<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><BRK/>
<HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA         UFGS-26 41 01.00 10 (November 2008)<BRK/>
                                       -----------------------------------<BRK/>
Preparing Activity:  <PRA>USACE</PRA>             Superseding<BRK/>
                                       UFGS-26 41 01.00 10 (April 2006)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 26 41 01.00 10</SCN><BRK/>
<BRK/>
<STL>LIGHTNING PROTECTION SYSTEM</STL><BRK/>
<DTE>11/08</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>lightning protection 
systems for buildings and other structures</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification.  The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
<BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
<BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)</ORG><BRK/><BRK/><RID>IEEE C135.30</RID><RTL>(1988) Zinc-Coated Ferrous Ground Rods for Overhead or Underground Line Construction</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/><RID>NFPA 780</RID><RTL>(2007) Standard for the Installation of Lightning Protection Systems</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 467</RID><RTL>(2007) Standard for Grounding and Bonding Equipment</RTL><BRK/><BRK/><RID>UL 96</RID><RTL>(2005) Standard for Lightning Protection Components</RTL><BRK/><BRK/><RID>UL 96A</RID><RTL>(2007) Standard for Installation Requirements for Lightning Protection Systems</RTL><BRK/><BRK/><RID>UL Electrical Constructn</RID><RTL>(2008) Electrical Construction Equipment Directory</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section <SRF>01 33 00</SRF> SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy, Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are for [Contractor Quality Control approval.] [information only.  When used, a designation following the "G" 
designation identifies the office that will review the submittal for the Government.]  Submit the following in 
accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Detail Drawings</SUB></ITM><BRK/>
<BRK/>
<ITM>  Detail drawings, as specified.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Materials</SUB></ITM><BRK/>
<BRK/>
<ITM>  Proof of compliance with requirements of UL, where material or equipment is specified to comply.  
The label of or listing in <RID>UL Electrical Constructn</RID> will be acceptable evidence.  In lieu of 
the label or listing, a written certificate from an approved nationally recognized testing organization 
equipped to perform such services, stating that the items have been tested and conform to the 
requirements and testing methods of Underwriters Laboratories may be submitted.  Submit a letter 
of findings certifying UL inspection of lightning protection systems provided on the following 
facilities:  [_____].</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<TXT>Submit <SUB>detail drawings</SUB> consisting of a complete list of material, including manufacturer's descriptive and technical 
literature, catalog cuts, drawings, and installation instructions.  Detail drawings shall demonstrate that the 
system has been coordinated and will function as a unit.  Drawings shall show proposed layout and mounting and 
relationship to other parts of the work.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   STANDARD PRODUCTS</TTL><BRK/>
<BRK/>
<TXT>Proide a system consisting of the standard products of a manufacturer regularly engaged in the production of 
lightning protection systems and which is the manufacturer's latest UL approved design.  The lightning protection 
system shall conform to <RID>NFPA 70</RID> and <RID>NFPA 780</RID>, <RID>UL 96</RID> and <RID>UL 96A</RID>, except where requirements in excess thereof are 
specified herein.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2   <SUB>MATERIALS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer will list facilities requiring certification of UL inspection.  
The list is to include all Army facilities used for manufacturing, processing, 
handling or storing explosives, ammunition or explosive ingredients.  On all 
other Army facilities and on Air Force facilities, this requirement will be 
deleted unless specifically requested by the facility user.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.2.1   General Requirements</TTL><BRK/>
<BRK/>
<TXT>Do not use any combination of materials that form an electrolytic couple of such nature that corrosion is accelerated 
in the presence of moisture, unless moisture is permanently excluded from the junction of such metals.  Where 
unusual conditions exist, which would cause corrosion of conductors, use conductors with protective coatings 
or oversize conductors.  Where a mechanical hazard is involved, increase the conductor size to compensate for 
the hazard or protect the conductors by covering them with molding or tubing made of wood or nonmagnetic material.  
When metallic conduit or tubing is used, the conductor shall be electrically connected at the upper and lower 
ends.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.2   Main and Secondary Conductors</TTL><BRK/>
<BRK/>
<TXT>Conductors shall be in accordance with <RID>NFPA 780</RID> and <RID>UL 96</RID> for Class I, Class II, or Class II modified materials 
as applicable.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.2.1   Copper</TTL><BRK/>
<BRK/>
<TXT>Copper conductors used on nonmetallic stacks shall weigh not less than<MET> 170 kg/300 m</MET><ENG> 375 pounds/thousand feet</ENG>, 
and the size of any wire in the cable shall be not less than No. 15 AWG.  The thickness of any web or ribbon 
used on stacks shall be not less than No. 12 AWG.  Counterpoise shall be copper conductors not smaller than No. 
1/0 AWG.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.2.2   Aluminum</TTL><BRK/>
<BRK/>
<TXT>Aluminum shall not contact the earth nor shall it be used in any other manner that will contribute to rapid deterioration 
of the metal.  Appropriate precautions shall be observed at connections with dissimilar metals.  Aluminum conductors 
for bonding and interconnecting metallic bodies to the main cable shall be at least equivalent to strength and 
cross-sectional area of a No. 4 AWG aluminum wire.  When perforated strips are provided, strips that are much 
wider than solid strips shall be.  A strip width that is at least twice that of the diameter of the perforations 
shall be used.  Aluminum strip for connecting exposed water pipes shall be not less than No. 12 AWG in thickness 
and at least<MET> 38.1 mm</MET><ENG> 1-1/2 inch</ENG> wide.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2.3   Air Terminals</TTL><BRK/>
<BRK/>
<TXT>Terminals shall be in accordance with <RID>UL 96</RID> and <RID>NFPA 780</RID>.  The tip of air terminals on buildings used for manufacturing, 
processing, handling, or storing explosives, ammunition, or explosive ingredients shall be a minimum of<MET> 600 mm</MET><ENG>
 2 feet</ENG> above the ridge parapet, ventilator or perimeter.  On open or hooded vents emitting explosive dusts or 
vapors under natural or forced draft, air terminals shall be a minimum of<MET> 1.5 m</MET><ENG> 5 feet</ENG> above the opening.  On 
open stacks emitting explosive dusts, gases, or vapor under forced draft, air terminals shall extend a minimum 
of<MET> 4.5 m</MET><ENG> 15 feet</ENG> above vent opening.  Air terminals more than<MET> 600 mm</MET><ENG> 24 inch</ENG> in length shall be supported by 
a suitable brace, with guides not less than one-half the height of the terminal.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.4   Ground Rods</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Designer will determine type and number of ground rods to be used; based 
on local conditions, earth resistivity data, and on the size and type of the 
electrical installation.  Copper clad steel rods will be specified for normal 
conditions.  Galvanized coated steel or stainless steel rods will be used where 
low soil resistivities are encountered and galvanic corrosion may occur between 
adjacent underground metallic masses and the copper-clad rods.  Stainless steel 
rods have a longer life than the zinc coated steel, but use must be justified 
based on the higher cost.  In high resistivity soils, 3.048 m (10 foot) sectional 
rods may be used to obtain the required resistance to ground; however where 
rock is encountered, additional rods, a counterpoise, or ground grid may be 
necessary.  Coordinate and standardize rod selection for individual facilities 
with other specification sections.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Rods made of [copper-clad steel] [stainless steel] [solid copper] shall conform to <RID>UL 467</RID> and galvanized ferrous 
rods shall conform to <RID>IEEE C135.30</RID>.  Ground rods shall be not less than<MET>19 mm</MET><ENG> 3/4 inch</ENG> in diameter and<MET> 3.048 m</MET><ENG>
 10 feet</ENG> in length.  Ground rods of copper-clad steel, stainless steel, galvanized ferrous, and solid copper 
shall not be mixed on the job.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.5   Connectors</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The bracketed area in this paragraph is only required on Air Force projects 
which have a facility which manufactures. processes, handles or stores explosives, 
ammunition or explosive ingredients.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Clamp-type connectors for splicing conductors shall conform to <RID>UL 96</RID>, class as applicable, and, Class 2, style 
and size as required for the installation.  [Clamp-type connectors shall only be used for the connection of the 
roof conductor to the air terminal and to the guttering.  All other connections, bonds, and splices shall be 
done by exothermic welds or by high compression fittings.  The exothermic welds and high compression fittings 
shall be listed for the purpose.  The high compression fittings shall be the type which require a hydraulically 
operated mechanism to apply a minimum of 10,000 psi.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.6   Lightning Protection Components</TTL><BRK/>
<BRK/>
<TXT>Lightning protection components, such as bonding plates, air terminal supports, chimney bands, clips, and fasteners 
shall conform to <RID>UL 96</RID>, classes as applicable.</TXT><BRK/>
<BRK/></SPT>
</SPT></PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   EXAMINATION</TTL><BRK/>
<BRK/>
<TXT>After becoming familiar with all details of the work, verify all dimensions in the field, and advise the Contracting 
Officer of any discrepancy before performing the work.  No departures shall be made without the prior approval 
of the Contracting Officer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   INTEGRAL SYSTEM</TTL><BRK/>
<BRK/>
<SPT><TTL>3.2.1   General Requirements</TTL><BRK/>
<BRK/>
<TXT>Provide a lightning protection system consisting of air terminals, roof conductors, down conductors, ground connections, 
and grounds, electrically interconnected to form the shortest distance to ground.  All conductors on the structures 
shall be exposed except where conductors are in protective sleeves exposed on the outside walls.  Secondary conductors 
shall interconnect with grounded metallic parts within the building.  Interconnections made within side-flash 
distances shall be at or above the level of the grounded metallic parts.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.2.1.1   Air Terminals</TTL><BRK/>
<BRK/>
<TXT>Air terminal design and support shall be in accordance with <RID>NFPA 780</RID>.  Terminals shall be rigidly connected to, 
and made electrically continuous with, roof conductors by means of pressure connectors or crimped joints of T-shaped 
malleable metal and connected to the air terminal by a dowel or threaded fitting.  Air terminals at the ends 
of the structure shall be set not more than<MET> 600 mm</MET><ENG> 2 feet</ENG> from the ends of the ridge or edges and corners of 
roofs.  Spacing of air terminals<MET> 600 mm</MET><ENG> 2 feet</ENG> in height on ridges, parapets, and around the perimeter of buildings 
with flat roofs shall not exceed<MET> 7.5 m</MET><ENG> 25 feet</ENG>.  In specific instances where it is necessary to exceed this spacing, 
the specified height of air terminals shall be increased not less than<MET> 50 mm</MET><ENG> 2 inch</ENG> for each<MET> 300 mm</MET><ENG> foot</ENG> of increase 
over<MET> 7.5 m</MET><ENG> 25 feet</ENG>.  On large, flat or gently sloping roofs, as defined in <RID>NFPA 780</RID>, air terminals shall be placed 
at points of the intersection of imaginary lines dividing the surface into rectangles having sides not exceeding<MET>
 15 m</MET><ENG> 50 feet</ENG> in length.  Air terminals shall be secured against overturning either by attachment to the object 
to be protected or by means of a substantial tripod or other braces permanently and rigidly attached to the building 
or structure.  Metal projections and metal parts of buildings, smokestacks, and other metal objects that do not 
contain hazardous materials and that may be struck but not appreciably damaged by lightning, need not be provided 
with air terminals.  However, these metal objects shall be bonded to the lightning conductor through a metal 
conductor of the same unit weight per length as the main conductor.  [Where metal ventilators are installed, 
air terminals shall be mounted thereon, where practicable.  Any air terminal erected by necessity adjacent to 
a metal ventilator shall be bonded to the ventilator near the top and bottom.]  Where metal ventilators are installed 
with air terminals mounted thereon, the air terminal shall not be more than<MET> 610 mm</MET><ENG> 24 inch</ENG> away from the farther 
edge or corner.  If the air terminal is farther than this distance, an additional air terminal shall be added 
in order to meet this requirement.  Where metal ventilators are installed with air terminals mounted adjacent, 
the air terminal shall not be more than<MET> 610 mm</MET><ENG> 24 inches</ENG> away from the farther edge or corner.  If the air terminal 
is farther than this distance, an additional air terminal shall be added in order to meet this requirement.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.1.2   Roof Conductors</TTL><BRK/>
<BRK/>
<TXT>Roof conductors shall be connected directly to the roof or ridge roll.  Sharp bends or turns in conductors shall 
be avoided.  Necessary turns shall have a radius of not less than<MET> 200 mm</MET><ENG> 8 inch</ENG>.  Conductors shall preserve a 
downward or horizontal course and shall be rigidly fastened every<MET> 900 mm</MET><ENG> 3 feet</ENG> along the roof and down the building 
to ground.  Metal ventilators shall be rigidly connected to the roof conductor at three places.  All connections 
shall be electrically continuous.  Roof conductors shall be coursed along the contours of flat roofs, ridges, 
parapets, and edges; and where necessary, over flat surfaces, in such a way as to join each air terminal to all 
the rest.  Roof conductors surrounding tank tops, decks, flat surfaces, and flat roofs shall be connected to 
form a closed loop.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.1.3   Down Conductors</TTL><BRK/>
<BRK/>
<TXT>Down conductors shall be electrically continuous from air terminals and roof conductors to grounding electrodes.  
Down conductors shall be coursed over extreme outer portions of the building, such as corners, with consideration 
given to the location of ground connections and air terminals.  Each building or structure shall have not less 
than two down conductors located as widely separated as practicable, at diagonally opposite corners.  On rectangular 
structures having gable, hip, or gambrel roofs more than<MET> 35 m</MET><ENG> 110 feet</ENG> long, there shall be at least one additional 
down conductor for each additional<MET> 15 m</MET><ENG> 50 feet</ENG> of length or fraction thereof.  On rectangular structures having 
French, flat, or sawtooth roofs exceeding<MET> 75 m</MET><ENG> 250 feet</ENG> in perimeter, there shall be at least one additional 
down conductor for each<MET> 30 m</MET><ENG> 100 feet</ENG> of perimeter or fraction thereof.  On an L- or T-shaped structure, there 
shall be at least one additional down conductor; on an H-shaped structure, at least two additional down conductors; 
and on a wing-built structure, at least one additional down conductor for each wing.  On irregularly shaped structures, 
the total number of down conductors shall be sufficient to make the average distance between them along the perimeter 
not greater than<MET> 30 m</MET><ENG> 100 feet</ENG>.  On structures exceeding<MET> 15 m</MET><ENG> 50 feet</ENG> in height, there shall be at least one 
additional down conductor for each additional<MET> 18 m</MET><ENG> 60 feet</ENG> of height or fraction thereof, except that this application 
shall not cause down conductors to be placed about the perimeter of the structure at intervals of less than<MET> 15 
m</MET><ENG> 50 feet</ENG>.  Additional down conductors shall be installed when necessary to avoid "dead ends" or branch conductors 
ending at air terminals, except where the air terminal is on a roof below the main protected level and the "dead 
end" or branch conductor is less than<MET> 5 m</MET><ENG> 16 feet</ENG> in length and maintains a horizontal or downward coursing.  
Down conductors shall be equally and symmetrically spaced about the perimeter of the structure.  [Down conductors 
shall be protected by placing in [pvc] [rigid steel] conduit for a minimum distance of<MET> 1800 mm</MET><ENG> 72 inch</ENG> above 
finished grade level.]  [If the conduit is metal, the down conductor shall be bonded at the top and bottom of 
the conduit.].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.1.4   Interconnection of Metallic Parts</TTL><BRK/>
<BRK/>
<TXT>Metal doors, windows, and gutters shall be connected directly to the grounds or down conductors using not smaller 
than No. 6 copper conductor, or equivalent.  Conductors placed where there is probability of unusual wear, mechanical 
injury, or corrosion shall be of greater electrical capacity than would normally be used, or shall be protected.  
The ground connection to metal doors and windows shall be by means of mechanical ties under pressure, or equivalent.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.1.5   Ground Connections</TTL><BRK/>
<BRK/>
<TXT>Ground connections comprising continuations of down conductors from the structure to the grounding electrode 
shall securely connect the down conductor and ground in a manner to ensure electrical continuity between the 
two.  All connections shall be of the clamp type.  There shall be a ground connection for each down conductor.  
Metal water pipes and other large underground metallic objects shall be bonded together with all grounding mediums.  
Ground connections shall be protected from mechanical injury.  In making ground connections, advantage shall 
be taken of all permanently moist places where practicable, although such places shall be avoided if the area 
is wet with waste water that contains chemical substances, especially those corrosive to metal.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.1.6   Grounding Electrodes</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where soil conditions indicate definitely that a counterpoise will not 
be required, all references to counterpoise should be deleted from the specifications.  
Using the soil resistance calculate the resistance of the ground rods.  When 
these calculations indicate a combination of two ground rods will exceed 50 
ohms or the system ground resistance will exceed [_____] ohms, provide a counterpoise.</NPR><BRK/>
<BRK/>
<NPR>For Air Force projects the words in the fourth sentence, "if a counterpoise 
is not used" should be deleted.</NPR><BRK/>
<BRK/>
<NPR>Ten ohms should be used for all installations covered by DARCOM-R 385-100, Safety 
Manual.  Twenty-five ohms is acceptable at most other installations.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>A grounding electrode shall be provided for each down conductor located as shown.  A driven ground shall extend 
into the earth for a distance of not less than<MET> 3.0 m</MET><ENG> 10 feet</ENG>.  Ground rods shall be set not less than<MET> 900 mm</MET><ENG> 
3 feet</ENG>, nor more than<MET> 2.5 m</MET><ENG> 8 feet</ENG>, from the structures foundation.  The complete installation shall have a total 
resistance to ground of not more than [_____] ohms if a counterpoise is not used.  Ground rods shall be tested 
individually prior to connection to the system and the system as a whole shall be tested not less than [24] [48] 
hours after rainfall.  When the resistance of the complete installation exceeds the specified value or two ground 
rods individually exceed [_____] ohms, the Contracting Officer shall be notified immediately.  A counterpoise, 
where required, shall be of No. 1/0 copper cable or equivalent material having suitable resistance to corrosion 
and shall be laid around the perimeter of the structure in a trench not less than<MET> 600 mm</MET><ENG> 2 feet</ENG> deep at a distance 
not less than<MET> 900 mm</MET><ENG> 3 feet</ENG> nor more than<MET> 2.5 m</MET><ENG> 8 feet</ENG> from the nearest point of the structure.  All connections 
between ground connectors and grounds or counterpoise, and between counterpoise and grounds shall be electrically 
continuous.  Where so indicated on the drawings, an alternate method for grounding electrodes in shallow soil 
shall be provided by digging trenches radially from the building.  The lower ends of the down conductors [or 
their equivalent in the form of metal strips or wires] are then buried in the trenches.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.2.2   Metal Roofs</TTL><BRK/>
<BRK/>
<TXT>Wood-Frame, Wall-Bearing Masonry or Tile Structure with Metallic Roof and Nonmetallic Exterior Walls, or Reinforced 
Concrete Building with Metallic Roof:  Metal roofs which are in the form of sections insulated from each other 
shall be made electrically continuous by bonding.  Air terminals shall be connected to, and made electrically 
continuous with, the metal roof as well as the roof conductors and down conductors.  Ridge cables and roof conductors 
shall be bonded to the roof at the upper and lower edges of the roof and at intervals not to exceed<MET> 30 m</MET><ENG> 100 
feet</ENG>.  The down conductors shall be bonded to roof conductors and to the lower edge of the metal roof.  Where 
the metal of the roof is in small sections, the air terminals and down conductors shall have connections made 
to at least four of the sections.  All connections shall have electrical continuity and have a surface contact 
of at least<MET> 1935 square mm</MET><ENG> 3 square inch</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.3   Metal Roofs With Metal Walls</TTL><BRK/>
<BRK/>
<TXT>Wood-Frame Building With Metal Roof and Metal Exterior Walls:  The metal roof and the metal walls shall be bonded 
and made electrically continuous and considered as one unit.  The air terminals shall be connected to and made 
electrically continuous with the metal roof as well as the roof and down conductors.  All connections shall have 
electrical continuity and have a surface contact of at least<MET> 1935 square mm</MET><ENG> 3 square inch</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.4   Steel Frame Building</TTL><BRK/>
<BRK/>
<TXT>The steel framework shall be made electrically continuous.  Electrical continuity may be provided by bolting, 
riveting, or welding steel frame, unless a specific method is noted on the drawings.  The air terminals shall 
be connected to the structural steel framework at the ridge.  Short runs of conductors shall be used as necessary 
to join air terminals to the metal framework so that proper placing of air terminals is maintained.  Separate 
down conductors from air terminals to ground connections are not required. Where a grounded metal pipe water 
system enters the building, the structural steel framework and the water system shall be connected at the point 
of entrance by a ground connector.  Connections to pipes shall be by means of ground clamps with lugs.  Connections 
to structural framework shall be by means of nut and bolt or welding.  All connections between columns and ground 
connections shall be made at the bottom of the steel columns.  Ground connections to grounding electrons or counterpoise 
shall be run from not less than one-half of all the columns distributed equally around the perimeter of the structure 
at intervals averaging not more than<MET> 18 m</MET><ENG> 60 feet</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.5   Ramps</TTL><BRK/>
<BRK/>
<TXT>Lightning protection for covered ramps (connecting passageways) shall conform to the requirements for lightning 
protection systems for buildings of similar construction.  A down conductor and a driven ground shall be placed 
at one of the corners where the ramp connects to each building or structure.  This down conductor and driven 
ground shall be connected to the counterpoise or nearest ground connection of the building or structure.  Where 
buildings or structures and connecting ramps are clad with metal, the metal of the buildings or structures and 
metal of the ramp shall be connected to ensure electrical continuity, in order to avoid the possibility of a 
flash-over or spark due to a difference in potential.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.6   Igloo-Type Magazines</TTL><BRK/>
<BRK/>
<TXT>In earth-covered reinforced-concrete, igloo-type magazines, the reinforcing steel shall be made electrically 
continuous.  Electrical continuity may be provided by clipping or brazing, unless a specific method is noted 
on the drawings.  The air terminals and roof conductors shall be securely connected to, and made electrically 
continuous with, the reinforcing steel.  One air terminal shall be located on the top of the front wall and one 
on or adjacent to the ventilator in the rear.  The air terminals shall extend vertically at least<MET> 600 mm</MET><ENG> 2 feet</ENG>
 above the top of the front wall and the highest point on the ventilator.  Down conductors and grounding electrodes 
shall be provided at diagonally opposite corners of the magazine and shall be connected together.  Grounding 
electrodes shall be connected to the horizontal reinforcing rods below the floor line of the wall system.  The 
steel door frame shall be made electrically continuous with the reinforcing steel.  The steel door shall be connected 
to the steel frame by means of a flexible copper strap or cable unless the steel hinges make the door and frame 
electrically continuous.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.7   Tanks and Towers</TTL><BRK/>
<BRK/>
<SPT><TTL>3.2.7.1   Wooden Tanks and Towers</TTL><BRK/>
<BRK/>
<TXT>The lightning protection system shall consist of air terminals, ridge cables, down conductors, ground connections, 
and grounds, electrically interconnected to form the shortest distance to ground.  Where the roof of the structure 
ends in a peak, a single air terminal not less than<MET> 600 mm</MET><ENG> 2 feet</ENG> high will be regarded as sufficient.  When 
the structure does not end in a peak, air terminals not less than<MET> 600 mm</MET><ENG> 2 feet</ENG> high shall be provided at intervals 
not exceeding<MET> 7.5 m</MET><ENG> 25 feet</ENG> along the perimeter of the structure.  When the tank or tower is an adjunct of a 
building, near or touching the perimeter, one of the down conductors shall be extended directly to a ground connection 
and the other shall be connected to the lightning protection system of the building.  When tank or tower is set 
well within the perimeter of a building, both down conductors shall be connected to the lightning protection 
system of the building.  When the height of the facility exceeds<MET> 18 m</MET><ENG> 60 feet</ENG>, the down conductors shall be cross-connected 
at intermediate levels not exceeding<MET> 18 m</MET><ENG> 60 feet</ENG>.  Where buried metal pipes enter the tank or tower, one down 
connector shall be connected to the pipes, approximately<MET> 300 mm</MET><ENG> 1 foot</ENG> below grade.  Metal guy wires or cables 
attached to steel anchor rods set in earth will be considered as grounded.  Metal guy wires or cables set in 
concrete or attached to buildings or nonconducting supports shall be grounded to a ground rod driven full length 
into the ground.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.7.2   Metal or Reinforced-Concrete Tanks and Towers</TTL><BRK/>
<BRK/>
<TXT>The metal or reinforcing steel shall be made electrically continuous.  Electrical continuity may be provided 
by bolting, riveting, or welding metal and tying or clipping reinforcing bars, unless a specific method is noted 
on the drawings.  Air terminals and down conductors are required except on bolted, riveted, or welded<MET> 4.8 mm</MET><ENG> 
3/16-inch</ENG> minimum, steel plate tanks.  Ground connections and grounding electrodes are not required on metal 
tanks that are electrically continuous with a metallic underground pipe system.  On other structures, two ground 
connections shall be provided approximately 180 degrees apart, at the base of the structure.  Where buried metal 
pipes enter the tank or tower, one ground connection shall be connected to them, approximately<MET> 300 mm</MET><ENG> 1 foot</ENG> 
below finished grade.  Metal guy wires on tanks and towers shall be grounded.  Metal guy wires or cables attached 
to steel anchor rods set in earth will be considered as grounded.  Metal guy wires or cables set in concrete 
or attached to buildings or nonconducting supports shall be grounded to a ground rod driven full length into 
the ground.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.2.8   Stacks</TTL><BRK/>
<BRK/>
<TXT>Metal guy wires for stacks shall be grounded.  Metal guy wires or cables attached to steel anchor rods set in 
the earth will be considered as sufficiently well grounded.  Metal guy wires or cables attached to anchor rods 
set in concrete or attached to buildings or nonconducting supports shall be grounded to a ground rod driven full 
length into the ground.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.2.8.1   Metal Stacks</TTL><BRK/>
<BRK/>
<TXT>Metal smokestacks shall be electrically continuous and be grounded.  Where the construction of the foundation 
does not provide [_____] ohms maximum to ground, the stack shall be grounded to two ground rods driven full length 
into the earth.  Ground rods shall be located approximately 180 degrees apart and shall be set not less than<MET> 
900 mm</MET><ENG> 3 feet</ENG> from the nearest point of the stack foundation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.8.2   Nonmetallic Stacks</TTL><BRK/>
<BRK/>
<TXT>On nonmetallic smokestacks constructed of brick, hollow tile, or concrete, the air terminals shall be made of 
solid copper, copper alloy, stainless steel or Monel metal.  Air terminals shall be uniformly distributed about 
the rim of the stack at intervals not exceeding<MET> 2.5 m</MET><ENG> 8 feet</ENG> and shall extend<MET> 450 to 750 mm</MET><ENG> 18 to 30 inch</ENG> above 
the stack if side mounted or<MET> 450 mm</MET><ENG>18 inch</ENG> above the stack if top mounted.  Air terminals shall be at least<MET> 18 
mm</MET><ENG> 5/8 inch</ENG> in diameter, exclusive of the corrosion protection.  Top-mounted air terminals shall not extend more 
than<MET> 450 mm</MET><ENG> 18 inch</ENG> above the top of the stack.  The air terminals shall be electrically connected together by 
means of a metal band or ring to form a closed loop about<MET> 600 mm</MET><ENG> 2 feet</ENG> below the top of the stack.  Where the 
stack has a metal crown, the air terminals shall be connected thereto.  Where stacks have a metal lining extending 
part way up, the lining shall be connected to the air terminal at its upper end and grounded at the bottom.  
At least two down conductors shall be provided on opposite sides of the stack leading from the ring or crown 
at the top to the ground.  When the stack is an adjunct of a building near or touching the building perimeter, 
one of the down conductors shall be extended directly to a ground connection while the other may be connected 
to a lightning protection system on the building.  On stacks exceeding<MET> 50 m</MET><ENG> 160 feet</ENG> in height, the down conductors 
shall be cross-connected approximately midway between the top and the bottom.  Joints in conductors shall be 
as few as practicable and shall provide a strength in tension equal to that of the conductor.  Fasteners of copper 
or copper-bronze alloy shall be spaced not over<MET> 900 mm</MET><ENG> 3 feet</ENG> apart for vertical conductors and not over<MET> 600 
mm</MET><ENG> 2 feet</ENG> apart for horizontal conductors.  To prevent corrosion by gases, copper air terminals, conductors, 
and fasteners within<MET> 8 m</MET><ENG> 25 feet</ENG> of the top of the stack shall have a continuous covering of lead at least<MET> 1.6 
mm</MET><ENG> 1/16-inch</ENG> thick.  Stacks partly or wholly of reinforced concrete shall conform to the requirements for nonmetallic 
stacks, and in addition, the reinforcing steel shall be electrically connected to down conductors at the top 
and bottom of the concrete.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.2.9   Post Tensioning Systems</TTL><BRK/>
<BRK/>
<TXT>On construction utilizing post tensioning systems to secure precast concrete sections, the post tension rods 
shall not be used as a path for lightning to ground.  Down conductors shall be provided on structures using post 
tensioning systems; down conductors shall have sufficient separation from post tension rods to prevent side-flashing.  
Post tension rods shall be bonded to the lightning protection and grounding systems only at the base of the structure; 
this bonding shall be performed in strict accordance with the recommendations of the post tension rod manufacturer, 
and shall be done by, or in the presence of, a representative of the manufacturer.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.3   RAILROADS</TTL><BRK/>
<BRK/>
<TXT>Rails that are not electrically continuous and rail switches shall be bonded together by means of flexible copper 
cable or straps for a distance of at least<MET> 30 m</MET><ENG> 100 feet</ENG> on each side of structures in which explosives, ammunition, 
or explosive ingredients are stored, handled, manufactured, or processed.  These rails shall also be grounded.  
Rails shall be grounded at points<MET> 45 m</MET><ENG> 150 feet</ENG> on each side of overhead line crossings in excess of 600 volts 
and rails shall be bonded between grounds.  At points where the tracks come within<MET> 7.5 m</MET><ENG> 25 feet</ENG> of structures 
provided with a grounding system, such grounds shall be interconnected to the nearest rail.  The cable used for 
the interconnection shall be at least<MET> 9.5 mm</MET><ENG> 3/8 inch</ENG> diameter or the same size as the conductors used on the 
structure.  Isolation joints shall be installed in metal rails outside of hazardous areas to avoid stray currents 
being conducted into the bonded or grounded area.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.4   PIERS AND WHARVES</TTL><BRK/>
<BRK/>
<TXT>Lightning protection systems for piers and wharves shall conform to the requirements specified for the type of 
construction involved.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5   INTERCONNECTION OF METAL BODIES</TTL><BRK/>
<BRK/>
<TXT>Metal bodies of conductance shall be protected if not within the zone of protection of an air terminal.  Metal 
bodies of conductance having an area of<MET> 0.258 square m</MET><ENG> 400 square inch</ENG> or greater or a volume of<MET> 0.0164 cubic 
m</MET><ENG> 1000 cubic inch</ENG> or greater shall be bonded to the lightning protection system using main size conductors and 
a bonding plate having a surface contact area of not less than<MET> 1935.5 square mm</MET><ENG> 3 square inch</ENG>.  Provisions shall 
be made to guard against the corrosive effect of bonding dissimilar metals.  Metal bodies of inductance shall 
be bonded at their closest point to the lightning protection system using secondary bonding conductors and fittings.  
A metal body that exceeds<MET> 1.5 m</MET><ENG> 5 feet</ENG> in any dimension, that is situated wholly within a building, and that 
does not at any point come within<MET> 1.8 m</MET><ENG> 6 feet</ENG> of a lightning conductor or metal connected thereto shall be independently 
grounded.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6   FENCES</TTL><BRK/>
<BRK/>
<TXT>Except as indicated below, metal fences that are electrically continuous with metal posts extending at least<MET> 
600 mm</MET><ENG> 2 feet</ENG> into the ground require no additional grounding.  Other fences shall be grounded on each side of 
every gate.  Fences shall be grounded by means of ground rods every<MET> 300 to 450 m</MET><ENG> 1000 to 1500 feet</ENG> of length 
when fences are located in isolated places, and every<MET> 150 to 225 m</MET><ENG> 500 to 750 feet</ENG> when in proximity (<MET>30 m</MET><ENG> 100 
feet</ENG> or less) to public roads, highways, and buildings.  [Where the fence consists of wooden posts and horizontal 
metal strands only, down conductors consisting of No. 8 copper wire or equivalent shall be run from the ground 
rod the full height of the fence and fastened to each wire, so as to be electrically continuous.]  The connection 
to ground shall be made from the post where it is of metal and is electrically continuous with the fencing.  
All metal fences shall be grounded at or near points crossed by overhead lines in excess of 600 volts and at 
distances not exceeding<MET> 45 m</MET><ENG> 150 feet</ENG> on each side of line crossings.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7   EXTERIOR OVERHEAD PIPE LINES</TTL><BRK/>
<BRK/>
<TXT>Overhead pipes, conduits, and cable tray that enter a building containing explosives shall be properly grounded 
on the exterior of the building, preferably to the building grounds at points where the pipes enter the building.  
Where a separate ground is used, the pipes shall also be bonded to the building ground at points where the pipes 
are closest to the ground connections.  In addition, the pipes shall be bonded to any metallic masses that are 
within<MET> 1.8 m</MET><ENG> 6 feet</ENG> of the pipes.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8   SEPARATELY MOUNTED SHIELDING SYSTEM, MAST-TYPE</TTL><BRK/>
<BRK/>
<TXT>The mast-type protection shall consist of a pole, which, when of a nonconducting material, shall be provided 
with an air terminal mounted to the top, extending not less than<MET> 600 mm</MET><ENG> 2 feet</ENG> nor more than<MET> 1.5 m</MET><ENG> 5 feet</ENG> above 
the top of the pole and a down conductor run down the side of the pole and connected to the ground rod.  When 
a metal pole is used, the pole will act as a down conductor, and an air terminal need not be provided.  Where 
the resistance of the pole to ground is [_____] ohms or less, additional grounding is unnecessary.  Where the 
resistance exceeds [_____] ohms, additional grounding shall be provided, and the ground connection shall be fastened 
to the metal pole and the ground.  When a ground rod is necessary, the rod shall be driven approximately<MET> 1.8 
m</MET><ENG> 6 feet</ENG> from the base of the pole.  When the combined measured resistance to ground of the pole and ground rod 
exceeds [_____] ohms, the Contracting Officer shall be notified immediately.  The grounding system at the base 
of the pole shall be interconnected with any grounding system provided for the protected structure.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.9   SEPARATELY MOUNTED SHIELDING SYSTEM, OVERHEAD GROUND-WIRE TYPE</TTL><BRK/>
<BRK/>
<TXT>This type of protection shall consist of two or more poles electrically connected to each other by overhead conductors.  
Where the poles are made of a nonconducting material, an air terminal shall be mounted to the top of each pole 
and shall extend not less than<MET> 600 mm</MET><ENG> 2 feet</ENG> nor more than<MET> 1.5 m</MET><ENG> 5 feet</ENG> above the top of the pole.  Down conductors 
shall be run down the side of the pole, or a guy wire may be used as a conductor.  When the guy wire is used, 
the guy wire and the overhead ground wire shall be dead-ended at the pole.  The overhead ground wire and the 
guy wire shall then be connected to each other by a separate cable using standard cable clamps in such manner 
that the discharge will not be reversed at any point.  Guy wires used as down conductors shall be grounded by 
means of separate ground rods with cable connections clamped to the lower end of guy wire.  Resistance to ground 
shall not exceed [_____] ohms.  Where metal poles are used, air terminals are not required and if resistance 
of the poles to ground is [_____] ohms or less, additional grounding is unnecessary.  Where the resistance to 
ground exceeds [_____] ohms, additional grounding shall be provided and the ground connection shall be fastened 
to the metal pole and the ground.  The height of the poles shall be sufficient to provide a clearance of not 
less than<MET> 1.8 m</MET><ENG> 6 feet</ENG> between the overhead ground wire and the highest projection of the building.  When the 
ground cable runs across and is used to protect stacks or vents that emit explosive dusts, vapors, or gases under 
forced draft, the cable shall have at least<MET> 4.5 m</MET><ENG> 15 feet</ENG> clearance above the stack or vent.  When grounding 
is required, a ground rod shall be driven approximately<MET> 1.8 m</MET><ENG> 6 feet</ENG> from the base of each pole.  When the combined 
measured resistance to ground of the pole and ground rod exceeds [_____] ohms, the Contracting Officer shall 
be notified immediately.  When a counterpoise is used, the entire system resistance requirement of [_____] ohms 
or less need not be met.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.10   INSPECTION</TTL><BRK/>
<BRK/>
<TXT>The lightning protection system will be inspected by the Contracting Officer to determine conformance with the 
requirements of this specification.  No part of the system shall be concealed until so authorized by the Contracting 
Officer.</TXT><BRK/>
<BRK/></SPT>
</PRT>    <END/><BRK/></SEC>