1.ALL WORK SHALL CONFORM TO THE LATEST ED OF THE NATIONAL ELECTRICAL CODE, THE GOVERNING ELECTRICAL CODE AND ALL OTHER INSPECTION DEPARTMENTS HAVING JURISDICTION. OBTAIN CERTIFICATES OR APPROVAL WHERE REQUIRED. 2.ALL MATERIALS FURNISHED SHALL BE NEW AND SHALL BE UL LISTED. 3.THE DRAWINGS INDICATE SIZE AND GENERAL LOCATION OF WORK SCALE DIMENSIONS SHALL NOT BE USED. THE EXACT LOCATION AND LOCATION OF ALL LIGHTING FIXTURES, RECEPTACLES AND TELEPHONE OUTLETS, ETC SHALL BE DETERMINED BY ACTUAL CONDITIONS IN THE FIELD. 4.PRIOR TO BIDDING, CONTRACTOR SHALL VISIT THE JOB SITE AND FAMILIARIZE THEMSELVES WITH THE EXISTING CONDITIONS. 5.ELECTRICAL CONTRACTOR SHALL COORDINATE HIS WORK W/ OTHER TRADES AND W/ OTHER CONTRACTORS WHOSE WORK MAY AFFECT THIS INSTALLATION. 6.ELEC CONTRACTOR SHALL COORDINATE INCOMING ELEC SERVICE W/ UTILITY COMPANY AND INCLUDE IN HIS BID ALL CHARGES AND FEES INCURRED IN MODIFICATIONS. 7.WHERE MORE THAN ONE SWITCH OCCURS IN THE SAME LOCATION, THEY SHALL BE INSTALLED IN A GANG TYPE BOX UNDER ONE COVER PLATE. 8.ELEC CONTRACTOR SHALL COORDINATE THE TELEPHONE INSTALLATION W/ THE TELEPHONE COMPANY AND THE GENERAL CONTRACTOR. 9.ELECTRICAL CONTRACTOR, BEFORE INSTALLING ANY OF THE WORK, SHALL SEE THAT IT DOES NOT INTERFERE W/ CLEARANCES REQUIRED FOR FINISHED COLUMNS, HUNG CEILINGS, PLASTER, PARTITIONS, WALLS, ETC AS SHOWN IN THE ARCH DRAWINGS AND DETAILS. IF ANY WORK IS INSTALLED AND IT LATER DEVELOPS THAT SUCH DETAILS OR DESIGN CANNOT BE FOLLOWED, THE CONTRACTOR, AT HIS OWN EXPENSE, SHALL MAKE SUCH CHANGES IN THE WORK AS DIRECTED BY THE ARCHITECT, AS WELL AS TO PERMIT THE INSTALLATION OF THE ARCH WORK AS SHOWN ON THE PLANS AND DETAILS. 10.PERFORM TEST REQUIRED BY THE OWNER OR THE ENGINEER IN CONNECTION W/ THE OPERATION OF THE ELEC SYSTEM IN THE BUILDING. 11.ALL TESTS SHALL BE MADE IN ACCORDANCE W/ THE LATEST STANDARD OF THE IEEE AND THE NATIONAL ELEC CODE. 12.MIN CONDUCTOR SIZE SHALL BE #12, 600V INSUL PER ARTICLE 300.22B; DUCTS SPECIFICALLY FABRICATED FOR ENVIRONMENTAL AIR. MIN SIZE CONDUIT SHALL BE 3/4" EMT FOR INTERIOR USE, AND 3/4" RIGID ALUMINUM FOR EXTERIOR USE. USE TYPE NMC CABLE COPPER, FOR LIGHTS AND RECEPTACLE CIRCUITS. EXTERIOR FITTINGS SHALL BE CAST BOXES AND COVERS. INTERIOR FITTINGS SHALL BE CAST WHERE EXPOSED ON WALLS. 13.CONTRACTOR SHALL INSTALL WIRING AND OTHER CIRCUIT COMPONENTS TO MATCH EQUIPMENT ACTUALLY INSTALLED. 14.INSTALL GROUND FAULT RECEPTACLES (GFCI) AT RECEPTACLE LOCATIONS WITHIN 5' OF SINKS OR LAVATORIES, AND AT EXTERIOR LOCATIONS. EXTERIOR RECEPTACLES SHALL ALSO BE WATERPROOF. 15.BONDING AND GROUNDING SHALL BE IN ACCORDANCE WITH NFPA 70:230-63, NFPR 250-23, 250-71, & 250-72. 16.GROUND NEUTRAL IN ACCORDANCE W/ NFPA 70:250-23b. 17.FUSES SHALL BE ITT CLASS K5, 250 VOLT, 200,000 AMP INTER-RUPTING CAP. 18.PROVIDE SERVICES OF A FIRE/SMOKE DETECTION AND ALARM COMPANY TO DESIGN AND INSTALL ALARM SYSTEM TO THE REQUIREMENTS OF THE STATE FIRE MARSHAL. 19.ALL ELEC, MECH, AND PLUMBING PENETRATING FIRE PARTITIONS SHALL BE FIRE CAULKED. (PENETRATIONS THROUGH RATED CONSTRUCTION SHALL BE SEALED W/ A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOT GASES WHEN TESTED IN ACCORDANCE WITH ASTM-E814). 20.ALL ELECTRICAL, MECHANICAL AND PLUMBING PIPES BELOW SLAB SHALL BE PLACED BELOW GRADE BEAMS AND SHALL NOT PENETRATE GRADE BEAMS UNLESS FIXTURE PLACEMENT DICTATES PLACEMENT OF PIPING INSIDE GRADE BEAM. 21.ALL WALL MTD ELEC OUTLETS SHALL BE LOCATED 18" AFF UNLESS OTHERWISE NOTED. 22.CONTRACTOR SHALL NOT SHARE NEUTRALS BETWEEN DIFFERENT CIRCUITS. INDIVIDUAL NEUTRALS SHALL BE RUN FOR EACH CIRCUIT.