<?xml version="1.0" encoding="windows-1252"?><SEC xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://si.ksc.nasa.gov/sidownloads/xml/specsintactSEC.xsd"><MTA NAME="SUBFORMAT" CONTENT="NEW"/><BRK/>
<HDR><AST/><BRK/>
USACE / NAVFAC / AFCESA / NASA                  UFGS-33 61 15 (July 2006)<BRK/>
                                                --------------------------<BRK/>
Preparing Activity:  <PRA>USACE</PRA>                      Superseding<BRK/>
                                                UFGS-33 61 15 (April 2006)<BRK/>
<BRK/>
<HL4>UNIFIED FACILITIES GUIDE SPECIFICATIONS</HL4><BRK/>
<BRK/>
<HL4>References are in agreement with UMRL dated January 2009</HL4><BRK/>
<AST/><BRK/></HDR>
<BRK/>
<SCN>SECTION 33 61 15</SCN><BRK/>
<BRK/>
<STL>HEAT DISTRIBUTION SYSTEMS IN CONCRETE TRENCHES</STL><BRK/>
<DTE>07/06</DTE><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This guide specification covers the requirements for <SCP>heat distribution 
systems of the concrete trench type for water systems from 66 to 232 degrees 
C (150 to 450 degrees F) and steam systems up to 1.72 MPa (250 psig)</SCP>.<BRK/>
<BRK/>
Edit this guide specification for project specific requirements by adding, deleting, 
or revising text.  For bracketed items, choose applicable items(s) or insert 
appropriate information.<BRK/>
<BRK/>
Remove information and requirements not required in respective project, whether 
or not brackets are present.<BRK/>
<BRK/>
Comments and suggestions on this guide specification are welcome and should 
be directed to the technical proponent of the specification.  A listing of <URL HREF="http://65.204.17.188/report/ufgs.html">technical 
proponents</URL>, including their organization designation and telephone number, is 
on the Internet.<BRK/>
<BRK/>
Recommended changes to a UFGS should be submitted as a  <URL HREF="http://65.204.17.188/projnet/cms/public.html">Criteria Change Request 
(CCR)</URL>.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<PRT><TTL>PART 1   GENERAL</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  For a complete system include Section <SRF>33 60 01</SRF> VALVES, PIPING, AND EQUIPMENT 
IN VALVE MANHOLES.  The designer will comply with the procedure as outlined 
in the following paragraphs 1 through 5 in determining site conditions and trench 
system design.  If specific site conditions are not suitable for a concrete 
trench system in accordance with following guidance, refer to Section 
<SRF>33 63 23</SRF> EXTERIOR ABOVEGROUND STEAM DISTRIBUTION or Section <SRF>33 61 13</SRF> PRE-ENGINEERED 
UNDERGROUND HEAT DISTRIBUTION SYSTEM.</NPR><BRK/>
<BRK/>
<NPR>SITE CLASSIFICATION AND CONCRETE TRENCH DESIGN GUIDANCE</NPR><BRK/>
<BRK/>
<NPR>1.  Classification of the Site:  A detailed site classification survey will 
be conducted by a geotechnical engineer using the following guidelines:</NPR><BRK/>
<BRK/>
<NPR>     a.  The survey will be made after the general layout of the system has 
been determined and will cover the entire length of the proposed system.  The 
geotechnical engineer must be a registered professional engineer with a minimum 
of 3 years of experience in the field of soil mechanics and foundation design.</NPR><BRK/>
<BRK/>
<NPR>     b.  The survey should be conducted during the time of the year when the 
groundwater table is historically at its highest point; if this is not possible, 
water table measurements will be corrected, on the basis of professional judgement, 
to indicate the highest seasonal water table when water table is at its highest 
point.</NPR><BRK/>
<BRK/>
<NPR>     c.  As a minimum, information on groundwater conditions, soil types, terrain, 
and precipitation rates and irrigation practices in the area of the system will 
be collected.  This information will be obtained from available records at the 
installation.</NPR><BRK/>
<BRK/>
<NPR>     d.  Information on groundwater conditions and soil types will be obtained 
through borings, test pits, or other suitable exploratory means.  Generally, 
in areas of prior construction, a boring or test pit will be made at least every 
30 m (100 feet) along the line of the proposed system.  In open undisturbed 
natural areas, the spacing of borings may be increased.  Each exploratory hole 
should extend to a level at least 1.5 m (5 feet) below the bottom of the tunnel.  
If a significant difference in underground conditions is found at adjacent exploratory 
points, additional explorations will be made between those points in order to 
determine where the change occurs.  Upon completion of the survey, each exploration 
point will be classified on the basis of the criteria presented in Table 1, 
ALLOWABLE SOIL CHARACTERISTICS and the soil classification system in ASTM D 
2487.  If the criteria of Table 1 is not met, the site conditions are not suitable 
for the use of a concrete trench.</NPR><BRK/>
<TBL><THD><BRK/>
<HL4>TABLE 1</HL4><BRK/>
<HL4>ALLOWABLE SOIL CHARACTERISTICS FOR CONCRETE TRENCH APPLICATION</HL4><BRK/>
<HL4>(SEE NOTE 1)</HL4><BRK/>
<BRK/>
                   General Conditions    Surface Water<BRK/>
                   of Ground Water       Accumulation<BRK/>
   Site Soil       During the Wettest    Rainfall/        Trench<BRK/>
   Conditions      Period of the Year    Irrigation       Construction<BRK/>
----------------------------------------------------------------------<BRK/></THD>
<BRK/>
   A.<BRK/>
   Fine Grained    Water table gen-      5 year - 7 day    Continuous<BRK/>
   Impervious      erally 300 mm         rainfall equal    wall and<BRK/>
   or              (1 foot) below        to or less        bottom<BRK/>
   Semipervious    lowest point of       than 250 mm<BRK/>
   and Coarse      water entry (See      (10 inches)<BRK/>
   Grained         Note 4) with not      (See Note 2)<BRK/>
   Impervious      more than 25 <BRK/>
                   percent of the<BRK/>
                   proposed concrete<BRK/>
                   trench system<BRK/>
                   showing water within<BRK/>
                   300 mm (1 foot) but<BRK/>
                   no higher than lowest<BRK/>
                   point of water entry<BRK/>
----------------------------------------------------------------------<BRK/>
   B.<BRK/>
   Coarse          Same as for           5 year - 7 day    Continuous<BRK/>
   Grained         A., above             rainfall equal    wall and<BRK/>
   Semipervious                          to or less        bottom<BRK/>
                                         than 250 mm <BRK/>
                                         (10 inches)<BRK/>
                                         (See Note 2)<BRK/>
                  ----------------------------------------------------<BRK/>
                   Water table gener-    5 year - 7 day    Continuous<BRK/>
                   ally 600 mm (2 feet)  rainfall equal    wall;<BRK/>
                   or more below lowest  to or less        opening may<BRK/>
                   point of water entry  than 200 mm       be provided<BRK/>
                   with not more than    (8 inches)        in trench<BRK/>
                   10 percent of the     (See Note 2)      bottom to<BRK/>
                   length of the pro-                      provide<BRK/>
                   posed concrete                          drainage<BRK/>
                   trench system show-<BRK/>
                   ing water within<BRK/>
                   600 mm (2 feet) but<BRK/>
                   no closer than 300 mm<BRK/>
                   (1 foot) to lowest<BRK/>
                   point of water entry<BRK/>
----------------------------------------------------------------------<BRK/>
   C.<BRK/>
   Swelling        Same as for           Same as for       Same as for<BRK/>
   Soils           A., above             A., above         A., above<BRK/>
                   (See Note 3)                            plus design<BRK/>
                                                           of joint<BRK/>
                                                           spacing and<BRK/>
                                                           joint<BRK/>
                                                           details to<BRK/>
                                                           accommodate<BRK/>
                                                           movement<BRK/>
----------------------------------------------------------------------<BRK/>
   Notes:<BRK/>
   1.  Concrete trench systems will not be used if any of the<BRK/>
       conditions defined by these criteria are exceeded.<BRK/>
<BRK/>
   2.  As shown in U.S. Weather Bureau (USWB) Tech. Paper 40 and<BRK/>
       confirmed with local data and local weather patterns.<BRK/>
<BRK/>
   3.  Swelling soils are defined as those which experience large<BRK/>
       volume changes with changes in moisture content.<BRK/>
<BRK/>
   4.  Lowest point of water entry is defined as the joint between<BRK/>
       trench wall and trench bottom.<BRK/></TBL>
<BRK/>
<NPR>2.  DESIGN:  The design will be completed based on the following soil conditions:</NPR><BRK/>
<BRK/>
<NPR>     a.  Fine grained impervious soils.  The highest groundwater level evident 
during the wettest period of the year should be a minimum of 300 mm (1 foot) 
below the lowest point of water entry into the concrete trench system.  The 
lowest point of entry is defined as the joint between the concrete trench wall 
and concrete trench bottom.  The concrete trench bottom will be continuous with 
no openings.  The above condition will allow the concrete trench to be constructed 
and will minimize potential infiltration of water into the trench.  Open drainage 
ways, swales, or swampy/boggy areas will preclude use of a concrete trench system 
because of ground water level guidance in Table 1.  The concrete trench system 
must be rerouted or regraded to bring the concrete trench out of the unsuitable 
conditions.  The geotechnical engineer who performed the detailed site classification 
survey will provide regrading instructions and will select the fill that will 
remain stable and will not be subject to future wash-outs.</NPR><BRK/>
<BRK/>
<NPR>     b.  Coarse grained semipervious/pervious soils.  The groundwater level 
during the wettest period of the year should be at least 300 mm (1 foot) below 
the lowest point of water entry into the concrete trench system.  For a water 
table 300 to 600 mm (1 to 2 feet) below the lowest point of water entry the 
criteria of paragraph 2.a., above apply.</NPR><BRK/>
<BRK/>
<NPR>     c.  Swelling Soils with high swell potential.  The design of the concrete 
trench system in materials having high swell potential will be in accordance 
with paragraph 2.a., above.  Soils having a liquid limit (LL) greater than 50 
and a plasticity index (PI) greater than 25 will require testing (consolidation 
swell) to determine the swell characteristics.  When the results of the swell 
test indicate high swell potential, special considerations such as over excavation 
(width and depth) and replacement with nonexpansive fill, under-trench drainage 
system, or other methods of minimizing differential heave will be provided.  
The design of special features such as described above will be in accordance 
with instructions provided by the geotechnical engineer who performed the detailed 
site classification survey.  Design of joint spacing and joint details to accommodate 
movements will be provided when required.</NPR><BRK/>
<BRK/>
<NPR>3.  SETTLEMENT OF TRENCHES:  Generally, settlement of concrete trenches will 
not be a problem since the unit load of the trench system will be similar to 
the existing unit overburden load.  Backfill adjacent to the concrete trench 
must be compacted to prevent settlement which would create ponding.  Positive 
slopes away from the concrete trench are required.  Special care of backfill 
and compaction will be required where the system crosses existing streets to 
preclude settlement and cracking of the roadway adjacent to the trench from 
repeated traffic loads.</NPR><BRK/>
<BRK/>
<NPR>4.  LOAD-BEARING QUALITIES:  The soil in which the system will be installed 
should be investigated by an experienced geotechnical engineer responsible for 
other soils engineering work, and the location and nature of potential soils 
problems should be identified.  Depending on the nature of the problem, the 
designer may choose to reroute the line, use a combination of concrete trench 
or aboveground low-profile systems, or elect to over-excavate and replace with 
nonexpansive fill.</NPR><BRK/>
<BRK/>
<NPR>5.  CONCRETE TRENCH DESIGN:  The concrete trench design will consist of poured 
concrete sides and floor with removable tops.  Portions of the floor may be 
omitted at locations specified under course grained soils with water table 600 
mm (2 feet) or more below lowest point of water entry.</NPR><BRK/>
<BRK/>
<NPR>The depth of the concrete trench will be sufficient to provide adequate protection 
to the piping system and the floor of the trench shall be sloped to provide 
adequate internal drainage, but in all cases will not be less than 150 mm (6 
inches) from the bottom surface of the suspended pipe insulation to the floor 
of the trench.  There will also be a minimum of 75 mm (3 inches) between the 
surface of the pipe insulation and the adjoining trench walls, and a minimum 
of 100 mm (4 inches) between surfaces of adjacent pipe insulation.</NPR><BRK/>
<BRK/>
<NPR>For those instances where natural drainage cannot be provided (storm water drainage 
system at least 600 mm (2 feet) below trench bottom at all times), a dual sump 
pump will be provided with failure annunciator.  This signal will be tied-in 
to the EMCS system, if any.</NPR><BRK/>
<BRK/>
<NPR>The tops of the concrete trenches will serve as sidewalks, if practical, and 
will be removable by use of a forklift or backhoe.  Earth must not cover the 
tops. Covers will be close tolerance fit with a maximum gap tolerance build 
up of 3 mm (1/8 inch) from all causes.</NPR><BRK/>
<BRK/>
<NPR>The pipes will be supported within the trenches by pipe supports fastened to 
the walls.  In no case will they be supported from either the floor of the trench 
or from the removable top.  All noninsulated ferrous parts of the piping, piping 
support system, or equipment will be hot-dipped galvanized.  The pipe hanger 
design must provide for adequate system expansion and contraction.</NPR><BRK/>
<BRK/>
<NPR>Use minimum of 25 mm (1 inch) pipe size for piping in trench system with all 
joints welded.  Smaller pipe sizes and screwed joints are allowable in valve 
manholes.</NPR><BRK/>
<BRK/>
<NPR>Provide the following information on the contract drawings for the concrete 
Trench System, as applicable:  (1) dimension on all runs of pipe; (2) pipe support 
spacings; (3) pipe support spacing at changes in direction and changes in elevation 
(MSS SP-69 is not applicable); (4) elevations of the pipe along the systems 
path; (5) sizes of the pipe; (6) location of all valve manholes; (7) location 
and details of all expansion loops, Z-and L-bends; (8) location of pipe anchors; 
(9) how changes in pipe direction are made; (10) thickness of the insulation 
on the pipe; (11) concrete trench details; (12) final elevations of concrete 
trench; (13) profile of trench showing all existing utilities; (14) valve manhole 
dimensions; (15) valve manhole cover details, including manway access details; 
(16) how valve manholes are drained and vented; (17) sump pump piping details; 
(18) sump pump capacity; (19) locations of inspection ports; (20) include specific 
requirements for modification to existing and new electrical wiring, devices, 
or equipment (dedicated service for sump pump); (21) steam drip trap locations 
with access and capacities; (22) system pipe vent locations with access details; 
(23) steam main drip leg sizes; and (24) other pertinent information and details 
required to clearly show the intent of the Concrete Trench Heat Distribution 
System.  Also, indicate any obstructions in the path of the distribution system 
that the Contractor may have to work around.<BRK/>
<BRK/>
Provide and edit for the project all other guide specifications as applicable 
to the trench design, and include and edit for the project the following Sections:  
<SRF>31 00 00</SRF> EARTHWORK; <SRF>32 10 00</SRF> BITUMINOUS CONCRETE PAVEMENT; <SRF>32 12 10</SRF> BITUMINOUS 
TACK AND PRIME COATS; <SRF>33 63 23</SRF> EXTERIOR ABOVEGROUND STEAM DISTRIBUTION; 
<SRF>33 71 01</SRF> OVERHEAD TRANSMISSION AND DISTRIBUTION; <SRF>33 70 02.00 10</SRF> ELECTRICAL DISTRIBUTION 
SYSTEM, UNDERGROUND; <SRF>03 15 13.00 10</SRF> EXPANSION JOINTS, CONTRACTION JOINTS, AND 
WATERSTOPS; <SRF>03 31 00.00 10</SRF> CAST-IN-PLACE STRUCTURAL CONCRETE; 
<SRF>05 05 23.00 10</SRF> WELDING, STRUCTURAL; <SRF>05 50 13</SRF> MISCELLANEOUS METAL FABRICATIONS; 
<SRF>07 13 53</SRF> ELASTOMERIC SHEET WATERPROOFING; <SRF>09 90 00</SRF> PAINTS AND COATINGS; 
<SRF>43 02 00</SRF> WELDING PRESSURE PIPING; <SRF>26 20 00</SRF> INTERIOR DISTRIBUTION SYSTEM; and 
others as applicable to the project.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>1.1   REFERENCES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  This paragraph is used to list the publications cited in the text of 
the guide specification.  The publications are referred to in the text by basic 
designation only and listed in this paragraph by organization, designation, 
date, and title.<BRK/>
<BRK/>
Use the Reference Wizard's Check Reference feature when you add a RID outside 
of the Section's Reference Article to automatically place the reference in the 
Reference Article.  Also use the Reference Wizard's Check Reference feature 
to update the issue dates.<BRK/>
<BRK/>
References not used in the text will automatically be deleted from this section 
of the project specification when you choose to reconcile references in the 
publish print process.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The publications listed below form a part of this specification to the extent referenced.  The publications are 
referred to within the text by the basic designation only.</TXT><BRK/>
<BRK/>
<REF><ORG>ASME INTERNATIONAL (ASME)</ORG><BRK/><BRK/><RID>ASME B1.20.1</RID><RTL>(1983; R 2006) Pipe Threads, General Purpose (Inch)</RTL><BRK/><BRK/><RID>ASME B16.11</RID><RTL>(2005) Forged Fittings, Socket-Welding and Threaded</RTL><BRK/><BRK/><RID>ASME B16.3</RID><RTL>(2006) Malleable Iron Threaded Fittings, Classes 150 and 300</RTL><BRK/><BRK/><RID>ASME B16.34</RID><RTL>(2004) Valves - Flanged, Threaded and Welding End</RTL><BRK/><BRK/><RID>ASME B16.39</RID><RTL>(1998; R 2006) Standard for Malleable Iron Threaded Pipe Unions; Classes 150, 250, and 300</RTL><BRK/><BRK/><RID>ASME B16.5</RID><RTL>(2003) Standard for Pipe Flanges and Flanged Fittings:  NPS 1/2 Through NPS 24</RTL><BRK/><BRK/><RID>ASME B16.9</RID><RTL>(2007) Standard for Factory-Made Wrought Steel Buttwelding Fittings</RTL><BRK/><BRK/><RID>ASME B31.1</RID><RTL>(2007; Addenda 2008) Power Piping</RTL><BRK/><BRK/><RID>ASME B40.100</RID><RTL>(2005) Pressure Gauges and Gauge Attachments</RTL><BRK/><BRK/></REF><REF><ORG>ASTM INTERNATIONAL (ASTM)</ORG><BRK/><BRK/><RID>ASTM A 106/A 106M</RID><RTL>(2008) Standard Specification for Seamless Carbon Steel Pipe for High-Temperature Service</RTL><BRK/><BRK/><RID>ASTM A 123/A 123M</RID><RTL>(2008) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products</RTL><BRK/><BRK/><RID>ASTM A 234/A 234M</RID><RTL>(2007) Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and High Temperature Service</RTL><BRK/><BRK/><RID>ASTM A 47/A 47M</RID><RTL>(1999; R 2004) Standard Specification for Steel Sheet, Aluminum-Coated, by the Hot-Dip Process</RTL><BRK/><BRK/><RID>ASTM A 53/A 53M</RID><RTL>(2007) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless</RTL><BRK/><BRK/><RID>ASTM A 733</RID><RTL>(2003) Standard Specification for Welded and Seamless Carbon Steel and Austenitic Stainless Steel Pipe Nipples</RTL><BRK/><BRK/><RID>ASTM B 209</RID><RTL>(2007) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate</RTL><BRK/><BRK/><RID>ASTM B 209M</RID><RTL>(2007) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate (Metric)</RTL><BRK/><BRK/><RID>ASTM C 533</RID><RTL>(2007) Standard Specification for Calcium Silicate Block and Pipe Thermal Insulation</RTL><BRK/><BRK/><RID>ASTM C 547</RID><RTL>(2008e1) Standard Specification for Mineral Fiber Pipe Insulation</RTL><BRK/><BRK/><RID>ASTM C 552</RID><RTL>(2007) Standard Specification for Cellular Glass Thermal Insulation</RTL><BRK/><BRK/><RID>ASTM C 920</RID><RTL>(2008) Standard Specification for Elastomeric Joint Sealants</RTL><BRK/><BRK/><RID>ASTM D 1056</RID><RTL>(2007) Standard Specification for Flexible Cellular Materials - Sponge or Expanded Rubber</RTL><BRK/><BRK/><RID>ASTM F 1139</RID><RTL>(1988; R 2004) Steam Traps and Drains</RTL><BRK/><BRK/></REF><REF><ORG>MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS INDUSTRY (MSS)</ORG><BRK/><BRK/><RID>MSS SP-25</RID><RTL>(2008) Standard Marking System for Valves, Fittings, Flanges and Unions</RTL><BRK/><BRK/><RID>MSS SP-45</RID><RTL>(2003) Bypass and Drain Connections</RTL><BRK/><BRK/><RID>MSS SP-58</RID><RTL>(2002) Standard for Pipe Hangers and Supports - Materials, Design and Manufacture</RTL><BRK/><BRK/><RID>MSS SP-69</RID><RTL>(2003; R 2004) Standard for Pipe Hangers and Supports - Selection and Application</RTL><BRK/><BRK/><RID>MSS SP-80</RID><RTL>(2008) Bronze Gate, Globe, Angle and Check Valves</RTL><BRK/><BRK/></REF><REF><ORG>NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)</ORG><BRK/><BRK/><RID>NFPA 70</RID><RTL>(2007; AMD 1 2008) National Electrical Code - 2008 Edition</RTL><BRK/><BRK/></REF><REF><ORG>THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)</ORG><BRK/><BRK/><RID>SSPC SP 10</RID><RTL>(2007) Near-White Blast Cleaning</RTL><BRK/><BRK/></REF></SPT><SPT><TTL>1.2   SUBMITTALS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review submittal description (SD) definitions in Section <SRF>01 33 00</SRF> SUBMITTAL 
PROCEDURES and edit the following list to reflect only the submittals required 
for the project.  Submittals should be kept to the minimum required for adequate 
quality control.<BRK/>
<BRK/>
A “G” following a submittal item indicates that the submittal requires Government 
approval.  Some submittals are already marked with a “G”.  Only delete an existing 
“G” if the submittal item is not complex and can be reviewed through the Contractor’s 
Quality Control system.  Only add a “G” if the submittal is sufficiently important 
or complex in context of the project.<BRK/>
<BRK/>
For submittals requiring Government approval on Army projects, a code of up 
to three characters within the submittal tags may be used following the "G" 
designation to indicate the approving authority.  Codes for Army projects using 
the Resident Management System (RMS) are:  "AE" for Architect-Engineer; "DO" 
for District Office (Engineering Division or other organization in the District 
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project 
Office.  Codes following the "G" typically are not used for Navy, Air Force, 
and NASA projects.<BRK/>
<BRK/>
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose 
the second bracketed item for Army projects.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Government approval is required for submittals with a "G" designation; submittals not having a "G" designation 
are for [Contractor Quality Control approval.] [information only.  When used, a designation following the "G" 
designation identifies the office that will review the submittal for the Government.]  Submit the following in 
accordance with Section <SRF>01 33 00</SRF> SUBMITTAL PROCEDURES:</TXT><BRK/>
<BRK/>
<LST><SUB>SD-02 Shop Drawings</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Heat Distribution System</SUB></ITM><BRK/>
<BRK/>
<ITM>  Detail drawings for steam traps, valves, sump pumps, pressure gauges, thermometers and insulation, 
including a complete list of equipment and material, including manufacturer's descriptive and 
technical literature, performance charts and curves, catalog cuts, and installation instructions.  
Show on the drawings complete wiring and schematic diagrams, pipe stress calculations for any 
revised expansion loops, and any other details required to demonstrate that the system has been 
coordinated and will properly function as a unit.  Show on the drawings proposed system layout, 
provisions for expansion, pipe anchors and guides, and layout and anchorage of equipment and 
appurtenances in valve manholes, and equipment relationship to other parts of the work including 
clearances for maintenance and operation.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-03 Product Data</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Spare Parts</SUB></ITM><BRK/>
<BRK/>
<ITM>  Spare parts data, as specified.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-04 Samples</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Insulation</SUB></ITM><BRK/>
<BRK/>
<ITM>  Display sample sections for insulation of pipe, elbow, tee, valve, support point, and terminating 
points.  After approval of material and prior to insulation of piping, prepare a display of 
insulated sections showing compliance with specifications, including fastening, sealing, jacketing, 
straps, waterproofing, supports, hangers, anchors, and saddles.  Keep sample sections on display 
at the jobsite during the construction period until no longer needed.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-06 Test Reports</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Tests</SUB></ITM><BRK/>
<BRK/>
<ITM>  Performance test reports in booklet form showing all field tests performed to adjust each 
component and all field tests performed to prove compliance with the specified performance criteria, 
upon completion and testing of the installed system.  Indicate on each test report the final 
position of controls and valves.</ITM><BRK/>
<BRK/>
<LST><SUB>SD-07 Certificates</SUB></LST><BRK/>
<BRK/>
<ITM><SUB>Flange Gasket Kits</SUB></ITM><BRK/>
<BRK/>
<ITM>  Certificate from the material supplier of the electrically insulating flange gasket kits stating 
that the supplied material meets specified requirements and that provides evidence that satisfactory 
operating requirements have been met, before the materials are delivered.  Certificate shall 
be signed by an official authorized to certify in behalf of material supplier or product manufacturer 
and shall identify quantity and date or dates of shipment or delivery to which the certificates 
apply.</ITM><BRK/>
<BRK/></SPT>
<SPT><TTL>1.3   DELIVERY, STORAGE, AND HANDLING</TTL><BRK/>
<BRK/>
<TXT>All materials and equipment delivered and placed in storage shall be stored with protection from the weather; 
excessive humidity and excessive temperature variation; and dirt, dust, or other contaminants.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.4   MAINTENANCE</TTL><BRK/>
<BRK/>
<TXT>Provide [six] [_____] copies of operation and [six] [_____] copies of maintenance manuals for the equipment furnished.  
One complete set prior to performance testing, and the remainder upon acceptance.  Detail in the operation manuals 
the step-by-step procedures required for system startup, operation, and shutdown and include the manufacturer's 
name, model number, parts list, and brief description of all equipment and their basic operating features.  List 
in the maintenance manuals routine maintenance procedures, possible breakdowns and repairs, and troubleshooting 
guides and include piping and equipment layout and simplified wiring and control diagrams indicating location 
of electrical components with terminals designated for wiring, as installed.  Operation and maintenance manuals 
shall be approved prior to performance testing.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>1.5   EXTRA MATERIALS</TTL><BRK/>
<BRK/>
<TXT>submit <SUB>spare parts</SUB> data for each different item of material and equipment specified, after approval of the related 
submittals and not later than the start of the field tests.  Include in the data a complete list of parts and 
supplies and source of supply.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 2   PRODUCTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1   GENERAL REQUIREMENTS</TTL><BRK/>
<BRK/>
<SPT><TTL>2.1.1   Standard Products</TTL><BRK/>
<BRK/>
<TXT>Provide materials and equipment which are the standard products of a manufacturer regularly engaged in the manufacture 
of such products and that essentially duplicate items that have been in satisfactory use for at least 2 years 
prior to bid opening.  Equipment shall be supported by a service organization that is, in the opinion of the 
Contracting Officer, reasonably convenient to the site.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.2   Nameplates</TTL><BRK/>
<BRK/>
<TXT>Each major item of equipment such as sump pumps, motors, steam traps, and pressure reducing valves shall have 
the manufacturer's name, address, type or style, model or serial number, and catalog number on a plate secured 
to the item of equipment.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.3   Asbestos Prohibition</TTL><BRK/>
<BRK/>
<TXT>Asbestos and asbestos-containing products will not be allowed.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.1.4   Electrical Work</TTL><BRK/>
<BRK/>
<TXT>Provide motors, manual or automatic motor control equipment, and protective or signal devices required for the 
operation specified under this section in accordance with <RID>NFPA 70</RID> and Section <SRF>33 70 02.00 10</SRF> ELECTRICAL DISTRIBUTION 
SYSTEM, UNDERGROUND.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2   PIPING AND FITTINGS</TTL><BRK/>
<BRK/>
<TXT>Unless otherwise specified, all pipe, fittings, valves, and piping accessories shall conform to the requirements 
of <RID>ASME B31.1</RID>, and shall be the proper type, class, and grade for pressure and temperature of the heating medium.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.1   Steel Pipe</TTL><BRK/>
<BRK/>
<TXT>Steel pipe<MET> 50 mm</MET><ENG> 2 inches</ENG> in diameter and larger shall be seamless or electric-resistance welded conforming to <RID>
ASTM A 53/A 53M</RID>, Grade B, Type E or S; or to <RID>ASTM A 106/A 106M</RID>, Grade B.  Steel pipe<MET> 40 mm</MET><ENG> 1-1/2 inches</ENG> in diameter 
and smaller shall be seamless conforming to <RID>ASTM A 106/A 106M</RID>, Grade B.  Condensate piping, gauge piping, and 
piping<MET> 19 mm</MET><ENG> 3/4 inch</ENG> in diameter and smaller shall be extra strong.  All other pipe shall be standard weight.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.1.1   Nipples</TTL><BRK/>
<BRK/>
<TXT>Nipples shall conform to <RID>ASTM A 733</RID>, standard weight or extra-heavy weight, as required to match adjacent piping.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.1.2   Steel Flanges</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Use not less than Class 150 for steam up to 862 kPa (125 psig), not less 
than Class 300 for steam 863 to 1724 kPa (126 to 250 psig), and for high temperature 
hot water.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Steel flanges shall conform to <RID>ASME B16.5</RID> Class [150] [and] [or] [300] and shall match valves or flanged fittings 
on which used.  Flanges shall have the manufacturer's trademark affixed in accordance with <RID>MSS SP-25</RID> so as to 
permanently identify the manufacturer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.1.3   Pipe Threads</TTL><BRK/>
<BRK/>
<TXT>Pipe threads shall conform to <RID>ASME B1.20.1</RID>.  Pipe threads may be used only on pipe<MET> 19 mm</MET><ENG> 3/4 inch</ENG> or smaller.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2.2   Fittings</TTL><BRK/>
<BRK/>
<TXT>Fittings shall have the manufacturer's trademark affixed in accordance with <RID>MSS SP-25</RID> so as to permanently identify 
the manufacturer.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.2.2.1   Welded Fittings</TTL><BRK/>
<BRK/>
<TXT>Welded fittings shall conform to <RID>ASTM A 234/A 234M</RID>, buttwelded or socket welded, standard weight or extra strong, 
as required to match connecting piping.  Buttwelded fittings shall conform to <RID>ASME B16.9</RID>, and socket welded fittings 
shall conform to <RID>ASME B16.11</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.2.2   Malleable Iron Fittings</TTL><BRK/>
<BRK/>
<TXT>Fittings shall conform to <RID>ASME B16.3</RID>, <RID>ASTM A 47/A 47M</RID>, class as required to match connecting piping.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.2.2.3   Unions</TTL><BRK/>
<BRK/>
<TXT>Unions shall conform to <RID>ASME B16.39</RID>, standard weight or extra heavy, as required to match adjacent piping.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.2.3   Insulating Flanges and Dielectric Waterways</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Where dissimilar metals are to be joined, or when connecting to cathodically 
protected systems, electrically insulating flanges or dielectric waterways will 
be provided.</NPR><BRK/>
<BRK/>
<NPR>For flanges, use not less than Class 150 for up to 862 kPa (125 psig) steam, 
not less than Class 300 for 863 to 1724 kPa (126 to 250 psig) steam, and for 
high temperature hot water.  Gaskets must have the following characteristics:  
(1) Impermeability with respect to the fluid/gas contained by the system; (2) 
Chemical stability with respect to the fluid/gas contained by the system; (3) 
Sufficient deformability so as to flow into the imperfections on the seating 
surfaces and provide intimate contact between the gasket and these surfaces; 
(4) Thermal stability with respect to the fluid/gas contained by the system; 
(5) Sufficient resiliency so as to support an adequate portion of the applied 
load when joint movements are not completely eliminated by the system design; 
(6) Sufficient strength to resist crushing under the applied load and blow-out 
under the system pressure; (7) Contain no products that could contaminate the 
fluid/gas contained by the system; (8) Contain no products that could cause 
corrosion of the seating surfaces; (9) Able to maintain integrity during handling 
and installation; (10) Able to be readily removed at the time of replacement; 
(11) Must have a sufficiently high dielectric strength; (12) Gaskets containing 
metallic graphite or wire cannot be used for this application; and (13) Must 
not contain asbestos.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Install insulating flanges or <SUB>flange gasket kits</SUB> at every pipe connection from the trench system to an underground 
system and at dissimilar metals.  The kit shall consist of a flange gasket, bolt sleeves, and one insulating 
washer and one steel washer for both ends of each bolt.  The gasket kits shall be capable of electrically isolating 
the pipe at the pressure and temperature of the heating medium at the point of application.  Material of the 
type being used must have been installed in an installation which has been satisfactorily operating for not less 
than 2 years.  Ensure that these kits are provided and properly installed according to manufacturer published 
instructions as indicated.  Provide dielectric waterways with temperature and pressure rating equal to or greater 
than that specified for the connecting piping used for joining dissimilar metals, <MET>19 mm</MET><ENG> 3/4 inch</ENG> and smaller 
threaded pipe.  Waterways shall have metal connections on both ends suited to match connecting piping.  Dielectric 
waterways shall be insternally lined with an insulator specifically designed to prevent current flow between 
dissimilar metals.  Dielectric flanges shall meet the performance requirements described herein for dielectric 
waterways.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.3   VALVES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Select the appropriate valves for the operating temperatures and pressures 
of all systems in the project.  Delete valve types not included in project.</NPR><BRK/>
<BRK/>
<NPR>Use not less than Class 150 for up to 862 kPa (125 psig) steam, and not less 
than Class 300 for 863 to 1724 kPa (126 to 250 psig) steam, and for high temperature 
hot water.  For isolation and shutoff, use gate valves only.  Steam pressure 
reducing valves are not normally part of the system.  If needed, designer should 
refer to Section <SRF>23 70 01.00 10</SRF> CENTRAL STEAM-GENERATING SYSTEM, COAL-FIRED.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Unless otherwise specified, valves shall comply with the material, fabrication, and operating requirements of <RID>
ASME B31.1</RID>.  Valves shall be suitable for the temperature and pressure requirements of the system on which used.  
Valves for [steam] [hot water] shall conform to <RID>ASME B31.1</RID>Class [150] [and] [or] [300], as suitable for the application.  
[Valves for condensate services shall conform to <RID>ASME B31.1</RID> Class 150.]  Valves<MET> 150 mm</MET><ENG> 6 inches</ENG> and larger shall 
have a<MET> 25 mm</MET><ENG> 1 inch</ENG> minimum gate or globe [integral] bypass valve sized in conformance with <RID>MSS SP-45</RID>.  Valves 
shall have the manufacturer's trademark.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.3.1   Steel Valves</TTL><BRK/>
<BRK/>
<TXT>Globe, gate, angle, and check valves shall conform to the requirements of <RID>ASME B16.34</RID> and <RID>ASME B31.1</RID> for the 
temperature and pressure requirements of the system.  Gate valves<MET> 65 mm</MET><ENG> 2-1/2 inches</ENG> and smaller shall be rising 
stem.  Gate valves<MET> 80 mm</MET><ENG> 3 inches</ENG> and larger shall be outside screw and yoke.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.2   Bronze Valves</TTL><BRK/>
<BRK/>
<SPT><TTL>2.3.2.1   Globe, Gate, and Angle Valves</TTL><BRK/>
<BRK/>
<TXT>Globe, gate, and angle valves shall conform to requirements of <RID>MSS SP-80</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.3.2.2   Check Valves</TTL><BRK/>
<BRK/>
<TXT>Check valves shall conform to the requirements of <RID>MSS SP-80</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.3.3   Packing</TTL><BRK/>
<BRK/>
<TXT>Packing used with valves shall not contain asbestos.  Valve stem packing shall be die-formed, ring type specifically 
designated as suitable for the temperature and pressure of the service and compatible with the fluid in the system.  
Packing rings shall be polytetrafluoroethylene with minimum 50 percent graphite filament top and bottom rings.  
Valves<MET> 40 mm</MET><ENG> 1-1/2 inches</ENG> and smaller shall have four or five packing rings and valves<MET> 50 mm</MET><ENG> 2 inches</ENG> and larger 
shall have at least six packing rings.  Spiral or continuous packing will not be acceptable.  A metal insert 
shall be provided having proper clearance around the valve stem at the bottom of the stuffing box and acting 
as a base for the packing material.  Packing glands shall be furnished with a liner of noncorrosive material 
and shall be of one piece construction with provisions for not less than two bolts for packing adjustment.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.4   STEAM TRAPS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  The following paragraphs are applicable to steam systems only.  Only 
these two types will be used.  A schedule of steam trap selections will be shown 
on the drawings.</NPR><BRK/>
<BRK/>
<NPR>Trap capacity (kg per hour (pounds per hour) during normal operation), pressure 
drop kPa (psi), and pressure rating kPa (psi) of each trap will be included 
in this schedule.  Show on drawings a vent valve or test valve connection downstream 
of traps for test of trap operation, a strainer ahead of trap, a check valve 
in outlet piping, and shut-off valves on both sides of trap for trap changeout.  
A means of bypassing the trap shall be provided for system warm-up.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Class of trap bodies shall be suitable for a working pressure of not less than 1.5 times the steam supply pressure, 
but not less than<MET> 1.38 MPa</MET><ENG> 200 psi</ENG>, and traps shall be capable of operation under a steam-supply pressure as 
indicated.  Traps shall have capacities as shown when operating under the specified working conditions.  Traps 
shall fail open.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.4.1   Bucket Traps</TTL><BRK/>
<BRK/>
<TXT>Traps shall be inverted-bucket type with automatic air discharge conforming to <RID>ASTM F 1139</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.4.2   Thermostatic Traps</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify thermostatic traps where the trap location is subject to freezing.  
Style B traps are bimetallic element traps.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Traps shall be thermostatic type with bimetallic element automatic air discharge conforming to <RID>ASTM F 1139</RID>.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.5   STRAINERS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete for high temperature water systems.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Strainers shall be basket or Y-type with connections the same size as the pipe lines in which the connections 
are installed.  Strainer shall be suitable for the temperature and pressure requirements of the system.  The 
strainer bodies shall be of cast steel with bottoms drilled and plugged.  The bodies shall have arrows clearly 
cast on the sides to indicate the direction of flow.  Each strainer shall be equipped with an easily removable 
cover and sediment basket.  The body or bottom opening shall be equipped with nipple and gate valve for blowdown.  
The basket shall be of not less than<MET> 0.6350 mm</MET><ENG> 0.025 inch</ENG> thick stainless steel, or monel with small perforations 
of sufficient number to provide a net free area through the basket of at least 2.5 times that of the entering 
pipe.  The flow shall be into the basket and out through the perforations.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.6   PRESSURE GAUGES</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete if not required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Gauges shall conform to <RID>ASME B40.100</RID> and shall be provided with throttling type needle valve or a pulsation dampener 
and shut-off valve.  Minimum dial size shall be<MET> 110 mm</MET><ENG> 4-1/4 inches</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7   THERMOMETERS</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete if not required.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Mercury shall not be used in thermometers.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.7.1   Liquid in Glass</TTL><BRK/>
<BRK/>
<TXT>Thermometer shall be liquid in glass type with well and separable corrosion-resistant steel socket.  Thermometer 
on insulated pipe shall have insulation stand-off provision.  Minimum scale length shall be<MET> 178 mm</MET><ENG> 7 inches</ENG>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.7.2   Dial</TTL><BRK/>
<BRK/>
<TXT>Dial type thermometer shall be<MET> 90 mm</MET><ENG> 3-1/2 inches</ENG> in diameter chromium plated case, remote-type bulb or direct-type 
bulb as required, plus or minus<MET> 1 degree C</MET><ENG> 2 degrees F</ENG> accuracy, white face with black digits graduated in<MET> 1 
degree C</MET><ENG> 2 degrees F</ENG> increments.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.8   INSULATION AND JACKETING</TTL><BRK/>
<BRK/>
<TXT>Comply with EPA requirements in accordance with Section <SRF>01 62 35</SRF> RECYCLED / RECOVERED MATERIALS.</TXT><BRK/>
<BRK/>
<SPT><TTL>2.8.1   Insulation for Piping in Concrete Trenches</TTL><BRK/>
<BRK/>
<TXT>Insulation for all piping, fittings, and valves shall be molded calcium silicate conforming to <RID>ASTM C 533</RID>, Type 
I, asbestos free, or molded mineral fiber insulation conforming to <RID>ASTM C 547</RID>, Class 2, asbestos free, or cellular 
glass insulation conforming to <RID>ASTM C 552</RID>.  Insulation shall be factory or field applied.  Other than FOAMGLAS, 
laminated construction shall not be used in thicknesses less than<MET> 102 mm</MET><ENG> 4 inches</ENG>.  Insulation on piping in concrete 
trenches shall be covered with aluminum or nonmetallic jacket.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.8.2   Aluminum Jacket</TTL><BRK/>
<BRK/>
<TXT>Jacket shall be smooth sheet, <MET>0.4064 mm</MET><ENG> 0.016 inch</ENG> nominal thickness; <MET><RID>ASTM B 209M</RID></MET><ENG> <RID>ASTM B 209</RID></ENG>, Type 3003, 3105, 
or 5005.  Aluminum jacket shall be used over calcium silicate insulation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.8.3   Nonmetallic Jacket</TTL><BRK/>
<BRK/>
<TXT>Nonmetallic jacket shall consist of a<MET> 203 grams/square meter</MET><ENG> 6 ounces per square yard</ENG> fiberglass fabric impregnated 
with chlorosulfanated polyethylene (Hypalon) and a<MET> 0.038 mm</MET><ENG> 1.5 mils</ENG> polyvinyl fluoride film (Tedlar) bonded 
to it.  Overall thickness of the composite shall be<MET> 0.254 mm</MET><ENG> 0.010 inch</ENG> and weigh approximately<MET> 356 grams/square 
meter</MET><ENG> 10.5 ounces per square yard</ENG>.  Jacket may be either field or factory applied to the insulation.  This jacket 
shall not be used with any calcium silicate insulation.  Nonmetallic jacket shall be used with molded mineral 
fiber insulation.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.8.4   Bands</TTL><BRK/>
<BRK/>
<TXT>Bands for aluminum jacket shall be<MET> 10 mm</MET><ENG> 3/8 inch</ENG> wide and<MET> 0.8128 mm</MET><ENG> 32 gauge</ENG> thickness made of aluminum or annealed 
stainless steel.  Bands for insulation shall be<MET> 13 mm</MET><ENG> 1/2 inch</ENG> wide and<MET> 0.8128 mm</MET><ENG> 32 gauge</ENG> thickness made of 
annealed stainless steel.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.8.5   Insulation for Flanges, Unions, Valves, and Fittings</TTL><BRK/>
<BRK/>
<TXT>Flanges, unions, valves, and fittings shall be insulated with premolded prefabricated, or field fabricated segments 
of insulation.  Insulation shall be removable and reusable and shall have essentially the same thermal characteristics 
and thickness as the adjoining piping.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.9   CONCRETE WORK</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Specify concrete work in detail in Section <SRF>03 31 00.00 10</SRF> CAST-IN-PLACE 
STRUCTURAL CONCRETE.  Specify precast concrete work in detail in SECTION 
<SRF>03 40 00.00 10</SRF> PLANT-PRECAST CONCRETE PRODUCTS FOR BELOW GRADE CONSTRUCTION.  
Use applicable requirements of, and edit the above guide specifications and 
include all specific requirements pertinent to local conditions.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>2.9.1   Concrete</TTL><BRK/>
<BRK/>
<LST>a. Cast-in-Place Concrete: Concrete shall be as specified in Section <SRF>03 31 00.00 10</SRF> CAST-IN-PLACE STRUCTURAL 
CONCRETE.</LST><BRK/>
<BRK/>
<LST>b. Precast Concrete Products: Provide as specified in Section <SRF>03 40 00.00 10</SRF> PLANT-PRECAST CONCRETE PRODUCTS 
FOR BELOW GRADE CONSTRUCTION.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9.2   Concrete Joint Sealants</TTL><BRK/>
<BRK/>
<TXT>Concrete joint sealants shall conform to <RID>ASTM C 920</RID>, Type M (multicomponent), Class 25, grade NS (nonsag) for 
vertical surfaces or grade P (pourable selfleveling).</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9.3   Gasket Material</TTL><BRK/>
<BRK/>
<TXT>Gasket material used between concrete trench covers and trench wall tops shall be<MET> 6 mm</MET><ENG> 1/4 inch</ENG> thick neoprene 
pad with a minimum width of<MET> 50 mm</MET><ENG> 2 inches</ENG> conforming to <RID>ASTM D 1056</RID>.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.9.4   Concrete Expansion Joints, Contraction Joints, and Waterstops</TTL><BRK/>
<BRK/>
<TXT>Concrete expansion joints, contraction joints, and waterstops shall be as specified in Section 
<SRF>03 15 13.00 10</SRF> EXPANSION JOINTS, CONTRACTION JOINTS, AND WATERSTOPS.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>2.10   BITUMINOUS PAVING</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete if not required or if roads are constructed after tunnel crossings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Bituminous course and tack coat used at street crossings shall be as specified in Section <SRF>32 12 16</SRF> HOT-MIX ASPHALT 
(HMA) FOR ROADS and Section <SRF>32 12 10</SRF> BITUMINOUS TACK AND PRIME COATS.<BRK/></TXT>
<BRK/>
<BRK/></SPT>
<SPT><TTL>2.11   MISCELLANEOUS METAL</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Include miscellaneous metals located in trenches or valve manholes in 
Section <SRF>05 50 13</SRF> MISCELLANEOUS METAL FABRICATIONS.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Miscellaneous metal not otherwise specified shall conform to Section <SRF>05 50 13</SRF> MISCELLANEOUS METAL FABRICATIONS.  
Miscellaneous metal bolted together, shop welded, or assembled in the field, and pipe supports including structural 
cross support members and anchors shall be hot-dip galvanized in accordance with Section <SRF>05 50 13</SRF> MISCELLANEOUS 
METAL FABRICATIONS.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>2.12   INSPECTION PORTS AND ACCESS COVERS</TTL><BRK/>
<BRK/>
<TXT>Inspection ports and access covers in concrete tops shall be standard cast iron frame and cover. Inspection ports 
shall be<MET> 300 mm</MET><ENG> 12 inch</ENG> nominal diameter and access covers shall be<MET> 600 mm</MET><ENG> 24 inch</ENG> nominal diameter unless otherwise 
indicated.</TXT><BRK/>
<BRK/></SPT>
</PRT><PRT><TTL>PART 3   EXECUTION</TTL><BRK/>
<BRK/>
<SPT><TTL>3.1   EXAMINATION</TTL><BRK/>
<BRK/>
<TXT>After becoming familiar with all details of the work, verify all dimensions in the field, and advise the Contracting 
Officer of any discrepancy before performing the work.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2   SITEWORK</TTL><BRK/>
<BRK/>
<SPT><TTL>3.2.1   Excavation, Trenching, and Backfilling</TTL><BRK/>
<BRK/>
<TXT>Excavation, trenching, and backfilling of concrete trench systems, [and relocation of interferences and modifications 
to existing facilities] shall be as shown and in accordance with Section <SRF>31 00 00</SRF> EARTHWORK.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.2   Removal, Replacement, or Relocation of Interferences</TTL><BRK/>
<BRK/>
<TXT>Interferences indicated or found during construction shall be removed, replaced, or relocated.  Removal, replacement, 
or relocation shall be as shown, or as approved by the Contracting Officer.  Examples of interferences include:</TXT><BRK/>
<BRK/>
<LST>a.  Storm and sanitary sewers and manholes.</LST><BRK/>
<BRK/>
<LST>b.  Water lines, gas lines, fire hydrants, and lawn sprinkler systems.</LST><BRK/>
<BRK/>
<LST>c.  Power and communication lines, conduits, poles, and guys.</LST><BRK/>
<BRK/>
<LST>d.  Fences, sidewalks, and signs.</LST><BRK/>
<BRK/>
<LST>e.  Grass, shrubs, trees, and rocks.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.3   Modifications to Existing Facilities</TTL><BRK/>
<BRK/>
<TXT>Modifications to existing facilities shall be made as shown.  Examples of modifications include:</TXT><BRK/>
<BRK/>
<LST>a.  Removal and replacement of street or parking area pavements.</LST><BRK/>
<BRK/>
<LST>b.  Removal and replacement of curbs, gutters, and sidewalks.</LST><BRK/>
<BRK/>
<LST>c.  Reconstruction of existing valve manholes.</LST><BRK/>
<BRK/>
<LST>d.  New heat distribution piping entrances to buildings, valve manholes, or trenches.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.4   Electric Work</TTL><BRK/>
<BRK/>
<TXT>Any wiring required for the operation of the equipment specified, but not shown on the electrical drawings, shall 
be provided under this section in accordance with Section <SRF>33 71 01</SRF> OVERHEAD TRANSMISSION AND DISTRIBUTION, and 
Section <SRF>33 70 02.00 10</SRF> ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.2.5   Painting</TTL><BRK/>
<BRK/>
<TXT>The heat affected zone of field welded galvanized surfaces and other galvanized surfaces damaged during installation 
shall be cleaned in compliance with <RID>SSPC SP 10</RID> and painted in accordance with Section <SRF>09 90 00</SRF> PAINTS AND COATINGS.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.3   PIPING</TTL><BRK/>
<BRK/>
<SPT><TTL>3.3.1   General Piping Requirements</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Expansion joints generally will not be used in the design of the piping 
layout.  If no other method is available to handle the expansion problem in 
a specific location, the design layout using an expansion joint at a specific 
location must be justified by a design analysis and approved in the planning 
phase of the piping layout prior to including expansion joints in the specifications.  
If expansion joints or ball joints are required, the locations will be indicated 
on the drawings.  Since expansion joints are high maintenance items, these must 
be located in a readily accessible location.  The following requirements must 
be added to the specification as paragraphs 2.14 through 2.16.  If these requirements 
are included in the specifications, the publications referenced in them must 
also be included in paragraph REFERENCES.</NPR><BRK/>
<BRK/>
<NPR>2.14   Bellows Type Joints:  Select bellows type or slip-type to satisfy specific 
design conditions.  Joints shall be flexible, guided expansion joints.  The 
expansion element shall be of stainless steel.  Bellows type expansion joints 
shall be in accordance with the applicable requirements of EJMA-01 and ASME 
B31.1 with internal liners.</NPR><BRK/>
<BRK/>
<NPR>2.15   Expansion Joints:  Expansion joints shall provide for either single or 
double slip of connected pipes, as required or indicated, and for not less than 
the traverse indicated.  The joints shall be designed for hot water working 
pressure and shall be in accordance with applicable requirements of EJMA-01 
and ASME B31.1.  Joints shall be designed for packing injection under full line 
pressure.  End connections shall be flanged or beveled for welding as indicated.  
Joints shall be provided with anchor base where required or indicated.  Where 
adjoining pipe is carbon steel, the sliding slip shall be seamless steel plated 
with a minimum of 0.0508 mm (2 mils) of hard chrome in accordance with ASTM 
B 650.  Joint components shall be fabricated from material equivalent to that 
of the pipeline.  Initial setting shall be made in accordance with the manufacturer's 
recommendations to compensate for ambient temperature at time of installation.  
Pipe alignment guides shall be installed as recommended by the joint manufacturer, 
but in any case shall not be more than 1.5 m (5 feet) from expansion joint except 
for lines 100 mm (4 inches) or smaller; guides shall be installed not more than 
600 mm (2 feet) from the joint.  Service outlets shall be provided where indicated.</NPR><BRK/>
<BRK/>
<NPR>2.16.  Flexible Ball Joints:  Flexible ball joints shall be constructed of alloys 
as appropriate for the service intended.  Where so indicated, the ball joint 
shall be designed for packing injection under full line pressure to contain 
leakage.  Joint ends shall be threaded to 50 mm (2 inches) only, grooved, flanged 
or beveled for welding as indicated or required, and shall be capable of absorbing 
a minimum of 15 degrees angular flex and 360 degrees rotation.  Balls and sockets 
shall be of equivalent material as the adjoining pipeline.  Exterior spherical 
surface of carbon steel balls shall be plated with 0.0508 mm (2 mils) of hard 
chrome in accordance with ASTM B 650.   Ball type joints shall be designed and 
constructed in accordance with ASME B31.1 and ASME BPVC SEC VIII D1, where applicable.  
Flanges where required shall conform to ASME B16.5.  Gaskets and compression 
seals shall be compatible with the service intended.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Pipe shall be accurately cut to measurements established at the site and shall be worked into place without springing 
or forcing.  Pipe shall clear all openings and equipment.  Excessive cutting or other weakening of structural 
members to facilitate piping installation will not be permitted.  Burrs shall be removed from ends of pipe by 
reaming.  Installation shall permit free expansion and contraction without damage to joints or hangers.  Piping 
shall be installed in accordance with <RID>ASME B31.1</RID>.  Joints for piping in  concrete trenches shall be welded [, 
except joints at traps, strainers, and at valves<MET> 19 mm</MET><ENG> 3/4 inch</ENG> and smaller in steam, condensate, and drip lines, 
which may use unions or may be threaded].  Supports, anchors, or stays shall not be attached where either expansion 
or the weight of the pipe will cause damage to permanent construction.  Noninsulated ferrous parts of the piping, 
piping support system, or equipment shall be hot-dip galvanized after fabrication in conformance with <RID>ASTM A 123/A 123M</RID>
.</TXT><BRK/>
<BRK/>
<LST>a.  Expansion of piping shall be provided for by changes in the direction of the run of pipe or by expansion 
loops as shown.</LST><BRK/>
<BRK/>
<LST>b.  Changes in direction may be made by bending the pipe, provided that a hydraulic pipe bender is used.  
Pipe to be bent shall be steel conforming to <RID>ASTM A 53/A 53M</RID> or <RID>ASTM A 106/A 106M</RID> type and grade for 
bending, and class required to match adjoining pipe.  Bent pipe showing kinks, wrinkles, or malformations 
will not be acceptable.</LST><BRK/>
<BRK/>
<LST>c.  All piping, unless otherwise indicated, shall be pitched with a grade of not less than<MET> 25 mm in 6 
m</MET><ENG> 1 inch in 20 feet</ENG> toward drain points.  The slope shall be maintained throughout the system, including 
through each leg of each expansion loop.</LST><BRK/>
<BRK/>
<LST>d.  Open ends of pipe lines and equipment shall be properly capped or plugged during installation to 
keep dirt and other foreign matter out of the system.</LST><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.2   Welded Joints</TTL><BRK/>
<BRK/>
<TXT>Joints between sections of pipe and between pipe and fittings shall be welded.  The welding shall conform to 
the requirements specified in paragraph WELDING.  Branch connections may be made with either welding tees or 
forged branch outlet fittings.  Branch outlet fittings where used, shall be forged and shall be no larger than 
two nominal pipe sizes smaller than the main run.  Branch outlet fittings shall be flared for improved flow where 
attached to the run, reinforced against external strains, and designed to withstand full pipe bursting strength.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.3   Flanged and Threaded Joints</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Flanged joints will be permitted for dielectric isolation only.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<SPT><TTL>3.3.3.1   Flanged Joints</TTL><BRK/>
<BRK/>
<TXT>Joints shall be faced true, provided with gaskets, and made perfectly square and tight.  Electrically isolated 
flange joints shall be provided at all connections to building underground systems and between dissimilar metals.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.3.2   Threaded Joints</TTL><BRK/>
<BRK/>
<TXT>Joints shall have graphite or inert filler and oil, graphite compound, or polytetrafluoroethylene tape applied 
to the male threads only.  Dielectric unions shall be used at connections of dissimilar metals in<MET> 19 mm</MET><ENG> 3/4 inch</ENG>
 and smaller piping.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.3.4   Reducing Fittings</TTL><BRK/>
<BRK/>
<SPT><TTL>3.3.4.1   Horizontal Water Heating Lines</TTL><BRK/>
<BRK/>
<TXT>In horizontal hot water heating lines, reducing fittings shall be the eccentric type to maintain the tops of 
adjoining pipes at the same level.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.4.2   Horizontal Steam Lines</TTL><BRK/>
<BRK/>
<TXT>In horizontal steam lines, reducing fittings shall be the eccentric type to maintain the bottom of adjoining 
pipes at the same level.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.3.5   Branch Connections</TTL><BRK/>
<BRK/>
<TXT>Branches from mains shall branch off top of mains as indicated or as approved.  Connections shall insure unrestricted 
circulation, elimination of air pockets, and shall permit the complete drainage of the system.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.3.6   Pipe Supports Exposed in Concrete Trenches</TTL><BRK/>
<BRK/>
<TXT>Horizontal and vertical runs of pipe in concrete trenches shall be securely supported.  Suspended pipe shall 
be held by adjustable pipe hangers having bolted hinged loops and turnbuckles or by other approved devices as 
shown on the drawings, and all conforming to <RID>MSS SP-58</RID> and <RID>MSS SP-69</RID>.  Chain or flat steel strap hangers or single 
point supports will not be acceptable.  Spacing between pipe supports shall be as indicated.  All pipe supports 
including the structural cross support member shall be hot-dip galvanized in accordance with Section 
<SRF>05 50 13</SRF> MISCELLANEOUS METAL FABRICATIONS.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.4   WELDING</TTL><BRK/>
<BRK/>
<TXT>Welding and radiographic examination of all steel carrier pipe welds shall be as specified in Section 
<SRF>43 02 00</SRF> WELDING PRESSURE PIPING.  Structural members shall be welded in accordance with Section <SRF>05 05 23</SRF> WELDING, 
STRUCTURAL.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.5   RADIOGRAPHIC TESTING</TTL><BRK/>
<BRK/>
<TXT>Radiographic examination of all field welds in the steel carrier piping of the <SUB>heat distribution system</SUB> shall 
be in accordance with <RID>ASME B31.1</RID> performed as specified in Section <SRF>43 02 00</SRF> WELDING PRESSURE PIPING.  An approved 
independent testing firm or firms regularly engaged in radiographic testing shall perform a radiographic examination 
of all field welds in the steel carrier piping of the heat distribution system in accordance with <RID>ASME B31.1</RID>.  
Furnish a set of films showing each weld inspected, a reading report evaluating the quality of each weld, and 
a location plan showing the physical location where each weld is to be found in the completed project, prior 
to backfilling and hydrostatic testing.  All radiographs shall be reviewed and interpreted by a Certified Level 
III Radiographer employed by the testing firm whose signature shall appear on the reading report.  The Contracting 
Officer reserves the right to review all inspection records, and if any welds inspected are found unacceptable 
they will be removed, rewelded, and radiographically examined at no cost to the Government.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6   <SUB>INSULATION</SUB></TTL><BRK/>
<BRK/>
<TXT>The insulation shall be installed in such a manner that it will not be damaged by pipe expansion or contraction.  
Insulation installed over welds shall be grooved to assure a snug fit.  Insulation shall be held in place with 
stainless steel straps.  A minimum of 2 bands shall be installed on each individual length of insulation and 
maximum spacing shall not exceed<MET> 450 mm</MET><ENG> 18 inch</ENG> centers.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.6.1   Installation</TTL><BRK/>
<BRK/>
<TXT>Material shall be installed in accordance with published installation instructions of the manufacturer.  Insulation 
materials shall not be applied until piping tests are completed.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.6.1.1   Preparation</TTL><BRK/>
<BRK/>
<TXT>Prior to application, surfaces shall be thoroughly cleaned of moisture, grease, dirt, rust, and scale.  Insulation 
manufacturer's published installation instructions shall be followed.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6.1.2   Thickness</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Delete inapplicable columns in Tables 1 and 2.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The minimum thickness of insulation for [the heat distribution system] [and] [condensate return system] [each 
section of pipe] shall be in accordance with Tables 1 and 2.</TXT><BRK/>
<MET><TBL><THD><BRK/>
<HL4>TABLE 1</HL4><BRK/>
<BRK/>
<HL4>Minimum Pipe Insulation Thickness (millimeters)</HL4><BRK/>
<HL4>_____________________________________________</HL4><BRK/>
<BRK/>
<HL4>For steam piping 1.10 MPa to 1.72 MPa and high temperature</HL4><BRK/>
<HL4>hot water supply and return piping up to 232 degrees C.</HL4><BRK/>
<HL4>__________________________________________________________</HL4><BRK/>
<BRK/>
Nominal Pipe                    Insulation Thermal Conductivity (k)<BRK/>
  Diameter                      __________________________________<BRK/>
  (mm)         k less than 0.29    k from 0.29 to 4.0    k greater than 0.40<BRK/>
_____________       _________        _________               _________<BRK/></THD>
<BRK/>
   25                  50               63                      100<BRK/>
   40                  50               63                      100<BRK/>
   50                  63               85                      110<BRK/>
   65                  63               85                      110<BRK/>
   80                  75              100                      125<BRK/>
  100                  75              100                      125<BRK/>
  125                  75              100                      125<BRK/>
  150                  85              110                      135<BRK/>
  200                  85              110                      135<BRK/>
  250                 100              125                      150<BRK/>
  300                 100              125                      150<BRK/>
  350                 100              125                      150<BRK/>
  400                 100              125                      150<BRK/>
  450                 100              125                      150<BRK/>
<BRK/>
  NOTE:  Insulation thermal conductivity (k-value) is in <BRK/>
  units of watt per meter-degree K at 93 degrees C mean temperature.<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
<HL4>TABLE 1</HL4><BRK/>
<BRK/>
<HL4>Minimum Pipe Insulation Thickness (inches)</HL4><BRK/>
<HL4>_____________________________________________</HL4><BRK/>
<BRK/>
<HL4>For steam piping 16 psig to 250 psig and high temperature</HL4><BRK/>
<HL4>hot water supply and return piping up to 450 degrees F</HL4><BRK/>
<HL4>_______________________________________________________</HL4><BRK/>
<BRK/>
Nominal Pipe                   Insulation Thermal Conductivity (k)<BRK/>
  Diameter                   _____________________________________<BRK/>
  (in.)         k less than 0.29    k from 0.29 to 4.0    k greater than 0.40<BRK/>
_____________      _________          _________              _________<BRK/></THD>
<BRK/>
   1.0                2.0                2.5                   4.0<BRK/>
   1.5                2.0                2.5                   4.0<BRK/>
   2.0                2.5                3.5                   4.5<BRK/>
   2.5                2.5                3.5                   4.5<BRK/>
   3.0                3.0                4.0                   5.0<BRK/>
   4.0                3.0                4.0                   5.0<BRK/>
   5.0                3.0                4.0                   5.0<BRK/>
   6.0                3.5                4.5                   5.5<BRK/>
   8.0                3.5                4.5                   5.5<BRK/>
  10.0                4.0                5.0                   6.0<BRK/>
  12.0                4.0                5.0                   6.0<BRK/>
  14.0                4.0                5.0                   6.0<BRK/>
  16.0                4.0                5.0                   6.0<BRK/>
  18.0                4.0                5.0                   6.0<BRK/>
<BRK/>
  NOTE:  Insulation thermal conductivity (k-value) is in<BRK/>
  units of Btu-inches/hour-square feet-degrees F at 200 degrees<BRK/>
  F mean temperature.<BRK/></TBL>
</ENG><MET><TBL><THD><BRK/>
<HL4>TABLE 2</HL4><BRK/>
<BRK/>
<HL4>Minimum Pipe Insulation Thickness (millimeters)</HL4><BRK/>
<HL4>_____________________________________________</HL4><BRK/>
<BRK/>
<HL4>(For low pressure (less than 1.10 MPa) steam, condensate <BRK/>
return, and low temperature (less than 121 degrees C) hot <BRK/>
water supply and return piping.)</HL4><BRK/>
<HL4>____________________________________________________________</HL4><BRK/>
<BRK/>
Nominal Pipe                   Insulation Thermal Conductivity (k)<BRK/>
  Diameter                  ______________________________________<BRK/>
(mm)             k less than 0.29    k from 0.29 to 4.0   k greater than 0.40<BRK/>
_____________        _________         _________           _________<BRK/></THD>
<BRK/>
   25                    35                50                 75<BRK/>
   40                    35                50                 75<BRK/>
   50                    35                50                 75<BRK/>
   65                    35                50                 75<BRK/>
   80                    50                63                 85<BRK/>
  100                    50                63                 85<BRK/>
  125                    50                63                 85<BRK/>
  150                    63                75                110<BRK/>
  200                    63                75                110<BRK/>
  250                    75               100                125<BRK/>
  300                    75               100                125<BRK/>
  350                    75               100                125<BRK/>
  400                    75               100                125<BRK/>
  450                    75               100                125<BRK/>
<BRK/>
  NOTE:  Insulation thermal conductivity (k-value) is in units<BRK/>
  of watt per meter - degree L at  93 degrees C mean temperature.<BRK/></TBL>
</MET><ENG><TBL><THD><BRK/>
<HL4>TABLE 2</HL4><BRK/>
<BRK/>
<HL4>Minimum Pipe Insulation Thickness (inches)</HL4><BRK/>
<HL4>_____________________________________________</HL4><BRK/>
<BRK/>
<HL4>(For low pressure (less than 16 psig) steam, condensate return,</HL4><BRK/>
<HL4>and low temperature (less than 250 degrees F) hot water</HL4><BRK/>
<HL4>supply and return piping.)</HL4><BRK/>
<HL4>________________________________________________________</HL4><BRK/>
<BRK/>
Nominal Pipe                   Insulation Thermal Conductivity (k)<BRK/>
  Diameter                   __________________________________<BRK/>
  (in.)         k less than 0.29    k from 0.29 to 4.0    k greater than 0.40<BRK/>
_____________       ________            _______              _________<BRK/></THD>
<BRK/>
  1.0                 1.5                 2.0                    3.0<BRK/>
  1.5                 1.5                 2.0                    3.0<BRK/>
  2.0                 1.5                 2.0                    3.0<BRK/>
  2.5                 1.5                 2.0                    3.0<BRK/>
  3.0                 2.0                 2.5                    3.5<BRK/>
  4.0                 2.0                 2.5                    3.5<BRK/>
  5.0                 2.0                 2.5                    3.5<BRK/>
  6.0                 2.5                 3.0                    4.5<BRK/>
  8.0                 2.5                 3.0                    4.5<BRK/>
  10.0                3.0                 4.0                    5.0<BRK/>
  12.0                3.0                 4.0                    5.0<BRK/>
  14.0                3.0                 4.0                    5.0<BRK/>
  16.0                3.0                 4.0                    5.0<BRK/>
  18.0                3.0                 4.0                    5.0<BRK/>
<BRK/>
  NOTE:  Insulation thermal conductivity (k-value) is in units<BRK/>
  of Btu-inches/hour-square feet-degrees F at 200 degrees F mean<BRK/>
  temperature.</TBL></ENG><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.6.2   Insulation on Pipes Passing Through Sleeves</TTL><BRK/>
<BRK/>
<TXT>Insulation shall be continuous through sleeves as shown.  Aluminum jackets shall be provided over the insulation.  
When penetrating building walls, aluminum jacket shall extend not less than<MET> 50 mm</MET><ENG> 2 inches</ENG> beyond the sleeve 
on each side of the wall and shall be secured with an aluminum band on each side of the wall.  Where flashing 
is provided, the jacket shall be secured with one band not more than<MET> 25 mm</MET><ENG> 1 inch</ENG> from the end of the jacket.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.6.3   Covering of Insulation in Concrete Trenches</TTL><BRK/>
<BRK/>
<TXT>The insulation for pipe, flanges, valves, and fittings shall be covered with aluminum jackets.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.7   CONCRETE TRENCH SYSTEM</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide details on plan/profile drawings showing concrete trench size, 
profile of existing grade, grading and drainage problems along trench route, 
elevations of trench floor and piping, and thickness of trench concrete cover.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>A concrete cast-in-place trench system shall be provided and installed with a removable top as shown on the drawings.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.7.1   Concrete</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Concrete work will be specified in detail in Section <SRF>03 31 00.00 10</SRF> CAST-IN-PLACE 
STRUCTURAL CONCRETE, edit the spec and include all specific requirements pertinent 
to local conditions and designers General Notes.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Materials and methods for mixing and placing of concrete shall be as specified in Section <SRF>03 31 00.00 10</SRF> CAST-IN-PLACE 
STRUCTURAL CONCRETE.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.2   Joint Sealants</TTL><BRK/>
<BRK/>
<TXT>Concrete joints shall be sealed as indicated.  Type II sealant (nonsagging) shall be used for vertical joints.  
Type I sealant shall be used for trench top butt joints.  All other joints shall be sealed with Type I or Type 
II sealant.  Sealant in trench bottom shall finish flush with floor.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.3   Concrete Trench Tops</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Tops must be square and not out of plane, and must be cast to lay flat 
in all directions.  Provide notes on drawings.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Concrete trench tops shall be precast or cast-in-place.  Concrete shall be as specified in Section 
<SRF>03 31 00.00 10</SRF> CAST-IN-PLACE STRUCTURAL CONCRETE.  The tops shall be flat and true and shall lay flat at all 
locations where contact on trench wall is to be made.  Tolerances shall be true planes within<MET> 4 mm in 3 m</MET><ENG> 1/8 
inch in 8 feet</ENG> as determined by<MET> 2.44 m</MET><ENG> 8 foot</ENG> straight edge placed diagonally on top.  Deviation from square 
or designated skew (difference in length of the two diagonal measurements) shall be<MET> 3 mm in 2 m</MET><ENG> 1/8 inch in 6 
feet</ENG> or<MET> 6 mm</MET><ENG> 1/4 inch</ENG> total, whichever is greater.  Maximum permissible warpage of one corner out of the plane 
of the other three shall be<MET> 5 mm per meter</MET><ENG> 1/16 inch per foot</ENG> distance from the nearest adjacent corner.  Concrete 
trench tops with defects which affect the strength of the cover unit, or which are warped, honeycombed, contain 
visible air pockets, exposed aggregate, or other surface defects such as spalled, chipped, or broken edges, shall 
not be installed.  Neoprene gasket material shall be placed on the top of concrete trench walls so as to provide 
a seal between the wall and the concrete trench covers.  Surfaces of joints to be in contact with gasket material 
shall be dry and free of oil, grease, dirt, loose concrete particles, or other foreign substances.  Gasket material 
shall be placed in a continuous length along the wall as much as practical.  Gasket ends shall be butted tightly 
together at splices.  Concrete trench tops shall be constructed in maximum lengths of<MET> 2.4 m</MET><ENG> 8 feet</ENG> and minimum 
lengths of<MET> 1.2 m</MET><ENG> 4 feet</ENG> and shall be a minimum of<MET> 100 mm</MET><ENG> 4 inches</ENG> thick, unless otherwise indicated.  Each top 
section shall be provided with means to accept a lifting device for removal of slab, as indicated on the drawings.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.4   Concrete Trench Construction</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide details on the drawings of the concrete trenches and concrete 
walks.  Provide details of the various trench sizes for the different sizes 
of heat distribution piping anticipated for this contract.</NPR><BRK/>
<BRK/>
<NPR>Where concrete trench tops are used in conjunction with sidewalks, provide sidewalk 
sections on the drawings between loop legs to maintain a continuous sidewalk.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>The concrete trench shall be of the sizes indicated on drawings.  Inside edge and top of walls shall have smooth 
even surfaces to accommodate trench tops.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.5   Final Elevations</TTL><BRK/>
<BRK/>
<TXT>The concrete trench floor shall slope continuously and drain toward valve manholes.  Construct the concrete trench 
at the elevation shown on the drawings and grade the adjacent areas.  Any cut or fill areas adjacent to the concrete 
trench shall be graded back to the existing grade at a 1 to 10 slope, or as indicated.  Care shall be taken to 
avoid forming pockets adjacent to the concrete trench; thereby, preventing surface drainage.  The concrete trench 
floor and pipe shall be parallel and shall maintain constant slope toward the drain points indicated.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.6   Coordination with Existing Utilities</TTL><BRK/>
<BRK/>
<TXT>Before beginning work in a given area, all utility information shall be field verified by surface markings made 
by the affected utility Owner's Representative.  Notify the Contracting Officer in advance, and receive prior 
approval before excavating in any areas.  The actual concrete trench routing may be offset or changed if approved 
by the Contracting Officer in order to reduce conflicts, interruptions, expedite the work, or for any other reason 
to the mutual benefit of the Contractor and the Government.  Utility conflicts may be cast into the floor of 
the trench providing they do not interfere with concrete trench drainage and are approved by the Contracting 
Officer.  [After the new heat distribution system is cut-in, the existing system can be [removed.] [abandoned 
in place if not in conflict with the new construction and not shown to be removed on the drawings.]]</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.7   Piping Support System</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Provide design details of pipe supports on drawings.  Show sizes, shapes 
and means of how the system is to function.  Supports may consist of welded 
plates, channels, structural tees, pipes or other support means.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Piping shall have supports as indicated.  No pipes, pipe supports, or other related items shall be permitted 
on the floor of the concrete trench system.  Pipe support members spanning traversely across the tunnel shall 
allow a minimum of<MET> 100 mm</MET><ENG> 4 inches</ENG> clearance between structural member and concrete trench floor.  Additional 
minimum clearances required from the pipe insulation surface shall be as follows:  <MET>200 mm</MET><ENG> 8 inches</ENG> to concrete 
trench floor, <MET>150 mm</MET><ENG> 6 inches</ENG> to side walls, <MET>150 mm</MET><ENG> 6 inches</ENG> to trench cover, and<MET> 150 mm</MET><ENG> 6 inches</ENG> between adjoining 
pipes.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.8   Pipe Expansion</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Coordinate this paragraph with the specified requirements in paragraph 
General Piping Requirements.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Expansion shall be accommodated by loops and bends as indicated on the drawings and specified.  Pipe in the loops 
and bends shall accommodate expansion while maintaining required insulation clearance from floors, walls, tops, 
and other pipes to avoid crushing or breaking of insulation.  Expansion loops may be designed around obstacles 
such as utility manholes, structures, or trees to avoid construction conflicts.  Slopes of pipe and trench bottoms 
shall be maintained.  Contractor shall have the option to adjust the loop dimensions around obstacles based on 
final field measurements, if approved by the Contracting Officer.  Submit pipe stress calculations for each revised 
expansion loop or bend based on the final actual measured lengths, or shall submit dimensions to the Contracting 
Officer for verification of loop and bend sizes before proceeding with that segment of work.  Allowable pipe 
stresses shall be in accordance with <RID>ASME B31.1</RID>.  Final expansion loop insulation method shall be submitted for 
approval to the Contracting Officer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.9   Pipe Anchors</TTL><BRK/>
<BRK/>
<TXT>Pipe anchors shall be as indicated on the drawings.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.10   Concrete Trench Inspection Ports</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Show inspection ports on plan view and detail them on the drawings.</NPR><BRK/>
<BRK/>
<NPR>Provide inspection ports at appropriate locations to enable the user to observe 
elbows in expansion loops and bends, at high point pipe vents, approximately 
every 30 m (100 feet) of straight run, and at locations requiring frequent (monthly) 
observation.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Inspection ports shall be provided as indicated.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.11   Road/Drive Crossings</TTL><BRK/>
<BRK/>
<TXT>Road/drive crossings shall be as indicated.  Handicap ramp style curb cuts shall be installed at all street and 
drive crossings as indicated.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.7.12   Railroad Crossings</TTL><BRK/>
<NTE><BRK/>
<AST/><BRK/>
<NPR>NOTE:  Review railroad track removal/replacement with respective authority and 
coordinate all activities.</NPR><BRK/>
<AST/><BRK/></NTE>
<BRK/>
<TXT>Railroad crossings shall be as indicated.  The tracks shall be restored to their original condition as approved 
by the Contracting Officer after construction is complete.</TXT><BRK/>
<BRK/></SPT>
</SPT><SPT><TTL>3.8   <SUB>TESTS</SUB></TTL><BRK/>
<BRK/>
<TXT>Tests shall be conducted before, during, and after the installation of the system.  Provide all instruments, 
equipment, facilities, and labor required to properly conduct the tests.  Test pressure gauges for a specific 
test shall be approved by the Contracting Officer and shall have dials indicating not less than 1-1/2 times, 
nor more than 3 times the test pressure.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.8.1   Cleaning of Piping</TTL><BRK/>
<BRK/>
<TXT>Prior to the hydrostatic and operating tests, the interior of the piping shall be flushed with clean water until 
the piping is free of all foreign materials.  Flushing and cleaning out of system pipe, equipment, and components 
shall not be considered completed until witnessed and accepted by the Contracting Officer.  After flushing the 
system is completed, the system shall be drained and filled with clean water.  Temporary bypasses or temporary 
strainers shall be provided around equipment and control valves to prevent clogging.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.2   Field Tests</TTL><BRK/>
<BRK/>
<TXT>Conduct the following field tests when applicable to the system involved.  If any failures occur, make such adjustments 
or replacements as the Contracting Officer may direct, and repeat the tests until satisfactory tests are completed.</TXT><BRK/>
<BRK/>
<SPT><TTL>3.8.2.1   <TST>Hydrostatic Tests of Service Piping</TST></TTL><BRK/>
<BRK/>
<TXT>Service piping shall be tested hydrostatically before insulation is applied at field joints, and shall be proved 
tight at a pressure 1.5 times the working pressure of [_____]<MET> kPa</MET><ENG> psig</ENG> or at<MET> 1.38 MPa</MET><ENG> 200 psig</ENG>, whichever is 
greater.  Hydrostatic test pressure shall not exceed<MET> 3.45 MPa</MET><ENG> 500 psig</ENG>.  Hydrostatic test pressures shall be 
held for a minimum of 4 hours.  If the hydrostatic test pressure cannot be held, make necessary adjustments or 
replacements and repeat the tests until satisfactory results are achieved.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.2.2   <TST>Equipment Tests</TST></TTL><BRK/>
<BRK/>
<TXT>All pumps, valves, traps, alarms, controls, and any other operable item of equipment shall be operated to verify 
proper operation and compliance with the specifications.  Pump voltage, current, and discharge readings shall 
be recorded and submitted for approval in accordance with SUBMITTALS paragraph (SD-06).</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.2.3   <TST>Insulating Flange Test</TST></TTL><BRK/>
<BRK/>
<TXT>Insulating flanges shall be tested for electrical isolation in accordance with the insulating flange manufacturer's 
standard test.  This test shall be witnessed and approved by the Contracting Officer.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.2.4   <TST>Operational Tests</TST></TTL><BRK/>
<BRK/>
<TXT>After installation of the concrete trench system, or testable portion thereof, operational tests shall be conducted.  
Trench covers shall not be placed prior to completion of operational tests.  Operational tests shall consist 
of operating the system at the pressure and temperature expected for the system when in normal service, and shall 
demonstrate satisfactory operating effectiveness.  The test on each system, or portion thereof, shall last a 
minimum of 24 hours.</TXT><BRK/>
<BRK/></SPT>
<SPT><TTL>3.8.2.5   <TST>Trench Water Removal Tests</TST></TTL><BRK/>
<BRK/>
<TXT>After the above tests are completed, and before concrete trench and valve manhole covers are placed, the concrete 
trenches, sumps, and valve manholes shall be cleaned of dirt and debris.  Concrete trench system shall be tested 
to ensure gravity drainage of water is maintained in trench bottom from high points to drained low points.  Verify 
water does not pond between high and low points, and that drained low points are operational either by use of 
sump pumps or by gravity drainage to storm drains, as indicated.  Test shall not be considered completed until 
witnessed and accepted by the Contracting Officer.  Trench tops shall be placed and sealed immediately after 
approval by the Contracting Officer.</TXT><BRK/>
<BRK/></SPT>
</SPT></SPT></PRT>     <END/><BRK/></SEC>