WPC4  
      2      B       P   Z            Courier 10cpi #| x              A~x 6X   @ 8 X@Canon BJ-200ex (LQ mode)             CB20LQMO.PRS x 
   @   ,hX@#| x           2        B   V   P   Z     F   `   Courier 10cpi  ? x x x h    Aox 6X   @ 8 X@Canon BJ-200ex (LQ mode)             CB20LQMO.PRS x 
   @   ,hX@ 2         2                                  
& SECTION 3

@ REPAIR AND REPLACEMENT OF PAVED AREAS

   ?  3.01 `	`	 General

  `	`	 The Contractor shall break out and remove from the siteexisting hard surface pavement, including sidewalks anddriveways, which are located in the alignment of thewater mains.  The pavement shall be broken out to theminimum width necessary for installation of the watermains.  Where existing pavement surface course isconcrete and pavement removed does not extend to existingjoint, the edge shall be saw cut one foot (1') more thanthe excavation.  All concrete streets shall be removedand replaced from joint to joint.  After water main hasbeen installed and backfilled with required material, thepavement will be replaced according to the following.(#`	

   ?  3.02 `	`	 Concrete Pavement

  `	`	 The area shall be repaired by placing a twelve inch (12")subgrade of tamped sand (95% compaction).  The edge ofadjacent concrete slabs shall be thoroughly cleaned anddampened.  The cut shall be filled with 4000 psi concreteas specified under Section 4.  All concrete shall have W.R. Grace polypropylene fibers added to concrete mix atthe batch plant.  Fibers to be added according tomanufacturer's specifications.  The concrete shall bestruck off and finished to conform to grade, thickness,and finish of existing adjacent surfaces.  Curing shallbe accomplished by spraying of approved curing compoundon surface immediately after finishing.  Where the cut isacross a street the replacement will include the curb ifa curb is present.  Finish shall match existing.(#`	

   ?  3.03 `	`	 Asphaltic Concrete Paving

  `	`	 The Contractor shall place a twelve (12") limestonesubgrade in cuts through asphaltic concrete paving.  Theasphalt shall be cut one foot (1') wider than theexcavation.  The edge of adjoining paving and thesubgrade shall be primed with approved asphalt primer. A hot plant mixed bituminous patch shall be applied tothe subgrade and rolled to conform to the thickness andgrade of adjacent paving (not to exceed 6 inches inthickness).  Hot plant mixed bituminous material shallmeet all applicable requirements of Section 501 of theLouisiana Department of Transportation and DevelopmentStandard Specifications for Roads and Bridges (1982Edition) for Type 3 mix.(#`	

( TS11   h)         0*0*0*  Ԍ

   ?  3.04 `	`	 Concrete Sidewalks

  `	`	 The Contractor shall break and remove from the sitesidewalks which are located in the alignment of the watermain and replace sidewalks after the water main line iscontructed.(#`	

  `	`	 Concrete walks shall be one (1) course Portland Cementconcrete pavement, as specified under Section 4, fourinches (4") in thickness.  A dummy joint one quarter inch(1/4") deep shall be made at four (4') intervals.  A onehalf inch (1/2") expansion joint with an approved asphaltfiller shall be installed at twenty feet (20') intervals,and also where walks adjoin existing walks are terminateat curbs.  The base material shall be four inches (4") ofcompacted sand.  All concrete shall have W. R. Gracepolypropylene fibers added according to manufacturer'sspecifications.(#`	

  `	`	 Concrete in walks shall be finished to conform withexisting adjacent surfaces.  All edges, including thoseat dummy joints and expansion joints, shall be rounded toa onequarter inch (1/4") radius.(#`	

   ? P 3.05 `	`	 Gravel or Shell Surface Repairs

  `	`	 The contractor shall repair the surfacing of all gravelor shell surfaced areas (driveways, streets, and parkingareas) damaged or removed by his operation.  Materialsused to resurface these areas shall be twelve inches(12") of shell or gravel compacted as directed by theEngineer.(#`	



















( TS12   h)         0*0*0*  Ԍ& SECTION 4

& CONCRETE

   ?   4.01 `	`	 General

  `	`	 This item consists in furnishing all plant, labor,equipment, appliances, and materials, and in performingall operations in connection with the installation ofconcrete work, complete, in strict accordance with theSpecificatins and the Drawings.  All items required to beembedded in the concrete shall have been made, to thesatisfaction of the Engineer, prior to placing concrete.(#`	

   ? 
 4.02 `	`	 Strength

  `	`	 All concrete will be designed to the compressive strengthindicated on the drawings, as determined by breakingstandard six inch (6") diameter by twelve inch (12")height test specimens in accordance with procedure setforth in ASTM Specification C31 and C39.(#`	

   ? 0 4.03 `	`	 Materials

   ?   `	`	 A. Cement

 `	`	   All cement shall conform to the StandardSpecifications of the ASTM, Serial DesignationC-150, Type I or III.(#

 `	`	   Cement shall be stored off the ground in a drayventilated building.  Cement which has hardened orpartially set shall be removed from the site.(#

   ?   `	`	 B.  Aggregates(#

 `	`	   Fine aggregates shall be sand having clean, hard,uncoated gains of uniform grading from fine tocoarse.  It shall be free from injurious amounts ofsalt, alkali, deleterious substances or organicimpurities.(#

 `	`	   Except for any specific gradation, fine aggregatesshall conform in all respects to the StandardSpecifications of the ASTM Designation C33 forConcrete Aggreagates(#






( TS13
   h)         0*0*0*  Ԍ `	`	   Coarse aggregate shall be thoroughly washed andscreened river or bank aggregates and shall be notlarger than that designated by ASTM as two inch(2") aggregate nor smaller than that designated asthreefourth inch (3/4").  In all other respects,coarse aggregate shall conform to StandardSpecifications of the ASTM Designation C33 forConcrete Aggregates.(#

 `	`	   Fine and coarse aggregates shall be storedseparately and in such a manner as to preventsegregation of sizes in each aggregate and to avoidthe inclusion of dirt or other foreign materials inthe concrete.(#

   ?   `	`	 C.  Admixtures(#

 `	`	   The admixture, when used, shall conform to ASTMC-494, Type A, and not contain any lignin orchloride ions added during manufacture.  When hightemperatures exceed 85 degrees F. and/or placingconditions dictate, the Engineer may require achange from the Type A (normal) admixture to a TypeD (retarding) formulation of the admixturesspecified above.  The air entraining admixtureshall conform to ASTM C260.(#

   ?   `	`	 D. Fine Sand and Mineral Filler

 `	`	   An approved fine sand or a limestone mineral fillermay be incorporated into the concrete at the optionof the Contractor.  The sand must be a finelygraded sand, predominantly of the minus 50 and 100mesh sieve, free from objectionable deleterioussubstances, organic to be used shall be determinedby laboratory test and shall not exceed fifteenpercent (15%) of the total sand used.  Thelimestone mineral filler shall be a finely groundlimestone.  The percent limestone mineral filler tobe used shall be determined by laboratory tests butshall not exceed six percent (6%) by weight of thetotal sand used in the mix.(#

   ? !  `	`	 E. Water

 `	`	   The water used in the preparation of mortar orconcrete shall be clean and free from oil, acid,alkali, sugar, or other deleterious substances. Wherever possible, water from the mains of thelocal Water Works shall be used, and the Contractor(#
( TS14

   h)         0*0*0*  Ԍ `	`	   shall comply with all the requirements of saidWater Works concerning arrangements for supply andpayment of water used.(#

   ?    `	`	 F. Reinforcing Steel 

 `	`	   Reinforcing steel shall be new billet steelconforming to the requirements of ASTM A615, Grade60.  Bars having laps, seams, slivers, or otherdefects shall be rejected and shall not be used inthe work.  Welded wire mesh shall conform to therequirements of the Standard Specifications forWelded Steel Wire Fabric for ConcreteReinforcement, ASTM A185.(#

   ?  4.04 `	`	 Testing and Control

   ? H  `	`	 A.  General(#

 `	`	   Testing and control of all concrete materials shallbe the responsibility of the Contractor.  Thetesting laboratory shall be approved by theEngineer.  No material shall be used in theconcrete until certified copies of the results oftests are approved in writing by the Engineer.(#

   ? P  `	`	 B. Concrete

 `	`	   One (1) set of four (4) cylinders for test purposesshall be taken from each one hundred (100) cubicyards or fraction thereof, or each day's placement,whichever is less.  Test specimens shall be made inaccordance with American Society for Testing andMaterials Standard Method C31 and shall be testedin accordance with American Society for Testing andMaterials Standard Method C39.  Of the four (4)cylinders taken two (2) will be tested for strengthat seven (7) days and one (1) will be tested forstrength at twentyeight (28) days.  The fourth(4th) cylinder will be tested at four (4) days,fourteen (14) days, or at twentyeight (28) days asdirected by the Engineer.(#

   ? ! 4.05 `	`	 Proportioning of Concrete

 `	`	 Concrete shall be proportioned by weight and in a manner `	`	 directed or approved by the Engineer.  The mix design `	`	 shall be proportioned to achieve an average strength 750 `	`	 psi higher than the design strength.  The proportions `	`	 shall be selected in accordance with the Specifications `	`	 for Structural Concrete for Buildings ACI 301, Section 
 `	`	 3.8.

( TS15   h)         0*0*0*  Ԍ
  `	`	 All necessary equipment shall be provided to determineand control the actual amounts of materials entering intoeach concrete mix.  The proportions will be changedwhenever, in the opinion of the Engineer, such changesbecome necessary to overcome deficiencies and obtain therequired strength, the desired durability, density,workability, or consistency.  Consistency in the fieldshall be measured by the slump test in accordance withthe American Society for Testing and Materials StandardMethod C143.  The slump shall fall within the followinglimits:(#`	

   Type of Structure                     Slump in Inches
 `	`	   hh# ( -     Minimum           Maximum

   ?   Massive sections, pavements-   pp2 11/2  < xxA   F 4
   and slabs on the ground

   ?   Heavy slabs, beams, or walls- pp2 37   < xxA   F 5

   ? h  Thin walls and columns( - pp2 31/2  < xxA   F 6
   ordinary slab or beams

   ?  4.06 `	`	 Batching and Mixing Concrete

  `	`	 Concrete shall be mixed by a mechanical batchtype mixingplant.  The rated capacity of any individual mixer shallbe one half (1/2) cubic yard or more.  Concrete shall betransit or plant mixed.  The plant and its location shallbe subject to approval by the Engineer.(#`	

   ?   4.07 `	`	 Preparation for Placing

  `	`	 Water shall be removed from excavations before concreteis deposited.  Hardened concrete, wood chips and shavingsand other debris shall be removed from the interior ofthe forms, and all hardened concrete and foreignmaterials shall be removed from the inner surfaces of themixing and conveying equipment.  Wood forms shall becoated with an approved form coating or, except infreezing weather, wetted with water in advance of placingso that joints will tighten and prevent seepage of cementgrout from the mix.  Reinforcement shall be secured inposition, inspected, and approved by the Engineer beforestarting the placing of concrete.(#`	






( TS16
   h)         0*0*0*  Ԍ
   ?   4.08 `	`	 Expansion Joints

  `	`	 Joints between slabs on earth and vertical surfaces whereindicated, or noted "Mastic Joint," shall be premoldedexpansion joint filler strips.  Such joints shall be notless that onehalf inch (1/2") thick and the full depthof slab.  The edges of concrete slabs shall be neatlyfinished along the edge of the premolded mastic stripswith a slightly rounded edging tool.(#`	

   ?  4.09 `	`	 Construction Joints

  `	`	 The unit of operation shall not exceed eighty feet (80')in any horizontal direction.  Concrete shall be placedcontinuously so that the unit will be monolithic inconstruction.  At least fortyeight (48) hours shallelapse between the casting of adjoining units, unlessthis requirement is waived by the Engineer.  Verticaljoints in wall footings shall be reduced to a minimum. No jointing shall be made in footings or foundation workwithout written approval from the Engineer.(#`	

   ?  4.10 `	`	 Placing Concrete

  `	`	 Methods of mixing, placing, and compacting of contractshall be subject to approval by the Engineer.  Concreteshall be handled from the mixer or transit truck mixer tothe place of final deposit in a continuous manner and asrapidly as possible.  Concrete that has attained itsinitial set or that has been mixed for more than thirty(30) minutes shall not be used.  Concrete shall be placedin forms in a manner to prevent segregation of theaggregate and shall not be placed in concrete alreadyhardened until provisions are made for proper bonding andkeying.  Concrete shall be thoroughly rodded, spaded,vibrated, or otherwise compacted to the satisfaction ofthe Engineer.  External vibration of forms will not bepermitted.  (#`	

   ? @  `	`	 A.  Cold Weather Placement(#

 `	`	   Unless authorized by the Engineer, concrete shallnot be mixed or placed when ambient temperature isbelow 40 degrees F.  Concrete shall be maintainedat not less than 50 degrees F. for a period ofseventytwo (72) hours after being placed.  Allslabs placed when the ambient temperature is below50 degrees F. shall contain a water reducing(#




( TS17   h)         0*0*0*  Ԍ

 `	`	   accelerator.  The admixture shall conform to ASTMC494, Types "C" or "E," and have longterm testdata proving its noncorrosive effect onmetal deckand reinforcing steel.  All concrete shall beplaced in accordance with Recommended Practice forCold Weather Concreting, ACI 306.(#

   ?   `	`	 B.  Foundation Placement(#

 `	`	   Concrete footings shall be placed upon undisturbed,clean surfaces, free from frost, ice, mud, standingor running water.  When the foundation is on drysoil, waterproof sheathing paper shall be laid overthe earth surfaces to receive the concrete.(#

   ? H 4.11 `	`	 Consolidation

  `	`	 Concrete shall be placed in layers not over twelve (12")deep, and each layer shall be consolidated with the aidof mechanical internal  vibrating equipment (minimumfrequency 8,000 vibrations per minute) supplemented byhand spading, rodding, and tamping as directed by theEngineer.  Vibrators shall be applied at uniformly spacedpoints not farther apart than eighteen inches (18").(#`	

   ?  4.12 `	`	 Concrete Finish Other Than Slabs

  `	`	 All concrete exhibiting any slight honeycomb and minordefects shall be patched, using cement mortar composed onone (1) part of cement to two (2) parts of fineaggregate.  All exposed concrete surfaces shall be smoothfinish obtained by use of wood forms.  Sections shall beas large as practicable, with smooth, even edges andshall be installed with closed joints.  Joint marks shallbe smoothed off and all blemishes removed, leavingfinished surfaces smoother and unmarred, subject toapproval by the Engineer.(#`	

   ? @ 4.13 `	`	 Concrete Slab Finishes

  `	`	 Concrete slab shall be finished as hereinafter described.(#`	

   ? `"  `	`	 A.  Troweled Finish(#

 `	`	   After the concrete has been placed, consolidated,struck off and leveled, the concrete shall not beworked further until ready for floating.  Floatingshall begin when the water sheen has disappearedand when the surface has stiffened sufficiently topermit the operation.(#

( TS18   h)         0*0*0*  Ԍ
 `	`	   The surface shall be floated at least twice.  Two(2) steel trowelings shall be given to yield afinished surface free from depressions and defectsof any kind, etc., and shall present a hard, smoothappearance.  (#

   ? x  `	`	 B.  Power Machine Finishing(#

 `	`	   In lieu of hand finishing, the Contractor has theoption of using a power machine for finishingconcrete surfaces, provided the machine is approvedby the Engineer.(#

 `	`	   Finishing by machine shall, in general, be ashereinbefore required for hand finishing.  Themethod of finishing by machine shall conform withthe directions of the manufacturer of the powermachine.(#

   ?  4.14 `	`	 Slabs on Earth

  `	`	 Before proceeding to construct concrete slabs on earth,all pipes under concrete floors on earth shall havereceived the required tests.  The earth fill shall betamped as approved by the Engineer.  Any unsuitablematerial encountered in the subgrade shall be removed andreplaced with material approved by the Engineer.  Thesubgrade shall be brought to a true, even plane, andcompacted to a solid bearing.  The concrete shall be ofcomparatively dry consistency and shall be screened levelor to the required grades, and the surface finished asherein specified.(#`	

   ?  4.15 `	`	 Protection and Curing

   ?    `	`	 A.  Curing(#
 
 `	`	   Immediately after placing or finishing, concretesurfaces not covered by forms shall be protectedfrom the loss of surface moisture for a period ofnot less than seven (7) days.  All slabs, withcarpet, resilient tile, or left exposed shall becured with compounds conforming to Federal SpecTT-C800A, 30% solids content minimum.(#

   ? #  `	`	 B. Protection

 `	`	   All other exposed surfaces shall be protectedagainst moisture loss by covering with Kraft paper,quilts, or burlap, lapped four inches (4") at edgesand ends.  Kraft paper, if used, shall be sealed. (#

( TS19   h)	         0*0*0*  Ԍ

 `	`	   The forms shall be sufficiently wetted with cleanwater to reduce cracks and to prevent the joints informs from opening and by keeping the protectivematerial thoroughly wet to prevent hair cracks fromoccurring in surface of the concrete.(#

   ? @ 4.16 `	`	 Forms

  `	`	 Forms shall be maintained sufficiently rigid to preventdeformation under load.  Temporary opening shall bearranged in wall and column forms and where otherwiserequired to facilitate cleaning and inspection.  Allforms shall be so constructed that they can be removedreadily without hammering or prying against the concrete.(#`	

   ? H  `	`	 A.  Form Ties(#

 `	`	   Bolts and rods used for internal ties which are tobe removed shall be coated with grease and soarranged that when the forms are removed all metalwill be not less than one inch (1") from anyconcrete surface.  Wire ties will not be permittedwhere the concrete surface will be exposed toweathering or any point where discoloration will beobjectionable.  The design of form ties shall besubject to the approval of the Engineer.(#

   ?   `	`	 B.  Control Joints(#

 `	`	   Control joints, when required, shall conform to thedetails and locations indicated on the plans.  Thesealant and caulking compound shall comply with therequirements and recommendations of themanufacturer.  The surface of the caulked slotshall be clean and smooth and any sagging orwrinkles shall be corrected.  The color of thecaulking compound shall match the concrete asapproved by the Engineer.(#

   ?    `	`	 C.  Filling TieRod or Bolt Holes(#

 `	`	   Holes remaining from bolts or tie rods shall befilled solid with cement mortar.  Holes passingentirely through the wall shall be filled frominside face with a device that will force themortar through to the outside face using a stopheld at the outside wall suface to ensure completefilling.  Holes which do not pass entirely(#


( TS20
   h)
         0*0*0*  Ԍ
 `	`	   through the walls shall be packed thoroughly full. All excess mortar at the face of filled holes shallbe struck off flush.(#

   ?  4.14 `	`	 Repair of Defective Areas

  `	`	 With the prior approval of the Engineer, as to method andprocedures, all repairs of defective areas shall conformto the requirements of ACI 301, Chapter 9.(#`	










































( TS21
   h)         0*0*0*  Ԍ
& SECTION 5

! EXISTING UTILITIESă

   ?  5.01 `	`	 Scope

  `	`	 This section covers the relocation of existing utilities,both known and unknown.(#`	

   ?  5.02 `	`	 City Water and Sewer Lines

   ? `	  `	`	 A.  The Contractor shall notify the Engineerimmediately if any existing water main or sewermain interferes with the Contractor's operations. City utilities shall be relocated by the City at nocost to the Contractor unless otherwise noted onthe Project Drawings.(#

   ?   `	`	 B.  The Contractor shall be responsible for locatingand avoiding water and sewer service lines toindividual properties.  Damages to service lineshall be repaired at the Contractor's cost.  TheContractor shall relocate water and sewer servicelines as required at no additional cost to theOwner.(#

   ?   `	`	 C.  Where existing utilities lines cannot be relocatedconflict boxes shall be installed.  Conflict boxesshall be approved by the Engineer prior toinstallation.(#

   ?   5.03 `	`	 Privately Owned Utilities

  `	`	 Existing privately owned utilities such as gas mains,power poles, telephone pole or telephone conduitsrequiring relocating to prevent interference with theContractor's work shall be relocated by the companyowning the utility except as designated on the drawings. The cost of such relocation shall be paid by the Owner.(#`	

   ?   5.04 `	`	 Unknown Utilities

   ? !  `	`	 A.  The drawings attempt to indicate the location ofall known utilities within the limits of the work. However, the Contractor shall be responsible tovisually inspect his entire project to determinethe existence of any additional constructionconflicting with his work.(#



( TS22
   h)         0*0*0*  Ԍ
   ?    `	`	 B.  In the event the Contractor encounters an unknownutility in his operations and such item willinterfere with the work and will requirerelocation, the Contractor shall expeditiouslyarrange such relocation in conformance with theapplicable paragraphs above.(#

   ? @ 5.05 `	`	 Coordination of Utilities Relocation

   ?   `	`	 A.  The Contractor shall be completely responsible tocoordinate and schedule such relocation ofutilities in a manner to prevent any delay in hisoperations due to relocation work.(#

   ?   `	`	 B.  No "standby" allowance will be paid to theContractor in the event of his failure to notifyand cause the proper agency to relocate any knownutility in such agency's charge which interfereswith the work.(#
































( TS23
   h)         0*0*0*  Ԍ
& SECTION 6

 MEASUREMENT AND PAYMENT

   ?  6.01 `	`	 Scope

  `	`	 This section shall cover all items for which theContractor is to be compensated.(#`	

   ?  6.02 `	`	 Water Mains

  `	`	 Measurement of accepted water mains shall be made alongthe centerline thereof, and no deductions shall be madefor valves or fittings.  Payment shall be made accordingto the unit price for furnishing and installing pipe ofthe specified size.  Unless otherwise indicated elsewherein these specifications, the bid price shall include thecost for all incidental work.(#`	

   ?  6.03 `	`	 Cast Iron Fittings

  `	`	 Payment of accepted cast iron fittings shall be by thenumber of units of cast iron fittings installed, and perthe unit price for each unit.(#`	

   ? P 6.04 `	`	 Gate Valves and Boxes

  `	`	 Measurement of gate valves and boxes, including concretebases and concrete slabs at grade, shall be the number ofunits installed and accepted.  Payment will be madeaccording to the unit price bid for furnishing andinstalling gate valves and boxes.(#`	

   ?  6.05 `	`	 Fire Hydrant Assemblies
 
  `	`	 Measurement of fire hydrant assemblies shall be a countof the actual number of assemblies furnished, installed,and accepted.  Each type of hydrant shall include thehydrant, piping, fittings from main, the 6" valve, box,and cover, reaction backing, and other incidental itemsnecessary to complete the work.  Payment shall be madeaccording to unit price bid.(#`	

   ? `" 6.06 `	`	 Connections to Existing Water Mains

  `	`	 Measurement of tiein assemblies shall be a count of thenumber and types of tieins made and accepted.  Tieinassemblies shall include all work necesary to complete(#`	



( TS24
   h)         0*0*0*  Ԍ
  `	`	 the pipe connection.  Fittings, pipe, valve, box, andcover as shown on Drawings to complete the connectionshall be paid for under various unit prices in thecontract.  Payment for tieins shall be made according tounit price bid.(#`	

   ? x 6.07 `	`	 Service Line

  `	`	 Measurement of accepted service line installations shallbe for each installation including all labor andmiscellaneous fittings required to tap new 3/4" line intomain, trench and lay new 3/4" line, supply and installservice clamp and corporation stop.(#`	

   ?  6.07 X  X`	`	 Meter Box(#`	

  `	`	 Measurement of accepted meter box installations shall befor each properly furnished and installed meter box. Work to include any labor and materials to connect meterto existing house service line.(#`	

   ? 0 6.09 `	`	 Limestone

  `	`	 Measurement and payment for accepted limestone shall beby the CY truck measure.  Payment shall include anymiscellaneous labor to place and compact material forpipe bedding, road bedding or driveways.(#`	

   ?  6.10 `	`	 Concrete and Asphalt

  `	`	 Measurement of pavement (roadways, driveways, parkingareas, and sidewalks), either concrete or asphaltic whichare cut and repaired as herein before specified shall beby the square yard.  Prices bid shall include the cost ofcutting and removing pavement, sand backfill, basematerial labor, and all incidental work required.(#`	

   ?  6.11 `	`	 Record Drawings

  `	`	 Measurement and payment for record drawings shall be forall labor, material and expense required to furnish theCity Engineering Department with an accurate set ofreproducible drawings reflecting all locations of mains,service lines, valves and fittings within the projectarea.(#`	






( TS25
   h)         0*0*0*  Ԍ
   ?   6.12 `	`	 Project Safety

  `	`	 Measurement and payment for project safety shall be atthe lump sum unit price bid.  Price shall include allcost for supplying and installation of barricades andtraffic control.(#`	

   ? @ 6.13 `	`	 Seeding

  `	`	 The Contractor shall seed all construction areas aftercompletion.  No additional payment shall be made forseeding, fertilizer, or watering to assure proper growthof the seeding.(#`	






































( TS26
   h)         0*0*0*  Ԍ& SECTION 7

 HORTICULTURAL REQUIREMENTS

   ?   7.01 `	`	 Description

  `	`	 This section shall consist of furnishing and installingall horticultural work required.(#`	

   ?  Note: `	`	 The Horticultural Requirements Section does not coverclearing and grubbing.  Provision for these items is madein the bid items.(#`	

   ? (
 7.02 `	`	 Definitions

   ?   `	`	 A. Primary Lawn Area

 `	`	   That portion of ground between the back of curb andthe font face and/or side face of an existingresidence and neutral grounds, which contains amostly solid covering of grass and/or grass sod,including shrubbery, plants, trees, landscaping,etc.(#

   ?   `	`	 B.  Secondary Lawn Area(#

 `	`	   That portion of ground in utility servitudes and/orcommon areas not considered residential yard areas,including shrubbery plants, trees, etc.(#

   ? p 7.03 `	`	 Horticultural Requirements

   ?    `	`	 A.  The Contractor is financially responsible for allnegligent damage or death of trees within theconstruction area.(#

   ?    `	`	 B.  Tree roots broken by construction shall be cutclean and painted with a commercial grade treepaint.  Above ground injuries shall be painted aswell as root cuts.(#

   ?    `	`	 C.  Contractor shall not store equipment or materials,nor park vehicles within the driplines of anytrees.  The dripline extends from one edge of atree's canopy to the other edge.(#

   ? #  `	`	 D.  City property shall be returned to existingcondition or better.  There shall be no shells,bricks, stones, concrete, asphalt, or other debris(#
 `	`	   left on the the surface or within the top sixinches (6") of backfill in the work area.  (#

( TS27
   h)         0*0*0*  Ԍ

 `	`	   Backfill shall be Batture sand, native soil, ortopsoil, as specified by the plans, specifications,or Project Engineer.  Any sand backfill in an areato be sodded shall be topped with two inches (2")to six inches (6") of a cohesive topsoil approvedby the Engineer.(#

   ?   `	`	 E.  Topsoil shall be fertile, friable, natural surfacesoil obtained from a well drained area, and free ofall stones, brush, weeds, shale, stumps, roots orother litter.  Topsoil shall have three percent(3%) to twenty percent (20%) organic matter, and anacidity range between pH 5.0 to 8.0 inclusive.  TheEngineer may accept a topsoil without certificationor statement of origin.  However, if the Engineerhas any doubt about the suitability of a proposedtopsoil, the Engineer may require the Contractor tofurnish a statement regarding the source of thetopsoil and a certified chemical and mechanicalanalysis made by an approved testing laboratory. Any cost incurred shall be borne by the Contractor.(#

   ?   `	`	 F.  Plant materials damaged or killed by Contractor'sactivities shall be replaced by the Contractor. Contractor is responsible for fertilizing,watering, and maintaining replaced plant materialsas required.  Contractor shall replace any plantmaterials which die within one hundred twenty (120)days of damage or installation.(#

   ?    `	`	 G.  In primary lawn areas disturbed by construction,the Contractor may salvage, and maintain alive,existing grass sod, from the areas of proposedconstruction.  For this alternative, bare earthareas shall be cultivated and fertilized beforeslab sod installation.  Salvaged slab sod shall bemostly composed of grass or grasses and approvedfor seeding.  Use of salvaged slab sod eliminatesthe requirement for cohesive topsil over sandbackfill.(#

   ? !  `	`	 H.  Alternative to salvaging grass sod, the Contractor,at his option, may elect to furnish and install newslab sod in primary lawn areas disturbed byconstruction.  For this alternative, bare earthareas shall be cultivated and fertilized beforeslab sod installation and watered before and(#



( TS28
   h)         0*0*0*  Ԍ
 `	`	   after installation.  Use of new slab sod eliminatesthe requirement for cohesive topsoil over sandbackfill.  New slab sod shall be one typethroughout the project.  This shall be determinedby the Engineer.(#

   ? x  `	`	 I.  Secondary lawn areas  once areas have been finishgraded, the Contractor shall seed bare earth areaswithin the limits of construction.  The type ofseed and rate of seeding shall be determined by thedate of planting, as follows:(#

   ? (
  `	`	  1. `	 March through September  Louisiana Office ofHighways Seed Mixture "G," (Hulled Bermuda)shall be spread at the rate of thirty (30)pounds per acre;(#

   ?   `	`	  2. `	 September through February  Louisiana Officeof Highways Seed Mixture "F," (50% Kentucky 31Fescue, 25% inoculated Crimson Clover, 25%Pensacola Bahia) shall be spread at the rateof forty (40) pounds per acre;(#

   ?   `	`	  3. `	 February through March  Louisiana OfficeHighways Seed Mixture "C," (33% HulledBermuda, 66% inoculated (Crimson Clover) shallbe spread at the rate of thirty (30) poundsper acre.(#

   ? p  Note: Ditch side slopes and bottoms shall be seeded as (#(#K 
 `	`	  well as ditch shoulder areas.

   ?  7.04 `	`	 Horticultural Outline

  `	`	 The Contractor shall prepare a written outline ofHorticultural work to be accomplished.  The outline shallbe type written and shall contain operational sequences,methods and procedures, watering schedules, etc.  Theoutline shall be submitted to the City of SlidellPlanning Department for review and approval.  ThePlanning Department must approve of the Horticulturaloutline prior to issuance of the "Notice to Proceed." The Contractor shall notify the Planning Department noless than fortyeight (48) hours prior to conducting anyHorticultural work.(#`	






( TS29
   h)         0*0*0*  Ԍ
& SECTION 8

x! SAFETY REQUIREMENTS

   ?  8.01 `	`	 Scope

  `	`	 This section shall cover all items necessary to ensurethat the Contractor performs his duties as specified inthe previous parts of these specifications with regard tosafety and protection of life and property.  It shall bethe responsibility of the Contractor to maintain safeworking conditions and observe safety standards.(#`	

   ? 
 8.02 `	`	 Barricades

  `	`	 The Contractor shall at all times provide barricades toprevent unauthorized passage in the work area bypedestrians and/or vehicular traffic.  Contractor shallfollow recommended guidelines of the Manual for uniformTraffic Control Devices for placement of all work zonetraffic control.(#`	

   ?  8.03 `	`	 Flagmen

  `	`	 The Contractor shall at all times provide a minimum ofone (1) flagman to safely route traffic (pedestrian andvehicular) around the work area.  The flagmen shallconform to any and all regulations governing the wearingapparel of flagmen as stated by Louisiana Department ofTransportation and Development.(#`	

   ?   8.04 `	`	 Flagging (Construction Tape)

  `	`	 When deemed necessary by the Engineer, the Contractorshall provide and place construction tape to preventunauthorized passage of traffic (pedestrian or vehicular)in work areas where impending danger exists.  No directpayment shall be made for this item.(#`	

   ? @ 8.05 `	`	 Interruption of Utility Service

  `	`	 Residents are to be promptly notified of any interruptionof utility service (pending or emergency) so that theymay take the necessary precautions.  The Contractor shallbe responsible for any damages resulting from theinterruption of utility services.  Gas and water serviceare of particular concern.(#`	




( TS30
   h)         0*0*0*  Ԍ
& SECTION 9

 PRESTART REQUIREMENTS

   ?   9.01`	`	  Project Sign
 
 `	`	   One sign required to be paut at Front and Clarastreets.(#

   ?   9.02`	`	  Project Video

 `	`	   The Contractor shall be required to video tape eachproject area before and after construction.  Thisvideo tape shall be a VHS tape.  This tape or acopy thereof shall be provided to the Owner forrecord purposes.  Work on the project may notcommence until the video taping prior toconstruction is completed.(#

  `	`	  No direct payment shall be made for this item.(#`	
































   h)         0*0*0*  Ԍ( TS31
   h)         0*0*0*  Ԍ


% SECTION 10

" PROJECT CLOSEOUTă

   ? x 10.01`	`	 Record Drawing

  `	`	 Upon completion of the project and before the finalpayment, the Contractor shall submit to the Owner, oneset of blueline record plans with the elevations andlocations of all improvements implemented in thisproject.  The surveying shall be by registered surveyor. All record drawings submitted shall be stamped by theregistered surveyor as an accurate description ofimprovements of this project.  Elevations shall bereferenced to M. S. L.(#`	

  `	`	 The City of Slidell is not responsible for providing abench mark for record drawings.(#`	

  `	`	 The City of Slidell will provide sepias to the Contractorfor completing record drawings.(#`	

 X  X`	`	 Payment of this item shall be at the bid price and madeas part of the final payment to the Contractor.(#`	

  `	`	 The final payment (retainage) shall not be released untilsatisfactory record drawings are submitted.(#`	

   ? 8 10.02`	`	 Completion Video

  `	`	 The Contractor shall deliver a satisfactory video tapewith the preconstruction and post constructioninformation.  Final payment (retainage) shall not be paiduntil receipt of the video.(#`	

   ?  10.03`	`	 Lien Period

  `	`	 The Contractor is responsible to record the completion ofthe contract with the Recorder of Mortgages in Covington,LA.  This will begin the Lien Period which is 45 days. Upon passage of the 45day period, the Contractor is tofile a request for final payment with the Owner.  Therequest for final payment shall be submitted to the Ownerwithin ninety (90) days of the completion of thecontract.  The start of the ninety day period shall beconsidered to be the date of the formal letter ofacceptance of the project by the Owner.  ANY RETAINAGEAMOUNTS NOT REQUESTED BY THE END OF THIS NINETYDAYPERIOD SHALL BE FORFEITED BY THE CONTRACTOR.(#`	

( TS32   h)         0*0*0*  Ԍ


















 PART III  SPECIFICATIONS

x! DIVISION II  PLANS


 X NOTE:  The drawings entitled "Install Fire Hydrants and WaterMains" prepared by the City of Slidell Engineering Departmentand made part of the specifications, are considered a part ofsame as if hereto attached.(#

























( TS33   h)         0*0*0*  Ԍ

 
















 

















 
 `	`	   
























 


   h)         0*0*0*  Ԍ
