4.  Calibrate and set all relays and timers.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.2   <SUB>Functional Acceptance Tests</SUB></TTL><BRK/>
<BRK/>
<TXT>Functional Acceptance Tests shall[ be coordinated with Section <SRF>26 32 13.00 20</SRF> SINGLE OPERATION GENERATOR SETS 
and shall] include simulating power failure and demonstrating the following operations for each automatic transfer 
switch.  Contractor shall show by demonstration in service that the automatic transfer switches are in good operating 
condition, and function not less than five times.</TXT><BRK/>
<BRK/>
<LST INDENT="-0.33">a.  Perform automatic transfer tests:</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Simulate loss of normal/preferred power.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  Return to normal/preferred power.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Simulate loss of emergency power.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">4.  Simulate all forms of single-phase conditions.</ITM><BRK/>
<BRK/>
<LST INDENT="-0.33">b.  Verify correct operation and timing of the following functions:</LST><BRK/>
<BRK/>
<ITM INDENT="-0.33">1.  Normal source voltage-sensing relays.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">2.  Engine start sequence.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">3.  Time delay upon transfer.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">4.  Alternate source voltage-sensing relays.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">5.  Automatic transfer operation.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">6.  Interlocks and limit switch function.</ITM><BRK/>
<BRK/>
<ITM INDENT="-0.33">7.  Time delay and retransfer upon normal power restoration.</ITM><BRK/>
<BRK/></SPT>
</SPT></PRT>    <END/><BRK/></SEC>