<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><BRK/>
<HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA                  UFGS-33 60 01 (April 2008)<BRK/>
                                                --------------------------<BRK/>
Preparing Activity:  <PRA>USACE</PRA>                      Superseding<BRK/>
                                                UFGS-33 60 01 (July 2006)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 33 60 01</SCN><BRK/>
<BRK/>
<STL>VALVES, PIPING, AND EQUIPMENT IN VALVE MANHOLES</STL><BRK/>
<DTE>04/08</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>valves, piping and 
equipment in valve manholes that form a part of an underground heat distribution 
system</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Design manual UFC 3-430-1 HEATING AND COOLING DISTRIBUTION SYSTEMS contains 
information that will assist the designer.  Do not allow chilled water lines 
or other plastic piping to be routed through manholes where high temperature 
piping systems (above 110 degrees C (230 degrees F)) are installed.<BRK/>
<BRK/>
Provide the following information on the contract drawings:  (1) valve manhole 
dimensions, (2) location of all valve manholes, (3) sizes of the pipe in the 
valve manholes, (4) location of all valves in the valve manholes, (5) thickness 
of the insulation on the pipe, (6) valve manhole details, (7) final elevations 
of the valve manholes, (8) valve manhole cover details including manway access 
details, (9) how valve manholes are drained and vented, (10) sump pump piping 
details, (11) valve manhole equipment dimensions and details, (12) sump pump 
capacity, (13) electrical wiring details for the equipment (dedicated service 
for sump pump), (14) steam drip trap locations with access and capacities, (15) 
steam main drip leg sizes.<BRK/>
<BRK/>
This guide specification is to be included as a part of a contract which includes 
Sections <SRF>33 61 00</SRF> PREFABRICATED UNDERGROUND HEATING/COOLING DISTRIBUTION SYSTEM 
or <SRF>33 52 13</SRF> EXTERIOR FUEL DISTRIBUTION; <SRF>33 61 13</SRF> PRE-ENGINEERED UNDERGROUND 
HEAT DISTRIBUTION SYSTEM or <SRF>33 63 16</SRF> EXTERIOR SHALLOW TRENCH STEAM DISTRIBUTION; 
<SRF>33 61 15</SRF> HEAT DISTRIBUTION SYSTEMS IN CONCRETE TRENCHES or <SRF>33 63 13</SRF>EXTERIOR 
UNDERGROUND STEAM DISTRIBUTION SYSTEM.  Include the following Sections as part 
of this contract:  <SRF>31 00 00</SRF> EARTHWORK; <SRF>33 71 01</SRF> OVERHEAD TRANSMISSION AND DISTRIBUTION 
or <SRF>33 71 01</SRF> OVERHEAD TRANSMISSION AND DISTRIBUTION; <SRF>33 70 02.00 10</SRF> ELECTRICAL 
DISTRIBUTION SYSTEM, UNDERGROUND or <SRF>33 71 02.00 20</SRF> UNDERGROUND TRANSMISSION 
AND DISTRIBUTION; <SRF>03 15 13.00 10</SRF> EXPANSION JOINTS, CONTRACTION JOINTS, AND WATERSTOPS; 
Section [<SRF>03 31 00.00 10</SRF> CAST-IN-PLACE STRUCTURAL CONCRETE][<SRF>03 30 00</SRF> CAST-IN-PLACE 
CONCRETE]; <SRF>05 05 23.00 10</SRF> WELDING, STRUCTURAL; <SRF>05 50 13</SRF> MISCELLANEOUS METAL 
FABRICATIONS; <SRF>07 13 53</SRF> ELASTOMERIC SHEET WATERPROOFING; <SRF>09 90 00</SRF> PAINTS AND 
COATINGS; <SRF>43 02 00</SRF> or <SRF>40 17 26.00 20</SRF> WELDING PRESSURE PIPING; <SRF>26 20 00</SRF> INTERIOR 
DISTRIBUTION SYSTEM or <SRF>26 51 00</SRF> INTERIOR LIGHTING; and others as applicable 
to the project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification.  The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
<BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
<BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ALUMINUM ASSOCIATION (AA)</ORG><BRK/><BRK/><RID>AA H35.1/35.1M</RID><RTL>(2007) Alloy and Temper Designation Systems for Aluminum</RTL><BRK/><BRK/></REF><REF><ORG>ASME INTERNATIONAL (ASME)</ORG><BRK/><BRK/><RID>ASME B1.20.1</RID><RTL>(1983; R 2006) Pipe Threads, General Purpose (Inch)</RTL><BRK/><BRK/><RID>ASME B16.11</RID><RTL>(2005) Forged Fittings, Socket-Welding and Threaded</RTL><BRK/><BRK/><RID>ASME B16.20</RID><RTL>(2007) Metallic Gaskets for Pipe Flanges - Ring-Joint, Spiral Wound, and Jacketed</RTL><BRK/><BRK/><RID>ASME B16.21</RID><RTL>(2005) Nonmetallic Flat Gaskets for Pipe Flanges</RTL><BRK/><BRK/><RID>ASME B16.3</RID><RTL>(2006) Malleable Iron Threaded Fittings, Classes 150 and 300</RTL><BRK/><BRK/><RID>ASME B16.34</RID><RTL>(2004) Valves - Flanged, Threaded and Welding End</RTL><BRK/><BRK/><RID>ASME B16.5</RID><RTL>(2003) Standard for Pipe Flanges and Flanged Fittings:  NPS 1/2 Through NPS 24</RTL><BRK/><BRK/><RID>ASME B16.9</RID><RTL>(2007) Standard for Factory-Made Wrought Steel Buttwelding Fittings</RTL><BRK/><BRK/><RID>ASME B31.1</RID><RTL>(2007; Addenda 2008) Power Piping</RTL><BRK/><BRK/><RID>ASME B40.100</RID><RTL>(2005) Pressure Gauges and Gauge Attachments</RTL><BRK/><BRK/><RID>ASME BPVC SEC IX</RID><RTL>(2007; Addenda 2008) Boiler and Pressure Vessel Code; Section IX, Welding and Brazing Qualifications</RTL><BRK/><BRK/></REF><REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 106/A 106M</RID><RTL>(2008) Standard Specification for Seamless Carbon Steel Pipe for High-Temperature Service</RTL><BRK/><BRK/><RID>ASTM A 123/A 123M</RID><RTL>(2008) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products</RTL><BRK/><BRK/><RID>ASTM A 193/A 193M</RID><RTL>(2008b) Standard Specification for Alloy-Steel and Stainless Steel Bolting Materials for High-Temperature Service</RTL><BRK/><BRK/><RID>ASTM A 194/A 194M</RID><RTL>(2008b) Standard Specification for Carbon and Alloy Steel Nuts for Bolts for High-Pressure or High-Temperature Service, or Both</RTL><BRK/><BRK/><RID>ASTM A 234/A 234M</RID><RTL>(2007) Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and High Temperature Service</RTL><BRK/><BRK/><RID>ASTM A 53/A 53M</RID><RTL>(2007) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless</RTL><BRK/><BRK/><RID>ASTM A 733</RID><RTL>(2003) Standard Specification for Welded and Seamless Carbon Steel and Austenitic Stainless Steel Pipe Nipples</RTL><BRK/><BRK/><RID>ASTM B 209</RID><RTL>(2007) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate</RTL><BRK/><BRK/><RID>ASTM B 209M</RID><RTL>(2007) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate (Metric)</RTL><BRK/><BRK/><RID>ASTM C 449</RID><RTL>(2007) Standard Specification for Mineral Fiber Hydraulic-Setting Thermal Insulating and Finishing Cement</RTL><BRK/><BRK/><RID>ASTM C 533</RID><RTL>(2007) Standard Specification for Calcium Silicate Block and Pipe Thermal Insulation</RTL><BRK/><BRK/><RID>ASTM C 547</RID><RTL>(2008e1) Standard Specification for Mineral Fiber Pipe Insulation</RTL><BRK/><BRK/><RID>ASTM C 552</RID><RTL>(2007) Standard Specification for Cellular Glass Thermal Insulation</RTL><BRK/><BRK/><RID>ASTM C 647</RID><RTL>(2008) Properties and Tests of Mastics and Coating Finishes for Thermal Insulation</RTL><BRK/><BRK/><RID>ASTM D 2822</RID><RTL>(2005) Asphalt Roof Cement</RTL><BRK/><BRK/><RID>ASTM D 3278</RID><RTL>(1996;  R 2004e1) Flash Point of Liquids by Small Scale Closed-Cup Apparatus</RTL><BRK/><BRK/><RID>ASTM E 84</RID><RTL>(2008a) Standard Test Method for Surface Burning Characteristics of Building Materials</RTL><BRK/><BRK/><RID>ASTM E 96/E 96M</RID><RTL>(2005) Standard Test Methods for Water Vapor Transmission of Materials</RTL><BRK/><BRK/><RID>ASTM F 1139</RID><RTL>(1988; R 2004) Steam Traps and Drains</RTL><BRK/><BRK/></REF><REF><ORG>MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS INDUSTRY (MSS)</ORG><BRK/><BRK/><RID>MSS SP-110</RID><RTL>(1996) Ball Valves Threaded, Socket-Welding, Solder Joint, Grooved and Flared Ends</RTL><BRK/><BRK/><RID>MSS SP-25</RID><RTL>(2008) Standard Marking System for Valves, Fittings, Flanges and Unions</RTL><BRK/><BRK/><RID>MSS SP-45</RID><RTL>(2003) Bypass and Drain Connections</RTL><BRK/><BRK/><RID>MSS SP-58</RID><RTL>(2002) Standard for Pipe Hangers and Supports - Materials, Design and Manufacture</RTL><BRK/><BRK/><RID>MSS SP-69</RID><RTL>(2003; R 2004) Standard for Pipe Hangers and Supports - Selection and Application</RTL><BRK/><BRK/><RID>MSS SP-72</RID><RTL>(1999) Standard for Ball Valves with Flanged or Butt-Welding Ends for General Service</RTL><BRK/><BRK/><RID>MSS SP-80</RID><RTL>(2008) Bronze Gate, Globe, Angle and Check Valves</RTL><BRK/><BRK/><RID>MSS SP-83</RID><RTL>(2006) Standard for Class 3000 Steel Pipe Unions Socket Welding and Threaded</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/><RID>NFPA 90A</RID><RTL>(2008) Standard for the Installation of Air Conditioning and Ventilating Systems</RTL><BRK/><BRK/></REF><REF><ORG>THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)</ORG><BRK/><BRK/><RID>SSPC Paint 16</RID><RTL>(2006) Paint Specification No. 16 Coal Tar Epoxy-Polyamide Black (or Dark Red) Paint</RTL><BRK/><BRK/><RID>SSPC SP 10</RID><RTL>(2007) Near-White Blast Cleaning</RTL><BRK/><BRK/></REF><REF><ORG>UNDERWRITERS LABORATORIES (UL)</ORG><BRK/><BRK/><RID>UL 723</RID><RTL>(2008) Standard for Test for Surface Burning Characteristics of Building Materials</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section <SRF>01 33 00</SRF> SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy, Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are for [Contractor Quality Control approval.][information only.  When used, a designation following the "G" 
designation identifies the office that will review the submittal for the Government.]  Submit the following in 
accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Detail Drawings</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>]</ITM><BRK/>
<BRK/>
<ITM>  Detail drawings, as specified, [_____] days after notice to proceed.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Piping and Fittings</SUB></ITM><BRK/>
<ITM><SUB>Valves</SUB></ITM><BRK/>
<ITM><SUB>Insulation</SUB></ITM><BRK/>
<ITM><SUB>Sump Pumps and Drainers</SUB></ITM><BRK/>
<ITM><SUB>Expansion Joints</SUB></ITM><BRK/>
<BRK/>
<ITM>  Manufacturer's descriptive data and technical literature, performance charts, catalog cuts 
and installation instructions.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-04 Samples</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Insulated Sections</SUB>[; <SUB>G</SUB>][; <SUB>G, [_____]</SUB>].</ITM><BRK/>
<BRK/>
<ITM>  Display of insulated sections, as specified, [_____] days after notice to proceed.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-10 Operation and Maintenance Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Valve Manholes and Accessories</SUB></ITM><BRK/>
<ITM><SUB>Data Package 2</SUB></ITM><BRK/>
<BRK/>
<ITM>  Data Package 2 in accordance with Section <SRF>01 78 23</SRF> OPERATION AND MAINTENANCE DATA.</ITM><BRK/>
<BRK/>
<ITM>  [Six] [_____] copies of operation and [six] [_____] copies of maintenance manuals for the 
equipment furnished.  Detail in the operation manuals the step-by-step procedures required for 
equipment startup, operation, and shutdown.  Include in the operation manuals the manufacturer's 
name, model number, parts list, and brief description of all equipment and their basic operating 
features.  List in the maintenance manuals routine maintenance procedures, possible breakdowns 
and repairs, and troubleshooting guides.  Include in the maintenance manuals piping and equipment 
layout and simplified wiring and control diagrams indicating location of electrical components 
with terminals designated for wiring, as installed.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   QUALITY ASSURANCE</TTL><BRK/>
<BRK/>
<SPT><TTL>1.3.1   <SUB>Detail Drawings</SUB></TTL><BRK/>
<BRK/>
<TXT>Submit detail drawings for valve manholes and the piping and equipment in the valve manholes, such as steam traps, 
valves, sump pumps, pressure gauges, thermometers and insulation, including a complete list of equipment and 
materials, manufacturer's descriptive and technical literature, performance charts and curves, catalog cuts, 
installation instructions, and complete wiring and schematic diagrams.  Show on the drawings pipe anchors and 
guides, and layout and anchorage of equipment and appurtenances in valve manholes, and equipment relationship 
to other parts of the work including clearances for maintenance and operation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3.2   <SUB>Insulated Sections</SUB></TTL><BRK/>
<BRK/>
<TXT>Submit sample sections for insulation of pipe, elbow, tee, valve, support point, and terminating points.  After 
approval of materials and prior to insulation of piping, a display shall be prepared of insulated sections showing 
compliance with specifications and showing fastening, sealing, jacketing, straps, waterproofing, supports, hangers, 
anchors, and saddles.  Approved display sample sections shall remain on display at the jobsite during the construction 
period until no longer needed by Contracting Officer, then removed.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>1.4   DELIVERY, STORAGE, AND HANDLING</TTL><BRK/>
<BRK/>
<TXT>Protect all materials and equipment delivered and placed in storage from the weather, excessive humidity, and 
excessive temperature variation; dirt, dust, or other contaminants.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   STANDARD PRODUCTS</TTL><BRK/>
<BRK/>
<TXT>Provide materials and equipment which are the standard products of a manufacturer regularly engaged in the manufacture 
of such products and that essentially duplicate items that have been in satisfactory use for at least 2 years 
prior to bid opening.  Equipment shall be supported by a service organization that is, in the opinion of the 
Contracting Officer, reasonably convenient to the site.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2   NAMEPLATES</TTL><BRK/>
<BRK/>
<TXT>Each major item of equipment such as sump pump, motor, steam trap, and pressure reducing valve shall have the 
manufacturer's name, address, type or style, model or serial number, and catalog number on a plate secured to 
the item of equipment.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3   ASBESTOS PROHIBITION</TTL><BRK/>
<BRK/>
<TXT>Asbestos and asbestos-containing products will not be allowed.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4   ELECTRICAL WORK</TTL><BRK/>
<BRK/>
<TXT>Motors, manual or automatic motor control equipment, and protective or signal devices required for the operation 
specified shall be provided under this section in accordance with <RID>NFPA 70</RID> and Section [<SRF>33 70 02.00 10</SRF> ELECTRICAL 
DISTRIBUTION SYSTEM, UNDERGROUND] [<SRF>33 71 02.00 20</SRF> UNDERGROUND TRANSMISSION AND DISTRIBUTION].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5   <SUB>PIPING AND FITTINGS</SUB></TTL><BRK/>
<BRK/>
<SPT><TTL>2.5.1   General Requirements</TTL><BRK/>
<BRK/>
<TXT>Piping, fittings and piping accessories inside the valve manholes shall conform to the requirements of <RID>ASME B31.1</RID>
 and shall be suitable for the working pressure and temperature requirements of the system.  To the greatest 
extent possible, the piping and fittings inside the valve manholes shall match the piping and fittings located 
on the outside of the valve manhole.  All piping in valve manholes shall be steel with joints welded except that 
joints<MET> 19 mm</MET><ENG> 3/4 inch</ENG> and smaller may be threaded.  When threaded joints are used on High Temperature Water Systems, 
the interface area where the pipe threads meet the threaded fittings shall be seal welded (continuous fillet 
weld) to preclude any water leakage.  No supports, anchors, or stays shall be attached to any piping system in 
places where either the installation of or the movement of the pipe and its contents will cause damage to the 
construction.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.2   Steel Pipe</TTL><BRK/>
<BRK/>
<TXT>Pipe shall be black steel, seamless or electric-resistance welded, conforming to the requirements of <RID>ASTM A 53/A 53M</RID>
, Grade B or <RID>ASTM A 106/A 106M</RID>, Grade B.  Pipe up to and including<MET> 250 mm</MET><ENG> 10 inches</ENG> in diameter shall be schedule 
40.  Pipe<MET> 300 mm</MET><ENG> 12 inches</ENG> in diameter and greater shall be<MET> 10 mm</MET><ENG> 0.375 inch</ENG> nominal wall thickness.  Gauge piping 
[, condensate piping,] [drip piping,] and piping<MET> 19 mm</MET><ENG> 3/4 inch</ENG> in diameter and smaller shall be schedule 80.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.5.2.1   Nipples</TTL><BRK/>
<BRK/>
<TXT>Nipples shall conform to <RID>ASTM A 733</RID> as required to match adjacent piping.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.2.2   Pipe Threads</TTL><BRK/>
<BRK/>
<TXT>Pipe threads shall conform to <RID>ASME B1.20.1</RID>.  Pipe threads may be used only on pipe<MET> 19 mm</MET><ENG> 3/4 inch</ENG> or smaller.  
All pipe which is to be threaded shall be schedule 80.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.5.3   Fittings</TTL><BRK/>
<BRK/>
<TXT>All fittings, valves, flanges and unions shall have the manufacturer's trademark affixed in accordance with <RID>MSS SP-25</RID>
 so as to permanently identify the manufacturer.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.5.3.1   Welded Fittings</TTL><BRK/>
<BRK/>
<TXT>Welded fittings shall conform to <RID>ASTM A 234/A 234M</RID>, buttwelded or socket welded, as required to match connecting 
piping.  Buttwelded fittings shall conform to <RID>ASME B16.9</RID>, and socket welded fittings shall conform to <RID>ASME B16.11</RID>
.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.3.2   Unions</TTL><BRK/>
<BRK/>
<TXT>Unions shall conform to <RID>MSS SP-83</RID> as required to match adjacent piping.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.3.3   Ball Valves</TTL><BRK/>
<BRK/>
<TXT>Ball valves shall conform to <RID>MSS SP-72</RID> for flanged or buttwelded valves or <RID>MSS SP-110</RID> for threaded ball valves.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.5.4   Insulating Flanges and Dielectric Waterways</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Electrically insulating flanges or dielectric waterways shall be shown 
in manholes where piping is connected to a system that is not cathodically protected.  
Insulating flanges and dielectric waterways must be in accessible locations, 
such as valve manholes or buildings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.5.4.1   Insulating Flanges</TTL><BRK/>
<BRK/>
<TXT>For systems in which cathodic protection is provided, insulating flanges or flange gasket kits shall be installed 
in the valve manhole at the pipe connection to or from the heat distribution system and at dissimilar metals 
and when the carrier pipe and appurtenances are supported in such a way as to electrically ground or alter the 
cathodic protection system voltages or currents.  The kit shall consist of flanges, a flange gasket, nuts and 
bolts, bolt sleeves, and one insulating washer and one steel washer for both ends of each bolt.  The manufacturer 
shall certify that the gasket kits are capable of electrically isolating the pipe at the [_____]<MET> kPa</MET><ENG> psig</ENG> pressure 
and [_____] degrees<MET> C</MET><ENG> F</ENG> temperature of the heating medium at the point of application.  Evidence of satisfactory 
installations operating not less than 2 years shall be submitted in accordance with paragraph SUBMITTALS before 
materials are delivered.  Ensure that these kits are provided and properly installed according to manufacturer's 
published instructions.  Bolts shall be torqued to the correct tightness and in the correct bolt pattern as recommended 
by the manufacturer's published instructions.  Steel flanges shall conform to <RID>ASME B16.5</RID> Class [150] [and] [or] 
[300] and shall match valves or flanged fittings on which used.  Steel flanges shall be flat faced.  Gaskets 
shall be non-asbestos compressed material in accordance with <RID>ASME B16.21</RID>, <MET>2 mm</MET><ENG> 1/16 inch</ENG> thickness, full face 
or self centering flat ring type.  Bolts shall conform to the requirements of <RID>ASTM A 193/A 193M</RID>, Grade B7.  The 
bolt head shall be marked to identify the manufacturer and the standard to which the bolt complies.  Lengths 
of bolts shall be such that not less than two full threads extend beyond the nut with the bolt tightened to the 
required tension and the washer seated.  Nuts shall conform to the requirements of <RID>ASTM A 194/A 194M</RID>, Grade 7.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.4.2   Dielectric Waterways</TTL><BRK/>
<BRK/>
<TXT>Dielectric waterways shall have temperature and pressure rating equal to or greater than that specified for the 
connecting piping and shall be used for joining dissimilar metals on<MET> 19 mm</MET><ENG> 3/4 inch</ENG> and smaller threaded pipe.  
Waterways shall have metal connections on both ends suited to match connecting piping.  Dielectric waterways 
shall be internally lined with an insulator specifically designed to prevent current flow between dissimilar 
metals.  Dielectric flanges shall meet the performance requirements described herein for dielectric waterways.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.5.4.3   Gaskets Non-Insulating</TTL><BRK/>
<BRK/>
<TXT>Provide spiral wound, non-asbestos gasket with centering ring in accordance with <RID>ASME B16.20</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT><SPT><TTL>2.6   <SUB>VALVES</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the appropriate valves for the operating temperatures and pressures 
of all systems in the project.  Delete valve types not included in project.</NPR><BRK/>
<BRK/>
<NPR>Use not less than Class 150 for up to 862 kPa (125 psig) steam, and not less 
than Class 300 for 863 kPa to 1724 kPa (126 to 250 psig) steam and high temperature 
water.  For isolation and shutoff, use gate valves only.  Steam pressure reducing 
valves are not normally part of the system.  If needed, designer should refer 
to Section <SRF>23 70 01.00 10</SRF> CENTRAL STEAM-GENERATING SYSTEM, COAL-FIRED or Section 
<SRF>23 22 26.00 20</SRF> STEAM SYSTEM AND TERMINAL UNITS for Navy jobs.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Unless otherwise specified, valves shall comply with the material, fabrication, and operating requirements of <RID>
ASME B31.1</RID>.  Valves shall be suitable for the temperature and pressure requirements of the system on which used.  
Valves for [steam] [hot water] shall conform to <RID>ASME B31.1</RID>Class [150] [and] [or] [300], as suitable for the application.  
[Valves for condensate services shall conform to <RID>ASME B31.1</RID> Class 150.]  Valves<MET> 19 mm</MET><ENG> 3/4 inch</ENG> and smaller may 
be bronze where seal welding is not required.  Valves<MET> 150 mm</MET><ENG> 6 inches</ENG> and larger shall have a<MET> 25 mm</MET><ENG> 1 inch</ENG> minimum 
gate or globe bypass valve sized in conformance with <RID>MSS SP-45</RID>.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.6.1   Steel Valves</TTL><BRK/>
<BRK/>
<TXT>Steel globe, gate, angle, and check valves shall conform to the requirements of <RID>ASME B16.34</RID> and <RID>ASME B31.1</RID> for 
the temperature and pressure requirements of the system.  Gate valves<MET> 65 mm</MET><ENG> 2-1/2 inches</ENG> and smaller shall be 
rising stem.  Gate valves<MET> 80 mm</MET><ENG> 3 inches</ENG> and larger shall be outside screw and yoke.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6.2   Bronze Valves</TTL><BRK/>
<BRK/>
<SPT><TTL>2.6.2.1   Globe, Gate, and Angle Valves</TTL><BRK/>
<BRK/>
<TXT>Bronze globe, gate, and angle valves shall conform to requirements of <RID>MSS SP-80</RID>, union bonnet type.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6.2.2   Check Valves</TTL><BRK/>
<BRK/>
<TXT>Bronze check valves shall conform to the requirements of <RID>MSS SP-80</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.6.3   Packing</TTL><BRK/>
<BRK/>
<TXT>Packing used with valves shall not contain asbestos.  Valve stem packing shall be die-formed, ring type specifically 
designated as suitable for the temperature and pressure of the service and compatible with the fluid in the system.  
Packing shall be polytetrafluoroethylene with minimum 50 percent graphite filament.  Valves<MET> 40 mm</MET><ENG> 1-1/2 inches</ENG>
 and smaller shall have four or five packing rings and valves<MET> 50 mm</MET><ENG> 2 inches</ENG> and larger shall have at least six 
packing rings.  Spiral or continuous packing will not be acceptable.  A metal insert shall be provided having 
proper clearance around the valve stem at the bottom of the stuffing box and acting as a base for the packing 
material.  Packing glands shall be furnished with a liner of noncorrosive material and shall be of one piece 
construction with provisions for not less than two bolts for packing adjustment.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.7   STEAM TRAPS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following paragraphs are applicable to steam systems only.  Only 
these two types will be used.  Delete these paragraphs when the distribution 
system is not a steam system.</NPR><BRK/>
<BRK/>
<NPR>A schedule of steam trap selection will be shown on the drawings.  Trap capacity 
(kg per second (pounds per hour)) during normal operation, pressure drop (kPa 
(psi)), and pressure rating (kPa (psi)) of each trap will be included in this 
schedule.  Also, show on the drawings a vent valve or test valve connection 
downstream of traps for test of trap operation, a strainer ahead of traps, a 
union, a check valve in the outlet piping, and shut-off valves on both sides 
of trap for trap changeout.  A means of bypassing the trap shall be provided 
for system warm-up.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Class of trap bodies shall be suitable for a working pressure of not less than 1.5 times the steam supply pressure, 
but not less than<MET> 1379 kPa</MET><ENG> 200 psi</ENG>, and traps shall be capable of operation under a steam-supply pressure as 
indicated.  Traps shall have capacities as shown when operating under the specified working conditions.  Traps 
shall fail open.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.7.1   Bucket Traps</TTL><BRK/>
<BRK/>
<TXT>Bucket traps shall be inverted-bucket type with automatic air discharge and conform to <RID>ASTM F 1139</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2   Thermostatic Traps</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify thermostatic traps where the trap location is subject to freezing.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Traps shall be thermostatic type; bimetallic element with automatic air discharge and conform to <RID>ASTM F 1139</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.8   STRAINERS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete this paragraph for high temperature water systems.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Strainers shall be basket or y-type with connections the same size as the pipe lines in which the connections 
are installed.  The strainer bodies for steam systems shall be heavy and durable, of cast steel, with bottoms 
drilled and plugged.  The strainers shall be suitable for the temperature and pressure requirements of the system 
on which they are installed.  The bodies shall have arrows clearly cast on the sides to indicate the direction 
of flow.  Each strainer shall be equipped with an easily removable cover and sediment basket.  The body or bottom 
opening shall be equipped with nipple and gate valve for blowdown.  The basket for steam systems shall be not 
less than<MET> 0.6350 mm</MET><ENG> 0.025 inch</ENG> thick stainless steel, Monel or sheet brass, with small perforations of sufficient 
number to provide a net free area through the basket of at least 2.5 times that of the entering pipe.  The flow 
shall be into the basket and out through the perforations.  For high temperature hot water systems, only cast 
steel bodies and stainless or Monel baskets shall be used.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9   PRESSURE GAUGES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete if not required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Gauges shall conform to <RID>ASME B40.100</RID>, and shall be provided with throttling type needle valve or a pulsation 
dampener and shut-off valve.  Minimum dial size shall be<MET> 110 mm</MET><ENG> 4-1/4 inches</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.10   DIAL THERMOMETERS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete if not required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Dial type thermometer shall be<MET> 90 mm</MET><ENG> 3-1/2 inches</ENG> in diameter with stainless steel case, remote-type bulb or 
direct-type bulb as required.  The thermometer shall have an accuracy of plus or minus<MET> 1 degree C</MET><ENG> 2 degrees F</ENG>
.  Thermometer wells of the separable socket type shall be provided for each thermometer with direct-type bulb.  
The thermometer shall have a white face with black digits graduated in<MET> 1 degree C</MET><ENG> 2 degrees F</ENG> increments.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11   INSULATION AND JACKETING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  All piping, valves and fittings for steam, hot water and dual temperature 
heat distribution systems in valve manholes require insulation for the protection 
of operating and maintenance personnel as well as for the conservation of energy; 
whether or not to insulate chilled water lines, valves, and fittings in the 
manholes can be determined by the necessity to prevent condensation on the piping 
and energy conservation.<BRK/>
<BRK/>
The energy savings will vary with the ambient temperature but will be a factor 
in warm climates.  There may be some isolated cases where the chilled water 
distribution pipes entering the manhole are not insulated; therefore, the piping 
in the manhole would not normally be insulated unless condensation from the 
air forming on the chilled water pipes causes a problem.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.11.1   General Provisions</TTL><BRK/>
<BRK/>
<TXT>All piping, fittings, valves, etc., in the valve manholes shall be insulated.  Insulation shall be premolded, 
precut or job fabricated to fit and shall be removable and reusable.  Thickness of insulation shall be in accordance 
with Tables 1 and 2.  Insulation jackets shall be provided for all pipe and fitting insulation.  Insulation shall 
conform to EPA requirements in accordance with Section <SRF>01 62 35</SRF> RECYCLED / RECOVERED MATERIALS.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11.2   <SUB>Insulation</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The insulations allowed in this paragraph have passed a 96 hour boiling 
test which indicates that satisfactory performance is expected.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Insulation for all piping, fittings, and valves shall be molded calcium silicate conforming to <RID>ASTM C 533</RID>, Type 
I, or molded mineral fiber insulation conforming to <RID>ASTM C 547</RID>, Class 2, or cellular glass insulation conforming 
to <RID>ASTM C 552</RID>.  All insulation shall be asbestos free.  Laminated construction shall not be used unless the thickness 
exceeds<MET> 100 mm</MET><ENG> 4 inches</ENG>.  Insulations and the manufacturers approved for use are:</TXT><BRK/>
<BRK/>
<ITM>a.  Delta, available from Rockwool in Leeds, Alabama.</ITM><BRK/>
<BRK/>
<ITM>b.  MPT-PC and MPT-PF, available from Mineral Products of Texas in Houston, TX.</ITM><BRK/>
<BRK/>
<ITM>c.  Thermo-12, Super Caltemp, available from Johns Manville in Denver, Colorado.</ITM><BRK/>
<BRK/>
<ITM>d.  Foamglass (cellular glass), available from Pittsburgh Corning Corporation.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11.3   Aluminum Jackets</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Vapor barrier requirements are only to be included for chilled water 
systems.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Aluminum jackets shall be smooth sheet, <MET>0.4064 mm</MET><ENG> 0.016 inch</ENG> nominal thickness and conform to the requirements 
of<MET> <RID>ASTM B 209M</RID></MET><ENG> <RID>ASTM B 209</RID></ENG>, Type 3003, 3105, or 5005.[  Aluminum jackets shall be supplied with a factory installed 
moisture barrier.  This moisture barrier shall consist of at least<MET> 18.1 kg</MET><ENG> 40 pound</ENG> kraft paper coated on one 
side with a<MET> 0.025 mm</MET><ENG> 1 mil</ENG> thick polyethylene film.  The moisture barrier shall be adhered to the aluminum jacket 
over the entire area of the aluminum jacket insulation-side surface.]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11.4   Bands</TTL><BRK/>
<BRK/>
<TXT>Bands for aluminum jacket shall be<MET> 10 mm</MET><ENG> 3/8 inch</ENG> wide and 32 gauge thickness made of aluminum or annealed stainless 
steel.  Bands for insulation shall be<MET> 13 mm</MET><ENG> 1/2 inch</ENG> wide and 32 gauge thickness made of annealed stainless steel.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11.5   Insulation for Flanges, Unions, Valves, and Fittings</TTL><BRK/>
<BRK/>
<TXT>Flanges, unions, valves, and fittings shall be insulated with premolded prefabricated, or field fabricated segments 
of insulation of the same material and thickness as the manhole pipe insulation.  Insulation shall be removable 
and reusable and shall have essentially the same thermal characteristics and thickness as the adjoining piping.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11.6   Vapor Barrier Coating</TTL><BRK/>
<BRK/>
<TXT>The vapor barrier coating shall be fire and water resistant and appropriately selected for either outdoor or 
indoor service.  Color shall be white.  The water vapor permeance of the compound shall not exceed 0.05 perm 
and shall be determined according to Procedure B of <RID>ASTM E 96/E 96M</RID>.  The coating shall be a nonflammable, fire 
resistant type conforming to <RID>ASTM E 84</RID>, <RID>NFPA 90A</RID> and <RID>UL 723</RID>.  The flash point of the compound shall not be less 
than<MET> 26.7 degrees C</MET><ENG> 80 degrees F</ENG> and shall be determined in accordance with <RID>ASTM D 3278</RID>.  All other application 
and service properties shall be in accordance with <RID>ASTM C 647</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11.7   Finishing Cement</TTL><BRK/>
<BRK/>
<TXT>Mineral fiber hydraulic-setting thermal insulating cement in accordance with <RID>ASTM C 449</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11.8   Glass Tape</TTL><BRK/>
<BRK/>
<TXT>Glass tape shall meet the requirements of <RID>UL 723</RID> and <RID>ASTM E 84</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11.9   Plain Weave, Untreated</TTL><BRK/>
<BRK/>
<TXT>The ends shall be properly interlocked with the picks to ensure that there shall be no raveling of the tape edges.  
The tape shall have an average weight of<MET> 196.7 plus or minus 10 percent grams per square meter</MET><ENG> 5.8 plus or minus 
10 percent ounces per square yard</ENG>.  An average thickness of<MET> 0.1778 plus or minus 0.0254 mm</MET><ENG> 0.007 plus or minus 
0.001 inches</ENG>.  Warp ends/wales of<MET> 17 plus or minus 1 per centimeter</MET><ENG> 42 plus or minus 2 per inch</ENG> or filling picks/courses 
of<MET> 13 plus or minus 1 per centimeter</MET><ENG> 32 plus or minus 2 per inch</ENG>, a minimum breaking strength of<MET> 2679 grams per 
mm</MET><ENG> 150 pounds per inch</ENG> of width, and after heating to<MET> 482 degrees C</MET><ENG> 900 degrees F</ENG> for 2 hours.  A minimum breaking 
strength of<MET> 714 grams per mm</MET><ENG> 40 pounds per inch</ENG> of width.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11.10   Knitted, Untreated</TTL><BRK/>
<BRK/>
<TXT>The wales shall be properly interlocked with the courses to ensure that there shall be no raveling of the tape 
edges.  The tape shall have an average weight of<MET> 153 plus or minus 10 percent grams per square meter</MET><ENG> 4.5 plus 
or minus 10 percent ounces per square yard</ENG>.  An average thickness of<MET> 0.1778 plus or minus 0.0254 mm</MET><ENG> 0.007 plus 
or minus 0.001 inches</ENG>, warp ends/wales of<MET> 6 plus or minus per 1 centimeter</MET><ENG> 16 plus or minus 2 per inch</ENG>.  A minimum 
breaking strength of<MET> 714 grams per mm</MET><ENG> 40 pounds per inch</ENG> of width and, after heating to<MET> 482 degrees C</MET><ENG> 900 degrees 
F</ENG> for 2 hours.  A minimum breaking strength of<MET> 375 grams per mm</MET><ENG> 21 pounds per inch</ENG> of width.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11.11   Distortion Requirements</TTL><BRK/>
<BRK/>
<TXT>There shall be no distortion of the tape when a sample<MET> 610 mm</MET><ENG> 24 inches</ENG> in length is spread across a flat horizontal 
surface and observed for evidence of distortion (such as tendency to curl rather than lie flat).  The width tolerance 
is plus or minus<MET> 3.175 mm</MET><ENG> 1/8 inch</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.11.12   Open-Weave Tape</TTL><BRK/>
<BRK/>
<TXT>Tape shall be open-weave type and shall have an average weight of [_____]<MET> kg per square meter</MET><ENG> ounce per square 
yard</ENG> and shall be used for embedding between coats of adhesive or coating materials.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.12   <SUB>SUMP PUMPS AND DRAINERS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete this paragraph when positive drainage of the valve manhole is 
provided and sump pumps are not needed.  Use of duplex sump pumps is encouraged.  
Delete text in brackets if a single sump pump is specified.</NPR><BRK/>
<BRK/>
<NPR>Provide one or two sump pumps in valve manholes.  Units should discharge by 
buried piping to the nearest storm sewer if possible.  Where not economical 
to discharge to a storm sewer, pumps are to discharge above grade.  Plan discharge 
locations carefully so water will not be discharged over valve manhole tops, 
sidewalks, etc.  Check available NPSH versus required NPSH for pump selected.  
Coordinate power requirements with electrical designer and provide tell-tale 
light above ground to indicate sump pump failure.<BRK/>
<BRK/>
Drawings will show the following:  (a) a dedicated circuit; (b) lockable switches 
and circuit breakers that can both be locked ON; (c) permanent labels at key 
positions indicated on the drawings so that personnel can understand that the 
circuit should be left ON.  The label shall be on a corrosion resistant metal 
plate and shall read as follows:  THIS CIRCUIT SUPPLIES POWER TO THE ELECTRIC 
SUMP PUMPS IN THE UNDERGROUND HEAT DISTRIBUTION SYSTEM.  THIS CIRCUIT MUST BE 
ON AT ALL TIMES; OTHERWISE EXTENSIVE DAMAGE WILL OCCUR TO THE UNDERGROUND HEAT 
DISTRIBUTION SYSTEM AND PREMATURE FAILURE WILL OCCUR.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.12.1   Sump Pumps</TTL><BRK/>
<BRK/>
<TXT>Sump pumps with the capacities indicated shall be installed in the valve manholes as shown.  The sump pumps furnished 
shall be a manufacturer's standard commercial product.  Sump pumps shall be electrically driven and submersible, 
capable of operating while completely submerged.  The pumps and motors shall be capable of continuously pumping 
liquids at a temperature of<MET> 93 degrees C</MET><ENG> 200 degrees F</ENG>.  The pumps and motors shall be capable of running without 
damage when not submerged.  Sump pumps shall have permanently lubricated bearings, monel shafts, bronze impellers, 
screened inlets and housings of bronze.  Each sump pump shall be capable of passing a<MET> 10 mm</MET><ENG> 3/8 inch</ENG> sphere.  
The motors shall have the<MET> wattage (horsepower)</MET><ENG> horsepower</ENG> indicated and shall have overload protection.  The 
discharge piping shall be schedule 80 or shall be protected from corrosion.  The pumps shall be automatically 
controlled by a submersible switch assembly with pump wiring and switch suitable for submersion in<MET> 93 degrees 
C</MET><ENG> 200 degrees F</ENG> liquids.  Motors shall be [120] [240] [_____] volts, 60 Hz, single phase.  [Two sump pumps in 
a duplex arrangement shall be provided as indicated.  An automatic alternating lead-lag controller shall be furnished.]  
All controllers, water level switches, and electrical connections shall be suitable for service at 100 percent 
humidity, at<MET> 93 degrees C</MET><ENG> 200 degrees F</ENG> temperature, and occasional water submersion.  The sump pumps automatic 
control switches shall have demonstrated 200,000 cycles at<MET> 93 degrees C</MET><ENG> 200 degrees F</ENG> and 100 percent relative 
humidity and shall withstand total submersion in water at<MET> 93 degrees C</MET><ENG> 200 degrees F</ENG>.  Another switch shall be 
provided to indicate high water level, and shall be connected to an emergency warning light mounted on or adjacent 
to the valve manhole as indicated.  This high water level alarm shall be set at a level which is below the bottom 
of any pipe in the valve manhole.  Auxiliary contacts in a separate junction box shall be provided to permit 
connection to a [future] Energy Monitoring and Control System (EMCS) for monitoring the operation of each pump 
motor and the high water level alarm system.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12.2   Drainers</TTL><BRK/>
<BRK/>
<TXT>Provide automatic type drainers to operate on<MET> 862 kPa (gage)</MET><ENG> 125 psig</ENG> steam supply.  The drainer shall operate 
when the water level rises sufficiently in the sump, the float shall rise and open the steam control valve to 
admit steam to the drainer, which in turn shall pump the water from the sump.  When the water level is lowered 
by the pumping action, the float shall lower and close the steam valve to stop the pumping action until water 
again gathers in the sump.  Provide each drainer with controls to accomplish the above sequence of operation.  
The automatic float-operated steam valve shall be designed to prevent dead centering under field conditions and 
to lengthen the life of the valve seat.  The valve shall have a high grade, renewable composition disc and a 
stainless steel or hard, noncorrosive bronze renewable seat inserted in the valve body.  The drainer shall be 
constructed of corrosion-resistant copper and bronze.  Piping from manhole drainers shall be <RID>ASTM A 53/A 53M</RID>, 
Weight Class XS (Extra Strong), hot-dip galvanized steel pipe with <RID>ASME B16.11</RID> or <RID>ASME B16.3</RID>, Class 300, hot-dip 
galvanized threaded fittings.  Provide a steam pressure regulating vaalve assembly for manhole drainers for operation 
on steam system above<MET> 862 kPa (gage)</MET><ENG> 125 psig</ENG>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.13   CONCRETE VALVE MANHOLES AND ACCESSORIES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If the referenced sections are not to be included in the project specifications, 
applicable paragraphs from the referenced sections must be incorporated into 
this specification.  The designer is also advised that, for Army projects, Section 
<SRF>31 00 00</SRF> EARTHWORK, and if electrically operated sump pumps are installed, either 
Section <SRF>33 71 01</SRF> OVERHEAD TRANSMISSION AND DISTRIBUTION or Section 
<SRF>33 70 02.00 10</SRF> ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND, or applicable portions 
of the above specifications, must be included as part of the project specifications.  
For Navy jobs, Section <SRF>31 23 00.00 20</SRF> EXCAVATION AND FILL, and if electrically 
operated sump pumps are installed, either Section <SRF>33 71 01</SRF> OVERHEAD TRANSMISSION 
AND DISTRIBUTION or Section <SRF>33 71 02.00 20</SRF> UNDERGROUND TRANSMISSION AND DISTRIBUTION, 
or applicable portions of the above specifications must be included as part 
of the project specifications.</NPR><BRK/>
<BRK/>
<NPR>The design of manholes including size, reinforcing, arrangement, penetrations, 
equipment and piping within the valve manholes is the responsibility of the 
designer.  Valve manholes shall be designed to provide proper venting and drainage 
and adequate room for maintenance without stepping on or over any equipment.  
When electric sump pumps are used, the electrical distribution and tie in points 
must be designed and shown on the drawings.</NPR><BRK/>
<BRK/>
<NPR>In most cases, valve manhole covers will consist of open grates.  If manhole 
top is to be used as part of a sidewalk and valve manhole is not deep, a solid 
plate cover may be used without special provisions for manhole ventilation.  
These tops must be designed to be removed or opened completely during maintenance 
operations.  For larger and deeper valve manholes, raised frame solid plate 
cover shall be required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.13.1   Valve Manhole Construction</TTL><BRK/>
<BRK/>
<TXT>Valve manhole dimensions shall be as indicated.  [The valve manholes shall be constructed of reinforced concrete 
as indicated and in accordance with Section <SRF>03 40 00.00 10</SRF> PLANT-PRECAST CONCRETE PRODUCTS FOR BELOW GRADE CONSTRUCTION.  
][Valve manholes shall be provided with a<MET> 762 mm</MET><ENG> 30 inch</ENG> standard cast iron frame and removable cover as a minimum, 
or a<MET> 900 by 900 mm</MET><ENG> 36 by 36 inch</ENG> watertight, hinged steel cover not less than<MET> 13 mm</MET><ENG> 1/2 inch</ENG> thick.]  Valve manholes 
shall be drained as shown.  Concrete sections shall not be less than<MET> 150 mm</MET><ENG> 6 inches</ENG> thick.  [The top shall be 
a cast concrete slab of the same strength and thickness as the valve manhole or fabricated from stainless steel, 
hot dipped galvanized steel or aluminum.] [The top shall be [open grate cover] [or] [raised frame] [solid plate 
cover (<MET>8 mm</MET><ENG> 5/16 inch</ENG> thick checker pattern) conforming to <RID>AA H35.1/35.1M</RID>].]  [When open grate covers are used 
for direct buried conduit systems, the top of the grate will be at least<MET> 150 mm</MET><ENG> 6 inches</ENG> above the surrounding 
grade.  When used for concrete shallow trenches, the top of the grate will be flush with the concrete trench 
top.  Open grates will be constructed of galvanized steel.  A checkered plate cover (also referred to as diamond 
plate or embossed plate), shall be installed over the grating in colder climates and where accumulation of trash 
is a problem.  This checkered plate shall be attached to the grating and shall be removable.] [Solid plate covers 
shall be used for HTHW and steam/condensate direct buried conduit systems only.  Solid plate covers shall not 
be used for shallow trench systems which are often used as sidewalks, or when substantial loadings are expected.  
Ventilation openings shall be provided around the entire perimeter below the raised top.  The solid plate cover 
assembly shall be removable.  The cover, constructed of aluminum, shall also provide sectionalized access for 
inspection and maintenance.] [When concrete covers are used for direct buried conduit systems, the top of the 
concrete cover shall be designed to be a minimum of<MET> 150 mm</MET><ENG> 6 inches</ENG> above the surrounding grade.  When used for 
concrete shallow trenches, the cover shall be designed to be flush with the trench top.  Concrete requirements 
for this cover shall be similar to those required for valve manhole construction.  Concrete cover shall be designed 
to support anticipated loadings.  A<MET> 1220 by 1220 mm</MET><ENG> 4 by 4 foot</ENG> aluminum access door (Bilco model JD-2AL or equal 
with slip resistant finish) shall be provided in the concrete top.  For concrete shallow trench systems, a single<MET>
 150 mm</MET><ENG> 6 inch</ENG> gooseneck pipe shall be used to allow steam to exit the valve manhole if a leak or excessive heat 
loss is present; the gooseneck shall be installed off to one side of the valve manhole concrete top to minimize 
pedestrian traffic interference.  For direct buried systems, two<MET> 150 mm</MET><ENG> 6 inch</ENG> goosenecks shall be used.  One 
shall extend below the top; the other shall be similar but shall extend to within<MET> 600 mm</MET><ENG> 2 feet</ENG> of the manhole 
floor to provide natural air movement.]  Valve manhole sides shall be constructed by one monolithic pour and 
shall extend not less than<MET> 150 mm</MET><ENG> 6 inches</ENG> above grade unless otherwise stated.  Valve manholes shall be waterproofed 
in accordance with Section <SRF>07 13 53</SRF> ELASTOMERIC SHEET WATERPROOFING.  All steel components shall be protected 
from corrosion.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.13.2   Ladders</TTL><BRK/>
<BRK/>
<TXT>Valve manhole ladders shall be steel, shall have nonslip surfaces, and shall consist of uprights with steps or 
rungs.  Ladders shall not be less than<MET> 406.4 mm</MET><ENG> 16 inches</ENG> in width, with<MET> 19.1 mm</MET><ENG> 3/4 inch</ENG> diameter rungs, spaced<MET>
 304.8 mm</MET><ENG> 12 inches</ENG> apart.  The two stringers shall be a minimum<MET> 9.5 mm</MET><ENG> 3/8 inch</ENG> thick and<MET> 63.5 mm</MET><ENG> 2-1/2 inches</ENG>
 wide.  Ladders shall be adequately anchored to the wall by means of steel inserts spaced not more than<MET> 2 m</MET><ENG> 6 
feet</ENG> apart vertically, and installed to provide at least<MET> 150 mm</MET><ENG> 6 inches</ENG> of space between the wall and rungs.  
Ladders and inserts shall be galvanized after fabrication in conformance with <RID>ASTM A 123/A 123M</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.13.3   Pipe Sleeves</TTL><BRK/>
<BRK/>
<TXT>Pipe sleeves of sufficient length to pass through valve manhole or building walls shall be provided.  Pipe sleeves 
shall be zinc-coated steel pipe, conforming to the requirement of <RID>ASTM A 53/A 53M</RID>, Schedule 40 or standard weight.  
The pipe sleeves shall be secured in the proper position and location during construction of the valve manhole 
or building wall.  For manhole top penetrations, the diameter of the pipe sleeve will be large enough to allow 
at least<MET> 6 mm</MET><ENG> 1/4 inch</ENG> of clearance between the pipe insulation and the sleeve, and, the sleeve will be sized 
to accommodate the specific mechanical seal size used for the [conduit] [or] [uninsulated chilled water pipe] 
penetration.  The space between the sleeve and the pipe casing, and the caulking and sealing materials shall 
be selected so there shall be NO electrical continuity between the pipe sleeve and the pipe casing when finished.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.13.3.1   Pipe Sleeves Through Valve Manhole Cover</TTL><BRK/>
<BRK/>
<TXT>Insulation shall be continuous through sleeves as shown on the drawings.  Aluminum jacket shall be provided over 
the insulation.  Aluminum jacket shall be smooth sheet<MET> 0.4064 mm</MET><ENG> 0.016 inch</ENG> nominal thickness, <MET><RID>ASTM B 209M</RID></MET><ENG> <RID>ASTM B 209</RID></ENG>
.  Where penetrating valve manhole top, pipe shall be insulated as required for valve manhole service up to a 
point flush with the top of the flashing and the end of the insulation shall be sealed with waterproof coating.  
Insulation exposed to the weather shall butt tightly against the flashing and valve manhole insulation, and the 
aluminum jacket required for piping exposed to the weather shall extend<MET> 50 mm</MET><ENG> 2 inches</ENG> beyond the insulation 
to form a counterflashing.  The entire valve manhole top penetration shall be flashed and counterflashed as shown 
on the drawings.  Waterproof coating shall conform to <RID>ASTM D 2822</RID>, Type I.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.13.3.2   Pipe Sleeves for Conduit Penetrations</TTL><BRK/>
<BRK/>
<TXT>A modular mechanical type sealing assembly will be used between the valve manhole pipe sleeve and the [conduit 
casing] [or] [uninsulated chilled water pipe].  The mechanical seal shall consist of interlocking elastomeric 
links shaped to continuously fill the annular space between the [casing] [or] [uninsulated chilled water pipe] 
and sleeve.  The link material shall be a synthetic elastomeric capable of withstanding long term exposure at<MET>
 205 degrees C</MET><ENG> 400 degrees F</ENG> without deterioration.  The links shall be attached to each other with corrosion 
resistant steel bolts, nuts and pressure plates.  The link, bolts, nuts and pressure plates shall be the product 
of single manufacturer and shall be furnished as the product of single manufacturer and shall be furnished as 
a package or kit.  The links shall be loosely assembled with bolts to form a continuous rubber belt around the 
[casing] [or] [uninsulated chilled water pipe] with a pressure plate under each bolt head and each nut.  After 
the seal assembly is properly positioned in the sleeve, tightening of the bolt shall cause the rubber sealing 
elements to expand and provide a watertight seal between the [casing] [or] [the uninsulated chilled water pipe] 
and the sleeve.  The pipe sleeve diameter shall be sized so that no more than one half of the seal assembly's 
expansion capability is used to achieve a water seal.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.13.4   Pipe Supports</TTL><BRK/>
<BRK/>
<TXT>Pipe Supports shall be in accordance with <RID>MSS SP-58</RID> and <RID>MSS SP-69</RID>, type as shown.  All pipe supports, including 
structural cross support members, shall be galvanized in accordance with Section <SRF>05 50 13</SRF> MISCELLANEOUS METAL 
FABRICATIONS.  Chains, straps, or single point supports shall not be used.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.14   <SUB>EXPANSION JOINTS</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Expansion joints generally will not be used in the design of the piping 
layout.  If no other method is available to handle the expansion problem in 
a specific location, the design layout using an expansion joint at a specific 
location must be justified by a design analysis and approved in the planning 
phase of the piping layout, prior to including expansion joints in the specifications.  
Cold spring (pipe expansion) will be shown on the drawings.  Sizing of expansion 
loops and bends will not be based on cold spring.</NPR><BRK/>
<BRK/>
<NPR>If expansion joints or ball joints are required, the locations will be indicated 
on the drawings.  Since expansion joints are high maintenance items, they must 
be located in a readily accessible location.  Type I and III slip joint, packed 
expansion joints are adjustable gland type and require continuing maintenance 
to contain leakage and are now manufactured by only one company making them 
proprietary.  For these reasons, these types are not specified.<BRK/>
<BRK/>
Coordinate this paragraph with paragraph PIPING in PART 3; remove this whole 
paragraph or subparagraphs not required in the project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
[<SPT><TTL>2.14.1   Guided Slip Tube</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Expansion joints shall provide for either single or double slip of the 
connected pipes, as required or indicated, and for not less than the traverse 
indicated.  The joints shall be designed for hot water working pressure in accordance 
with applicable requirements of EJMA-01 and ASME B31.1.  This joint is designed 
for packing injection under full line pressure.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Internally-externally guided type, injected semiplastic type packing, with service outlets.  Joints shall be 
for minimum working pressure of ASME Class 150.  Provide single or double slip tube type as indicated.  Provide 
flanged or buttwelding end connections as indicated.</TXT><BRK/>
<BRK/></SPT>
][<SPT><TTL>2.14.2   Flexible Ball</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The ball joint will be designed for packing injection under full line 
pressure to contain leakage.  Balls and sockets will be of equivalent material 
as the adjoining pipeline.  The exterior spherical surface of carbon steel balls 
will be plated with 0.051 mm (2 mils) of hard chrome in accordance with ASTM 
B 650.  The ball type joints will be designed and constructed in accordance 
with ASME B31.1 and Section VIII, Boiler and Pressure Vessel Code, where applicable.  
Flanges where required will conform to ASME B16.5.  Gaskets and compression 
seals will be compatible with the service intended.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Provide chromium plated steel balls capable of 360-degree rotation plus 15-degree angular flex movement.  Provide 
pressure molded composition gaskets designed for continuous operation temperature of<MET> 274 degrees C</MET><ENG> 525 degrees 
F</ENG>.  Joints shall be for minimum working pressure of ASME Class 150.  Provide flanged or buttwelding end connections 
as indicated.</TXT><BRK/>
<BRK/></SPT>
][<SPT><TTL>2.14.3   Bellows-Type</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Bellows type joints must be flexible, guided expansion joints.  The expansion 
element will be stabilized corrosion resistant steel.  Bellows type expansion 
joints will conform to the applicable requirements of EJMA-01 and ASME B31.1 
with internal liners.  The joints will be designed for the working temperature 
and pressure suitable for the application but will not be less than 1034 kPa 
(150 psig).</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Type 304 staniless steel corrugated bellows, reinforced with rings, internal sleeves, and external protective 
covers.  Provide limit stops to limit total movement in both directions.  Cold set the joints to compensate for 
temperature at time of installation.  Joints shall withstand 10,000 cycles over a 20 year period.  Joints shall 
be for minimum working pressure of ASME Class 150.  Provide single or double bellows expansion joint as indicated.  
Provide first pipe alignment guide no more than four pipe diameters from the expansion joint; provide second 
pipe alignment guide no more than 14 pipe diameters from the first guide.  Provide flanged or buttwelding end 
connections as indicated.</TXT><BRK/>
<BRK/></SPT>
]</SPT><SPT><TTL>2.15   MISCELLANEOUS METAL</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include miscellaneous metals located in trenches or valve manholes in 
Section <SRF>05 50 13</SRF> MISCELLANEOUS METAL FABRICATIONS.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Miscellaneous metal not otherwise specified, shall conform to Section <SRF>05 50 13</SRF> MISCELLANEOUS METAL FABRICATIONS.  
Miscellaneous metal bolted together, shop welded, or assembled in the field, and pipe supports, including structural 
cross support members and anchors, shall be hot-dip galvanized in accordance with Section <SRF>05 50 13</SRF> MISCELLANEOUS 
METAL FABRICATIONS.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   EXAMINATION</TTL><BRK/>
<BRK/>
<TXT>After becoming familiar with all details of the work, verify all dimensions in the field, and advise the Contracting 
Officer of any discrepancy before performing the work.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   SITE WORK</TTL><BRK/>
<BRK/>
<SPT><TTL>3.2.1   Excavation, Trenching, and Backfilling</TTL><BRK/>
<BRK/>
<TXT>Excavation, trenching, and backfilling of the valve manholes shall be as shown and in accordance with Section 
<SRF>31 00 00</SRF> EARTHWORK.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.2   Electric Work</TTL><BRK/>
<BRK/>
<TXT>Any wiring required for the operation of the equipment specified, but not shown on the electrical drawings, shall 
be provided under this section in accordance with Sections [<SRF>33 71 01</SRF> OVERHEAD TRANSMISSION AND DISTRIBUTION, 
and Section <SRF>33 70 02.00 10</SRF> ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND] [<SRF>33 71 01</SRF> OVERHEAD TRANSMISSION AND DISTRIBUTION 
and Section <SRF>33 71 02.00 20</SRF> UNDERGROUND TRANSMISSION AND DISTRIBUTION].</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.3   Painting</TTL><BRK/>
<BRK/>
<TXT>The heat affected zone of field welded galvanized surfaces and other galvanized surfaces damaged during installation 
shall be cleaned in compliance with <RID>SSPC SP 10</RID>, and painted in accordance with Section <SRF>09 90 00</SRF> PAINTS AND COATINGS.  
Steel and iron appurtenances, piping, and supports shall be cleaned in compliance with <RID>SSPC SP 10</RID>, and painted 
in accordance with <RID>SSPC Paint 16</RID>, coal-tar epoxy-polyamide.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.3   PIPING</TTL><BRK/>
<BRK/>
<SPT><TTL>3.3.1   General</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete provisions in brackets and all other references to threaded connections 
for high temperature water systems.</NPR><BRK/>
<BRK/>
<NPR>If expansion joints are required, coordinate this paragraph with paragraph EXPANSION 
JOINTS in PART 2.<BRK/>
<BRK/>
For Guided Slip Tube expansion joints the end connections will be flanged or 
beveled for welding as indicated.  Joint shall be provided with an anchor base 
where required or indicated.  Where adjoining pipe is carbon steel, the sliding 
slip shall be seamless steel plated with a minimum of 0.051 mm (2 mils) of hard 
chrome in accordance with ASTM B 650.  All joint components shall be fabricated 
from material equal to that of the pipeline.  Initial setting shall be made 
in accordance with the manufacturer's recommendations to compensate for ambient 
temperature at time of installation.  Pipe alignment guides shall be installed 
as recommended by the joint manufacturer, but in any case shall not be more 
than 1.5 m (5 feet) from expansion joint except that in lines 100 mm (4 inches) 
or smaller, guides will be installed not more than 600 mm (2 feet) from the 
joint.  Service outlets will be provided where indicated.</NPR><BRK/>
<BRK/>
<NPR>Flexible ball joints will be constructed of alloys as appropriate for the service 
intended.  Joint ends will be threaded (to 50.8 mm (2 inches) only), grooved, 
flanged or beveled for welding as indicated or required, and must be capable 
of absorbing a minimum of 15-degree angular flex and 360-degree rotation.</NPR><BRK/>
<BRK/>
<NPR>For Bellows-Type joints, guiding of piping on both sides of expansion joint 
will be in accordance with the published recommendations of the manufacturer 
of the expansion joint.  When a joint is installed within four pipe diameters 
of an anchor, only one side needs guiding.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>All piping in valve manholes shall be steel and insulated.  Insulation shall be protected with [an aluminum] 
[galvanized steel] jacket [, except for chilled water lines where indicated not to be insulated.]  Pipe shall 
be accurately cut to measurements established at the site and shall be worked into place without springing or 
forcing.  Pipe and insulation shall clear all openings and equipment.  Excessive cutting or other weakening of 
structural members to facilitate piping installation will not be permitted.  Burrs shall be removed from ends 
of pipe by reaming.  Installation shall permit free expansion and contraction without damage to joints or hangers.  
Piping shall be installed in accordance with <RID>ASME B31.1</RID>.  Joints for piping in valve manholes shall be welded 
[, except joints at traps, strainers, and at valves and piping<MET> 19 mm</MET><ENG> 3/4 inch</ENG> and smaller which may be threaded].  
[Flanged joints will be permitted for dielectric isolation only.]  Supports, anchors, or stays shall not be attached 
where either expansion or the weight of the pipe will cause damage to permanent construction.  The method of 
attaching supports shall not interfere with the operation of the cathodic protection system.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.2   Welded Joints</TTL><BRK/>
<BRK/>
<TXT>Joints between sections of pipe, between sections of pipe and valves, and between sections of pipe and fittings 
shall be welded [except where joints are allowed to be screwed for pipe sizes<MET> 19 mm</MET><ENG> 3/4 inch </ENG> and smaller].  
The welding shall conform to the requirements specified in paragraph WELDING.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.3   Flanged and Threaded Joints</TTL><BRK/>
<BRK/>
<SPT><TTL>3.3.3.1   Flanged Joints</TTL><BRK/>
<BRK/>
<TXT>Flanged joints shall be faced true, provided with gaskets, and made perfectly square and tight.  Flanged joints 
shall be used only for electrical isolation and in other special cases where connected equipment is available 
with only flanged joints, or when specifically shown on the drawings.  Electrically isolated flange joints shall 
be provided at all connections to or from the heat distribution system and between dissimilar metals.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.3.2   Threaded Joints</TTL><BRK/>
<BRK/>
<TXT>Threaded joints shall have graphite or inert filler and oil, graphite compound, or polytetrafluoroethylene tape 
applied to the male threads only.  Unions shall be provided at all screwed valves, strainers and connections 
to equipment<MET> 19 mm</MET><ENG> 3/4 inch</ENG> and smaller.  Dielectric unions shall be used at connections of dissimilar metals 
in<MET> 19 mm</MET><ENG> 3/4 inch</ENG> and smaller piping.  When used on High Temperature Water Systems, threaded joints shall be 
seal welded.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.3.4   Reducing Fittings</TTL><BRK/>
<BRK/>
<TXT>Eccentric reducers in horizontal runs shall be installed with the straight side down.  Changes in horizontal 
piping sizes shall be made through eccentric reducing fittings.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.5   Branch Connections</TTL><BRK/>
<BRK/>
<TXT>Branches from mains shall branch off top of mains as indicated or as approved.  Connections shall ensure unrestricted 
circulation, elimination of air pockets, and shall permit the complete drainage of the system.  Branch connections 
may be made with either welding tees or forged branch outlet fittings.  Branch outlet fittings where used shall 
be forged and shall be no larger than two nominal pipe sizes smaller than the main run.  Branch outlet fittings 
shall be reinforced to withstand external strains and designed to withstand full pipe bursting strength.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.6   Pipe Supports in Valve Manholes</TTL><BRK/>
<BRK/>
<TXT>Horizontal and vertical runs of pipe in valve manholes shall be securely supported.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.4   WELDING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  If the need exists for more stringent pipe welding requirements, delete 
the sentences in the first set of brackets.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>[Piping shall be welded in accordance with qualified procedures, using performance qualified welders and welding 
operators.  Procedures and welders shall be qualified in accordance with <RID>ASME BPVC SEC IX</RID>.  Welding procedures 
qualified by others, and welders and welding operators qualified by another employer may be accepted as permitted 
by <RID>ASME B31.1</RID>.  The Contracting Officer shall be notified 24 hours in advance of tests and the tests shall be 
performed at the work site.  The welder or welding operator shall apply his assigned symbol near each weld he 
makes as a permanent record.] [Welding and nondestructive testing procedures for piping shall be as specified 
in Section [<SRF>43 02 00</SRF>] [<SRF>40 17 26.00 20</SRF>] WELDING PRESSURE PIPING.]  Structural members shall be welded in accordance 
with Section <SRF>05 05 23</SRF> WELDING, STRUCTURAL.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5   INSULATION</TTL><BRK/>
<BRK/>
<TXT>The insulation shall be installed so that it will not be damaged by pipe expansion or contraction.  Insulation 
shall not become wet before, during, or after installation.  Insulation installed over welds shall be grooved 
to assure a snug fit.  Insulation shall be held in place with stainless steel straps.  A minimum of 2 bands shall 
be installed on each individual length of insulation and maximum spacing shall not exceed<MET> 450 mm</MET><ENG> 18 inch</ENG> centers.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.5.1   Installation</TTL><BRK/>
<BRK/>
<TXT>Material shall be installed in accordance with published installation instructions of the manufacturer.  Insulation 
materials shall not be applied until piping tests are completed.  Prior to application, surfaces shall be thoroughly 
cleaned of moisture, grease, dirt, rust, and scale, and painted where required.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.2   Insulation on Pipes Passing Through Sleeves</TTL><BRK/>
<BRK/>
<TXT>Insulation shall be continuous, as required by paragraph Pipe Sleeves Through Valve Manhole Cover.  Aluminum 
jackets shall be provided over the insulation.  When penetrating valve manhole walls, aluminum jacket shall extend 
not less than<MET> 50 mm</MET><ENG> 2 inches</ENG> beyond the sleeve on each side of the wall and shall be secured with an aluminum 
band on each side of the wall.  Where flashing is provided, the jacket shall be secured with not less than one 
band located not more than<MET> 25 mm</MET><ENG> 1 inch</ENG> from the end of the jacket.  When penetrating valve manhole tops, pipe 
shall be insulated as required for valve manhole service as indicated.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.3   Covering of Insulation in Valve Manholes</TTL><BRK/>
<BRK/>
<TXT>The insulation for pipe, flanges, valves, and fittings shall be covered with [aluminum] [galvanized steel] jackets.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.4   Insulation of Piping Accessories in Valve Manholes</TTL><BRK/>
<BRK/>
<TXT>Flanges, couplings, unions, valves, fittings, and other pipe accessories, unless otherwise shown or approved, 
shall be insulated with removable and reusable factory premolded, prefabricated, or field fabricated insulation.  
For accessories in valve manholes, [aluminum] [galvanized steel] sheet shall be applied over the insulation.  
Where accessories are designated not to be insulated, the adjoining insulation and jacket shall terminate neatly.  
The terminations for the chilled water systems shall provide a complete vapor seal.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.5   Insulation Sealing for Chilled Water Systems</TTL><BRK/>
<BRK/>
<TXT>The ends of insulation shall be sealed with vapor barrier.  Penetrations shall be caulked.  Caulking shall be 
applied to parting line between equipment and removable section insulation.  Upon completion of installation 
of the insulation, including removable sections, two coats of vapor barrier coating shall be applied with a layer 
of glass cloth embedded between the coats.  The total dry thickness of the finish shall be<MET> 1.6 mm</MET><ENG> 1/16 inch</ENG>.  
The coating shall be applied so that the removable sections are coated separate from the body of the equipment 
so these sections remain removable.  Coating shall be applied to flanges, unions, valves, anchors, fittings and 
accessories, all terminations, and all insulation not protected by factory vapor barrier jackets or PVC fitting 
covers.  Tape seams shall overlap<MET> 25 mm</MET><ENG> 1 inch</ENG>.  The coating shall extend out onto the adjoining pipe insulation<MET>
 50 mm</MET><ENG> 2 inches</ENG>.  Insulation terminations shall be tapered to unions at a 45-degree angle.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5.6   Insulation Thickness</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete inapplicable columns in Tables 1 and 2.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The minimum thickness of insulation for [the heat distribution system] [and] [condensate return system] [each 
section of pipe] shall be in accordance with Tables 1 and 2.</TXT><BRK/>
<MET><BRK/>
<HL4>TABLE 1</HL4><BRK/>
<HL4>Minimum Pipe Insulation Thickness (In millimeters)</HL4><BRK/>
<BRK/>
<HL4>For steam (110 to 2,800 kPa (gage)) and High Temperature</HL4><BRK/>
<HL4>Hot Water Supply and Return (120 to 230 degrees C)</HL4><BRK/>
<TBL><THD><BRK/>
    Nominal     MPT-PC     Delta       Thermo-12       Foamglass<BRK/>
     Pipe       MPT-PF                 Super                    <BRK/>
   Diameter                            Caltemp                  <BRK/>
     (mm)                                                       <BRK/></THD>
<BRK/>
      25          50         63          100              115<BRK/>
      40          50         63          100              115<BRK/>
      50          65         85          110              125<BRK/>
      65          65         85          110              125<BRK/>
      80          75        100          125              150<BRK/>
     100          75        100          125              150<BRK/>
     125          75        100          125              150<BRK/>
     150          85        110          135              150<BRK/>
     200          85        110          135              150<BRK/>
     250         100        125          150              165<BRK/>
     300         100        125          150              165<BRK/>
     350         100        125          150              165<BRK/>
     400         100        125          150              165<BRK/>
     450         100        125          150              165<BRK/></TBL>
</MET><ENG><BRK/>
<HL4>TABLE 1</HL4><BRK/>
<HL4>Minimum Pipe Insulation Thickness (In inches)</HL4><BRK/>
<BRK/>
<HL4>For steam (16 to 408 psig) and High Temperature</HL4><BRK/>
<HL4>Hot Water Supply and Return (250 to 450 degrees F)</HL4><BRK/>
<TBL><THD><BRK/>
    Nominal     MPT-PC     Delta       Thermo-12       Foamglass<BRK/>
     Pipe       MPT-PF                 Super                    <BRK/>
   Diameter                            Caltemp                  <BRK/>
   (inches)                                                     <BRK/></THD>
<BRK/>
     1.0          2.0       2.5          4.0                 4.5<BRK/>
     1.5          2.0       2.5          4.0                 4.5<BRK/>
     2.0          2.5       3.5          4.5                 5.0<BRK/>
     2.5          2.5       3.5          4.5                 5.0<BRK/>
     3.0          3.0       4.0          5.0                 6.0<BRK/>
     4.0          3.0       4.0          5.0                 6.0<BRK/>
     5.0          3.0       4.0          5.0                 6.0<BRK/>
     6.0          3.5       4.5          5.5                 6.0<BRK/>
     8.0          3.5       4.5          5.5                 6.0<BRK/>
    10.0          4.0       5.0          6.0                 6.5<BRK/>
    12.0          4.0       5.0          6.0                 6.5<BRK/>
    14.0          4.0       5.0          6.0                 6.5<BRK/>
    16.0          4.0       5.0          6.0                 6.5<BRK/>
    18.0          4.0       5.0          6.0                 6.5<BRK/>
<BRK/></TBL>
</ENG><MET><BRK/>
<HL4>TABLE 2</HL4><BRK/>
<HL4>Minimum Pipe Insulation Thickness (In millimeters)</HL4><BRK/>
<BRK/>
<HL4>For Low Pressure Steam (less than 110 kPa (gage)), Condensate Return</HL4><BRK/>
<HL4>and Low Temperature Hot Water (less than 120 degrees C)</HL4><BRK/>
<HL4>Supply and Return</HL4><BRK/>
<TBL><THD><BRK/>
    Nominal     MPT-PC     Delta       Thermo-12       Foamglass<BRK/>
     Pipe       MPT-PF                 Super                    <BRK/>
   Diameter                            Caltemp                  <BRK/>
     (mm)                                                       <BRK/></THD>
<BRK/>
      25          40        50           80                   80<BRK/>
      40          40        50           80                   80<BRK/>
      50          40        50           80                   80<BRK/>
      65          40        50           80                   80<BRK/>
      80          50        65           85                   85<BRK/>
     100          50        65           85                   85<BRK/>
     125          50        65           85                   85<BRK/>
     150          65        80          110                  110<BRK/>
     200          65        80          110                  110<BRK/>
     250          80       100          125                  125<BRK/>
     300          80       100          125                  125<BRK/>
     350          80       100          125                  125<BRK/>
     400          80       100          125                  125<BRK/>
     450          80       100          125                  125<BRK/></TBL>
</MET><ENG><BRK/>
<HL4>TABLE 2</HL4><BRK/>
<HL4>Minimum Pipe Insulation Thickness (In inches)</HL4><BRK/>
<BRK/>
<HL4>For Low Pressure Steam (less than 16 psig), Condensate Return</HL4><BRK/>
<HL4>and Low Temperature Hot Water (less than 250 degrees F)</HL4><BRK/>
<HL4>Supply and Return</HL4><BRK/>
<TBL><THD><BRK/>
    Nominal     MPT-PC     Delta       Thermo-12       Foamglass<BRK/>
     Pipe       MPT-PF                 Super                    <BRK/>
   Diameter                            Caltemp                  <BRK/>
   (inches)                                                     <BRK/></THD>
<BRK/>
     1.0          1.5       2.0          3.0                 3.0<BRK/>
     1.5          1.5       2.0          3.0                 3.0<BRK/>
     2.0          1.5       2.0          3.0                 3.0<BRK/>
     2.5          1.5       2.0          3.0                 3.0<BRK/>
     3.0          2.0       2.5          3.5                 3.5<BRK/>
     4.0          2.0       2.5          3.5                 3.5<BRK/>
     5.0          2.0       2.5          3.5                 3.5<BRK/>
     6.0          2.5       3.0          4.5                 4.5<BRK/>
     8.0          2.5       3.0          4.5                 4.5<BRK/>
    10.0          3.0       4.0          5.0                 5.0<BRK/>
    12.0          3.0       4.0          5.0                 5.0<BRK/>
    14.0          3.0       4.0          5.0                 5.0<BRK/>
    16.0          3.0       4.0          5.0                 5.0<BRK/>
    18.0          3.0       4.0          5.0                 5.0<BRK/></TBL>
</ENG><BRK/></SPT>
</SPT><SPT><TTL>3.6   <SUB>VALVE MANHOLES AND ACCESSORIES</SUB></TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide design details on drawings of concrete reinforcing, size, dimensions 
of valve manhole, piping arrangements, type of removable cover, valve manhole 
penetrations, pipe and equipment supports, etc.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>3.6.1   Piping and Equipment in Valve Manholes</TTL><BRK/>
<BRK/>
<TXT>Piping and equipment in valve manholes shall be installed to provide easy access without stepping on piping or 
equipment, and to provide sufficient working room.  Piping and equipment in valve manholes shall be installed 
and supported as shown on the drawings.  All globe, angle and gate valves shall be installed with the stems horizontal 
or above.  Submit <SUB>Data Package 2</SUB> as related to all equipment provided for the project.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6.2   Sump Pumps Installation</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate this paragraph with the specified requirements in paragraph 
SUMP PUMPS.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Sump pumps shall be installed as indicated.  All electrical connections shall be hard wired.[  Monitoring of 
each pump motor and the high water alarm shall be connected to the Energy Monitoring and Control System (EMCS).  
Coordinate electrical requirements of EMCS with Section <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM].  Electrical circuits 
to the sump pumps shall be dedicated circuits.  All circuit breakers and switches in the electrical power distribution 
to the sump pumps shall be capable of being locked in the "ON" position and will be signed as follows:</TXT><BRK/>
<BRK/>
<LST>a.  THIS CIRCUIT SUPPLIES POWER TO THE ELECTRIC SUMP PUMPS IN THE UNDERGROUND DISTRIBUTION SYSTEM.  THIS 
CIRCUIT MUST BE "ON" AT ALL TIMES; OTHERWISE EXTENSIVE DAMAGE WILL OCCUR TO THE UNDERGROUND HEAT DISTRIBUTION 
SYSTEM AND PREMATURE FAILURE WILL OCCUR.</LST><BRK/>
<BRK/>
<LST>b.  The words on the sign shall be stamped on a corrosion resistant metal plate with letters<MET> 10 mm</MET><ENG> 3/8 
inch</ENG> high, and the plate shall be affixed permanently near the switch or circuit breaker.</LST><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.7   TESTS</TTL><BRK/>
<BRK/>
<TXT>Tests of piping in the valve manholes will be performed as part of the testing of the direct buried conduit system.  
These tests shall include the piping in the valve manhole and performed in accordance with the system supplier's 
Approved Brochure or the contract specifications.</TXT><BRK/>
<BRK/></SPT>
</PRT>   <END/><BRK/></SEC>