Notes for Pre-Construction Meeting: 1. Cover the Partition types on A101 and A501. Partition types P-1 and P-10 are metal stud partitions and they have fire rating. a. A101 detail #4 has incorrect partitions at the IT Closet. P-1 is shown however these should be P-8 b. A101 detail #2 has incorrect partition at the wall between the Utility Rm and the Storage, shown as P-1 but probably should be P-8, however this partition requires R-19 insulation. Note P-1 shows R-19 insulation. Utility Room is conditioned space and the Storage 1 and Restroom are not conditioned. c. A101 detail #2 has incorrect partition at the wall between the Utility Rm and the Restroom, shown is P-3 which is technically correct but requires R-19 insulation. d. A101 detail #2 has incorrect partition at the wall between the Utility Rm and the Maintenance Bay, shown is P-9 which is technically correct but requires R-19 insulation. 2. Need to add a conduit for the antenna coax cable to the antenna. Use of sweeping ells is required. 3. All sheetrock corner molding shall be screwed.